SLC
Wiring Manual
ECN 06-320
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH, NIS, Notifier Integrated Systems, and ONYXWorks are all trademarks; and Acclimate, FlashScan, NION, NOTIFIER, ONYX, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Monday, March 26, 2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information: Product name and version number (if applicable) Printed manual or online Help Topic Title (for online Help) Page number (for printed manual) Brief description of content you think should be improved or corrected Your suggestion for how to correct/improve documentation FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Table of Contents
Section 1: Introduction ............................................................................................................ 7
1.1: About This Manual ........................................................................................................................................7 1.2: UL 864 Compliance.......................................................................................................................................7 1.2.1: Products Subject to AHJ Approval......................................................................................................7 1.3: Reference Documentation ............................................................................................................................8 1.4: SLC Overview ...............................................................................................................................................9 1.5: Polling Protocols ...........................................................................................................................................9 1.6: Devices .......................................................................................................................................................10 1.6.1: Monitor/Zone Interface Modules.......................................................................................................10 1.6.2: Control Modules ................................................................................................................................10 1.6.3: Isolator Modules ................................................................................................................................10 1.6.4: Relay Modules...................................................................................................................................10 1.6.5: Transponders .....................................................................................................................................11 1.6.6: Plug-in Detector Bases ......................................................................................................................11 1.6.7: Intelligent Detectors .........................................................................................................................11 1.6.8: Addressable Manual Pull Stations.....................................................................................................12 1.6.9: RFX Wireless Interface .....................................................................................................................12 1.6.10: ACPS-2406 Addressable Charger/Power Supply............................................................................12 1.7: SLC Capacity...............................................................................................................................................12 1.8: SLC Performance.........................................................................................................................................13 1.9: LED Operation.............................................................................................................................................13
Table of Contents
Index ........................................................................................................................................ 56
Section 1: Introduction
1.1 About This Manual
This document covers the installation and wiring of various Signaling Line Circuit (SLC) devices, when used with the following Fire Alarm Control Panels (FACPs): MICRO-200I MICRO-300I/MICRO-400 MICRO-640I/E MICRO-320
This document also provides basic information that applies to Chemetron SLC loops in general, such as the branch resistance measurements. See Section 2.4, Control Panel Terminal Blocks, on page 17 for basic panel-end SLC connections. Additional information about each control panel and the modules and detectors referenced in this document, and the part numbers for their manuals, can be found in the respective installation manual as listed in Section 1.3, Reference Documentation below.
MICRO-200I MICRO-300I, MICRO-400I CMX-1 CMX-2 LIB-400 MMX-1 MMX-101 MMX-2 MPS-24A/E MPS-24B/E MPS-400 MICRO-NCA MICRO-640I/E XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) XP5-C XP5-M ACPS-2406 B224RB B501BH B501BHT FCPS-24/E
Introduction
Reference Documentation
SLC Overview FSP-851, FSP-851T and FAPT-851 Photoelectric Detectors Installation Document FST-751 Thermal Detector Installation Document FST-751R Rate of Rise Sensor Installation Document FST-851, FST-851R, and FST-851H Thermal Detectors Installation Document FTM-1 Firephone Control Module FZM-1 Zone Interface Module Installation Document HPX-751 HARSH Installation Document ISO-X Isolator Module Installation Document LPX-751 Laser Detector Installation Document LPX-751L Laser Detector Installation Document NBG-12LX Pull Station Installation Document Note: Refer to the Device Compatibility Document for compatible conventional devices.
Introduction I56-1925 I56-1234 I56-1242 I56-1926 I56-1391 I56-1172 I56-1250 I56-1380 I56-748 I56-1793 51093
CAUTION: Do not program more than 99 addresses on a CLIP-mode SLC loop, because this will slow the system down and compromise the response time of the panel to display off-normal events.
3.
CAUTION: Do not program modules as CLIP and detectors as FlashScan on the same SLC. This combination does not work.
Introduction
Devices
1.6 Devices
1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and supervisory devices. FMM-1 Monitor Module; FlashScan or CLIP mode. (An earlier module named MMX-1 was CLIP mode only.) FDM-1 Dual Monitor Module; FlashScan or CLIP mode. FMM-101 Addressable Mini-Monitor Module; FlashScan or CLIP mode. (An earlier module named MMX-101 was CLIP mode only.) FZM-1 Zone Interface Module; FlashScan or CLIP mode. (An earlier module named MMX-2 was CLIP mode only). XP5-M Supervises five Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices. Supports FlashScan or CLIP mode. This module is capable of participating in degraded mode where supported by the FACP. (See the XP5 Series Manual) XP6-MA Allows an intelligent alarm system to monitor six zones of conventional two-wire detectors; FlashScan or CLIP mode. XP10-M Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices; FlashScan or CLIP mode. This module is capable of participating in degraded mode where supported by the FACP.
10
Devices
Introduction
1.6.5 Transponders
XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) Provides the FACP with an efficient multiplex subsystem capability. It communicates with the FACP and functions as a data-gathering panel for alarm Initiating Device Circuits and as a remote switching center for Notification Appliance Circuits (NAC), telephone circuits or relays. Not FlashScan capable.
For information on connecting these transponders to the SLC, refer to the XP Transponder Manual or the .
11
Introduction
SLC Capacity
FSD-751PL Low-flow Photoelectric Duct Detector, with extended speed range of 1004000 FPM (0.5 m/s to 20.3 m/s). FSD-751RPL adds a relay. Both models support FlashScan or CLIP mode. FSH-751 (HARSH) A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical. Supports FlashScan or CLIP mode. (An earlier model named HPX-751 was CLIP mode only.) FSL-751 VIEW An advanced intelligent photoelectric detector that uses a laser diode, special optics, and signal processing to obtain extremely high sensitivity. Supports FlashScan and CLIP mode; compatible with MICRO-320, MICRO-300I, MICRO-400I, and MICRO-640I only. LPX751L is compatible with MICRO-200I; CLIP mode only. (An earlier version named LPX-751 was CLIP mode only and compatible with MICRO-300I, MICRO-400I.)
12
SLC Performance
Introduction
Single Open Single Ground Short Short and open Short and ground Open and ground Communications loss
Alarm, Trouble Alarm, Trouble (ground) Trouble Trouble Trouble Alarm, Trouble Trouble
Alarm, Trouble Alarm, Trouble (ground) Alarm, Trouble Trouble Alarm, Trouble Alarm, Trouble Trouble
Trouble - The control panel will indicate a trouble condition for this type of fault. Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.
Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7
MICRO-320, MICRO-640I
NOTE: In CLIP mode, the LPX-751 and HPX-751 blink GREEN in standby and stay RED when activated.
13
To maximize distance on the SLC loop, use the recommended type of wire. Using other wiring types makes the SLC circuit more susceptible to electrical interference and thus reduces its maximum loop length.
FACP: Wire Type and Limitations Recommended Max. Distance Wire Gauge*
MICRO-640I and LEM-320 on MICRO-640I Twisted-unshielded pair, 12 to 18 AWG (3.31 mm to 0.82 mm). 50 ohms maximum per length of Style 6 & 7 loops. 50 ohms per branch maximum for Style 4 loop. Untwisted, unshielded wire, in conduit or outside of conduit. 12,500 ft. (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m) 1,000 ft. (304.8 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm) 12 to 18 AWG (3.31 mm to 0.82 mm)
Note: Twisted-shielded pair is not recommended for use with this panel. Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads. MICRO-320 Twisted-unshielded pair, 12 to 18 AWG (3.31 mm to 0.82 mm). 50 ohms, maximum per length of Style 6 & 7 loops. 50 ohms per branch maximum for Style 4 loop. Untwisted, unshielded wire, in conduit or outside of conduit. Twisted, shielded pair 12,500 ft. (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m) 1,000 ft (304.8 m) 1,000 ft. (304.8 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm) 12 to 18 AWG (3.31 mm to 0.82 mm) 12 to 18 AWG (3.31 mm to 0.82 mm)
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads.
14
Wiring Requirements
Wire Gauge
Note: Twisted-unshielded pair wire is not recommended for use with this panel. Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to earth) should not exceed 0.5 microfarads. MICRO-300I, MICRO-400I Twisted-shielded pair, 12 to 18 AWG. 40 ohms, maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops. Untwisted, unshielded wire, in conduit or outside of conduit. 10,000 ft. (3,048 m) 8,000 ft. (2,438.4 m) 4,875 ft. (1,485.9 m) 3,225 ft. (982.98 m) 1,000 ft. (304.8 m) 12 AWG (3.31 mm) 14 AWG (2.08 mm) 16 AWG (1.31 mm) 18 AWG (0.82 mm) 12 to 18 AWG (3.31 mm to 0.82 mm)
Note: Twisted-unshielded pair wire is not recommended for use with this panel.
Measure DC resistance as detailed and shown below: 1. 2. With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch. Repeat this procedure for all remaining branches in the SLC.
In Figure 2.1, Branches A, B, and C all begin at the SLC terminal, even though Branch B is T-tapped.
Branch A Branch B Branch C
SLC-meas5.cdr
SLC Out
B+
15
Wiring Requirements
Segment Five
Segment Four
Segment One
Measure DC resistance as detailed and shown below: 1. 2. 3. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel. Short the SLC at the last device and measure the resistance at SLC Out. Record resistance and remove the short. Short the SLC at the first device and measure the resistance at SLC return. Record resistance and remove the short.
16
SLC-meas2.cdr
Segment Two
Segment Three
Wiring Requirements
SLC Out
First Device
STEP 2 Last Device SLC Return Short Point SLC Out First Device STEP 3 SLC Return Last Device
SLC-meas5.cdr
NFS2640-SLC-TB.wmf
17
Wiring Requirements
B+ A+ B- A- TB1
TB16
2.4.3 MICRO-200I
MICRO-200I supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB5.
18
slc-200.wmf
Shielding of the SLC is not recommended for use with MICRO-320, MICRO-640I/E or LEM-320. If twisted-shielded wire is used in one of these installations, use a floating shield to terminate the wire as shown in Section 3.5, Floating Shield, on page 21. Use of good wiring practice consistent with local electrical codes is expected.
3.2 No Conduit
For use with Micro-200I and Micro-300I/400I only Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Fold the foil and drain wire back over the cable jacket. Slide the cable into the connector clamp and secure. The drain wire should be connected to the connector screw. Do not allow the shield drain wire or foil to enter the system cabinet.
Connector Screw Shield Drain Wire Foil
SLC-swterm1.cdr
Cabinet
19
Full Conduit
Conduit Tape over foil. Cabinet Example at right illustrates shield drain wire connection to an SLC terminal block without a reference or shield connection. Foil Shield Drain Wire
Shield2.wmf, SLC-swterm2a.wmf SLC-swterm3.cdr
Conduit
NOTE: For Style 6 or Style 7 SLC wiring, connect one end of the shield to the reference/negative side of the respective channel
Conduit
20
Floating Shield
NOTE: Using shielded wire in applications where it is not recommended will reduce the maximum SLC length. If shielded wire must be used where not recommended, failing to float the ends will reduce the maximum SLC length even further.
SLC-swterm4.cdr
21
Addressable Module
T-tapped Circuits
22
SLC Out
NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
23
A Fault Isolator Module on both sides of a device, or the combination of an Isolator Base and Isolator Module are required to comply with NFPA Style 7 requirements.
CAUTION: If relay or sounder bases are not used, a maximum of 25 addressable devices can be connected between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum number of addressable devices that can be connected between Isolators is reduced to seven. Isolator modules will not function properly when these limits are exceeded. When more than 100 Isolator Modules and/or Isolator Bases are connected from the MICRO-400 to an SLC loop, the address capacity of the loop is reduced by two (2) addresses for every isolator device in excess of 100. The address capacity of the loop is reduced by two (2) addresses for every isolator device in excess of 200 when the Isolator Modules and/or Isolator Bases are connected to the SLC loop from the MICRO-320, MICRO-640I/E or MICRO-200I.
IN IN OUT
SLC-isowire.cdr
OUT
SLC
24
Detector 1 Detector 5 Z
Detector 2 Y
Detector 3
SLC-isowork.wmf
Control Panel
Isolator Base
Non-Isolating Device
Short-circuit path
NOTE: For information on wiring an isolator base, refer to Figure 9.3, Wiring an Isolator Base on page 44.
25
26
SLC-style4iso.cdr
B B+
Isolator Module
Isolator Module
Section C
Section A
Isolator Module
Additional isolator module required when first device in the section is more than 20 feet from the control panel.
Isolator Module
Isolator Module
The first isolator module on SLC Out and SLC Return is optionalfor MICRO-320, MICRO-640/e, MICRO-300I or MICRO-400I because the panels provide the functionality.
Isolator Module
SLC Out MICRO-200I: The first isolator module on SLC Out and SLC Return must be contained within the same enclosure as the FACP, or these isolator modules must be connected within 20 ft. (6.1 m) of the FACP enclosure in conduit.
SLC Return
Control Panel
SLC-style6iso.cdr
27
Isolator Module
Isolator Module
Addressable Detector
Isolator Module
Isolator Module
Isolator Module
The first isolator module on SLC Out and SLC Return is optionalfor MICRO-320, MICRO-640/e, MICRO-300I or MICRO-400I because the panels provide the functionality. SLC Out SLC Return
Isolator Module
Control Panel
28
SLC-style7iso.cdr
MICRO-200I: The first isolator module on SLC Out and SLC Return must be contained within the same enclosure as the FACP, or these isolator modules must be connected within 20 ft. (6.1 m) of the FACP enclosure in conduit.
Rotary Switches IDC Return 9 IDC Return 8 IDC Out 7 IDC Out 6 SLC SLC+ 24 VDC 24 VDC +
On addressable monitor modules in FlashScan mode with MICRO-320, MICRO640/E , pins 3 & 4 can be jumpered to enable the fire panels Communication Loss (Degraded mode) feature.
SLCModule-simplified.wmf
29
Monitor Modules
Description
{ {
9 H 8 H+ 7L+ 6L
ADDRESS LOOP
0 1
TENS
9 8 7 6
2 3 4 5
Label Use to record the device address and SLC number. SLC (+) Red
FMM-101.cdr
ONES
30
SLCDualMod-simplified.wmf
SLC SLC+
Monitor Modules
5 4 3 2
10 ONES
Dual monitor modules: On dual monitor modules, only even numbers appear on the ONES rotary switch. The module takes both the selected address and the next-higher address.
SLC-setadd.cdr, SLCbrktabs.cdr
Breakaway Tab - Modules come with a raised breakaway tab on the TENS rotary switch. This tab must be removed when the module is on an FACP that uses more than 99 addresses.
31
Monitor Modules
Refer to the Device Compatibility Document for compatible smoke detectors. See Power Considerations on page 47 for information on supervising 24 VDC power.
From Supply 24 VDC Four-wire Detector Base
SLC-idcB1.wmf
IDC FlashScan only: Jumper terminals 3 and 4 to enable the fire panels Communication Loss (Degraded mode) feature.
32
Monitor Modules
3. 4.
From Supply 24 VDC Four-wire Detector Base Manual pull station To Next IDC or Supervision Device SLC
Heat detector
SLC-idcD1.cdr
IDC
FlashScan only: Jumper terminals 3 and 4 to enable the fire panels Communication Loss (Degraded mode) feature.
33
Monitor Modules
3.
SLC
34
Monitor Modules
3.
IDC
SLC-idcB2.wmf
90 mA External 24 volt supply required 24 VDC Resettable power. (Resettable power is not necessary for MICRO-320 or MICRO640/E when operating in FlashScan mode.)
35
Monitor Modules
Typical Style B IDC Wiring with FZM-1NFPA Style D IDC Using Zone Interface Modules
6.7
Interface Modules
Connect the SLC wiring to the FZM-1 module terminals 1 () and 2 (+). Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Figure 6.8 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using the FZM-1 zone interface module . Module installation notes: 1. 2. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps @ 24 VDC (nominal). The IDC provides the following services (do not mix): Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervisory service with normally open contact devices Security service Refer to the Device Compatibility Document for compatible smoke detectors.
3.
SLC FZM-1
IDC
SLC-idcD2.wmf
24 VDC Resettable power. (Resettable power is not necessary for MICRO-320 or MICRO-640/E when operating in FlashScan mode.)
Figure 6.8 Typical Style D IDC Wiring with the FZM-1 Figure 6.9
36
Style Z NAC (+) Style Z NAC () Style Y/Z NAC () Style Y/Z NAC (+) SLC () SLC (+)
SLCModule-simplified.wmf
Label
The label must be cut and removed from over the recessed area to access the resistor.
FMM-1back.cdr
This resistor must be removed when supervising 24VDC NAC power using the no-relay alternative wiring (see Appendix A.2.2, Using the Addressable Control Module Without Relay).
Remove the resistor, then place a piece of tape over the recessed area.
37
Control Modules
A power supervision relay is required only on the last module of the power run.
NAC
38
SLC-nacY.wmf
Control Modules
See Power Considerations on page 47 for information on supervising 24 VDC power. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns). A power supervision relay is required only on the last module of the power run.. Do not T-Tap or branch a Style Z circuit. Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device. Refer to the Device Compatibility Document for compatible notification appliances and relays.
SLC
NAC Return NAC Out A power supervision relay is required only on the last module of the power .
39
SLC-nacZ.wmf
Control Modules
0 1 2 3 4
Brown
6 5
LOOP
(Use with Type Code Rel Ckt ULC, or see Circuit Requirement 3.)
ADDRESS
FCM-1
Figure 7.5 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module Circuit Requirements. When connecting a releasing device to the FCM-1 module, note the following: 1. 2. Refer to your FACPs Programming Manual for instructions on setting the Soak Timer. For applications using power-limited circuits: a) Use an End-of-Line device (P/N REL-47K) with the FCM-1 module. Connect the End-ofLine device as shown in Figure 7.5. b) Program the releasing circuit for Type Code REL CKT ULC. c) Circuits are supervised against opens and shorts. For applications not requiring power-limited circuits a) End-of-Line devices (P/N REL-47K) are not required; however, the releasing device circuit is not supervised against shorts. b) In non-power-limited applications, program the releasing circuit for Type Code RELEASE CKT c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit. d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit device wiring and any power-limited circuit wiring.
3.
The FCM-1 module must be programmed with the correct releasing type code listed in your FACPs Programming Manual.
40
For more information on the module specifications refer to the Installation Instructions provided with this device. For information on transponders, refer to the specific transponder manual. Setting an SLC Address Each relay module is factory preset with an address of 00. To set an SLC address refer to Section 6.2, Setting an SLC Address for a Module, on page 31.
C NC NO C NC NO
SLC-frmC.wmf
41
NOTE: The B710LP base wiring is identical to the B501, except there is no shield terminal.
42
SLC-B501wire.wmf
B710HDHARSH detector) connected to an SLC. An optional RA400Z Remote LED Annunciator is shown connected to the base.
SLC To next device on SLC
NOTE: Use a spade lug to wire the Remote LED Annunciator () to Terminal 2 ().
43
SLC In
Conduit
SLC-224BIwire.wmf
SLC
44
b224rb.wmf
4 5 3
IN -3
21
External supply 2 +1
Class A Optional Wiring Optional Sounder Interconnect* SLC B+ UL-listed Compatible FACP SLC B-
(-) Power
B501BHWiring.wmf
45
+
SLC
46
SLC-nbg12.cdr
Where: Rmax = maximum resistance of the 24 VDC wires Vms = minimum supply voltage (see Table A.1 below) Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current Nb = number of Notification Appliance Devices Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by Chemetron and Notifier power supplies are listed below:
FACP MICRO-200I MICRO-640/E KAPS-24 on MICRO-320 Vms 19.4 19.15 20.16V Power Supply FCPS-24/E FCPS-24S6/FCPS-24S8 MPS-24A/E MPS-24B/E MPS-400 ACPS-2406/E Vms 19.1 19.1 19.6 20.1 19.23 19.8
47
Power Considerations
Figure A.1 Supervised 24 VDC Circuit Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit
48
SLC-psr.cdr
Power Considerations
End-of-line Resistor
FCM-1
Note: Drawing shows power wiring only; SLC Wiring not shown.
SLC-nacY1.cdr
49
Power Considerations
FCM-1
SLC-nacZ1.cdr
Note: Drawing shows power wiring only; SLC Wiring not shown.
50
Secondary Surge Protectors: DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Largo, FL 33771 (800) 753-2345. SLCP-30: EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029 PLP-42N: Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800) 727-9119
NOTE: For detailed information refer to the installation documentation supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. Install primary protection only as shown in this document. Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC wiring at the building entry/exit. Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1
P P = Primary S = Secondary P
Surge Suppressor
P FACP S P S
SLC-ssbuild1.cdr
51
Installation
B.2 Installation
Mounting of the secondary surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use. Locate on an available stud and secure with nut. Unit is connected in series with the SLC Loop to protect the Control Panel. Provide a common ground to eliminate the possibility of a differential in ground potentials.
B.2.1 MICRO-300I/MICRO-400I
DTK-2LVLP-F Connections
2LVLP-F
IN
OUT
SLC Loop
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4
OUTPUT
INPUT
L3
L2
L1
L1
L2
L3
L4
PLP-42N
OUTPUT
INPUT
L3
L2
L3
+
SLC Loop
GRND
L4
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection
52
SLC-plpn2.cdr
L1
L1
L2
SLC-lvlp2.cdr
Installation
SLCP-30 Connections
SLCP-30
IN
OUT
SLC Loop +
SLCP-30
IN
OUT
B.2.2 MICRO-640I
DTK-2LVLP-F Connections
2LVLP-F
+ + IN OUT
SLC-slcp2.cdr
NOTE: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
PLP-42N
GRND
L4 L4
L1
L1
OUTPUT
INPUT
L3
L2
L2
L3
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection. Do not connect shield (if present) to surge protector or fire panel.
SLC-plpn3.cdr
SLC-lvlp3.cdr
53
Installation
SLCP-30 Connections
SLCP-30
+ + IN OUT
NOTE: Do not connect shield (if present) to surge protector or fire panel.
54
SLC-slcp3.cdr
Notes
55
Index
Numerics
24 VDC power 4749 alternate method of supervising 49 monitoring and switching NAC power 37 devices addressable 24 auxiliary 10 isolator 24 maximum number between isolators 24 SLC capacity 12 supervised 48 dry contact ratings 41 dry-contact 10 DTK-2LVLP-F 51 dual monitor module 10, 30, 34 duplicate addressing 34
A
A77-716B Replaced by EOLR-1 See power supervision relay ACPS-2406 12 ACPS-2406/E 47 address capacity 24 addressable devices 24 addressable modules 10, 29 analog intelligent devices 9 auxiliary devices 10
E
electrical interference 14 End-of-Line-Resistor 38, 49, 50 EOLR-1 See power supervision relay
B
B224BI, see isolator bases B501 42 B710HD 11 B710LP 42 backup alarm, see degraded mode bases 11 building entry/exit 51
F
FACP, see Fire Alarm Control Panels factory preset 31 FAPT-751 11 FAPT-851 11 fault 13, 25, 27 fault condition 24 Fault Isolator Module, see isolator module FCM-1 37, 38, 39, 40, 48, 49, 50 FCPS-24 47 FDM-1, see dual monitor module Fire Alarm Control Panels 7, 51 Fire alarm service 32, 33, 34, 35, 36 FlashScan 9, 13, 25 floating segments 21 FMM-1, see monitor module FMM-101, see miniature monitor module Form-C contacts 41 four-wire configuration 39 FRM-1, see Relay modules FSB-200, FSB-200S 11 FSI-751 11 FSI-851 11 FSL-751 12 FSP-751/T 11 FSP-851/T 11 FST-751/R 11 FST-851/R 11 FZM-1, see zone interface module 29 FZM-1, see zone interface module
C
cabinet 19 circuit fault 10 circuit, speaker/telephone 10 CLIP (Classic Loop Interface Protocol) 9, 13 coded output 49, 50 common ground 52 communications loop 25 conduit, types of 1921 connector screw 19 connectors, crimp-on 52, 53 control modules 10 CPX-551 11 CPX-751 11
D
DC resistance 15 degraded mode 10, 29, 32, 33 detector bases list of 11 see also isolator bases detectors 24 VDC 48 listing 11
G
general alarm 49, 50
Chemetron SLC Wiring Manual P/N 52217:B 01/02/2007
56
Index
HR
H
HARSH 43
I
IDC, see Initiating Device Circuits Initiating Device Circuits 10, 2936 integral relay 24 IPX-751 Discontinued December 1, 2001 isolator bases 11, 24, 25, 28 how they work 25 wiring 44 isolator devices 24 isolator modules 10, 27, 28 how they work 24 wiring of 24
relay 10 monitor module 10, 29, 32, 33 dual see dual monitor module miniature, see miniature monitor module zone interface see zone interface module MPS-24A 47 MPS-24B 47 MPS-400 47 multiplex subsystem 11
N
NAC 10 NAC power 37, 50 wiring 49 NAC terminal block 49 NBG-12LX 46 NEC Article 800 51 NFPA Style 4 wiring 22 NFPA Style 6 wiring 23 with isolator modules 27 NFPA Style 7 24 with isolator device 28 NFPA Style B IDC wiring 32, 34, 35 NFPA Style D IDC wiring 33, 36 NFPA Style Y 37 wiring 38 NFPA Style Z 37 wiring 39 normally closed contacts 48 Notification Appliance Circuit 10, 49 see also NAC notification appliances 48
J
junction box 20
K
key-lock reset 46
L
LED Annunciator, remote 42, 43 LED operation 13 LEM-320 on MICRO-640I 14, 18 local building code 51 Loop Resistance 14, 15 Style 6 & 7 16 loops 17 LPX-751/L 12
P
PLP-42N 51 Polling Protocols 9 power run 47, 48 power supervision relay 38, 39, 48 power supplies 47 power-limited 49 proper gauge wire 47 pull stations 12, 28 addressable manual, wiring 46
M
metal conduit 20, 27 MICRO-200I 7, 15, 18 MICRO-300I, MICRO-400I 15 MICRO-300I/MICRO-400 7 MICRO-300I/MICRO-400I 18 MICRO-320 7 MICRO-640I 14, 18 MICRO-640I/E 7 Miniature monitor module 30 module circuits, configuring 29 modules addressable 10 control 10 isolator 10 monitor 10
R
RA400Z 42, 43 ratings, dry contact 41 relay bases 11, 24 relay module 10, 41 wiring 41 Releasing Device
57
SZ
Index
FCM-1 Connections 40 remote switching center 11 RFX Wireless Interface (Discontinued as of Dec. 31, 2005) 12 rotary switches 31, 34, 35, 36
S
SDRF-751 12 Security service 32, 33, 34, 35, 36 shield 54 shield drain wire 19 shielded wire 20 shield-termination 19 short circuit 24, 25 Signaling Line Circuit 9 see also SLC SLC capacity of devices 12 performance 13 setting an SLC address 31 terminal block 20 trouble conditions 13 wiring 32, 33, 34, 35, 36 SLC-30 51 sounder bases 11, 24 speaker circuit 10 Sprinkler supervision 32, 33, 34, 35, 36 standard bases 11 Style 4, Style 6, Style 7, Style B,Style D, Style Y, Style Z see NFPA Style 22 supervised circuits 48, 49 supervised devices 48 suppressors, surge 51 surge protector 9, 51
32, 33, 34, 35, 36 wire length four-wire SLC 17 two-wire SLC 16 wire nuts 20 wire size 14 wiring isolater bases 44 isolator modules 24 NACs 49 pull stations 46 relay modules 41 SLCs 32, 33, 34, 35, 36 wiring pair 51 wiring style requirements 13
X
XP Series Transponders 11 XP5-C Transponder 10 XP5-M Transponder 10
Z
zone interface module 10, 29, 35, 36
T
telephone circuit 10 terminal block, NAC 50 termination of shield 19 transponders 11 trouble conditions 13, 24 trouble warning 25 T-tapping 15, 22, 23, 27, 28 twisted shielded pair wiring 14 twisted unshielded pair wiring 14 twisted-pair wire 20 two-wire configuration 38 two-wire detectors 48
V
VIEW 12
W
Waterflow alarm service, automatic and manual
58
Limited Warranty
The manufacturer warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. The manufacturer does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than the manufacturer or as expressly authorized by the manufacturer in writing, or is serviced by anyone other than the manufacturer or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department. This writing constitutes the only warranty made by the manufacturer, with respect to its products. The manufacturer, does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer, is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident. THE MANUFACTURER GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURERS PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.