NIVEAU-MESSTECHNIK AG

Installation and Operation Manual MD-...


Circuit diagram
Level Sensor
blue brown black

Output 0/4 ... 20mA +

9-

10+

12

13

15

16

Power supply

Relay K2

Relay K1

Dimensions
45
1 2 3 4 5 6 7 8

110

MD

K1 K2 A

9 10 11 12 13 14 15 16

Manual MD-...

Niveau-Messtechnik AG

75

1
MD Manual.DOC / 01.07.99

We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.

NIVEAU-MESSTECHNIK AG

Parameter Settings
Defaults:
Display: Analogue output: Press approx. 5 sec Enter code 955 0 100% 4 20 mA CodE 100 CodE 955 RAnG Corr xxx

P P

Confirm selection Settings menu Change settings

Confirm new settings and go on to next parameter. After all parameters are selected, the unit will switch back to measurement mode. For available parameters please see below.

Parameter
Cable compensation Display lower limit Display upper limit Direct set point access Configuration analogue output (depending on type ordered) OFF: 0...20 mA ON: 4...20 mA Analogue output lower limit Analogue output upper limit Position of decimal point

Display Range
Corr InLo Inhi Lusr Con.A -999...3000 -999...9999 -999...9999 ON ... OFF ON ... OFF

Default
0 0 100 ON ON

AnLo Anhi DEC.P

Dependent on display settings Dependent on display settings 00...03

0 100 1 (0.1)

Parameters not shown in above list are not applicable for a level sensing application.

Manual MD-...

2
MD Manual.DOC / 01.07.99

We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.

NIVEAU-MESSTECHNIK AG

Switch point settings


Defaults:
Switch points: Hysteresis: Press approx. 5 sec Enter code 55 0% 1% CodE 100 CodE 55 PArA xxx xxx

P P

Confirm selection Settings menu Change settings

Confirm new settings and go on to next parameter. After all parameters are selected, the unit will switch back to measurement mode. For available parameters please see below.

Parameter
K1 set point absolute (referring to display value) Hysteresis K2 set point absolute (referring to display value) Hysteresis

Display Range
LA.1 HY.1 LA.2 HY.2 0-9999 1...2000 0-9999 1...2000

Default
0 1 0 1

If direct set point access is ON (see page 2) then LA.1 can be accessed directly from measurement mode by pressing

. Use function keys as indicated above to

change set points and to switch between LA.1, LA.2, and measurement mode.

Manual MD-...

3
MD Manual.DOC / 01.07.99

We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.

NIVEAU-MESSTECHNIK AG

Relay settings
Defaults:
Direct set point access: Press approx. 5 sec Enter code 855 CodE 100 CodE 855 CFG xxx xxx active

P P

Confirm selection Settings menu Change settings

Confirm new settings and go on to next parameter. After all parameters are selected, the unit will switch back to measurement mode. For available parameters please see below.

Parameter
K1 set point 00 output not active 01 NO 04 NC K2 set point 00 output not active 01 NO 04 NC Automatic

Display Range
LI.1 00...13

Default
01

LI.2

00...13

01

Auto

NA

NA

NIVEAU-MESSTECHNIK AG

Im Kohlstatterfeld 17 Tel: (+49) 6263/87-0 http://www.ksr-kuebler.com


Manual MD-...

D-69439 Zwingenberg Fax: (+49) 06263/87-99 e-mail: info@ksr-kuebler.com


4
MD Manual.DOC / 01.07.99

We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.