Power supply
Relay K2
Relay K1
Dimensions
45
1 2 3 4 5 6 7 8
110
MD
K1 K2 A
9 10 11 12 13 14 15 16
Manual MD-...
Niveau-Messtechnik AG
75
1
MD Manual.DOC / 01.07.99
We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.
NIVEAU-MESSTECHNIK AG
Parameter Settings
Defaults:
Display: Analogue output: Press approx. 5 sec Enter code 955 0 100% 4 20 mA CodE 100 CodE 955 RAnG Corr xxx
P P
Confirm new settings and go on to next parameter. After all parameters are selected, the unit will switch back to measurement mode. For available parameters please see below.
Parameter
Cable compensation Display lower limit Display upper limit Direct set point access Configuration analogue output (depending on type ordered) OFF: 0...20 mA ON: 4...20 mA Analogue output lower limit Analogue output upper limit Position of decimal point
Display Range
Corr InLo Inhi Lusr Con.A -999...3000 -999...9999 -999...9999 ON ... OFF ON ... OFF
Default
0 0 100 ON ON
0 100 1 (0.1)
Parameters not shown in above list are not applicable for a level sensing application.
Manual MD-...
2
MD Manual.DOC / 01.07.99
We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.
NIVEAU-MESSTECHNIK AG
P P
Confirm new settings and go on to next parameter. After all parameters are selected, the unit will switch back to measurement mode. For available parameters please see below.
Parameter
K1 set point absolute (referring to display value) Hysteresis K2 set point absolute (referring to display value) Hysteresis
Display Range
LA.1 HY.1 LA.2 HY.2 0-9999 1...2000 0-9999 1...2000
Default
0 1 0 1
If direct set point access is ON (see page 2) then LA.1 can be accessed directly from measurement mode by pressing
change set points and to switch between LA.1, LA.2, and measurement mode.
Manual MD-...
3
MD Manual.DOC / 01.07.99
We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.
NIVEAU-MESSTECHNIK AG
Relay settings
Defaults:
Direct set point access: Press approx. 5 sec Enter code 855 CodE 100 CodE 855 CFG xxx xxx active
P P
Confirm new settings and go on to next parameter. After all parameters are selected, the unit will switch back to measurement mode. For available parameters please see below.
Parameter
K1 set point 00 output not active 01 NO 04 NC K2 set point 00 output not active 01 NO 04 NC Automatic
Display Range
LI.1 00...13
Default
01
LI.2
00...13
01
Auto
NA
NA
NIVEAU-MESSTECHNIK AG
We reserve the right to make modifications without prior notice and no guarantee of the accuracy of information contained herein is given.