Sei sulla pagina 1di 19

Issued November 2009

12486

DATA SHEET

GV2ME & GV2P MOTOR CIRCUIT BREAKER


Based on Schneider DIA1ED2090201EN Catalogue

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers

12486

1 2

Circuit-breaker type Conforming to standards

Environment

GV2 ME GV2 P IEC 60947-1, 60947-2, 60947-4-1, EN 60204, UL 508, CSA C 22.2 n 14-05, NF C 63-650, 63-120, 79-130, VDE 0113, 0660

GV3 P IEC/EN 60947-1, 60947-2, 60947-4-1, UL 508 type E, CSA C 22.2 n 14-05 type E

GV3 ME80 IEC/EN, NF EN, BS EN, DINEN60947-2, 60947-4-1

Product certifications

3
Protective treatment Degree of protection Conforming to IEC 60529 Open mounted In enclosure

UL, CSA, CCC, CEBEC, GOST, TSE, BV, GL, LROS , DNV, PTB, EZU, SETI, RINA, ATEX TH IP 20 GV2 Mp01: IP 41 GV2 Mp02: IP 55 30 gn -11 ms

UL (1), CSA, PTB, EZU, GOST, TSE, DNV, LROS, GL, BV, RINA, CCC, ATEX

UL, CSA, CCC (pending), GOST, ATEX (pending)

UL, CSA, LROS

GV7 R IEC 60947-1, 60947-2, 60947-4-1, EN 60947-1, 60947-2, EN 60947-4-1, NF C 63-650, NF C 63-120, 79-130, VDE 0113, 0660 UL, DNV, CCC

TH IP 20

TC IP 20

4
Shock resistance Vibration resistance

GV3 PC01 and GV3 CE01: GV3 PC02: IP 55 IP 55 22 gn - 20 ms 2.5 gn (025 Hz) - 40+ 80 - 20+ 60 - 20+ 40 - 20+ 60 - 20+ 40 960 3000 0.5

TC IP 405 with terminal shrouds

Conforming to IEC 60068-2-27 Conforming to IEC 60068-2-6 Storage Operation C C C C C C m J

5 6 7 8 9 10

Ambient air temperature

Open mounted In enclosure Temperature compensation Open mounted In enclosure Flame resistance Conforming to IEC 60695-2-1 Maximum operating altitude Suitable for isolation Conforming to IEC 60947-1 7-1-6 Resistance to mechanical impact

Sensitivity to phase failure Circuit-breaker type Utilisation category

On: 15 gn -11 ms Off: 30 gn -11 ms 5 gn (5150 Hz) 4 gn (5300 Hz) - 40+ 80 - 40+ 80 - 40+ 80 - 20+ 60 - 20+ 60 - 20+ 60 (2) - 20+ 40 - 20+ 40 - 20+ 40 - 20+ 60 - 20+ 60 - 20+ 60 - 20+ 40 - 20+ 40 - 20+ 40 960 960 2000 3000 Yes Yes 0.5 0.5 10 IK 04 IK 09 (in enclosure) Yes, conforming to IEC 60947-4-1 7-2-1-5-2 GV2 ME GV2 P A AC-3 690 690 600 50/60 6 2.5 100 000 GV2 RT GV3 P A AC-3 690 690 600 50/60 6 8 50 000 GV3 ME80 A AC-3 690 690 600 (B600) 50/60 6 8 30 000

15 gn -11 ms 2.5 gn (25 Hz) - 55+ 95 - 25 + 70 - 25 + 55 (3) 960 2000 Yes 0.5

Technical characteristics

Conforming to IEC 60947-2 Conforming to IEC 60947-4-1 Rated operational voltage Conforming to IEC 60947-2 (Ue) Rated insulation voltage Conforming to IEC 60947-2 (Ui) Rated voltage Conforming to CSA C22-2 n 14, UL 508 Rated operational Conforming to IEC 60947-4-1 frequency UL, CSA Rated impulse withstand Conforming to IEC 60947-2 voltage (U imp) Total power dissipated per pole Mechanical durability (C.O.: Close, Open) Electrical durability 440 V In/2 for AC-3 duty 440 V In Duty class (maximum operating rate) Maximum conventional Conforming to IEC 60947-4-1 rated thermal current (Ith) Rated duty Conforming to IEC 60947-4-1

V V V Hz kV W C.O. C.O. C.O. C.O./h A

GV7 Rp20... Rp100 A AC-3 690 750 600 50/60 8 5 50 000

GV7 Rp150

GV7 Rp220

8.7 40 000

14.5 20 000

100 000 30 000 50 000 40 000 20 000 50 000 30 000 20 000 10 000 25 25 25 25 0.16 0.16 0.40 13 80 12 150 220 32 32 23 65 100 Continuous duty (1) UL 508 type E for GV2 PppH7 (2) Leave a space of 9 mm between 2 circuit-breakers: either an empty space, or side mounting addon contact blocks. Side by side mounting is possible up to 40 C. (3) For operation up to 70 C, please consult your Regional Sales Office.

Based on Schneider DIA1ED2090201EN Catalogue

Page 1 of 18

Characteristics (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers

12486

Mounting characteristics
Operating position Without derating, in relation to normal vertical mounting plane (1)
90 90

1 2 3

0 90

90

Connection characteristics
Bare cables

Connection to screw clamp terminals or spring terminals

Circuit-breaker type Connection to screw clamp terminals (2) Solid cable (Max. number of conductors x c.s.a.) Flexible cable without cable end Flexible cable with cable end Tightening torque Connection to spring terminals Number of conductors x c.s.a. Solid cable Flexible cable without cable end

mm2 mm2 mm2 N.m mm2 mm2

GV2 ME Min. 2x1 2 x 1.5 2x1 1.7 2 x 1 (3)

Max. 2x6 2x6 2x4 1.7 2x6

GV2 P Min. 2x1 2 x 1.5 2x1 1.7

Max. 2x6 2x6 2x4 1.7

GV3 P Min. 2x1 2x1 2x1 5

Max. 1 x 25 and 1 x 35 1 x 25 and 1 x 35 1 x 25 and 1 x 35 5: 25 mm2 8: 35 mm2

GV3 ME80 Min. Max. 1 x 2.5 1 x 35 1 x 2.5 1 x 2.5 5 2 x 16 2 x 16 5

4 5 6 7 8 9 10

2 x 1.5 (3) 2 x 4

Connection by bars or lugs


Bars or lugs

6
d

e
Circuit-breaker type Pitch Without spreaders With spreaders Bars or cables with lugs e L L d Screws Tightening torque Bare cables (copper or aluminium) with connectors Height (h) C.s.a. Tightening torque N.m mm mm2 N.m mm mm mm mm mm mm

L
GV3 Ppp6 17.5 y6 y 13.5 y 16.5 y 10 M6 6

L
GV7 Rp20...Rp100 35 45 y6 y 25 y 10 M6 10 20 1.5...95 15

L'
GV7 Rp150 35 45 y6 y 25 y 10 M8 15 20 1.5...95 15 GV7 Rp220 35 45 y6 y 25 y 10 M8 15 20 1.5...185 15

GV2 MEpp6 13.5 y6 y 9.5 y 9.5 y 10 M4 1.7

(1) When mounting on a vertical rail, fit a stop to prevent any slippage. (2) For motor circuit-breakers GV3 P: BTR hexagon socket head screws, EverLink system. Require use of an insulated Allen key, in compliance with local electrical wiring regulations. (3) For cross-sections 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.

Based on Schneider DIA1ED2090201EN Catalogue

Page 2 of 18

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Breaking capacity of GV2 ME and GV2 P

1 2 3 4

Circuit-breaker type

Rating Breaking capacity conforming to IEC 60947-2 230/240 V Icu Ics % (1) 400/415 V Icu Ics % (1) 440 V Icu Ics % (1) 500 V Icu Ics % (1) 690 V Icu Ics % (1)

A kA

GV2 ME 01 07 08 to 06 0.1 2.5 4 to 1.6 g g g g g g

10

14

16 14 g g

20 18 g g

6.3 10 g g g g

21 & 22 23 & 25 50

32 32 50

GV2 P 01 07 08 to 06 0.1 2.5 4 to 1.6 g g g g g

10

14

16 14 g g

20 18 g g

6.3 10 g g g g

21 & 22 23 & 25 g g

32 32 g g

100 100 g 15 40 6 50 4 75 3 75 80 10 50 6 50 4 75 3 75 g g

kA

g g

g g

g g

g g

g g

15 50 8

15 50 8 50 6 75 3 75 g g

g g

g g

g g

g g

g g

50 50 20 75 10 75 4

50 50 20 75 10 75 4

50 50 20 75 10 75 4

kA

g g

g g

g g

50

15

g g

g g

g g

g g

g g

50 75 42

100 100 50 50 10 6

kA

g g

g g

g g

g g

g g

g g

g g

50

100 100 75 3 75 g g 3 75 g g 3 75 g g

100 75 6 6

kA

g g

3 75 g g

3 75 g g

g g

100 100 100 100 100 100 100 100 g g g g g g g g g g g g g g g g

5 6

Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2

230/240 V

aM gG

A A A A A A A A A A

g g

80 g

100 100 g 80 80 g

400/415 V

aM gG

g g

g g

g g

g g

g g

63 80 50 63 50 63 40 50

63

g g

g g

g g

g g

g g

100 100 100 125 125 125 63 80 80

80 100 100 g 50 63 50 63 40 50 63 80 50 63 40 50 63 80 50 63 40 50 g g

440 V

aM gG

g g

g g

g g

50 63 50 63 32 40

50 63 50 63 32 40

g g

g g

g g

g g

50 63 50 63 50 63

80 100 100 50 63 50 63 50 63 50 63 50 63 50 63

7 8 9 10

500 V

aM gG

g g

g g

g g

g g

g g

g g

g g

50 63 40 50

690 V

aM gG

g g

16 20

25 32

g g

20 25

25 32

40 50

g > 100 kA. (1) As % of Icu.

Based on Schneider DIA1ED2090201EN Catalogue

Page 3 of 18

Characteristics (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Breaking capacity of GV2 ME and GV2 P (used in association with current limiter GV1 L3)
Circuit-breaker type Rating Breaking capacity conforming to IEC 60947-2 230/240 V Icu Ics % (1) 400/415 V Icu Ics % (1) 440 V Icu Ics % (1) 500 V Icu Ics % (1) Circuit-breaker type Rating Breaking capacity conforming to IEC 60947-2 230/240 V Icu Ics % (1) 400/415 V Icu Ics % (1) 440 V Icu Ics % (1) 500 V Icu Ics % (1) 690 V (3) Circuit-breaker type Rating Cable protection against thermal stress in the event of short-circuit (PVC insulated copper cables) Minimum c.s.a. protected at 40 C at Isc max. 1 mm2 1.5 mm2 2.5 mm2 46 mm2 A Icu = Ics kA kA kA kA A kA kA kA kA A kA GV2 ME 01 to 06 07 0.1 to 2.5 1.6 g g g g g g g g g g g g g g g g 08 4 g g g g g g g g 10 6.3 g g g g g g g g 14 10 g g g g g g 50 100 16 14 g g 100 50 50 75 42 100 20 18 g g 100 50 20 75 10 75 21 23 g g 100 40 20 75 10 75 22 25 g g 100 40 20 75 10 75 32 32 g g 100 40 20 75 10 75

1 2 3 4 5 6 7 8 9 10

GV2 P 01 to 06 07 0.1 to 2.5 1.6 g g g g g g g g g g g g g g g g g 50

08 4 g g g g g g g g 50

10 6.3 g g g g g g g g 50

14 10 g g g g g g 100 50 50

16 14 g g g g 100 50 100 50 50

20 18 g g g g 100 50 100 50 50

21 23 g g g g 100 50 100 50 50

22 25 g g g g 100 50 100 50 50

32 32 g g g g 100 50 100 50 50

GV2 ME 01 to 06 07 0.1 2.5 to 1.6 p p p p p p p p

08 4 p p p p

10 6.3

14 10

16 14 (2)

20 18 (2) (2) p p

21 23 (2) (2) p p

22 25 (2) (2) p p

32 32 (2) (2) (2) p

y 10 kA y 6 kA

y 20 kA y 10 kA (2) p p p p p p

g > 100 kA p Cable c.s.a. protected (1) As % of Icu (2) Cable c.s.a. not protected (3) With limiter LA9 LB920

Based on Schneider DIA1ED2090201EN Catalogue

Page 4 of 18

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers
Electric trips

12486

Characteristics of electric trips

1 2 3 4 5 6 7 8 9 10

Circuit-breaker type Type of trip Rated insulation voltage (Ui)

Conforming to IEC 60947-1

GV2 ME, GV2 P GV3 P, GV3 L GV AU GV AS 690 690 600 0.85 1.1 Un 0.7 0.35 Un 12 8 3.5 1.1 600 0.7 1.1 Un 0.75 0.2 Un 14 10.5 5 1.6

GV2 ME only GV AX (1) 500 0.85 1.1 Un 0.7 0.35 Un 12 8 3.5 1.1

GV3 ME80 GV3 B 690 GV3 D 690

GV7 R GV7 AU 690 GV7 AS 690 600 0.7 1.1 Un 0.2 0.75 Ue

Operational voltage Drop-out voltage Inrush consumption

Conforming to CSA C22-2 n 14, V UL 508 Conforming to IEC 60947-1 V V a c VA W VA W

600 (B600) 600 (B600) 600 0.81.1 Un 0.70.35 Un 12 7 7 2.5 0.85 1.1 Un 0.35 0.7 Ue < 10 <5 <5 <5

Sealed consumption

a c

Operating time

Conforming to IEC 60947-1 ms

From the moment the voltage reaches its operational value until opening of the circuit-breaker. 1015 10 15 < 50 100 % 100 % 1 or 2 12.5 0.752.5 0.752.5 1.2 100 % 1 1.5 1.5 1 1.2

On-load factor Cabling Number of conductors Solid cable Flexible cable without cable end Flexible cable with cable end Tightening torque Mechanical durability (C.O.: Close - Open) mm2 mm2 mm2 N.m C.O.

2 or 4 12.5 0.752.5 0.751.5 1.4 max

30 000 (GV2 ME and GV2 P) 50 % of the mechanical durability of the 10 000 (GV3 P and GV3 L) circuit-breaker (1) Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only.

Based on Schneider DIA1ED2090201EN Catalogue

Page 5 of 18

Characteristics

TeSys protection components


Thermal-magnetic and magnetic motor circuit-breakers GV2 and GV3
Accessories

12486

Characteristics of 3-pole busbars GV2 Gppp and GV3 Gp64


Rated insulation voltage (Ui) Conventional thermal current (Ith) Permissible peak current (I peak) Permissible thermal limit (I2t) Degree of protection Terminal block Conforming to IEC 60947-1 Conforming to IEC 60439-1 V A kA kA2s Conforming to IEC 60529 GV2 Gppp 690 63 11 104 IP 20 Yes GV3 Gp64 690 115 20 300 IP 20

1 2 3 4 5

Characteristics of terminal blocks GV2 G05 and GV1 G09 (for GV2 ME and GV2 P)
Rated insulation voltage (Ui) Conventional thermal current (Ith) Degree of protection Connection Conforming to IEC 60947-1 Conforming to IEC 60439-1 Conforming to IEC 60529 Solid cable Flexible cable without cable end Flexible cable with cable end Flexible or solid cable AWG Tightening torque Connector Screw clamp terminals N.m N.m mm
2

V A

690 63 IP 20 1 x 1.5 to 25 conductor or 2 x 1.5 to 6 conductors 1 x 1.5 to 16 conductor or 2 x 2.5 to 4 conductors 1 x 1.5 to 10 conductor or 2 x 1.5 to 2 conductors 1 AWG 4 2.2 1.7

mm2 mm
2

Characteristics of current limiters (GV2 ME and GV2 P)


Type Rated insulation voltage (Ui) Conventional thermal current (Ith) Operating threshold Connection Solid cable Flexible cable without cable end Flexible cable with cable end Tightening torque mm2 mm2 mm2 N.m Conforming to IEC 60947-1 Conforming to IEC 60947-1 rms current V A A GV1 L3 690 63 1500 (non adjustable threshold) 1 conductor 1.525 1.525 1.516 2.2 2 conductors 1.510 2.510 1.5 4 LA9 LB920 690 63 1000 (non adjustable threshold) 1 conductor 1.525 1.525 1.516 2 conductors 1.510 1.510 1.5 4

6 7 8 9 10

Based on Schneider DIA1ED2090201EN Catalogue

Page 6 of 18

Curves

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Thermal-magnetic tripping curves for GV2 ME and GV2 P

1 2 3 4

Average operating times at 20 C related to multiples of the setting current


Time (s)

10 000

1000

100

1
10

2 3

5
0,1

6 7 8 9 10

0,01

0,001

1,5

10

100
x the setting current (Ir)

1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state

Based on Schneider DIA1ED2090201EN Catalogue

Page 7 of 18

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Dynamic stress

Current limitation on short-circuit for GV2 ME and GV2 P (3-phase 400/415 V)

I peak = f (prospective Isc) at 1.05 Ue = 435 V


Limited peak current (kA)

1
1

100

=0

.3

=0

2 3 4 5

.25

2 3 4

=0

.5

5 6

10

=0 .7

7 8

0.9

0.8

9
=0 co s .95

10

11

6 7

0,1 0,1

10

15 (12)

100 Prospective Isc (kA)

1 Maximum peak current 2 24 -32 A 3 20 -25 A 4 17 -23 A 5 13 -18 A 6 9 -14 A 7 6 -10 A 8 4 -6.3 A 9 2.5 -4 A 10 1.6 -2.5 A 11 1 -1.6 A 12 Limit of rated ultimate breaking capacity on short-circuit of GV2 ME (14, 18, 23 and 25 A ratings)

8 9 10

Based on Schneider DIA1ED2090201EN Catalogue

Page 8 of 18

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME

12486

Thermal limit on short-circuit for GV2 ME

1 2 3 4

Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100 1

2 3 4 5 6 7

10

9
1

5 6 7 8 9 10
0,1

10

0,01

0,1

10

100 Prospective Isc (kA)

1 24 -32 A 2 20 -25 A 3 17 -23 A 4 13 -18 A 5 9 -14 A 6 6 -10 A 7 4 -6.3 A 8 2.5 -4 A 9 1.6 -2.5 A 10 1 -1.6 A

Based on Schneider DIA1ED2090201EN Catalogue

Page 9 of 18

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 P

12486

Thermal limit on short-circuit for GV2 P


Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

Thermal limit in kA2s in the magnetic operating zone

1
1 2 3 4 5 6

100

2 3

10

8
1

4 5 6 7

0,1

0,01

0,1

10

100 Prospective Isc (kA)

1 1 2 3 4 5 6 7 8 9

24 -32 A 20 -25 A 17 -23 A 13 -18 A 9 -14 A 6 -10 A 4 -6.3 A 2.5 -4 A 1.6 -2.5 A 1 -1.6 A

8 9 10

Based on Schneider DIA1ED2090201EN Catalogue

Page 10 of 18

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME

12486

533886

Motor circuit-breakers from 0.06 to 15 kW / 400 V, with screw clamp terminals


GV2 ME with pushbutton control
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 500 V 690 V P Icu Ics P Icu Ics (1) P Icu (1) kW kA % kW kA % kW kA GV2 ME10 0.06 0.09 g g 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 g g g g g g g g g g 0.160.25 0.250.40 0.400.63 0.631 116 1.62.5 2.54 46.3 610 914 1318 1723 2025 2432 2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 416 GV2 ME02 GV2 ME03 GV2 ME04 GV2 ME05 GV2 ME06 GV2 ME07 GV2 ME08 GV2 ME10 GV2 ME14 GV2 ME16 GV2 ME20 GV2 ME21 GV2 ME22 (3) GV2 ME32 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 0.260 Setting range of thermal trips Ics (1) (2) % A 0.10.16 Magnetic tripping current Id 20 % A 1.5 Reference Weight

1 2 3 4 5 6 7 8 9 10

GV2 ME01

kg 0.260

0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15

g g g

g g g

0.37 g 0.55 g 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 g g 3 3 3 3 3 3 3 3 3

g g g

g g g

g g 75 75 75 75 75 75 75 75 75 75 75

g g g

g g g

g g 50 10 10 6 6 4 4

g g 100 100 100 75 75 75 75 75

g g 15 15 15 15 10

g g 50 50 40 40 50

18.5 3 22 3

18.5 4

To order thermal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected above. Example: GV2 ME08 becomes GV2 ME086. Thermal magnetic circuit-breakers GV2 ME with built-in auxiliary contact block With instantaneous auxiliary contact block : b GV AE1, add suffix AE1TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE1TQ. b GV AE11, add suffix AE11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE11TQ. b GV AN11, add suffix AN11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AN11TQ. These circuit-breakers with built-in contact block are sold in lots of 20 units in a single pack.
(1) As % of Icu. 1) (2) The thermal trip setting must be within the range marked on the graduated knob. (3) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office. g > 100 kA.

Motor circuit-breakers from 0.06 to 15 kW / 400 V, with lugs

Based on Schneider DIA1ED2090201EN Catalogue

Page 11 of 18

References (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME

12486

533897

Motor circuit-breakers from 0.06 to 11 kW, with spring terminal connections


GV2 ME (1) with pushbutton control
400/415 V P kW 0.06 GV2 MEpp3 0.09 0.12 0.18 0.25 0.37 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 11 Icu kA g g g g g g g g g g g g g g 15 15 15 15 15 Ics (2) % g g g g g g g g g g g g g g 50 50 40 40 40 500 V P kW 0.37 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 Icu kA g g g g g g g 50 10 10 6 6 4 4 Ics (2) % g g g g g g g 100 100 100 75 75 75 75 Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 Setting range of thermal trips (3) A 0.10.16 0.160.25 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 610 914 1318 1723 2025 Magnetic tripping current Id 20 % A 1.5 2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 Reference Weight

1 2 3 4 5 6 7 8 9 10

GV2 ME013 GV2 ME023 GV2 ME033 GV2 ME043 GV2 ME053 GV2 ME063 GV2 ME073 GV2 ME083 GV2 ME103 GV2 ME143 GV2 ME163 GV2 ME203 GV2 ME213 GV2 ME223

kg 0.280 0.280 0.280 0.280 0.280 0.280 0.280 0.280 0.280 0.280 0.280 0.280 0.260 0.260

Contact blocks
Description Instantaneous auxiliary contacts Mounting Front LH side Maximum number 1 2 Type of contacts N/O + N/C N/O + N/O N/O + N/C N/O + N/O Sold in lots of 10 10 1 1 Unit reference GV AE113 GV AE203 GV AN113 GV AN203 Weight kg 0.030 0.030 0.060 0.060

Accessory
Description Cable end reducer LA9 D99 (1) For connection of conductors from 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended. (2) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office (3) The thermal trip setting must be within the range marked on the graduated knob. g > 100 kA. Application For connection of conductors from 1 to 1.5 mm2 Sold in lots of 20 Unit reference LA9 D99 Weight kg

Based on Schneider DIA1ED2090201EN Catalogue

Page 12 of 18

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 P, GV3 P and GV3 ME80 0

12486

510564

Motor circuit-breakers from 0.06 to 30 kW / 400 V


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 500 V 690 V P Icu Ics P Icu Ics P Icu (1) (1) kW kA % kW kA % kW kA Setting range of thermal trips (2) A Magnetic tripping current Id 20 % A Reference Weight

1 2 3 4

GV2 P: control by rotary knob


g g g g g 50 42 10 10 10 10 g g g g g 100 75 75 75 75 75

Ics (1) %

kg

GV2 P10

Screw clamp terminals g 0.06 g g 0.09 g g 0.12 g g 0.18 g g 0.25 g g 0.37 g 0.37 g 0.55 g 0.55 g 0.75 g 1.1 g 1.1 g 1.5 g 2.2 g 3 g g 3 5 g 5.5 g 7.5 7.5 50 50 9 9 50 50 11 11 50 50 15 15 35 50 18.5

0.37 0.55 0.75 1.5 2.2 4 5.5 9 11 15 18.5 22

g g g 8 8 6 6 6 6 4 4 4

g g g 100 100 100 100 100 100 100 100 100

0.10.16 0.160.25 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 610 914 1318 1723 2025 2432

1.5 2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 416

GV2 P01 GV2 P02 GV2 P03 GV2 P04 GV2 P05 GV2 P06 GV2 P07 GV2 P08 GV2 P10 GV2 P14 GV2 P16 GV2 P20 GV2 P21 GV2 P22 GV2 P32

0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350 0.350

510617

GV3 P: control by rotary knob

5 6 7 8
GV3 P651
510992

Connection by EverLink BTR screw connectors (3) 5.5 100 100 7.5 12 50 11 6 50 9 12 50 15 6 50 7.5 100 100 11 100 100 15 12 50 18.5 6 50 15 100 100 18.5 12 50 22 6 50 18.5 50 100 22 12 50 37 6 50 22 50 100 30 12 50 45 6 50 30 50 100 45 12 50 55 6 50

913 1218 1725 2332 3040 3750 4865

182 252 350 448 560 700 910

GV3 P13 GV3 P18 GV3 P25 GV3 P32 GV3 P40 GV3 P50 GV3 P65

0.960 0.960 0.960 0.960 0.960 0.960 0.960

GV3 P65

To assemble a GV3 P40 to P65 circuit-breaker with an LC1 D40A to D65A contactor, it is possible to use the circuit-breaker supplied without downstream EverLink power terminal block. To order this product, add the digit 1 to the end of the references selected above. Example: GV3 P65 becomes GV3 P651.
Connection by lugs

Connection by EverLink BTR screw connectors, for assembly with a contactor

To order thermal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected above. Example: GV3 P18 becomes GV3 P186. GV3 ME80: pushbutton control, screw clamp terminals
37 15 50 45 4 100 55 2 100 5680 GV3 ME80 (4) 0.700

9 10

GV2 (5) To obtain a GV2 P motor circuit-breaker, UL 508 type E, combine: b a circuit-breaker GV2 PppH7 (except 32 A), b and a Large Spacing adapter GV2 GH7. GV3 (6) To obtain a motor-circuit-breaker GV3 P, UL 508 type E, use the following with the circuit-breaker: b a Large Spacing cover GV3 G66, b a short-circuit signalling contact GV AM11. GV3 with connection by lugs (6) To obtain a motor-circuit-breaker GV3 P, UL 508 type E, with connection by lugs, add the digit 6 to the end of reference selected above and use the following with the circuit-breaker: b two IP 20 covers LAD 96570, b a short-circuit signalling contact GV AM11.
(1) As % of Icu. 1) (2) The thermal trip setting must be within the range marked on the graduated knob. (3) BTR screws: hexagon socket head. Require use of an insulated Allen key, in compliance with local wiring regulations. (4) Recommended for use in association with a contactor. (5) Accessory. (6) Accessories. g > 100 kA.

Motor circuit-breakers up to 50 hp / 600 V, UL 508 type E

Based on Schneider DIA1ED2090201EN Catalogue

Page 13 of 18

Dimensions

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Dimensions
GV2 ME

GV AX

GV AD, AM, AN, AU, AS, AX


Block GV AD, AM, AN Block GV AU, AS, AX

GV AE

X1

11

67,2

15
10

15,7

X1

46

44,5

45

16

9,3

9,3 81(1)

18

b GV2 MEpp 89 101 GV2 MEpp3 (1) Maximum Maximum X1 Electrical clearance = 40 mm for e 690 V 1 Electrical clearance = 40 mm for e y

GV2 P
X1

GV AD, AM, AN, AU, AS


Block GV AD, AM, AN Block GV AU, AS

GV2 AK00
14 98
32

89

45

15

X2

26

50 82

44,5

61

9,3

9,3 81(1)

18

44,5

(1) Maximum X1 Electrical clearance = 40 mm for e 1 Electrical clearance = 40 mm for e y 415 V, or 80 mm for e = 440 V, or 120 mm for e = 500 and 690 V X2 = 40 mm

GV2 GH7
70
15

44,5

Based on Schneider DIA1ED2090201EN Catalogue

Page 14 of 18

Mounting, dimensions

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Mounting
GV2 ME
On 35 mm 5 rail On panel with adapter plate GV2 AF02 On pre-slotted plate AM1 PA On rails DZ5 MB201

4,2

AF1 EA4

15

35

50/60

50/60

50

c
c = 78.5 on AM1 DP200 (35 x 7.5) c = 86 on AM1 DE200, ED200 (35 x 15)

80

35

35 GV2 AF02

DZ5 ME8 DZ5 MB201

GV2 P
On rail AM1 DE200, ED200 (35 x 15) Panel mounted On pre-slotted plate AM1 PA Adapter plate GK2 AF01

45 AF1 EA4
35 5

44,5

55

44,5

45

106

13,5

13,5

24

9,5

35

54

Dimensions
GV2 AF01
Combination GV2 ME + TeSys k contactor

GV2 AF3
Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor

152

105 5

135

84

84

79

45

c1 c

45

c1 c d1 d
GV2 P + b c1 c d1 d LC1 D09 D18 176.4 100.1 105.6 95 100.5

45

GV2 ME + b c1 c

LC1 D09 D18 176.4 94.1 99.6

LC1 D25 and D32 186.8 100.4 105.9

LC1 D25 and D32 186.8 106.4 111.9 95 100.5

Based on Schneider DIA1ED2090201EN Catalogue

Page 15 of 18

60

Dimensions, mounting (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

Dimensions (continued) GV2 AF4 + LAD 311


Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor

125 3

125 3

234

c1 c d1 d
GV2 ME + b c1 c d1 d LC1 D09D18 176.4 103.1 135.6 107 112.5

45

c1 c

45

LC1 D25 and D32 186.8 136.4 141.9 107 112.5

GV2 P + b c1 c

LC1 D09D18 176.4 136.5 141.6

b 234
LC1 D25 and D32 186.8 142.4 147.9 Door cut-out

GV2 ME + GV1 L3 (current limiter)


X1

7.5 mm height compensation plate GV1 F03


39

40

13
129

35

77

44,5

X1 = 10 mm for e = 230 V or 30 mm for 230 V < Ue y 690 V

Mounting

Mounting of external operator GV2 AP01 or GV2 AP02 for motor circuit-breakers GV2 P

X1

45

89

65

1,5...5 53 135284 5,2 = =

= 54

Based on Schneider DIA1ED2090201EN Catalogue

Page 16 of 18

54

Dimensions, mounting (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

12486

GV2 ME, GV2 P

Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05
a 3
18

63

45
l 179 206 260 p 45 54 72 a 5 224 260 332

GV2 G445 (4 x 45 mm) GV2 G454 (4 x 54 mm) GV2 G472 (4 x 72 mm)

Number of tap-offs GV2 G445 GV2 G454 GV2 G472

6 269 314 404

7 314 368 476

8 359 422 548

Sets of busbars GV2 Gppp with terminal block GV1 G09


GV1 G09
38

Sets of busbars GV2 G245, GV2 G254, GV2 G272


l

GV2 G245 (2 x 45 mm) GV2 G254 (2 x 54 mm) GV2 G272 (2 x 72 mm)

l 89 98 116

Sets of busbars GV2 G554


260

Sets of busbars GV2 G345 and GV2 G354


l

GV2 G345 (3 x 45 mm) GV2 G354 (3 x 54 mm)

l 134 152

Based on Schneider DIA1ED2090201EN Catalogue

Page 17 of 18

Schemes

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P, GV3 P and GV2 RT

12486

Schemes
1/L1 3/L2

GV2 MEpp and GV2 RT


5/L3

GV2 Ppp
1/L1 3/L2 5/L3

GV3 Ppp
1/L1 3/L2 4/T2 5/L3 6/T3

2/T1

4/T2

6/T3

2/T1

4/T2

6/T3

Front mounting add-on contact blocks Instantaneous auxiliary contacts


GV AE1
or

Front mounting add-on contact blocks Instantaneous auxiliary contacts and fault signalling contacts
GV AED101 GV AED011

GV AE11

GV AE20

97 98 97 98
10Agl max

97

13

13

21

11

13

23

23

98

12

14

14

22

14

Side mounting add-on contact blocks Instantaneous auxiliary contacts and fault signalling contacts
GV AD0110 GV AD0101 GV AD1010 GV AD1001

95

53

95

51

24

24

97

53

96

96

54

52

98

Instantaneous auxiliary contacts


GV AN11
(61) 31 43 (73)

Short-circuit signalling contacts


GV AM11
08 06

GV AN20
(63) 33 43 (73)

(62) 32

44 (74)

(64) 34

44 (74)

Voltage trips
GV AUppp GV ASppp GV AXppp
D1 D2

Current limiter
GV1 L3
1/L1 3/L2 5/L3

D1

D2

D2

D1

E1

Use of fault signalling contact se and short-circuit signalling contact


GV AM11 GV AD10pp

E2

Connection of undervoltage trip for dangerous machines onnection (conforming to INRS) on GV2 ME only

1/L1

05

3/L2

54

5/L3

D1

Short-circuit signalling

D2
E2 E1

Trip signalling N/C or N/O Start-Stop contact

2/T1

4/T2

Based on Schneider DIA1ED2090201EN Catalogue

6/T3

52

51

22

21

2/T1

Page 18 of 18