fP600
firE rESiStant caBlES
fP600 ®
BS7346-6
StanDarDS > FP600 meets the 120 min survival time of BS7346-6.
inStallatiOn > FP600 is an easy to install cable that requires no special tools
or techniques. It is however important to follow the installation
recommendations given in this document to ensure a trouble free
installation and to ensure that the fire integrity of the installed
system is not compromised.
caBlE cHaractEriSticS
Temperature Bending Radius Mechanical Impact Fire Performance Flexibilty Halogen Free Low Smoke Emissions Fire Resistant
Range Fixed r=8D Excellent BSEN60332-1-2 Rigid BSEN50267-2-1 BSEN61034-2 BS7346-6
-25 to +90˚C BSEN50266-2-4 120min
BSEN60332-1-2
BSEN61034-2
EN50200 PH30 & PH60
®
FP 600 FIRE RESISTANT CABLES
Nominal Approximate Approximate Maximum Current rating Current rating Volt drop Volt drop Recommended accessories
cross overall cable conductor DC or single DC or single DC single phase
sectional diameter weight resistance phase phase AC
area at 20°C AC AC Claw Cleat Brass gland
Free Air Clipped direct Ref No. Ref No.
mm 2
mm kg/km ohms/km Amps Amps mV/A/m mV/A/m
Two core
10 24.3 900 1.83 90 85 4.7 4.7 370CG05 416FP55
50* 33.4 2200 0.387 228 219 0.98 1.0 370CG07 416FP56
70* 36.6 2775 0.268 291 279 0.67 0.69 370CG07 416FP57
95* 38.3 3375 0.193 354 338 0.49 0.52 370CG08 416FP57
120* 41.9 4050 0.153 410 392 0.39 0.42 370CG08 416FP59
Nominal Approximate Approximate Maximum Short Current rating Current Volt drop Recommended accessories
cross overall cable conductor circuit Three phase rating Three phase
sectional diameter weight resistance rating AC Three phase AC
area at 20°C (1 sec) Clipped direct AC Claw Cleat Brass gland
of conductor Free Air Ref No. Ref No.
mm 2
mm kg/km ohms/km KA Amps Amps mV/A/m
Three core
10 24.9 1125 1.83 1.4 73 78 4.0 370CG05 416FP55
50* 36.2 2775 0.387 7.1 187 187 0.87 370CG07 416FP57
70* 39.8 3550 0.268 10.0 238 251 0.60 370CG08 416FP57
95* 43.7 4500 0.193 13.6 289 304 0.45 370CG08 416FP59
120* 46.0 5400 0.153 17.2 335 353 0.37 370CG09 416FP59
Four core
10 26.5 1250 1.83 1.4 73 78 4.0 370CG06 416FP55
50* 39.1 3400 0.387 7.1 187 197 0.87 370CG08 416FP57
70* 43.8 4450 0.268 10.0 238 251 0.60 370CG08 416FP59
95* 47.6 5625 0.193 13.6 289 304 0.45 370CG09 416FP59
120* 51.8 6900 0.153 17.2 335 353 0.37 370CG09 416FP59
Ambient Tempareture°C 25 30 35 40 45 50 55 60
Correction Factor 1.02 1.0 0.96 0.91 0.87 0.82 0.76 0.71
Single layer multicore on a Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72
perforated metal cable tray,
vertical or horizontal Spaced* 0.91 0.89 0.88 0.87 0.87 - - -
INSTALLATION METHOD • P
ull the cable in the normal manner taking into account all limiting
FP600 cables are primarily intended for use in buildings. They may be factors. If the cable is to be pulled where there is a possibility that
fixed directly to the building structure or be carried upon suitable cable water, mud, etc. may be present, then, before the cable stocking is
management systems (e.g. tray, ladder). Due to its extremely robust placed into position, a self amalgamating tape should be applied to
nature, FP600 does not require additional mechanical protection. the cable to stop any ingress of water between the cable bedding
and armour and within the inner cores.
Minimum installation temperature
The cable should not be installed at temperatures below 0ºC. • O
nce the cable has been pulled into position, the excess core/bedding
shall be cut back to the armour/sheath and a heat shrink capping shall
Minimum Bending Radius be applied.
The minimum recommended bending radius for FP600 cables during
installation is 12x the cable overall diameter. Under controlled The maximum stocking pulling tension is 5 Kg per sq.mm of total
bending conditions the bending radius may be reduced to 8x the overall conductor cross sectional area up to a maximum of 1000Kgs. The use
diameter. of guide rollers or other friction reducing devices is recommended.
• P
lace a cable stocking of at least 1 metre in length over the inner Health and Safety
bedding and outer sheath, ensuring that the stocking firmly grips both Please refer to Prysmian Cables leaflet ‘Statement to Cable Users on
the outer sheath and the inner bedding. the Health & Safety at Work Act 1974 and to the Control of Substances
Hazardous to Health Regulation (COSHH).
Maximum Resistance of conductor and armour and gross cross-sectional areas of armour tape
Maximum
Conductor Calculated maximum Resistance of Armour at 20°C Effective Cross Sectional Area of Tape Armour
Resistance
cross - sectional
of Conductor
area
at 20°C 2 Core 3 Core 4 Core 2 Core 3 Core 4 Core
mm2 ohms/km Ωohms/km Ωohms/km ohms/km mm2 mm2 mm2
Ref:FP600/PY/08/06