Sei sulla pagina 1di 10

Electrical Power and Energy Systems 28 (2006) 669–678

www.elsevier.com/locate/ijepes

An analytical approach for DG allocation in primary


distribution network
Naresh Acharya, Pukar Mahat, N. Mithulananthan *

Electric Power System Management, Energy Field of Study, Asian Institute of Technology, P.O. Box 4, Klong luang, Pathumthani 12120, Thailand

Received 22 March 2005; received in revised form 15 December 2005; accepted 24 February 2006

Abstract

This paper proposes an analytical expression to calculate the optimal size and an effective methodology to identify the corresponding
optimum location for DG placement for minimizing the total power losses in primary distribution systems. The analytical expression and
the methodology are based on the exact loss formula. The effect of size and location of DG with respect to loss in the network is also
examined in detail. The proposed methodology was tested and validated in three distribution test systems with varying size and complex-
ity. Results obtained from the proposed methodology are compared with that of the exhaustive load flows and loss sensitivity method.
Results show that the loss sensitivity factor based approach may not lead to the best placement for loss reduction.
Ó 2006 Elsevier Ltd. All rights reserved.

Keywords: Distributed generation; Exact loss formula; Optimum size; Optimum location; Sensitivity factors

1. Introduction out the world also indicate that the number will grow rap-
idly. As the penetration of DG in distribution system
The share of distributed generators (DGs) in power sys- increases, it is in the best interest of all players involved
tems has been slowly increasing in the last few years. to allocate DG in an optimal way such that it will reduce
According to CIGRE report [1], the contribution of DG system losses and hence improve voltage profile.
in Denmark and the Netherlands has reached 37% and Studies have indicated that inappropriate selection of
40%, respectively, as a result of liberalization of power location and size of DG, may lead to greater system losses
market in Europe. Electric Power Research Institute’s than the losses without DG [3,4]. Utilities already facing
(EPRI) study forecasts that 25% of the new generation will the problem of high power loss and poor voltage profile,
be distributed by 2010 and a similar study by the Natural especially, in the developing countries cannot tolerate any
Gas Foundation believes that the share of DG in new gen- increase in losses. By optimum allocation, utilities take
eration will be 30% by the year 2010 [2]. The numbers may advantage of reduction in system losses; improve voltage
vary as different agencies define DG in different way, how- regulation and improvement in reliability of supply [3–5].
ever, with the Kyoto protocol put in place where there will It will also relieve capacity from transmission and distribu-
be a favorable market for DG that are coming from tion system and hence, defer new investments, which have a
‘‘Green Technologies,’’ the share of DG would increase long lead-time.
and there is no sign that it would decrease in near future. DG could be considered as one of the viable options to
Moreover, the policy initiatives to promote DG through- ease some of the problems (e.g. high loss, low reliability,
poor power quality, congestion in transmission system)
*
Corresponding author. Tel.: +66 2 524 5405; fax: +66 2 524 5439. faced by the power systems, apart from meeting the
E-mail address: mithulan@ieee.org (N. Mithulananthan). energy demand of ever growing loads. In addition, the

0142-0615/$ - see front matter Ó 2006 Elsevier Ltd. All rights reserved.
doi:10.1016/j.ijepes.2006.02.013
670 N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678

modular and small size of the DG will facilitate planner to 2. Distributed generation
install it in a shorter time frame compare to the conven-
tional solution. It would be more beneficial to install Distributed generation is an electric power source con-
DG in the present utility setup, which is moving towards nected directly to the distribution network or customer side
a more decentralized environment, where there is a larger of the meter [12]. It may be understood in simple term as
uncertainty in demand and supply. However, given the small-scale electricity generation. The definition of distrib-
choices they need to be placed in appropriate locations uted generation takes different forms in different markets
with suitable sizes. Therefore, tools are needed to be and countries and is defined differently by different agencies.
developed to examine locations and sizing of such DG International Energy Agency (IEA) defines Distributed gen-
installation. eration as generating plant serving a customer on-site or pro-
The optimum DG allocation can be treated as optimum viding support to a distribution network, connected to the
active power compensation, like capacitor allocation for grid at distribution-level voltages [12]. CIGRE defines DG
reactive power compensation. DG allocation studies are as the generation, which has the following characteristics
relatively new, unlike capacitor allocation. In Ref. [6,7], [1]: It is not centrally planned; It is not centrally dispatched
power flow algorithm is presented to find the optimum at present; It is usually connected to the distribution net-
DG size at each load bus assuming every load bus can have work; It is smaller than 50–100 MW. Other organization like
DG source. Such methods are, however, inefficient due to a Electric Power Research Institute defines distributed gener-
large number of loadflow computations. The genetic algo- ation as generation from a few kilowatts up to 50 MW [13].
rithm (GA) based method to determine size and location is In general, DG means small scale generation.
used in [8–10]. GA is suitable for multi-objective problems There are a number of DG technologies available in the
like DG allocation and can give near optimal results, but market today and few are still in research and development
they are being computationally demanding and slow in stage. Some currently available technologies are reciprocat-
convergence. In Ref. [11], analytical method to place DG ing engines, micro turbines, combustion gas turbines, fuel
in radial as well as meshed systems to minimize power loss cells, photovoltaic, and wind turbines. Each one of these
of the system is presented. In this method separate expres- technologies has its own benefits and characteristics.
sions for radial and network system are derived and a com- Among all the DG, diesel or gas reciprocating engines
plex procedure based on phasor current is proposed to and gas turbines make up most of the capacity installed
solve the location problem. However, this method only so far. Simultaneously, new DG technology like micro tur-
optimizes location and considers size of DG as fixed. bine is being introduced and an older technology like recip-
In this paper, an analytical expression to calculate rocating engine is being improved [12]. Fuel cells are
optimum size and an effective methodology to identify technology of the future. However, there are some proto-
the optimum location for DG placement are proposed. type demonstration projects. The costs of photovoltaic sys-
The methodology is computationally less demanding. tems are expected to falling continuously over the next
The DG is considered to be located in the primary distri- decade. This all underlines the statement that the future
bution system and the objective of DG placement is to of power generation is DG.
reduce the losses. The cost of DG and the other associ- Supplying peaking power to reduce the cost of electric-
ated benefits have not been considered while solving the ity, reduce environmental emissions through clean and
location and sizing problem. The sizing and placement renewable technologies (Green Power), combined heat
of DG is based on single instantaneous demand at peak, and power (CHP), high level of reliability and quality of
where the losses are maximum. The proposed methodol- supplied power and deferral of the transmission and distri-
ogy is suitable for allocation of single DG in a given bution line investment through improved loadability are
distribution network. the major applications of the DG [14]. Other than these
The rest of the paper is organized as follows: Section 2 applications, the major application of DG in the deregu-
gives a brief introduction to distributed generation, includ- lated environment lies in the form of ancillary services.
ing definition, characteristic and applications. Section 3 These ancillary services include spinning and non-spinning
presents the importance of selection of proper location reserves, reactive power supply and voltage control etc.
and size of DG for minimizing distribution losses. A widely [15]. DG also has several benefits like reducing energy costs
used loss sensitivity factor method is presented in Section 4. through combined heat and power generation, avoiding
A novel and fast methodology for determining the opti- electricity transmission costs and less exposure to price vol-
mum size and location of DG in distribution network is atility. Though the DG is considered as a viable solution to
described in Section 5. Section 6 portrays the test distribu- most of the problems that today’s utility are facing, there
tion systems used in the paper. A brief summary of the are many problems (e.g. DG integration into grid, pricing,
software tool used to obtain the result also included in this change in protection scheme, nuisance tripping etc.) that
section. Numerical results along with some observations need to be addressed. Furthermore, the type of DG tech-
and discussions are presented in Section 7. Finally, the nology adopted will have significant bearing on the solu-
major contributions and conclusions of the papers are sum- tion approach. In this study, DGs capable of supplying
marized in Section 8. real power only are considered.
N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678 671

3. Location and sizing issues in the best choice. A brief description of loss sensitivity fac-
tor method and associated problems are presented below.
Fig. 1 shows a 3D plot of typical power loss versus size
of DG at each bus in a distribution system. From the fig- 4. Loss sensitivity factor method
ure, it is obvious that for a particular bus, as the size of
DG is increased, the losses are reduced to a minimum value Sensitivity factor method is based on the principle of lin-
and increased beyond a size of DG (i.e. the optimal DG earization of original nonlinear equation around the initial
size) at that location. If the size of DG is further increased, operating point, which helps to reduce the number of solu-
the losses starts to increase and it is likely that it may over- tion space. Loss sensitivity factor method has been widely
shoot the losses of the base case. Also notice that location used to solve the capacitor allocation problem [16]. Its
of DG plays an important role in minimizing the losses. application in DG allocation is new in the field and has
The important conclusion that can be drawn from Fig. 1 been reported in [4].
is that, given the characteristics of the distribution system, it
is not advisable to construct sufficiently high DG in the net- 4.1. Loss sensitivity
work. The size at most should be such that it is consumable
within the distribution substation boundary. Any attempt The real power loss in a system is given by (1). This is
to install high capacity DG with the purpose of exporting popularly referred to as ‘‘exact loss’’ formula [17].
power beyond the substation (reverse flow of power though
distribution substation), will lead to very high losses. So, the
N X
X N
PL ¼ ½aij ðP i P j þ Qi Qj Þ þ bij ðQi P j  P i Qj Þ ð1Þ
size of distribution system in term of load (MW) will play i¼1 j¼1
important role is selecting the size of DG. The reason for
r r
higher losses and high capacity of DG can be explained where aij ¼ V iijV j cosðdi  dj Þ, bij ¼ V iijV j sinðdi  dj Þ and rij +
by the fact that the distribution system was initially jxij = Zij are the ijth element of [Zbus] matrix with [Zbus] =
designed such that power flows from the sending end
[Ybus]1.
(source substation) to the load and conductor sizes are
gradually decreased from the substation to consumer point. The sensitivity factor of real power loss with respect to
Thus without reinforcement of the system, the use of high real power injection from DG is given by
capacity DG will lead to excessive power flow through oP L XN

small-sized conductors and hence results in higher losses. ai ¼ ¼2 ðaij P j  bij Qj Þ ð2Þ
oP i i¼1
Based on this the DG allocation can be handled by resolv-
ing the sizing issue first followed by the location issue. How- Sensitivity factors are evaluated at each bus, firstly using
ever, existing technique such as loss sensitivity method finds the values obtained from the base case power flow. The
the location issue before and sizing issue. This may not result buses are ranked in descending order of the values of their
sensitivity factors to form a priority list. The top-ranked
buses in the priority list are the first to be studied alterna-
tives location. This is generally done to take into account of
the effect of nonlinearities in the system. The first order sen-
sitivity factor are based on linearization of the original
nonlinear equation around the initial operating condition
and is biased towards function which has higher slope at
the initial condition, that might not identify the global opti-
mum solution. This condition is depicted in Fig. 2. There-
fore, priority list of candidate location is prerequisite to get
the optimum solution.
Fig. 2 shows a probable case, captured from the trend of
losses in Section 3. The curve with solid line has highest
sensitivity factor at the initial operating condition than dot-
ted curve, but does not give the lowest loss, as PL1 > PL2.
It shows why the sensitivity factor may not give the opti-
mum result if a number of alternative locations are not
taken into account.

4.2. Priority list

The sensitivity factor will reduce the solution space to


few buses, which constitute the top ranked buses in the
Fig. 1. Effect of size and location of DG on system loss. priority list. The effect of number of buses taken in priority
672 N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678

losses the rate of change of losses with respect to injected


power becomes zero.

oP L XN
¼2 ðaij P j  bij Qj Þ ¼ 0 ð3Þ
oP i j¼1

It follows that
X
N
aii P i  bii Qi þ ðaij P j  bij Qj Þ ¼ 0
j¼1;j6¼i
" # ð4Þ
1 X
N
Pi ¼ b Q þ ðaij P j  bij Qj Þ
aii ii i j¼1;j6¼i

where, Pi is the real power injection at node i, which is the


difference between real power generation and the real
Fig. 2. Nonlinearity in loss curve.
power demand at that node:
P i ¼ ðP DGi  P Di Þ ð5Þ
where, PDGi is the real power injection from DG placed at
will have effect the optimum solution obtained for some
node i, and PDi is the load demand at node i. By combining
system. For each bus in the priority list, the DG is placed
(4) and (5) one can get (6).
and the size is varied from minimum (0 MW) to a higher " #
value until the minimum system losses is found with the 1 XN

DG size. In this study, 30% of the total number of buses P DGi ¼ P Di þ b Q  ðaij P j  bij Qj Þ ð6Þ
aii ii i j¼1;j6¼i
is considered in preparing the priority list for each case.
The process is computationally demanding as one needs a The above equation gives the optimum size of DG for
large number of load flow solution. each bus i, for the loss to be minimum. Any size of DG
other than PDGi placed at bus i, will lead to higher loss.
4.3. Computational procedure This loss, however, is a function of loss coefficient a and
b. When DG is installed in the system, the values of loss
Step 1: Run the base case load flow. coefficients will change, as it depends on the state variable
Step 2: Find the sensitivity factor using Eq. (2) and rank voltage and angle. Updating values of a and b again
the sensitivity in descending order to form priority requires another load flow calculation. But numerical result
list. shows that the accuracy gained in the size of DG by updat-
Step 3: Select the bus with the highest priority and place ing a and b is small and is negligible. With this assumption,
DG at that bus. the optimum size of DG for each bus, given by relation (6)
Step 4: Change the size of DG in ‘‘small’’ step and calcu- can be calculated from the base case load flow (i.e. without
late loss for each by running load flow. GD case).
Step 5: Store the size of DG that gives the minimum loss.
Step 6: Compare the loss with the previous solution. If loss 5.2. Location to minimize losses
is less than previous solution, store this new solu-
tion and discard previous solution. The next step is to find the optimum DG location, which
Step 7: Repeat Step 4 to Step 6 for all buses in the priority will give the lowest possible total losses. Calculation of loss
list. with DG one at a time at each bus again requires several
load flow solutions, as many as number of buses in the sys-
5. Proposed methodology tem. Therefore a new methodology is proposed to quickly
calculate approximate loss, which would be used for the
In this section, a new methodology is proposed to find purpose of identifying the best location. Numerical result
the optimum size and location of DG in the distribution shows that approximate loss follows the same pattern as
system. This methodology requires load flow to be carried that calculated by accurate load flow. It means that, if
out only two times, one for the base case and another at the accurate loss calculation from load flow gives minimum
end with DG included to obtain the final solution. for a particular bus then, loss calculated by approximate
loss method will also be minimum at that bus. This is ver-
5.1. Sizing at various locations ified by the simulation results shown in Figs. 9–11. What
differs is the amount of losses, which is not a concern for
According to Section 3, the total power loss against identifying location. With this methodology one can avoid
injected power is a parabolic function and at minimum exhaustive computation and save time.
N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678 673

5.3. Computational procedure single line diagram of the test system is shown in Fig. 3.
The second test system as depicted on Fig. 4 contains 33
Step 1: Run the base case load flow. buses and 32 branches. It is a radial system with the total
Step 2: Find the optimum size of DG for each bus using load of 3.72 MW and 2.3 MVAR [18]. The third test system
Eq. (6). shown in Fig. 5 is the widely used 69 bus-68 branches radial
Step 3: Compute approximate loss using Eq. (1) for each system with the total load demand of 3.80 MW and
bus by placing DG of optimum size obtained in 2.69 MVAR [19].
step 2 for that bus. Add the injection from DG A computer program has been written in MATLAB 7 to
for that bus and use base case values for state calculate the optimum sizes of DG at various buses and
variables. approximate total losses with DG at different locations to
Step 4: Locate the bus at which the loss is minimum after identify the best location. A Newton–Raphson algorithm
DG placement. This is the optimum location for based load flow program is used to solve the load flow
DG. problem.
Step 5: Run load flow with DG to get the final result.
7. Simulation results

6. Test system and analytical tools 7.1. Sizes allocation

The proposed methodology is tested on three different Based on the proposed analytical expression, optimum
test systems, of different sizes to show that it can be imple- sizes of DGs are calculated at various nodes for the three
mented in distribution systems of various configuration test systems. Figs. 6–8 show optimum sizes of DG at various
and size. The first system is a 30 bus-32 branches loop sys- nodes for 30, 33 and 69 bus distribution test systems, respec-
tem with the total load of 4.43 MW and 2.72 MVAR [3]. A tively. As far as one location is concerned, in a distribution

Fig. 3. Single line diagram of 30 bus distribution test system.

Fig. 4. Single line diagram of 33 bus distribution test system.


674 N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678

Fig. 5. Single line diagram of 69 bus distribution test system.

4
Optimum DG Size (MW)

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Bus No.

Fig. 6. Optimum size of DG at various nodes for 30 bus distribution test system.

test system, corresponding figure would give the value of the help of the approximate method described in subsec-
DG size to have a ‘‘possible minimum’’ total loss. Any reg- tion 5.2.
ulatory body can use this as a lookup table for restricting
the sizes of DG for minimizing the total power losses in 7.2. Location selection
the system.
In 30 bus distribution test system, the optimum sizes Figs. 9–11 show the approximate total power losses for
ranging from 2.5 to 4.75 MW as shown in Fig. 6. The rang 30, 33 and 69 bus distribution systems, respectively, with
of DG sizes for the other two test systems at various loca- optimum DG sizes obtained at various nodes of respective
tions are 0.3–4.0 MW and 0.1–4 MW, respectively. How- systems. The figures also show the accurate loss. As can be
ever, it is important to identify the location in which the from these figures the trend of the losses is captured with
total power loss is minimum. This can be identified with the help of approximate solution which is good enough
N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678 675

4
Optimum DG Size (MW)

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
Bus No.

Fig. 7. Optimum size of DG at various locations for 33 bus distribution system.

Fig. 8. Optimum size of DG at various locations for 69 bus distribution system.

to identify the location that would lead to the least total In 33 bus distribution test system, the best location is bus 6
power losses. Notice that approximated losses pattern of with a total power loss of 0.111 MW and the second best loca-
the system with optimum sizes of DG at various nodes fol- tion is bus 7 with slightly higher total power losses as shown in
lows the accurate losses in all the cases. Fig. 10. In 69 bus distribution test system the optimum loca-
In 30 bus distribution test system the best (optimum) tion is obvious as shown in Fig. 10. The best location for DG
location of DG is bus 12, where the total power losses installation is bus 61, in one of the lateral feeders, with a total
reduced to 0.154 MW, as depicted in Fig. 9. The second power loss of 0.081 MW. The second best location in this test
best location is bus 27, where the total power losses is system is bus 62 with a total power loss of 0.083 MW. All
0.156 MW, little higher than the first location. these results are summarized in the next section.
676 N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678

0.4

Approximate Loss
Accurate Loss
0.35
Total Power Losses (MW)

0.3

0.25

0.2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
DG Location

Fig. 9. Approximate and accurate losses of 30 bus distribution test system.

0.22

Approximate Loss

Accurate Loss
0.2

0.18
Total Power Losses (MW)

0.16

0.14

0.12

0.1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
DG Location

Fig. 10. Approximate and accurate losses of 33 bus distribution test system.
N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678 677

0.22

0.2

0.18
Total Power Losses (MW)

0.16

0.14

0.12

0.1 Approximate Loss


Accurate Loss

0.08
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69
DG Location

Fig. 11. Approximate and accurate losses of 69 bus distribution test system.

7.3. Summary sequent results apart from power quality and reliability
improvement.
Table 1 shows the summary of results, optimum loca-
tion, corresponding optimum size of DG and total power
loss with and without DG, of all the test systems. The 7.4. Comparison of results
reduction in real power loss for the three cases is 59.6%,
47.3% and 62.8%, respectively. As can be seen from results In this section, the traditional sensitivity approach for
of various systems the location and size of DG play an DG location selection is compared with the proposed
important role in loss reduction of primary distribution approach and repeated load flow.
systems. Table 2 shows the best locations obtained from the loss
From the results obtained for the three systems one can sensitivity factor, proposed approach are repeated load
conclude that by placing DG of optimum size at optimum flow or ‘‘exhaustive’’ approach. For the first two test sys-
location, significant reduction in loss can be achieved. Volt- tems the loss sensitivity approach is not able to identify
age profile improvement, reduction in thermal capacity of the best locations, instead it picked up the second best loca-
the main feeder and better voltage regulation are some con- tion as its first choice in the 30 bus distribution test system
and ninth optimum location as its first choice in the 33 bus
distribution test system. This happens due to the lineariza-
Table 1
tion and approximation as explained Section 4. Table 2
Summary of the simulation results
also shows the optimum sizes of DG. The optimum sizes
Test systems Optimum Optimum DG Power loss (kW)
for locations bus 27 of 30 bus distribution system and
location size (MW) Without DG With DG bus 10 of 33 bus system can be verified from Figs. 6 and
30 bus Bus 12 3.3 383.61 154.87 7, respectively.
33 bus Bus 6 2.49 211.20 111.24 In calculating the optimum sizes of DG at various loca-
69 bus Bus 61 1.81 219.28 81.44
tions, using Eq. (6), it was assumed that the values of

Table 2
Comparison of the results of different approaches
Test systems Loss sensitivity Proposed approach Repeated load flow
Optimum Optimum DG Real power Optimum Optimum DG Real power Optimum Optimum DG Real power
location size (MW) loss (kW) location size (MW) loss (kW) location size (MW) loss (kW)
30 bus Bus 27 3.2 156.28 Bus 12 3.3 154.87 Bus 12 3.5 154.5
33 bus Bus 10 1.4 123.82 Bus 6 2.49 111.24 Bus 6 2.6 111.1
69 bus Bus 61 1.9 81.33 Bus 61 1.81 81.44 Bus 61 1.9 81.33
678 N. Acharya et al. / Electrical Power and Energy Systems 28 (2006) 669–678

variable remain unchanged. This is the reason why there is a [4] Griffin T, Tomosovic K, Secrest D, Law A. Placement of dispersed
small difference between the optimum size obtained from generations systems for reduced losses. In: Proceedings of the 33rd
Hawaii international conference on sciences, Hawaii, 2000.
the proposed approach and repeated load flow. However, [5] Borges CLT, Falcao DM. Impact of distributed generation allocation
in reality, one would go for the closest size available in and sizing on reliability, losses and voltage profile. In: Proceedings of
the market and these differences are within margin of error. IEEE Bolonga power technology conference, 2003.
[6] Row NS, Wan Y-H. Optimum location of resources in distributed
planning. IEEE Trans PWRS 1994;9(4):2014–20.
8. Conclusion [7] Kim JO, Nam SW, Park SK, Singh C. Dispersed generation planning
using improved Hereford ranch algorithm. Electric Power Syst Res
Size and location of DG are crucial factors in the appli- 1998; 47(1):47–55.
cation of DG for loss minimization. This paper presents an [8] Kim K-H, Lee Y-J, Rhee S-B, Lee S-K, You S-K. Dispersed
generator placement using fuzzy-GA in distribution systems. In:
algorithm to calculate the optimum size of DG at various
Proceedings of 2002 IEEE power engineering society summer
buses and proposes a fast methodology to identify the best meeting, Chicago, IL, July 2002;3:1148–53.
location corresponding to the optimum size for reducing [9] Silvestri A, Berizzi A, Buonanno S. Distributed generation plan-
total power losses in primary distribution network. The ning using genetic algorithms. In: Proceedings of international
benefit of the proposed algorithm for size calculation is conference on electric power engineering, Power Tech Budapest,
1999. p. 99.
that a look up table can be created with only one power
[10] Carpinelli G, Celli G, Russo A. Distributed generation siting and
flow calculation and the table can be used to restrict the sizing under uncertainty. In: Proceedings IEEE Porto power tech-
size of DG at different buses, with the view of minimizing nology, 2001.
total losses. However, if a DG is installed in the system, [11] Wang C, Nehrir MH. Analytical approaches for optimal placement
the look up table needs to be updated with new calculation. of distributed generation sources in power systems. IEEE Trans
PWRS 2004;19(4):2068–76.
The proposed methodology for location selection correctly
[12] IEA Publication. Distributed generation in liberalized electricity
identifies the best location for single DG placement in market, 2002. Available from: http://www.iea.org/dbtw-wpd/text-
order to minimize the total power losses. base/nppdf/free/2000/distributed2002.pdf.
In practice, the choice of the best site may not be always [13] Thomas Ackermann, Goran Anderson, Lennart Soder. Distributed
possible due to many constraints. However, the analysis generation: a definition. Electric Power Syst Res 2001;57:195–204.
[14] Francesco Gulli. Distributed generation versus centralized supply: a
here suggests that the losses arising from different place-
social cost–benefit analysis. Institute di Economia e Politica dell’Ener-
ment varies greatly and hence this factor must be taken gia e dell’Ambiente (Iefe), Università Bocconi, Milano, July 2003.
into consideration while determining appropriate location. Available from: http://www.econ.cam.ac.uk/dae/repec/cam/pdf/
The paper also shows that the loss sensitivity factor cwpe0336.pdf.
approach for location selection may not lead to the best [15] Resource Dynamics Corporation. Assessment of distributed genera-
tion technology applications. February 2001. Available from: http://
choice.
www.distributed-generation.com/Library/Maine.pdf.
[16] Bala JL, Kuntz PA, Pebles MN. Optimum capacitor allocation using
References a distribution-analyzer-recorder. IEEE Trans PWRD 1997;12(1):
464–9.
[1] CIGRE. Impact of increasing contribution of dispersed generation on [17] Elgerd IO. Electric energy system theory: an introduction. McGraw-
the power system. Working Group 37.23, 1999. Hill; 1971.
[2] CIGRE. CIGRE technical brochure on modeling new forms of [18] Kashem MA, Ganapathy V, Jasmon GB, Buhari MI. A novel method
generation and storage, November 2000. Available from: http:// for loss minimization in distribution networks. In: Proceedings of
microgrids.power.ece.ntua.gr/documents/CIRE-TF-380110.pdf. international conference on electric utility deregulation and restruc-
[3] Mithulananthan N, Oo Than, Van Phu Le. Distributed generator turing and power technologies, 2000. p. 251–5.
placement in power distribution system using genetic algorithm to [19] Baran ME, Wu FF. Optimum sizing of capacitor placed on radial
reduce losses. TIJSAT 2004;9(3):55–62. distribution systems. IEEE Trans PWRD 1989;4:735–43.

Potrebbero piacerti anche