Sei sulla pagina 1di 1

TYPE OF FITTING

CROSS W/PLUG

TEE W/PLUG 100%

TEE OR DEAD END

TYPICAL INSTALLATION

75%
B

75%

75%

TYPE OF FITTING

90 BEND

45 THRU 11 1/4" BEND

SECTION

TYPICAL INSTALLATION

H=1/2 B
B

THRUST BLOCK BEARING AREA (SQ. FT.) TYPE OF FITTING 4" 6"
SIZE OF PIPE

90 BEND 3 4 8 12 16 22 29 36

45 BEND 2 3 4 6 9 12 16 20

11 1/4" OR 22 1/2" BEND 2 2 2 3 5 6 8 10

TEE OR DEAD END 2 3 5 8 12 16 21 26

8" 10" 12" 14" 16" 18"

1. INSPECTION: Prior to backfilling around thrust block, secure inspection of installation by ENGINEER. 2. BACKFILL: Install and compact all backfill material per APWA SECTION 02320. 3. CONCRETE: Class 2,000 minimum per APWA Section 03304. Pour concrete against undisturbed soil. 4. PIPE JOINTS: DO NOT COVER WITH CONCRETE. Leave completely accessible. 5. GREASE: Apply poly-fm grease to all buried metal surfaces. Wrap with 8 mil thick polyethylene sheet and tape wrap. 6. SPECIAL CONSTRUCTION REQUIREMENTS: A. Thrust design for pipe sizes or configurations not shown require special design. B. Bearing areas, volumes, and special thrust blocking details shown on construction drawings take precendence over this plan. C. Pipes 20" and larger must be designed and approved by engineer.

City of West Jordan

THRUST BLOCK DETAIL

PLAN

SW-03