Investigation of Anti-Islanding Protection of


Power Converter based Distributed Generators
using Frequency Domain Analysis
Vinod John, Member, IEEE, Zhihong Ye, Member, IEEE, Amol Kolwalkar

leading to damage to the DG, neighboring loads and utility


Abstract--Islanding of a grid connected Distributed equipment.
Generation (DG) unit occurs when a section of the utility system Many techniques have been proposed to prevent islanding
containing such generators is disconnected from the main utility, caused by DGs [1]-[9]. An algorithm proposed by the Sandia
but the independent DGs continue to energize the utility lines in
National Laboratories is analyzed in this study because it is
the isolated section (termed as an island). Unintended islanding
is a concern, primarily because it poses a hazard to utility and considered to be effective in detecting the formation of such
customer equipment, maintenance personnel and the general islands [1], [4]. Sandia’s active islanding algorithms had been
public. The algorithm proposed by the Sandia National developed for single-phase inverter units. The algorithm
Laboratories is analyzed in this study because it is considered to consists of the Sandia frequency shift (SFS) and the Sandia
be effective in detecting the formation of such islands. voltage shift (SVS) schemes. The principle behind both the
Previously, there has not been any quantitative analysis for
methods is an accelerated frequency and voltage drift created
tuning the control gains of the algorithm based on the rating and
bandwidth of the DG power converter. The paper interprets the with positive feedback. In the presence of the utility, the
components of the algorithm that affect the voltage magnitude frequency and voltage shifts are not effective in drifting the
and frequency into block diagrams that can be linearized and two parameters. However, once the grid is disconnected,
studied using continuous time approximations. The model these methods force the frequency and/or voltage to shift
represents DG operation while connected or disconnected from outside the operating windows, causing the inverter to
the main utility. This paper uses frequency domain approach to
disconnect due to o/u voltage and frequency protection.
analyze the range for the gains required by anti-islanding
algorithm to effectively determine the disconnection of the mains Since these were originally developed for a single-phase
grid within an acceptable time duration. The effect of variation of inverter, the technique adopted to measure frequency is based
DG’s operating power level is studied and demonstrated how the on the zero crossing of the voltage waveform, and the voltage
gains of the algorithm can be set to be effective for a wide power magnitude is obtained from RMS calculations. This method
range. The results are validated using detailed time domain DG has been extended to three phase DGs that utilize three-phase
and power system simulations.
continuous tracking Phase Locked Loop (PLL) in a
Index Terms--Distributed generation, anti-islanding, inverters, synchronous reference frame [10].
Sandia voltage scheme, Sandia frequency scheme, power
conditioning, power system protection, power system simulation,
II. ANALYSIS OF SANDIA ANTI-ISLANDING ALGORITHM
power system state estimation.
Implementation of the Sandia anti-islanding algorithm is
I. INTRODUCTION described in [1]. However, a systematic approach to tuning
these algorithms has not been described in literature before. A
I slanding of a grid connected DG occurs when a section of
the utility system containing such generators is
disconnected from the main utility, but the independent
block diagram interpretation of the Sandia’s algorithm is
shown in Fig. 1. This block diagram model of the anti-
DGs continue to energize the utility lines in the isolated islanding algorithms is to determine the gain settings for the
section (termed as an island). Unintended islanding is a Sandia voltage scheme (SVS) and the Sandia frequency
concern primarily because it poses a hazard to utility and scheme (SFS) algorithms. The critical gains of the Sandia
customer equipment, maintenance personnel and the general anti-islanding algorithm are:
public. Poor power quality can damage loads in the island. • Kf for the SFS
Another concern is the out of phase switching of the recloser • Kvp and Kv for SVS
• ωf1 for the wash out functions
• ωf2 for the power regulation loop
This work was supported by National Renewable Energy Laboratories
(NREL) under award number NAD-1-30605-01. The critical gains for SFS and SVS have to be determined
Vinod John is with Northern Power Systems, Waitsfield, VT 05602 USA (e- for RLC loads (set according to IEEE P1547) so as to mitigate
mail: vjohn@northernpower.com). islanding situations [11]. The gain settings of the algorithm,
Zhihong Ye is with General Electric Global Research Center, Niskayuna,
NY 12309 USA. (email: ye@crd.ge.com) shown in Fig. 1, have been obtained by performing a small
Amol Kolwalkar is with General Electric Global Research Center,
Bangalore, India 560 066. (email: amol.kolwalkar@geind.ge.com)
2

Q*
nr
|V| 1 dr Iq* I
% Iq*2 + Id*2
1 + s/ω f2 P*
dr

(I,θ i)
s/ω f1 ∆P + P Id*
tan-1(Iq*/Id*) Inverter
Grid/
P*Kvp+Kv % (V,θ v) Load
1 + s/ω f1 + nr
φ (ω g)
s/ω f1 ∆ω Rθ ∆ θ* + θi
GP
Kf 2ω g
1 + s/ω f1 +
SA +
Anti-islanding algorithm
^
θ
1/s

ω^ θV
ZCD PLL

Fig. 1. The block diagram representation of the Sandia’s anti-islanding algorithm


system frequency (ωg). This can be explained by considering
signal analysis of the DG system with the tuned RLC load the single-phase implementation where the frequency
(according to IEEE 929 2 and IEEE P1547 anti-islanding test command from the SFS is higher than the nominal frequency
specifications) [11], [12]. and reset period of 180o, as shown in Fig. 3.
The algorithm gains are determined by investigating the ∆ωT
open loop behavior as a function of frequency. The voltage ∆θ = , (1)
2π/Rθ
magnitude and the phase signal flow paths were opened so as where, T is the period and Rθ is the reset angle. Simplifying
to obtain the SVS and SFS gains, respectively. The Sandia for the period in terms of ωg, we get
voltage and frequency schemes and the derivation of the block ∆ω Rθ
diagram representations are explained in detail below. ∆θ = . (2)
ωg
A. Sandia Frequency Shift (SFS) Algorithm The effective phase shift φ = ∆θ/2. For the situation of
The block diagram of the SFS algorithm is shown in Fig. 2. π radians for Rθ, the phase shift is given by
The frequency estimate from the PLL is passed through a ∆ω π
φ= , (3)
washout function to determine changes in the ambient 2ωg
frequency. This information multiplied by the SFS gain, is at 60 Hz the relationship is φ = 4.1666e-3 ∆ω.
added to the frequency reference of the current injected by the In standalone mode (SA), the frequency of the island is set
DG inverter. As the DG commanded frequency on average by the interaction of the DG and the load. Hence, in the SA
cannot be different from the grid frequency, the phase angle mode, the phase angle error (∆θ*) caused by SFS is
has to be periodically reset for meaningful power transfer represented by the integral of the frequency error. This can
from the DG to the rest of the grid system to occur. In the be observed from the waveforms of the SFS algorithm shown
single-phase case, this reset of the phase angle in the DG in Fig. 3. This ∆θ* is then added to the reference phase angle,
current reference waveform occurs at the voltage zero and the power factor angle reference, to provide the reference
crossings. command for the phase angle of the current injected by the
In the SFS modification for a three-phase DG, the DG. The magnitude of the DG current is determined by the
frequency of the system is determined using a continuous SVS loop, as explained below. Note that the SA mode
tracking PLL. This frequency estimate is then passed through considered in this analysis is during the transition of from grid
a washout, to determine the trend in system frequency. The parallel mode. In this condition the grid has been
change in estimated system frequency is multiplied by the SFS disconnected but the DG has not yet made any decision for
gain constant (Kf) to obtain the increment or decrement in the mode transition and continues to inject current out of its
output frequency of the DG inverter's current injection into terminals without consideration for instantaneous DG
the grid. terminal voltage regulation.
In grid parallel mode (GP), the grid sets the frequency of
operation of the DG. The Rθ/2ωg block in Fig. 2 is an B. Sandia Voltage Shift (SVS) Algorithm
equivalent representation of the actual DG system behavior The block diagram of the SVS algorithm is shown in Fig. 4.
that captures the change in the phase corresponding to the The input to this block is the magnitude of the system voltage.
error in frequency. The derivation of this block in the GP is The error in the system voltage determines the shift in the
based on the equivalent phase angle change (φ) calculated in reference power, to drive the DG voltage further away from
response to a change in frequency (∆ω) as a function of the the operating voltage range. The voltage magnitude, after a
low pass filter, is also used to determine the
3

Power factor
reference φ
s/ω f1 ∆ω Rθ ∆θ* + θi
GP
Kf 2ω g
1 + s/ω f1 + Phase angle for
SA + current injection
SFS ^
Anti-islanding algorithm θ
1/s

ω^ θV
ZCD PLL
Fig. 2. Block diagram highlighting the SFS component of the Sandia’s anti-islanding algorithm.

sinω gt
SA mode

sin(ω + ∆ ω )t

∆θ θ
GP mode
φ 2π

Fig. 3. Nature of waveforms caused by the SFS algorithm.

magnitude of the reference current settings for the DG. This during the study of SFS algorithms. The frequency
is to ensure that the desired level of real and reactive power is measurement into SFS is held at the nominal value (60 Hz)
being delivered by the DG. As compared to the SFS, the gain during the analysis of the SVS algorithm.
in the feedback loop is not a constant, but is a function of the Fig. 5 shows the open loop gain frequency response of the
real power reference setting. SFS algorithm with the RLC load at 50% and 100% power
The anti-islanding algorithm works by forcing the island level for 3 different values of Kf. The plot shows the open
with the DG to become unstable whenever the grid is loop gains obtained by breaking the θv signal flow path in Fig.
disconnected. Hence, for the active anti-islanding to be 1. All gains referred to in the analysis are calculated in per
effective, the open loop gain has to be greater than one. The unit on the DG base. It can be seen the response is nearly flat
next section interprets the characteristics of the SFS and SVS for low frequencies (10 Hz and below) and droops down at
active anti-islanding algorithms based on frequency domain higher frequencies. Gains greater than 0 dB are inherently
analysis. unstable because it results in positive feedback under closed
loop conditions with phase angle approximately zero (not
C. Implications of the Gains Settings of the Sandia Anti-
Islanding Algorithm shown in the plot). It can be observed that the load power
levels did not affect the loop gain of the SFS algorithm. This
The analysis of block diagram representation of the anti-
implies that the power level of DG operation does not affect
islanding algorithm can be used to evaluate the dependence of
the SFS.
the gain settings of the SFS and SVS on various types of
Similarly, Fig. 6 shows the open loop gain frequency
loads. The gains should be designed for the worst-case load
response of SVS algorithm. As there are two gains to be set
for the schemes to be effective under all circumstances. The
for the SVS, each gain (Kvp and Kv) is independently studied.
RLC load has a quality factor of 2.5 as defined in IEEE 929
In this case the loop gains are obtained by opening the |V|
[12] and UL 1741 [13] testing requirements. The SFS and
signal flow path shown in Fig. 1. The loop gain
SVS algorithms are analyzed separately assuming that they
are decoupled with respect to each other. The voltage
magnitude fed back into SVS is held at the nominal value
4

Magnitude of
Q* output voltage
nr
|V| 1 dr Iq*
% Magnitude for
1 + s/ω f2 P* current injection
I
dr Iq*2 + Id*2
s/ω f1 ∆P + P Id*
P*Kvp+Kv %
1 + s/ω f1 + nr
SVS
Anti-islanding algorithm
Fig. 4. Block diagram highlighting the SVS component of the Sandia’s anti-islanding algorithm.

Fig. 5. Loop gain (in db) of the SFS algorithm with RLC load at 50% (lower Fig. 6. Loop gain of the SVS algorithm for varying Kvp, with Kv = 1, for RLC
subplot) and 100% (upper subplot) power level between 1Hz and 300Hz. loads.

characteristics of the SVS algorithm is flat at low frequencies


(below 5 Hz). The magnitude of the gain is higher than 0dB
indicating that the SVS algorithm will be effective (i.e.
unstable) for the gains shown in Fig. 6.
Fig. 7 indicates additional characteristics of the SVS loop
gain, as a function of the gain constants Kv and Kvp. It can be
observed that the SVS loop gain characteristics have a
tendency to reduce as power is increased. At low power
operation (light loads), it can be observed that there is lower
sensitivity of the SVS loop gain to variations in Kvp (keeping
Kv = 1). It can be observed from Fig. 7 that at overloads the
SVS loop has lower sensitivity to Kv (keeping Kvp = 1). In
general it is observed for all loads, there is a cross over of the Fig. 7. Variations of loop gain in dB at 2 Hz for varying load power level and
dominant gain from Kvp to Kv at the value of 1. gain constants of the SVS (keeping the other parameters fixed at 1.0).
Fig. 7 also indicates that as the loading on the DG
increases, the loop gain has a decreasing trend. This means Hence, an optimum tradeoff between Kv and Kvp has to be
that the SVS algorithm tends to be less effective for higher obtained that minimizes the sensitivity of SVS to load power
loadings. This is because a portion of the SVS response is level. The term Kvp, which multiplied by Power, tries to make
independent of the operating power level (Fig 4). At high it more insensitive to load power level when compared to
loadings, the system is less sensitive; meaning the voltage using a single gain constant in the feedback path of the SVS.
change per Watt of DG output power change is less. Ideally, Figs. 8 (a) and (b) indicate that higher the gain the higher
the gains should have remained constant (same detection the instability causing faster detection of an islanding
time) even for any change in power output. situation. However, setting the gains too high leads to greater
Fig. 8(a) shows the effect of increasing Kvp at different harmonic distortion in the DG load current. Hence, a
minimum acceptable gain has to be selected for both SFS and
load levels. The curves at different power levels tend to
SVS. Besides, too strong positive feedback or too aggressive
converge as the gain is increased. Fig. 8(b) shows the effect
tripping may impose power systems stability issue when DG
of increasing Kv at different load levels. The curves at
penetration is high [14].
different power levels tend to diverge as the gain is increased.
5

(a) (b)
Figure 8. Influence of load and gain constants on the SVS loop gain. (a) effect of Kvp gain (p.u.) on loop gain (dB) at various loads (%); (b) effect of Kv gain (p.u.) on
loop gain (dB) at various loads (%).
shown in Fig. 4. In case the DG terminal voltage rises, the
anti-islanding algorithm tries to increase the power command,
while the power regulation loop through ωf2 lowers the
reference current magnitude to maintain constant real and
reactive power level. The corner frequency of ωf2 has been
set to be decade lower than ωf1 in the anti-islanding algorithm,
so that the change in current magnitude due to voltage
regulation and anti-islanding do not counteract each other.
The setting of 0.01 Hz corner frequency will also allow the
DG prime mover to respond and change its power level in a
time frame (of the order of 10 s) to a change in the measured
output voltage.
The range of values for the SFS and SVS gain determined
from the above analysis provides design space for time
domain simulations of the DG system. The time domain
simulations are application dependent and need to be
considered on an individual basis. The time domain
simulations will provide acceptance trade-off for the time to
detect island.

III. TIME-DOMAIN VALIDATION


Fig. 9. Single line diagram for testing the anti-islanding scenario.
The RLC resonant load as shown in Fig. 9 was first tested
The range of values for the SFS and SVS gain determined without any anti-islanding protection. The waveforms for this
from the above analysis provides design space for time case are shown in Fig. 10. It can be observed from the
domain simulations of the DG system. voltage and current waveforms, that the DG continues to feed
D. Washout and Power Regulation Time Constants the RLC load and forms an island. The frequency and voltage
drift by a small amount due to a minor difference in RLC
The schemes use a number of parameters (ωf1, ωf2, Kvp, Kv, values and due to the small numerical mismatch between the
Kf) that have to be set appropriately for the algorithm to real and reactive power in the load and generator. However,
operate properly. The corner frequency ωf1 is set to the drifts in frequency and voltage magnitude are not
differentiate between a change in measured frequency or sufficient to detect an islanding situation in an acceptable time
voltage due to variation in DG’s operating point and other frame (based on the passive anti-islanding limits on voltage
slow dynamics of the power system. Hence, ωf1 is set to 0.1 and frequency set according to IEEE P1547).
Hz. Hence, voltage or frequency changes that occur in a time Fig. 11 depicts the voltage and current at the DG terminals
of less that 10s can excite the anti-islanding algorithm. If the for the RLC load, for the case where the active anti-islanding
voltage or frequency change sustains for longer than 10 s then algorithm is enabled. The system was islanded at time
it is considered a change in the nominal operating condition. 0.70037 s by disconnecting the grid. The DG detected the
The corner frequency ωf2 is set to 0.01 Hz. This is used to island and tripped due to a drift in the frequency because of
filter the measured voltage amplitude, which is then used to the active anti-islanding algorithm.
obtain the current command from the power command, as
6

The single-phase Sandia’s anti-islanding algorithm can be


effectively adapted for three phase DG applications. In
frequency domain it has been observed that the SFS loop gain
did not vary with the load power, while SVS loop gain varies
with power level. The algorithm when tuned for rated DG
power level will be effective under all realistic operating
conditions.
The model presented in the paper will help the algorithms
optimization. The approach can be extended to other anti-
islanding schemes. Future work will be preformed to study
(a)
these algorithms with dynamic load, such as motors.

V. REFERENCES
[1] J. Stevens, R. Bonn, J. Ginn, S. Gonzalez, and G. Kern, “Development and
testing of an approach to anti-islanding in utility-interconnected
photovoltaic systems,” Sandia Report SAND 2000-1939, August, 2000.
http://www.sandia.gov/pv/0800steve.pdf.
[2] G.A. Smith, P.A. Onions, D.G. Infield, “Predicting islanding operation of
grid connected PV inverters,” IEEE Proc. Electrical Power Applications.,
Vol 147, No. 1, Jan. 2000.
[3] S.-J. Huang and F.-S. Pai, “A new approach to islanding detection of
dispersed generators with self-commuted static power converters,” IEEE
(b) Transactions on Power Delivery, vol. 15, no. 2, April 2000.
Fig. 10. Waveforms for the RLC load without anti-islanding protection (a) load [4] Michael Eugene Ropp, “Design issues for grid-connected photovoltaic
phase voltage, (b) current systems,” Ph.D. Dissertation, GeorgiaTech, October 12, 1998.
[5] P. O’Kane and B. Fox, “Loss of mains detection for embedded generation
by system impedance monitoring,” In International Conference on
Developments in Power System Protection, 25-27th March, 1997, pp. 95-
98.
[6] P.D. Hopewell, N. Jenkins and A.D. Cross, “Loss-of-mains detection for
small generators,” IEE Proc.-Electr. Power Appl., vol. 143, no. 3, May
1996.
[7] A. Kitamura, M. Okamoto, F. Yamamoto, K. Nakaji, H. Matsuda, K.
Otta, “Islanding phenomenon elimination study at Rokko Test Center,” 1st
WCPEC, Hawaii, December 5-9, 1994.
[8] R. W. Wills, “Anti-islanding method and apparatus for distributed power
generation,” US Patent no. 6,219,623. April 17, 2001.
[9] M. Eguchi, H. Kodama, T. Takebayashi and H. Nakata, “Inverter
(a) apparatus islanding operation detecting method and inverter apparatus
capable of surely detecting and islanding operation with a simple
construction,” US Patent no. 6,172,889. January 9, 2001.
[10] “DG Power Quality, Protection and Reliability Case Studies Report”
Program: Reliable, Low Cost Distributed Generator/Utility System
Interconnect, Contract No NAD-1-30605-01, National Renewable Energy
Laboratory, September 28, 2001.
[11] IEEE P1547/D08 Draft Standard for Interconnecting Distributed
Resources with Electric Power Systems, 2001.
[12] IEEE 929 – 2000, IEEE Recommended Practice for Utility Interface of
Photovoltaic (PV) Systems, 2000.
[13] UL 1741, “Inverters, converters, and controllers for use in independent
power systems.
[14] R. A. Walling, N. W. Miller, “Distributed Generation Islanding –
(b) Implications on Power System Dynamic Performance,” Proceedings of the
Figure 11. Waveforms for RLC load with Kf = 10 and Kv and Kvp = 2 (a) load IEEE/PES Summer Power Meeting, Chicago, July, 2002.
phase voltage and (b) current.
VI. BIOGRAPHIES
IV. CONCLUSIONS
This paper modeled and analyzed Sandia Frequency Shift Vinod John (S’92, M’99) received the B.Tech.
(SFS) and Sandia Voltage Shift (SVS) anti-islanding schemes degree in electrical engineering from the Indian
Institute of Technology, Madras, India, in 1992 and
in frequency domain. The implications of the their gains with the M.S.E.E. degree from the University of
respective to effectiveness and power variation are discussed. Minnesota, Minneapolis, in 1994, and the Ph.D. at the
Time domain simulation is provided to validate the gain University of Wisconsin, Madison, in 1999.
He was with General Electric Corporate Research and
settings. The DG without active anti-islanding has a tendency
development between 1999 and 2002. Since June
to island for a resonant RLC load, thus creating a number of 2002, he has been with Northern Power Systems in
possible hazardous conditions for the system. Waitsfield, Vermont. His primary areas of interest are
7

power converters, wind turbine technology, microgrid systems and alternate


energy.

Zhihong Ye (S’98-M’00) received the B.S. and


M.S. degrees in electrical engineering from
Tsinghua University, Beijing, China, in 1992 and
1994, respectively, and the Ph.D. degree from the
Virginia Polytechnic Institute and State University
(Virginia Tech), Blacksburg, in 2000.
Prior to joining Virginia Tech in 1996, he was a
Research Assistant with the Department of
Electrical and Applied Electronics Engineering,
Tsinghua University. Since September 2000, Dr. Ye has been with General
Electric Corporate Research and Development Center, where he is involved with
several alternative energy and distributed generation programs, including power
conditioning systems design for fuel cell and microturbine, distributed generation
and grid interconnection studies, etc. His research interests are multi-phase
power conversion, power conditioning systems for alternative energy, stability
and interaction analysis of distributed power electronics systems.

Amol Kolwalkar received the Bachelor degree in


electrical engineering from SPCE, Mumbai, India, in
1997 and the MTech degree from the Indian Institute
of Technology, Mumbai, India in 2001. He was
employed with TCE from 1997 to 1999. Currently,
he is working with General Electric, Global
Research Centre. His areas of interest include
analysis of distributed generation systems and power
electronics application in power systems.

Potrebbero piacerti anche