Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
slow down so that at the moment of reclosing, in the worst nected to the primary substation. A scheme of the network
case there is phase opposition between the islanded part of the model is presented in Fig. 2.
network and the feeding grid. This can lead to serious current,
voltage or torque transients [11]. Damage to both DG units
and network components are possible. Although there is little
documentation of actual damage to turbine-generators, cumu-
lative impact of these stresses must be taken into account [7].
D. Difficulty of ground-fault detection
An especially challenging anti-islanding issue appears to
come from the difficulty to detect ground fault, occurring in
3-wire MV network, on the low voltage side of delta-wye
connected distribution transformer. Delta-wye connection
breaks the zero sequence system, so zero sequence voltage
cannot be detected on the LV side. Thus DG units connected
to LV network are not able to detect the fault. The phase volt-
ages remain normal until the MV feeder breaker trips.
Fig. 2. Scheme of the network model used in the simulations.
If tripping of DG unit is arranged by means of zero se-
quence voltage, measured by voltage transformers connected The network model was based on Finnish rural 3-wire
to the MV side of the distribution transformer, there is still overhead network. Similar network structures are common
selectivity problem. Protection based on MV zero sequence also in other parts of Europe. The network model was
voltage is not able to distinguish the faulty feeder from equipped with basic overcurrent and ground-fault relays, and
healthy ones. To prevent nuisance tripping caused by faults in there was an option for high-speed 3-pole reclosing. For
adjacent feeders, time selectivity in coordination with feeder ground-fault protection directional ground-fault relays were
directional ground-fault protection could be used. This would, applied since the grounding practices of the simulated cases
however, disturb possible automatic reclosing, as described included ungrounded and resonant grounded systems that are
below. Furthermore, zero sequence voltage detection on the typical in Europe.
MV side of the transformer hardly is feasible for small-scale
DG units deep in LV network. The simulations were based on several types of DG unit
models. In principle there are three different types of genera-
V. SYSTEM MODELING FOR SIMULATION STUDIES tor models: asynchronous generator, synchronous generator
Because it is not possible to carry out extensive testing of and inverter based unit. For simulations reported in this paper,
the behavior of DG units and protection equipment in various only rotating generator models were applied, since the impact
power system faults, simulation studies are indispensable. of inverter based units on fault current is much lower than the
Dynamic modeling for DG and the power system is a key is- impact of rotating generators, and it will be studied later. The
sue. A good survey of relay and power system modeling and asynchronous generator (wind power plant, 1.65 MW) was
interfacing techniques has been given in [12]. applied in a directly connected fixed speed wind generator.
The diesel power plant (7.94 MVA) model was based on a
In this study electromagnetic transient simulation software synchronous generator and the model was developed together
PSCAD™ was used for modeling of power system, DG units with a power plant manufacturer. In the simulations one or
and protective relays. The software package includes many several generators could be connected to any point in feeder 1
power system component models, but most of the models of the network model.
applied in these simulations were from a custom made com-
ponent library that has been developed in research projects The DG units were also equipped with appropriate protec-
during a period of several years. tion devices. So far specific loss-of-mains relay models have
not been included in the models. Typically DG unit models
A typical system model applied when studying the impact have both under-/overvoltage and under-/overfrequency re-
of DG on distribution system protection consists of a simpli- lays.
fied network model with relay models and detailed models of
DG units. In this study the simplified three-wire medium volt- VI. FAULT ARC MODEL
age network model consisted of an equivalent circuit repre- A third party developed prototype of an arc model was ap-
senting the feeding HV network, primary transformer and two plied in some of the simulations. The model has been devel-
MV feeders. One of the feeders was modeled with more de- oped according to theory presented in [13]. The arc model
tails and the other feeder was used only for studying faults consists of two separate models, primary arc and secondary
located in the adjacent feeder. In addition to these there was arc. Primary arc model is applied before the tripping of the
an equivalent circuit representing all the other feeders con- circuit breaker and secondary arc model after breaker trip-
ping. In 1-pole reclosing of HV networks the mutual coupling
4
of phases sustains voltage of the faulty phase and the fault there had been a reclosing trial after a typical 0.3 second auto-
arc. In these MV network simulations reclosing is 3-pole, and reclose open time, the reclosure would certainly have been
DG units sustain the secondary arc. unsuccessful.
VII. SIMULATIONS
A. Objectives
The main objective of the simulations was to analyse the
performance of the protection of the system. Therefore the
simulated cases were fault cases. The distribution system
model included several predefined fault locations. For a simu-
lation run any of these fault locations could be selected as
active. Also the fault type could be selected; it could be either
a phase-to-phase fault or a phase-to-ground fault.
Fig. 5. Simulated phase voltages in a ground fault, unsuccessful reclose attempt.
Special focus area of the simulations was analyzing the
potential impact of DG on automatic reclosing. The fault arc
model was applied in some of the ground fault simulations.
Fig. 9b. When there are no DG units running, there is virtually no arc current
after tripping of the feeder breaker at t = 2.0 s.
Fig. 7. Phase difference between the feeder fed by wind power plants and the
feeding grid during an autoreclosing sequence.
VIII. DISCUSSION
The simulations confirm the challenges to protection of
overhead distribution networks caused by distributed genera-
tion. In order to secure the correct operation of automatic
reclosing, and to prevent out-of-phase reclosure, DG units
must be disconnected clearly before the reclosure. The impor-
tance of the question is growing, because increasing DG pene-
tration makes traditional voltage and frequency based anti-
islanding methods less efficient due to increased likeliness of
load matching.
X. BIOGRAPHIES
Lauri Kumpulainen was born in Padasjoki, Finland,
on April 8, 1962. He received his Master's degree
(1987) and Licentiate degree (2000) in Electrical
Power Engineering from Tampere University of
Technology.
His employment experience includes posts as
development engineer with Hämeen Sähkö Oy and
principal lecturer with Central Ostrobothnia Poly-
technic. Currently he works as a research scientist
with VTT Technical Research Centre of Finland. His
field of interest is electricity distribution networks.