Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Rating Range Prime Rated Current Voltage Frequency Power Factor kW kVA It V F pF 480 600 834 amps 415 Volts 50 Hz 0.8 lag
Standards The Engine Performance corresponds to ISO 3046, BS 5514, DIN 6271 The Genset ratings are based on ISO 8528 The transient performance of the D.G. set conforms to ISO 8528-5, class G-3 The fuel consumption data is based on calorific value and parameters of fuel confirming to IS 1460 The Alternator confirms to IEC 60034 - B Features Global presence Most energy efficient D.G. set in its own rating The DG set and the related accessories are prototype tested, factory built and production tested at the respective factories. Fully automatic. Wider maintenance intervals and as such longer TBO 100% testing of each set with computerized test bench Well experienced and trained engineers for 24 X 7 After sale support Designed to meet the latest environmental norms and certified by CPCB nodal Agency Rating Guide - Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. Note: Rating guidelines conforms to ISO 8528 - 1 and the generators are prime rated generators.
Manufactured by,
Survey No. 59, 343/1, Village Kala, Kherdi, Khanvel, Silvassa - 396 230 U. T. of Dadra & Nagar Haveli.
Design Data Make Model No. Cylinders Cylinder arrangement Method of Operation Speed Aspiration Cooling Method Governor Type Governing Class Compression ratio Displacement Bore / Stoke Dry weight Fuel System Type of Fuel Filters No. of Fuel Filters Filter Capacity Filter change period
Air Intake System Type of Air Filter No. of Air Filters Make Frame Rating KVA KW Voltage Variation
Rated Full Load Current
Engine Technical Details Air Intake System Volvo Air Intake restriction TAD 1642GE 6 Inline 4 - Stroke Cooling System 1500 rpm Radiator cooling Turbo Charged,Inter-cooled Coolant capacity Radiator Radiator fan load Volvo EMSII Type of water pump ISO 8528-5, better than Class A1 16.5:1 Lubrication System 16.12 liter Type Oil 144 / 165 mm Type of Oil Filters 1480 Kgs. No. of Oil Filters Oil Sump capacity Oil system capacity Spin on type paper elem. Oil cooling method Primary - 1 no. Oil Change Intervals Secondary - 1 no. 5 Micron Exhaust System 500 Hours. / 6 months Silencer type (whichever is earlier) No. of Silencers Silencer out let Dia Silencer Insertion loss Dry type Max. allowable Back Pressure One
5kPa -
15W40 API - CI4 Spin on Replaceable 1 42 liters 48 liters Water cooled 500 hrs.
Enclosure -as per IS: 4691 Altitude Ambient Insulation - Stator - Rotor Temp. Rise - IS : 12802 above 40 C Amb Governing Standards Excitation Type Rectifier Bridge Type Excitation Current in Adc - No load - Full load MSL
Alternator Technical Details Leroy Somer AVR Type R-448 54 L 1 % From no load to full 600 Voltage Regulation load with speed drop of 480 less than or equal to 4 % 5% of RV System Response Time 300 ms 835 Amp. Short Circuit Ratio 0.37 IP 23 Wave form distortion THF Less than 4% Stator Winding <=1000 m Star connected Connection Left hand side as seen 40o C Cable Entry from Driving End side Mounted on top of H Terminal Box Position stator body H Over speed 1800 RPM Max Stator - 125 Rotor - 125 Weight 1372Kg IS : 4722 (1992) or BS : 5000 Castrol AP3 / Shell Lubrication or IEC 34 or DIN VDE : 530 Alvania G3 Self Excited Self Regulated Bearings - DE N.A. Brushless 3 phase, 6 pulse with varistor - NDE 6315 for diode protection Direction of rotation Clock wise from Drive End 0.9 Cooling air 0.9 m3/Sec 3.7
2
Genset Control Panel SG 1000 : Standard Supply Features Start/Stop Local and Remote Start/Stop Generator Set Breaker Control Easily Accessible Display Engine Parameters: RPM Oil Pressure Coolant Temperature Hour Meter Battery Volts Running Status Event Recording Electrical Parameters Voltage, Current, Hz, kVA, PF, kWh, kW and kVAR Genset Breaker Status Engine Protection High Water Temperature Low Lube Oil Pressure Engine Over speed Shutdown Electrical Protection kW Overload Unbalanced Load Under/Over Voltage Under/Over Frequency Over Current Protection Running Status Event Recording Electrical Parameters Voltage, Current, Hz, kVA, PF, kWh, kW and kVAR Breaker Status Engine Protection High Water Temperature Low Lube Oil Pressure Engine Over speed Shutdown Electrical Protection kW Overload Unbalanced Load Under/Over Voltage Under/Over Frequency Over Current Protection Generator Set Parameters Performance Data Fuel Consumption:( L/Hrs.) - 100 % Load - 75 % Load - 50 % Load g/KW-h 191.0 197.0 198.0 ( with 5% tolerance) L/Hr. 116.38 95.70 65.12 Display Engine Parameters: RPM Oil Pressure Coolant Temperature Hour Meter Battery Volts SG 2000 : Optional Features Start/Stop Local and Remote Start/Stop Mains Monitoring Generator Set Breaker Control Main Breaker Control Easily Accessible
Generator set accessories Base Frame Construction Colour Fuel Tank Capacity Location Construction Attachments Batteries Make Rating AH capacity High & Low fuel level switch Electronic Fuel Level gauge DG Isolator Panel Genset Dimensions 1X24 Volts 180 Optional Accessories Synchronising Panel Alternator with RTD, BTD and Space Heater Inside canopy M. S. CRCA, 2.0 Thk. Colour Breather Ventilation - Fresh Air Dial type level gauge - Hot Air Lighting system HBL Nife Total Air Requirement Antivibration mounts Folded sheet metal, CRCA Make Black Location Canopy 750 liters. Material M. S. CRCA, 1.6 Thk. 35mm synth. Foam Royal Blue From Alternator end From Radiator front end D C Bulb 12480 CFM Polybond Above the base frame
900
900
INLET
OUTLET
900
Length (mm) 6000 Width (mm) 2000 Height (mm) H 3200 Weight (Dry) Kgs. 8000 Weight (Wet) Kgs. 8200
1000
900
1000
2200
1950
3200
Fresh Air In
1000
2200
2000
LHSV
6000
FRONT VIEW
2000
RHSV
1500
2200
1000
7 9 8