CONTENTS
Page
INTRODUCTION ..........................................................................................................................................................................................................5&6

SECTION ONE - FIXED WIRING & MAINS CABLES


PVC insulated wiring cable 6491X (1.5mm2 to 630mm2) ..............................................................................................................................8
PVC insulated PVC sheathed surface wiring cable type 6181Y (1mm2 to 35mm2) ............................................................................9
XLPE insulated mains and control cable (1.5mm2 to 16mm2)....................................................................................................................10
XLPE insulated mains cable (25mm2 to 400mm2) ..........................................................................................................................................11
XLPE insulated mains cable 3300v (16mm2 to 400mm2) ............................................................................................................................12
XLPE insulated mains cable with aluminium conductors (25mm2 to 300mm2)................................................................................13
XLPE insulated single core non-armoured mains cable (50mm2 to 1000mm2)..................................................................................14
XLPE insulated single core armoured mains cable (50mm2 to 1000mm2) ..........................................................................................15
XLPE insulated non-armoured and armoured single core cable for cathodic protection (6mm2 to 185mm2) ....................16
Low smoke insulated wiring cable 6491B (1.5mm2 to 630mm2)..............................................................................................................17
XLPE insulated low smoke mains and control cable (1.5mm2 to 16mm2) ............................................................................................18
XLPE insulated low smoke mains cable (25mm2 to 400mm2) ..................................................................................................................19
XLPE insulated low smoke single core non-armoured mains cable 1000 volt (50mm2 to 1000mm2) ....................................20
XLPE insulated low smoke single core armoured mains cable (50mm2 to 1000mm2)....................................................................21
Mechanically protected wiring cable (1.0mm2 to 6.0mm2) ........................................................................................................................22
XLPE insulated medium voltage mains cable 11000 volt (25mm2 to 400mm2) and (50mm2 to 630mm2) ..........................23
XLPE insulated medium voltage mains cable 11000 volt (95mm2 to 300mm2) ................................................................................24
XLPE insulated low smoke medium voltage mains cable 11000 volt (35mm2 to 300mm2 and (50mm2 to 630mm2) ............25
Paper insulated medium voltage mains cable 11000 volt (25mm2 to 400mm2) ..............................................................................26
Paper insulated corrugated aluminium sheathed medium voltage mains cable 11000 volt (95mm2 to 300mm2)..........27
XLPE insulated mains cable with 60% conductivity in armour. (Mines & quarries & British Coal) (10mm2 to 300mm2)........28
XLPE insulated lead sheathed control cable for petro-chemical industries (1.5mm2 to 4mm2) ................................................29
XLPE insulated lead sheathed mains cable for petro-chemical industries (25mm2 to 300mm2) ..............................................30
XLPE insulated lead sheathed mains cable for petro-chemical industries (1.5mm2 to 16mm2) ................................................31
XLPE insulated lead sheathed mains cable for petro-chemical industries 3300 volt (25mm2 to 300mm2) ..........................32
PVC insulated single phase split and straight concentric service cable (4mm2 to 35mm2)..........................................................33

SECTION TWO - FLEXIBLE CABLES


PVC insulated flexible cords type 318*y (0.5mm2 to 2.5mm2) ..................................................................................................................36
PVC insulated heat resisting flexible cords type 309*y (0.5mm2 to 2.5mm2)......................................................................................37
LSF insulated flexible cords type 318*B (0.75mm2 to 2.5mm2)..................................................................................................................38
PVC insulated flexible power and control cable type “YY” (0.75mm2 to 1.5mm2) and (2.5mm2 to 50mm2) ..............39 & 40
LSF insulated flexible control cable type “YY” (1.5mm2 to 4.0mm2) ........................................................................................................41
PVC insulated braided flexible control cable type “SY” (0.75mm2 to 2.5mm2) and (4mm2 to 95mm2) ........................42 & 43
PVC insulated braid screened flexible power and control cable type “CY” (0.75mm2 to 10mm2) ..............................................44
Tri-rated and Bi-rated switch gear and control panel wire (0.5mm2 to 400mm2) ............................................................................45
EPR insulated HOFR sheathed flexible power and control cable (0.75mm2 to 2.5mm2) ................................................................46
EPR insulated heavy duty HOFR sheathed flexible mains cable (4mm2) ..............................................................................................47
EPR insulated HOFR sheathed power and control cable (6mm2 to 630mm2) ....................................................................................48
Rubber insulated neoprene sheathed flexible power cable (1.5mm2 to 300mm2) ..........................................................................49
EPR insulated braided screen flexible mains and control cable (1.0mm2 to 16mm2)......................................................................50
EPR insulated flexible coil lead (0.5mm2 to 400mm2)....................................................................................................................................51
EPR insulated flexible welding cable type 0361TQ (16mm2 to 185mm2) ............................................................................................52
Rubber insulated flat cable (1.5mm2 to 70mm2) and PVC insulated flat cable (1.5mm2 to 95mm2) ......................................53
Silicone insulated flexible cable (0.75mm2 to 2.5mm2) ................................................................................................................................54
CONTENTS 4

SECTION THREE - INSTRUMENTATION, CONTROL & COMMUNICATION CABLES


Control and instrumentation cable non-armoured with collective screen (0.5mm2 to 1.5mm2) ..............................................56
Control and instrumentation cable non-armoured with individual and collective screens (0.5mm2 to 1.5mm2)..............57
Control and instrumentation cable armoured with collective screen (0.5mm2 to 2.5mm2) ........................................................58
Control and instrumentation cable armoured with individual and collective screens (0.5mm2 to 1.5mm2)........................59
Control and instrumentation cable lead sheathed armoured with collective screen (0.75mm2 to 1.5mm2) ......................60
Control and instrumentation cable lead sheathed armoured with individual and collective screens (0.75mm2 to 1.5mm2) ..........61
BS5308 part 1 core identification ..........................................................................................................................................................................62
BS5308 part 2 core identification ..........................................................................................................................................................................63
Instrumentation cable to British Steel specification CES20 type 134 (0.75mm2) ............................................................................64
Instrumentation cable to British Steel specification CES20 type 143 (0.75mm2) ............................................................................65
Internal telephone cable type CW1308 ..............................................................................................................................................................66
PVC insulated multipair armoured cable to ESI standard ................................................................................................................67 & 68
ESI 09-6 section 3.6 core identification ................................................................................................................................................................69
ESI 09-6 section 4.5 core identification ................................................................................................................................................................70
Petroleum jelly filled telemetry cable to BS3573 and CW1128/1198 ....................................................................................................71
Defence screened multicore cable ‘C’ type..........................................................................................................................................................72
Defence standard 61-12 parts 4 &5 core identification ..............................................................................................................................73
PVC insulated collective screened thermocouple extension and compensating cable (0.75mm2)............................................74
PVC insulated armoured traffic signal cable, loop feeder cable and loop detector cable ..................................................75 & 76
Colour coding of thermocouple extension and compensating cable ....................................................................................................77

SECTION FOUR - RAILWAY CABLES


Signalling cables types A1, A2, A3, B1 and B2 (0.75mm2 to 95mm2) ......................................................................................................80
Signalling cables types C1, C2, C3, D1, D2, D3, E1, E2 & E3 (0.75mm2 to 35mm2) ..........................................................................81
Power cables and Trackfeeder cables (16mm2 to 1000mm2)......................................................................................................................82

SECTION FIVE - MARINE & OFFSHORE CABLES


EPR insulated non-armoured shipwiring cable (1.5mm2 to 6mm2) ........................................................................................................84
EPR insulated non-armoured shipwiring cable (10mm2 to 630mm2) ....................................................................................................85
EPR insulated braided armour shipwiring cable (1.5mm2 to 4mm2) ......................................................................................................86
EPR insulated braided armoured shipwiring cable (6mm2 to 300mm2)................................................................................................87
EPR insulated single core braided shipwiring cable (6mm2 to 630mm2) ..............................................................................................88

SECTION SIX - FIREPROOF CABLES


Mineral insulated cable ..............................................................................................................................................................................................90
Fire resistant security cable (1.0mm2 to 4mm2) ..............................................................................................................................................91
Fire resistant power and control cable (1.5mm2 to 16mm2) ......................................................................................................................92
Fire resistant power cable (25mm2 to 400mm2) ..............................................................................................................................................93

SECTION SEVEN - INSTALLATION ACCESSORIES ................................................................................................................................................95

SECTION EIGHT - CURRENT RATINGS ................................................................................................................................................................109


5

CLEVELAND CABLE COMPANY


Cleveland Cable Company
Cleveland Cable Company, established in 1978, is
undoubtedly the foremost distributor of electrical
cables in Great Britain and possibly Europe.
The Head Office and principal
stocking location is located at
Middlesbrough in the North East of
England. This site covers an area of
twelve acres and includes over
160,000 square feet of warehousing.
Additionally there are regional depots
at Bristol, Glasgow, London, Milton
Keynes, Newcastle and Warrington.
Each location holds comprehensive
stocks and is equipped with the most
modern handling and measuring
equipment. Deliveries
are made by our own fleet of
purpose-designed vehicles, all of
which are fitted with hydraulic
lifting equipment for safe offloading
onsite and also efficient collection of
empty drums.
CLEVELAND CABLE COMPANY 6

As is illustrated within our catalogue, we stock an


extremely large range of cables for every
conceivable application. All types shown are
considered as standard items to our range and are
always available for immediate delivery. Our stocks
are extremely large and unrivalled in the industry.
We are fortunate to have a very
experienced and dedicated team of
people who are able to assist and
advise. Additionally our policy of
continuing investment in the best
available technology, warehousing,
handling and measuring equipment
and delivery vehicles enables us to
guarantee all our customers an
extremely high quality service.

Enquiries are welcome from


customers worldwide. Our export
service is efficient and reliable with
the ability to ship by air or sea freight
to any destination.

Please feel free to contact the depot of your


choice for an immediate, professional
and trouble free service.
7

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND
MAINS CABLES
FIXED WIRING AND MAINS CABLES 8

FIXED WIRING AND MAINS CABLES


Stranded plain annealed compacted circular copper conductor, PVC outer sheath.
Ref 6491X. Harmonised code HO7V-R. 450 volts grade to BS6004.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING WEIGHT OVERALL


CODE SIZE (MM2) (MM) KG/KM DIAMETER
(MM)
6491X1/5 1.5 7/0.53 21 3.5
6491X2/5 2.5 7/0.67 35 4.2
6491X4 4.0 7/0.85 50 4.8
6491X6 6.0 7/1.04 71 5.4
6491X10 10.0 7/1.35 120 6.8
6491X16 16.0 7/1.70 180 8.0
6491X25 25.0 7/2.14 280 9.8
6491X35 35.0 19/1.53 380 11.0
6491X50 50.0 19/1.78 510 13.0
6491X70 70.0 19/2.14 720 15.0
6491X95 95.0 19/2.52 990 17.0
6491X120 120.0 37/2.03 1200 19.0
6491X150 150.0 37/2.25 1500 21.0
6491X185 185.0 37/2.52 1900 23.5
6491X240 240.0 61/2.25 2500 26.5
6491X300 300.0 61/2.52 3000 29.5
6491X400 400.0 61/2.85 3950 33.5
6491X500 500.0 61/3.20 4950 37.0
6491X630 630.0 127/2.50 6250 41.0

Temperature limits: 4mm2-630mm2 - Brown, Black, Grey,


-15 to +70°C. Blue, Green/Yellow.
Bending radius: Should not be installed at
up to 10mm2 - 3 x overall diameter. temperatures below 0°C.
above 25mm2 - 6 x overall diameter.
Current ratings see page 110
Standard colours available:
1.5mm2 & 2.5mm2 - Brown, Black,
Grey, Blue, Green/Yellow, White,
Orange, Turquoise, Violet, Pink.

PVC INSULATED WIRING


CABLE 6491X
(1.5MM2 TO 630MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
9

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Plain annealed stranded circular copper conductor, single core, PVC insulated,
PVC sheathed, Ref 6181 Y. 300/500 volts grade to BS6004. Brown/Grey or
Blue/Grey. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
6181Y1 1.0 1/1.13 1 28 4.5 20/16
6181Y1/5 1.5 1/1.38 1 36 5.1 20/16
6181Y2/5 2.5 1/1.78 1 51 6.0 20/16
6181Y4 4.0 7/0.85 1 75 6.8 20/16
6181Y6 6.0 7/1.04 1 98 7.4 20/16
6181Y10 10.0 7/1.35 1 150 8.8 20S
6181Y16 16.0 7/1.70 1 220 10.5 20S 0.5
6181Y25 25.0 7/2.14 1 340 12.5 20 0.5
6181Y35 35.0 19/1.53 1 440 13.5 25 0.6
6181Y50 50.0 19/1.78 1 540 14.38 25A2
6181Y70 70.0 19/2.14 1 750 15.3 25A2
6181Y95 95.0 19.2.52 1 1010 17.7 25A2
6181Y120 120.0 37/2.03 1 1250 19.3 32A2

Temperature limits:
-15 to +70°C.
Bending radius:
up to 10mm2 - 3 x overall diameter.
over 10mm2 - 4 x overall diameter.
Should not be installed at
temperatures below 0°C.

Plain annealed stranded circular copper conductor, single core, XLPE insulated,
(LSOH) sheathed, Ref 6181B. 300/500 volts grade to BS7889. Brown/Grey or
Blue/Grey. Flame propagation to BS4066 PT1 and IEC332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER REF
(MM)
6181B1 1.0 1/1.13 1 28 4.5 20/16
6181B1/5 1.5 1/1.38 1 34 5.1 20/16
6181B2/5 2.5 1/1.78 1 49 6.0 20/16
6181B4 4.0 7/0.85 1 75 6.8 20/16
6181B6 6.0 7/1.04 1 99 7.4 20/16
6181B10 10.0 7/1.35 1 155 8.8 20s
6181B16 16.0 7/1.04 1 225 10.5 20s
6181B25 25.0 7/2.14 1 340 12.5 20
6181B35 35.0 19/1.53 1 440 13.5 25
PVC INSULATED
PVC SHEATHED SURFACE
WIRING CABLE
TYPE 6181Y
1MM2 TO 120MM2

XLPE INSULATED
LSOH SHEATHED SURFACE
WIRING CABLE
TYPE 6181B
1MM2 TO 35MM2
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 10

FIXED WIRING AND MAINS CABLES


Stranded plain annealed copper conductors, XLPE insulated, PVC bedding,
galvanised steel wire armour, PVC outer sheath. Black. 600/1000 volts grade to
BS5467. Flame propagation to IEC 332 PT1 and BS4066 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
XLPE2X1/5 1.5 7/0.53 2 305 12.4 20/16 0.5
XLPE3X1/5 1.5 7/0.53 3 338 12.9 20/16 0.6
XLPE4X1/5 1.5 7/0.53 4 381 13.7 20S 0.6
XLPE5X1/5 1.5 7/0.53 5 426 14.2 20S 0.6
XLPE7X1/5 1.5 7/0.53 7 488 15.6 20S 0.7
XLPE8X1/5 1.5 7/0.53 8 501 16.7 20 0.7
XLPE10X1/5 1.5 7/0.53 10 777 18.7 20 0.8
XLPE12X1/5 1.5 7/0.53 12 817 20.1 20 0.8
XLPE19X1/5 1.5 7/0.53 19 1225 24.0 25 1.0
XLPE27X1/5 1.5 7/0.53 27 1553 27.7 32 1.1
XLPE37X1/5 1.5 7/0.53 37 1859 30.3 32 1.2
XLPE48X1/5 1.5 7/0.53 48 2236 32.3 32 1.4
XLPE2X2/5 2.5 7/0.67 2 352 13.2 20S 0.6
XLPE3X2/5 2.5 7/0.67 3 397 13.8 20S 0.6
XLPE4X2/5 2.5 7/0.67 4 452 14.7 20S 0.6
XLPE5X2/5 2.5 7/0.67 5 549 16.3 20S 0.6
XLPE7X2/5 2.5 7/0.67 7 685 17.6 20 0.7
XLPE10X2/5 2.5 7/0.67 10 1000 21.4 25 0.9
XLPE12X2/5 2.5 7/0.67 12 910 21.8 25 0.9
XLPE19X2/5 2.5 7/0.67 19 1500 26.1 25 1.1
XLPE27X2/5 2.5 7/0.67 27 1928 30.3 32 1.2
XLPE37X2/5 2.5 7/0.67 37 2360 33.4 32 1.4
XLPE48X2/5 2.5 7/0.67 48 3888 38.8 40 1.6
XLPE2X4 4.0 7/0.85 2 419 14.3 20S 0.6
XLPE3X4 4.0 7/0.85 3 481 14.9 20S 0.6
XLPE4X4 4.0 7/0.85 4 563 16.2 20 0.7
XLPE5X4 4.0 7/0.85 5 810 18.9 20 0.8
XLPE7X4 4.0 7/0.85 7 912 19.7 20 0.8
XLPE12X4 4.0 7/0.85 12 1400 25.0 25 1.0
XLPE19X4 4.0 7/0.85 19 1852 28.1 32 1.2
XLPE27X4 4.0 7/0.85 27 2630 35.2 40 1.4
XLPE2X6 6.0 7/1.04 2 498 15.4 20S 0.7
XLPE3X6 6.0 7/1.04 3 639 17.4 20 0.7
XLPE4X6 6.0 7/1.04 4 795 18.3 20 0.8
XLPE5X6 6.0 7/1.04 5 970 20.5 25 0.8
XLPE7X6 6.0 7/1.04 7 1180 21.9 25 0.9
XLPE2X10 10.0 7/1.35 2 764 17.9 20 0.8
XLPE3X10 10.0 7/1.35 3 908 18.9 25 0.8
XLPE4X10 10.0 7/1.35 4 1064 20.3 25 0.8
XLPE5X10 10.0 7/1.35 5 1150 22.0 25 0.9
XLPE7X10 10.0 7/1.35 7 1560 25.0 25 1.0
XLPE2X16 16.0 7/1.70 2 900 21.9 25 0.9
XLPE3X16 16.0 7/1.70 3 1220 24.4 25 1.0
XLPE4X16 16.0 7/1.70 4 1410 26.3 25 1.1
XLPE5X16 16.0 7/1.70 5 1800 26.0 25 1.1
XLPE7X16 16.0 7/1.70 7 2237 28.1 32 1.2

Temperature limits: 5 core and above - 10mm2 and


-15 to +90°C. 16mm2 - Brown, Black, Grey, Blue,
Green/Yellow
Bending radius:
6 x overall diameter. 1.5 & 2.5 - 2,3,4 core also available in
white numbered cores to ESI 09-6
Core identification:
2 core - Brown, Blue. Should not be installed at
3 core - Brown, Black, Grey. temperatures below 0°C.
XLPE INSULATED 4 core - Brown, Black, Grey, Blue.
Current ratings, see page 112.
MAINS AND 5 core and above - up to 6mm2 -
White with Black numbers.
CONTROL CABLE
(1.5MM2 TO 16MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
11

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed copper conductors, XLPE insulated, PVC bedding,
galvanised steel wire armour, PVC outer sheath. Black. 600/1000 volts grade to
BS5467. Flame propagation to IEC 332 PT1 and BS4066 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
6942X25 25 7/2.14 2 1000 20.4 25 0.9
6943X25 25 7/2.14 3 1500 23.6 32 1.0
6944X25 25 7/2.14 4 1950 26.1 32 1.2
6945X25 25 7/2.14 5 2370 31.0 32 1.2
6942X35 35 7/2.52 2 1490 27.9 32 1.2
6943X35 35 7/2.52 3 1940 29.6 32 1.2
6944X35 35 7/2.52 4 2350 32.1 32 1.4
6945X35 35 7/2.52 5 3150 35.0 40 1.4
6942X50 50 19/1.78 2 1750 25.8 32 1.2
6943X50 50 19/1.78 3 2225 28.5 32 1.2
6944X50 50 19/1.78 4 2875 32.0 32 1.4
6945X50 50 19/1.78 5 4260 40.0 50S 1.6
6942X70 70 19/2.14 2 2300 29.0 32 1.2
6943X70 70 19/2.14 3 3025 32.2 32 1.4
6944X70 70 19/2.14 4 4250 37.7 40 1.6
6945X70 70 19/2.14 5 5685 43.0 50S 1.8
6942X95 95 19/2.52 2 3100 33.1 40 1.6
6943X95 95 19/2.52 3 4275 37.0 40 1.6
6944X95 95 19/2.52 4 5475 41.7 50S 1.8
6945X95 95 19/2.52 5 7700 52.0 50 R9
6942X120 120 37/2.03 2 3700 36.1 40 1.6
6943X120 120 37/2.03 3 5250 40.4 50S 1.8
6944X120 120 37/2.03 4 7175 47.1 50 2.0
6942X150 150 37/2.25 2 4400 39.3 40 1.8
6943X150 150 37/2.25 3 6650 45.5 50S 2.0
6944X150 150 37/2.25 4 8475 51.4 50 R9
6942X185 185 37/2.52 2 5700 44.7 50S 2.0
6943X185 185 37/2.52 3 8000 49.8 50 2.0
6944X185 185 37/2.52 4 10350 56.6 63S R10
6942X240 240 61/2.25 2 7100 49.0 50 2.0
6943X240 240 61/2.25 3 10150 55.1 63S R9
6944X240 240 61/2.25 4 13000 63.0 63 R10
6942X300 300 61/2.52 2 8500 53.5 63S R9
6943X300 300 61/2.52 3 12400 60.2 63 R10
6944X300 300 61/2.52 4 15750 68.8 75S R11
6942X400 400 61/2.85 2 10650 58.0 63S R10
6943X400 400 61/2.85 3 14770 65.8 75S R11
6944X400 400 61/2.85 4 19950 75.4 90 R12

Temperature limits: Should not be installed at


-15 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 112.
8 x overall diameter.
Core identification:
2 core - Brown, Blue.
3 core - Brown, Black, Grey.
4 core - Brown, Black, Grey, Blue.
5 core - Brown, Black, Grey, Blue,
Green/Yellow.

XLPE INSULATED
MAINS CABLE
(25MM2 TO 400MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 12

FIXED WIRING AND MAINS CABLES


Stranded plain annealed copper conductors, XLPE insulated, PVC bedding,
galvanised steel wire armour, PVC outer sheath. Black. 1900/3300 volts grade
to BS5467. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
XLPE3X16/3 16 7/1.70 3 1600 29.5 32 1.2
XLPE3X25/3 25 7/2.14 3 2060 32.3 32 1.4
XLPE3X35/3 35 7/2.52 3 2330 35.0 40 1.4
XLPE3X50/3 50 19/1.78 3 3040 34.9 40 1.4
XLPE3X70/3 70 19/2.14 3 3800 38.0 40 1.6
XLPE3X95/3 95 19/2.52 3 4730 41.4 50S 1.8
XLPE3X120/3 120 37/2.03 3 6070 45.6 50S 1.8
XLPE3X150/3 150 37/2.25 3 7010 48.3 50 2.0
XLPE3X185/3 185 37/2.52 3 8270 51.6 50 R9
XLPE3X240/3 240 61/2.25 3 10310 56.5 63S R9
XLPE3X300/3 300 61/2.52 3 12300 60.7 63 R10
XLPE3X400/3 400 61/2.85 3 14780 65.8 75S R11

Temperature limits: Should not be installed at


-15 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 116.
8 x overall diameter.
Core identification:
Brown, Black, Grey.

XLPE INSULATED
MAINS CABLE
3300 VOLT
(16MM2 TO 400MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
13

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Solid plain aluminium sectoral conductors, XLPE insulated, PVC bedding,
galvanised steel wire armour, PVC outer sheath. Black. 600/1000 volts grade to
BS5467. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
SAC4X25 25 4 1235 25.4 25 1.0
SAC4X35 35 4 1515 28.9 32 1.2
SAC4X50 50 4 1686 29.5 32 1.2
SAC4X70 70 4 2401 34.7 40 1.4
SAC4X95 95 4 2905 38.3 40 1.6
SAC4X120 120 4 3705 42.2 50S 1.8
SAC4X150 150 4 4550 46.0 50 2.0
SAC4X185 185 4 5076 51.1 50 9
SAC4X240 240 4 6104 56.4 63S 9
SAC4X300 300 4 7212 61.4 63 10

Temperature limits: Should not be installed at


-15 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 114.
8 x overall diameter.
Core identification:
Brown, Black, Grey, Blue.

XLPE INSULATED
MAINS CABLE
WITH ALUMINIUM
CONDUCTORS
(25MM2 TO 300MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 14

FIXED WIRING AND MAINS CABLES


Plain annealed stranded compacted circular copper conductor, single core,
XLPE insulated, PVC outer sheath Black. 600/1000 volts grade to BS7889/97.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND SINGLE TREFOIL


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE CLEAT CLEAT
(MM) (MM)
6181X50 50 19/1.78 540 13.6 25 0.6
6181X70 70 19/2.14 750 15.6 25 0.7
6181X95 95 19/2.52 1010 17.5 25 0.7
6181X120 120 37/2.03 1250 19.2 32 0.8
6181X150 150 37/2.25 1530 21.3 32 0.9
6181X185 185 37/2.52 1900 23.4 32 1.0 207
6181X240 240 61/2.25 2470 26.3 40 1.1 502
6181X300 300 61/2.52 3080 29.0 40 1.2 504
6181X400 400 61/2.85 3890 32.7 50S 1.4 506
6181X500 500 61/3.20 4970 36.6 50S 1.6 509
6181X630 630 127/2.52 6370 41.3 50 1.8 511
6181X800 800 127/2.85 8150 46.3 63S 2.0 515
6181X1000 1000 127/3.20 9860 53.0 63 R9 519

Temperature limits: Should not be installed at


-15 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 116.
8 x overall diameter.
Core identification:
Brown inner / Black outer.

XLPE INSULATED
SINGLE CORE
NON-ARMOURED
MAINS CABLE
(50MM2 TO 1000MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
15

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed compacted circular copper conductor, XLPE insulated,
PVC bedding, aluminium wire armour, PVC outer sheath. Black. 600/1000 volts
grade to BS5467. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOIL


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT
(MM) (MM)
6941AX50 50 19/1.78 1 800 17.7 20 0.8
6941AX70 70 19/2.14 1 940 19.6 25 0.9
6941AX95 95 19/2.52 1 1220 21.5 25 1.0
6941AX120 120 37/2.03 1 1490 23.2 25 1.2
6941AX150 150 37/2.25 1 1870 26.3 32 1.2 502
6941AX185 185 37/2.52 1 2290 28.7 32 1.4 504
6941AX240 240 61/2.25 1 2880 31.4 40 1.4 505
6941AX300 300 61/2.52 1 3520 34.1 40 1.8 507
6941AX400 400 61/2.85 1 4520 38.9 50S 1.8 510
6941AX500 500 61/3.20 1 5680 42.8 50S 1.8 512
6941AX630 630 127/2.52 1 7120 47.3 50 2.0 515
6941AX800 800 127/2.85 1 9220 53.9 63S R9 519
6941AX1000 1000 127/3.20 1 11270 58.8 63S R10 523

Temperature limits: Should not be installed at


-15 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 111.
6 x overall diameter.
Core identification:
Brown inner / Black outer.

XLPE INSULATED
SINGLE CORE ARMOURED
MAINS CABLE
(50MM2 TO 1000MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 16

FIXED WIRING AND MAINS CABLES


Plain annealed compacted circular copper conductor, XLPE insulated, PVC
outer sheath, 600/1000 volts grade generally to BS5467 & IEC 502/1. Colours
Black/Black or Red/Red.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE
(MM) (MM)
6181X6 6 7/1.04 105 7.2 20/16
6181X10 10 7/1.35 150 8.1 20/16
6181X16 16 7/1.70 210 9.0 20S
6181X25 25 7/2.14 305 10.6 20S
6181X35 35 7/2.52 395 11.6 20
6181X50 50 19/1.78 515 13.0 20
6181X70 70 19/2.14 725 14.9 25
6181X95 95 19/2.52 1230 17.5 25
6181X120 120 37/2.03 1355 19.2 32
6181X150 150 37/2.25 1695 21.3 32
6181X185 185 37/2.52 2110 23.4 32

Bending radius: Should not be installed at


4 x overall diameter. temperatures below 0°C.

XLPE INSULATED NON-


ARMOURED AND Plain annealed compacted circular copper conductor, XLPE insulated, PVC
bedding, galvanised steel wire armour, PVC outer sheath. Black. 600/1000
ARMOURED SINGLE CORE
volts grade generally to IEC 502/1 & BS5467.
CABLE FOR CATHODIC
PROTECTION
CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND
(6MM2 TO 185MM2) CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE
(MM) (MM)
6941X6 6 7/1.04 285 11.5 20/16
6941X10 10 7/1.35 355 12.5 20/16
6941X16 16 7/1.70 435 13.5 20S
6941X25 25 7/2.14 585 15.0 20S
6941X35 35 7/2.52 685 16.0 20
6941X50 50 19/1.17 835 17.5 20
6941X70 70 19/2.14 1080 19.5 20
6941X95 95 19/2.52 1375 21.6 25
6941X120 120 37/2.03 1685 23.4 25
6941X150 150 37/2.25 2120 26.4 25
6941X185 185 37/2.52 2505 28.9 32

Bending radius: Should not be installed at


4 x overall diameter. temperatures below 0°C.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
17

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed compacted circular copper conductor, low smoke and
zero halogen (LSOH) outer sheath. 450/750 volts grade to BS7211. Flame
propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING WEIGHT OVERALL


CODE SIZE (MM2) (MM) KG/KM DIAMETER
(MM)
6491B1/5 1.5 7/0.53 22 3.5
6491B2/5 2.5 7/0.67 33 4.2
6491B4 4.0 7/0.85 49 4.8
6491B6 6.0 7/1.04 69 5.4
6491B10 10.0 7/1.35 116 6.8
6491B16 16.0 7/1.70 175 8.0
6491B25 25.0 7/2.14 273 9.8
6491B35 35.0 19/1.53 367 11.0
6491B50 50.0 19/1.78 510 11.8
6491B70 70.0 19/2.14 715 13.6
6491B95 95.0 19/2.52 990 15.9
6491B120 120.0 37/2.03 1230 17.5
6491B150 150.0 37/2.25 1510 19.4
6491B185 185.0 37/2.52 1900 21.7
6491B240 240.0 61/2.25 2490 24.5
6491B300 300.0 61/2.52 3050 27.5
6491B400 400.0 61/2.85 3842 28.5
6491B500 500.0 61/3.20 4900 32.0
6491B630 630.0 127/2.50 6334 38.2

Temperature limits: Should not be installed at


-15 to +70°C. temperatures below 0°C.
Bending radius: Current ratings, see page 110.
up to 10mm2 - 3 x overall diameter
Brass A2 gland size only.
above 25mm2 - 6 x overall diameter
Standard colours available:
1.5mm2 & 2.5mm2 - Brown, Black,
Grey, Blue, Green/Yellow, White,
Orange, Turquoise, Violet, Pink.

LOW SMOKE ZERO


HALOGEN INSULATED
WIRING CABLE 6491B
(1.5MM2 TO 630MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 18

FIXED WIRING AND MAINS CABLES


Plain annealed stranded copper conductors, XLPE insulated, low smoke and
zero halogen (LSOH) bedding, galvanised steel wire armour, low smoke and
zero halogen (LSOH) outer sheath. Black. 600/1000 volts grade to BS6724.
Flame propagation to BS4066 PT1 and IEC 332 PT1.
(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
LSF2X1/5 1.5 7/0.53 2 310 12.5 20/16 0.5
LSF3X1/5 1.5 7/0.53 3 340 13.0 20S 0.6
LSF4X1/5 1.5 7/0.53 4 390 14.0 20S 0.6
LSF5X1/5 1.5 7/0.53 5 426 14.2 20 0.6
LSF7X1/5 1.5 7/0.53 7 490 15.9 20 0.7
LSF12X1/5 1.5 7/0.53 12 830 20.2 20 0.8
LSF19X1/5 1.5 7/0.53 19 1070 23.2 25 1.0
LSF27X1/5 1.5 7/0.53 27 1580 27.9 32 1.2
LSF37X1/5 1.5 7/0.53 37 1880 30.6 32 1.4
LSF48X1/5 1.5 7/0.53 48 2236 32.2 32 1.4
LSF2X2/5 2.5 7/0.67 2 360 13.6 20S 0.6
LSF3X2/5 2.5 7/0.67 3 410 14.1 20S 0.6
LSF4X2/5 2.5 7/0.67 4 470 15.0 20S 0.6
LSF5X2/5 2.5 7/0.67 5 549 16.3 20 0.7
LSF7X2/5 2.5 7/0.67 7 600 17.1 20 0.7
LSF12X2/5 2.5 7/0.67 12 1020 22.4 25 0.9
LSF19X2/5 2.5 7/0.67 19 1530 26.6 25 1.1
LSF27X2/5 2.5 7/0.67 27 1960 30.7 32 1.4
LSF37X2/5 2.5 7/0.67 37 2370 33.8 40 1.4
LSF48X2/5 2.5 7/0.67 48 3888 38.8 40 1.6
LSF2X4 4.0 7/0.85 2 430 14.7 20S 0.6
LSF3X4 4.0 7/0.85 3 500 15.3 20S 0.7
LSF4X4 4.0 7/0.85 4 580 16.4 20 0.7
LSF5X4 4.0 7/0.85 5 810 18.9 20 0.8
LSF7X4 4.0 7/0.85 7 950 20.4 20 0.9
LSF12X4 4.0 7/0.85 12 1400 25.0 25 1.0
LSF27X4 4.0 7/0.85 27 2630 35.2 40 1.4
LSF2X6 6.0 7/1.04 2 500 15.9 20 0.7
LSF3X6 6.0 7/1.04 3 770 16.6 20 0.7
LSF4X6 6.0 7/1.04 4 820 18.7 20 0.8
LSF5X6 6.0 7/1.04 5 970 20.5 25 0.9
LSF7X6 6.0 7/1.04 7 1180 21.9 25 0.9
LSF2X10 10.0 7/1.35 2 800 18.0 20 0.8
LSF3X10 10.0 7/1.35 3 900 19.5 25 0.8
LSF4X10 10.0 7/1.35 4 1060 21.1 25 0.9
LSF5X10 10.0 7/1.35 5 1131 22.0 25 0.9
LSF7X10 10.0 7/1.35 7 1560 25.0 25 1.0
LSF2X16 16.0 7/1.70 2 940 20.0 20 0.8
LSF3X16 16.0 7/1.70 3 1180 21.2 25 0.9
LSF4X16 16.0 7/1.70 4 1410 22.9 25 1.0
LSF5X16 16.0 7/1.70 5 1880 26.2 25 1.1
LSF7X16 16.0 7/1.70 7 2237 28.1 32 1.2

Temperature limits: 1.5 & 2.5 - 2,3,4 core also available in


to +90°C. white numbered cores to ESI 09-6
Bending radius: Should not be installed at
6 x overall diameter. temperatures below 0°C.
Core identification: Current ratings, see page 112.
2 core - Brown, Blue.
3 core - Brown, Black, Grey.
XLPE INSULATED 4 core - Brown, Black, Grey, Blue.
LOW SMOKE ZERO 5 core and above - Up to 6mm2 -
HALOGEN MAINS AND White with Black numbers.
5 core and above - 10mm2 and
CONTROL CABLE
16mm2 - Brown, Black, Grey, Blue,
(1.5MM2 TO 16MM2) Green/Yellow.
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
19

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed copper conductors, XLPE insulated, low smoke and
zero halogen (LSOH) extruded bedding, galvanised steel wire armour, low
smoke and zero halogen (LSOH) outer sheath. Black. 600/1000 volts grade to
BS6724. Flame propagation to BS4066 PT1 and IEC 332 PT1.
(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
LSF2X25 25 7/2.14 2 1250 24.3 25 1.2
LSF3X25 25 7/2.14 3 1720 26.9 32 1.2
LSF4X25 25 7/2.14 4 2090 29.1 32 1.2
LSF5X25 25 7/2.14 5 2370 31.0 32 1.4
LSF2X35 35 7/2.52 2 1720 27.9 32 1.2
LSF3X35 35 7/2.52 3 2130 29.6 32 1.2
LSF4X35 35 7/2.52 4 2590 32.1 32 1.4
LSF5X35 35 7/2.52 5 3150 35.0 40 1.4
LSF2X50 50 19/1.78 2 1800 25.3 32 1.2
LSF3X50 50 19/1.78 3 2380 28.4 32 1.2
LSF4X50 50 19/1.78 4 2960 31.3 32 1.4
LSF5X50 50 19/1.78 5 4260 40.0 50S 1.6
LSF2X70 70 19/2.14 2 2330 28.1 40 1.2
LSF3X70 70 19/2.14 3 3150 32.0 32 1.4
LSF4X70 70 19/2.14 4 4240 36.8 40 1.6
LSF5X70 70 19/2.14 5 5685 43.0 50S 1.8
LSF2X95 95 19/2.52 2 3170 31.9 32 1.6
LSF3X95 95 19/2.52 3 4320 36.7 40 1.6
LSF4X95 95 19/2.52 4 5410 40.6 50S 1.8
LSF5X95 95 19/2.52 5 7700 52.0 50 R9
LSF2X120 120 37/2.03 2 3810 35.1 40 1.6
LSF3X120 120 37/2.03 3 5200 40.0 50S 1.8
LSF4X120 120 37/2.03 4 6980 45.8 50 2.0
LSF5X120 120 37/2.03 5 9030 56.7 63S R9
LSF2X150 150 37/2.25 2 4530 38.2 40 1.8
LSF3X150 150 37/2.25 3 6630 45.1 50S 2.0
LSF4X150 150 37/2.25 4 8320 49.9 50 R9
LSF2X185 185 37/2.52 2 5860 43.3 50S 2.0
LSF3X185 185 37/2.52 3 7980 49.3 50 2.0
LSF4X185 185 37/2.52 4 10080 54.9 63S R9
LSF2X240 240 61/2.25 2 7300 48.3 50 2.0
LSF3X240 240 61/2.25 3 9960 54.5 63S R9
LSF4X240 240 61/2.25 4 12690 61.0 63 R10
LSF2X300 300 61/2.52 2 8790 52.5 63S R9
LSF3X300 300 61/2.52 3 12060 59.5 63 R10
LSF4X300 300 61/2.52 4 15420 66.5 75S R11
LSF3X400 400 61/2.85 3 15330 68.0 75S R11
LSF4X400 400 61/2.85 4 20215 77.5 75 R12M

Temperature limits: Should not be installed at


-25 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 112.
8 x overall diameter.
Core identification:
2 core - Brown, Blue.
3 core - Brown, Black, Grey.
4 core - Brown, Black, Grey, Blue.
5 core - Brown, Black, Grey, Blue,
Green/Yellow.

XLPE INSULATED
LOW SMOKE ZERO
HALOGEN MAINS CABLE
(25MM2 TO 400MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 20

FIXED WIRING AND MAINS CABLES


Plain annealed stranded compacted circular copper conductor, single core,
XLPE insulated, low smoke and zero halogen (LSOH) outer sheath. Black.
600/1000 volts grade to BS6724.
Flame propagation to BS4066 PT1 and IEC 332 PT1.
(Bunched cables to BS4066 PT3 and IEC PT3).

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND SINGLE TREFOIL


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE CLEAT CLEAT
(MM) (MM)
6181B50 50 19/1.78 540 13.6 25 0.6
6181B70 70 19/2.14 750 15.6 25 0.7
6181B95 95 19/2.52 1010 17.5 25 0.7
6181B120 120 37/2.03 1250 19.2 32 0.8
6181B150 150 37/2.25 1530 21.3 32 0.9
6181B185 185 37/2.52 1900 23.4 32 1.0 207
6181B240 240 61/2.25 2470 26.3 40 1.1 502
6181B300 300 61/2.52 3080 29.0 40 1.2 504
6181B400 400 61/2.52 3890 32.7 50S 1.4 506
6181B500 500 61/3.20 4970 36.6 50S 1.6 509
6181B630 630 127/2.52 6370 41.3 50 1.8 511
6181B800 800 127/2.85 8150 46.3 63S 2.0 515
6181B1000 1000 127/3.20 9860 53.00 63 R9 519

Temperature limits: Should not be installed at


-25 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 116.
6 x overall diameter.
Core identification:
Brown inner/Black outer.

XLPE INSULATED
LOW SMOKE ZERO
HALOGEN SINGLE CORE
NON-ARMOURED
MAINS CABLE
1000 VOLT
(50MM2 TO 1000MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
21

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed compacted circular copper conductor, XLPE insulated,
low smoke and zero halogen (LSOH) extruded bedding, aluminium wire
armour, low smoke and zero halogen (LSOH) outer sheath. Black. 600/1000
volts grade to BS6724. Flame propagation to BS4066 PT1 and IEC 332 PT1.
(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOIL


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT
(MM) (MM)
6941AB50 50 19/1.78 1 800 17.7 20 0.8
6941AB70 70 19/2.14 1 940 19.6 25 0.9
6941AB95 95 19/2.52 1 1220 21.5 25 1.0
6941AB120 120 37/2.03 1 1490 23.2 25 1.2
6941AB150 150 37/2.25 1 1870 26.3 32 1.2 502
6941AB185 185 37/2.52 1 2290 28.7 32 1.4 504
6941AB240 240 61/2.25 1 2880 31.4 40 1.4 505
6941AB300 300 61/2.52 1 3520 34.1 40 1.8 507
6941AB400 400 61/2.85 1 4520 38.9 50S 1.8 510
6941AB500 500 61/3.20 1 5680 42.8 50S 1.8 512
6941AB630 630 127/2.52 1 7120 47.3 50 2.0 515
6941AB800 800 127/2.85 1 9220 53.9 63S R9 519
6941AB1000 1000 127/3.20 1 11270 58.8 635 R10 523

Temperature limits: Should not be installed at


-25 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 111.
6 x overall diameter.
Core identification:
Brown inner/Black outer.

XLPE INSULATED
LOW SMOKE ZERO
HALOGEN SINGLE CORE
ARMOURED MAINS CABLE
(50MM2 TO 1000MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 22

SCREENED FIXED WIRING AND MAINS CABLES TO BS 8436


Plain annealed stranded copper, XLPE insulated, tinned annealed stranded
copper earth wire, bonded aluminium tube applied longitudinally low smoke
and zero halogen (LSOH) outer sheath, to BS EN 50267-1:1998 and BS EN
50268-2:2000, UV Stable. 300/500v to BS8436, White.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND 1 HOLE GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLIP REF
(MM) (MM) REF
FSX2X1WH 1.0 7/0.44 2 85 8.60 20S RCHL20 20SA2
FSX3X1WH 1.0 7/0.44 3 105 9.40 20S RCHL20 20SA2
FSX4X1WH 1.0 7/0.44 4 130 10.00 20 RCHL20 20A2
FSX2X1/5WH 1.5 7/0.53 2 106 9.80 20 RCHL20 20A2
FSX3X1/5WH 1.5 7/0.53 3 140 10.40 20 RCHL20 20A2
FSX4X1/5WH 1.5 7/0.53 4 158 11.30 20 RCHL20 20A2
FSX2X2/5WH 2.5 7/0.67 2 135 10.80 20 RCHL20 20A2
FSX3X2/5WH 2.5 7/0.67 3 182 11.10 20 RCHL20 20A2
FSX4X2/5WH 2.5 7/0.67 4 259 12.60 20 RCHL20 20A2
FSX2X4WH 4 7/0.85 2 206 11.50 20 RCHL20 20A2
FSX3X4WH 4 7/0.85 3 265 13.10 25 RCHL25 25A2
FSX4X4WH 4 7/0.85 4 320 13.90 25 RCHL25 25A2
FSX2X6WH 6 7/1.04 2 258 13.10 25 RCHL25 25A2
FSX3X6WH 6 7/1.04 3 328 14.20 25 RCHL25 25A2
FSX4X6WH 6 7/1.04 4 450 14.90 25 RCHL25 25A2

Minimum installation temperature: *Solid cores available on request.


-10°C. Different sheath and core colours
available on request.
Maximum continuous conductors
operating temperature: 10mm2 and 16mm2 available
+90°C. on request
Core identification:
2 core - Brown, Blue.
3 core - Brown, Black, Grey.
4 core - Brown, Black, Grey, Blue.

MECHANICALLY
PROTECTED
WIRING CABLE
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
23

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed circular compacted copper conductors, XLPE
insulated, semi-conducting tape insulated, each core copper tape screened,
PVC bedding, galvanised steel wire armour, PVC outer sheath - Red.
6350/11000 volts grade to BS6622 and IEC 502/1. Flame retardant to BS 4066
PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE RAYCHEM


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT TERMINATION
(MM) (MM) REFERENCE
11KV XLPE3X25RD 25 7/2/14 3 4400 48.8 50 2.0 EPKT 17A3XIH2
11KV XLPE3X35RD 35 19/1/53 3 4900 51.6 50 R9 EPKT 17B3XIH2
11KV XLPE3X50RD 50 19/1/78 3 5600 54.6 63S R9 EPKT 17B3XIH2
11KV XLPE3X70RD 70 19/2/14 3 6500 58.5 63S R10 EPKT 17B3XIH2
11KV XLPE3X95RD 95 19/2/52 3 7800 62.6 63 R10 EPKT 17C3XIH2
11KV XLPE3X120RD 120 37/2/03 3 8900 66.6 75S R11 EPKT 17C3XIH2
11KV XLPE3X150RD 150 37/2/25 3 10000 68.8 75S R11 EPKT 17C3XIH2
11KV XLPE3X185RD 185 37/2/52 3 11600 74.1 75 R12 EPKT 17C3XIH2
11KV XLPE3X240RD 240 61/2/25 3 14800 81.2 90 R14 EPKT 17C3XIH2
11KV XLPE3X300RD 300 61/2/52 3 17300 86.8 90 R15 EPKT 1D3XIH2
11KV XLPE3X400RD 400 61/2/85 3 19300 93.0 R15 EPKT 17D3XIH2

Temperature limits: Should not be installed at


up to 90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 119.
12 x overall diameter.
Core identification:
Brown, Black, Grey tapes.

3 CORE Stranded plain annealed circular compacted copper conductors, XLPE


XLPE INSULATED insulated, semi-conducting tape insulated, copper tape screen, PVC bedding,
MEDIUM VOLTAGE aluminium wire armour, PVC outer sheath - Red. 6350/11000 volts grade to
MAINS CABLE 11000 VOLT BS6622 and IEC 502/1.
(25MM2 TO 400MM2) Flame retardant to BS4066 PT1 and IEC 332 PT1.
AND SINGLE CORE
(50MM2 TO 630MM2) CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOIL RAYCHEM
CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT TERMINATION
(MM) (MM) REFERENCE
10001 50 19/1.78 1 1200 28.0 32 1.2 503/504 EPKT 17B1XI
10002 70 19/2.14 1 1500 29.9 32 1.2 504 EPKT 17B1XI
10003 95 19/2.52 1 1600 31.7 32 1.4 506 EPKT 17C1XI
10004 120 37/2.03 1 2100 33.3 40 1.4 506 EPKT 17C1XI
10005 150 37/2.25 1 2500 35.7 40 1.6 508/509 EPKT 17C1XI
10006 185 37/2.52 1 2900 37.5 40 1.6 508/509 EPKT 17C1XI
10007 240 61/2.25 1 3600 40.1 50S 1.6 510/511 EPKT 17C1XI
10008 300 61/2.52 1 4300 42.4 50S 1.8 512/513 EPKT 17D1XI
10009 400 61/2.85 1 5200 45.8 50S 2.0 514 EPKT 17D1XI
10010 500 61/3.20 1 6500 50.5 50 2.0 516/517 EPKT 17E1XI
10011 630 127/2.52 1 8000 54.7 63S R9 519/521 EPKT 17E1XI

Temperature limits: Should not be installed at


up to 90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 118.
12 x overall diameter.
Core identification:
Brown.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 24

FIXED WIRING AND MAINS CABLES


Plain stranded aluminium conductors, XLPE insulated, semi-conducting tape
insulated, each core copper tape screened, PVC bedding (extruded), galvanised
steel wire armour, PVC outer sheath.
Red. 6350/11000 volts grade to BS6622 and IEC 502/1. Flame propagation to
BS4066 PT1 and IEC 332 PT1

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE RAYCHEM


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT TERMINATION
(MM) (MM) REFERENCE
10115RD 95 19/2.52 3 5800 62.6 63 R10 EPKT 17C3XIH2
10116RD 120 37/2.03 3 6400 66.6 75S R11 EPKT 17C3XIH2
10117RD 150 37/2.25 3 7000 68.6 75S R11 EPKT 17C3XIH2
10118RD 185 37/2.52 3 7800 74.1 75 R12 EPKT 17C3XIH2
10119RD 240 61/2.25 3 9800 81.2 90 R14 EPKT 17C3XIH2
10120RD 300 61/2.52 3 11000 86.8 90 R15 EPKT 17D3XIH2

Temperature limits: Should not be installed at


up to 90°C. temperatures below 0°C.
Bending radius: Current ratings see page 120.
13 x overall diameter.
Core identification:
Brown, Black, Grey tapes.

XLPE INSULATED
MEDIUM VOLTAGE
MAINS CABLE
11000 VOLT
(95MM2 TO 300MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
25

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded plain annealed compacted circular copper conductors, XLPE
insulated, semi-conducting tape insulated, each core copper tape screened,
low smoke and zero halogen (LSOH) bedding, galvanised steel wire armour,
low smoke and zero halogen (LSOH) outer sheath - Red. 6350/11000 volts
grade to BS7835. Flame retardant to BS4066 PT1 and IEC 332 PT1.
(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE RAYCHEM


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT TERMINATION
(MM) (MM) REFERENCE
10302RD 35 19/1.53 3 4900 51.6 50 R9 EPKT 17B3XIH2
10304RD 50 19/1.78 3 5600 54.6 63S R9 EPKT 17B3XIH2
10306RD 70 19/2.14 3 6500 58.5 63S R10 EPKT 17B3XIH2
10308RD 95 19/2.52 3 7800 62.6 63 R10 EPKT 17C3XIH2
10310RD 120 37/2.03 3 8900 66.6 75S R11 EPKT 17C3XIH2
10312RD 150 37/2.25 3 10000 68.8 75 R11 EPKT 17C3XIH2
10314RD 185 37/2.52 3 11600 74.1 75 R12 EPKT 17C3XIH2
10316RD 240 61/2.25 3 14800 81.2 90 R14 EPKT 17C3XIH2
10318RD 300 61/2.52 3 17300 86.8 90 R15 EPKT 17D3XIH2

Temperature limits: Should not be installed at


up to 90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 119.
12 x overall diameter.
Core identification:
Brown, Black, Grey tapes.

3 CORE
XLPE INSULATED LOW Stranded plain annealed compacted circular copper conductor, XLPE insulated,
semi-conducting tape insulated, copper tape screen, low smoke and zero
SMOKE ZERO HALOGEN halogen (LSOH) bedding, aluminium wire armour, low smoke and zero
MEDIUM VOLTAGE halogen (LSOH) outer sheath - Red. 6350/11000 volts grade to BS7835. Flame
MAINS CABLE 11000 VOLT retardant to BS4066 PT1 and IEC 332 PT1.
(35MM2 TO 300MM2) (Bunched cables to BS4066 PT3 and IEC 332 PT3).
AND SINGLE CORE
(50MM2 TO 630MM2) CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOIL RAYCHEM
CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT TERMINATION
(MM) (MM) REFERENCE
10050 50 19/1.78 1 1200 28.8 32 1.2 504 EPKT 17B1XI
10051 70 19/2.14 1 1500 29.9 32 1.2 504 EPKT 17B1XI
10052 95 19/2.52 1 1600 31.7 32 1.4 505 EPKT 17C1XI
10053 120 37/2.03 1 2100 33.3 40 1.4 506 EPKT 17C1XI
10054 150 37/2.25 1 2500 35.7 40 1.6 508 EPKT 17C1XI
10055 185 37/2.52 1 2900 37.5 40 1.6 509 EPKT 17C1XI
10056 240 61/2.25 1 3600 40.1 50S 1.6 511 EPKT 17C1XI
10057 300 61/2.52 1 4300 42.4 50S 1.8 512 EPKT 17D1XI
10058 400 61/2.85 1 5200 45.8 50S 2.0 514 EPKT 17D1XI
10059 500 61X3.20 1 6500 50.5 50 2.0 517 EPKT 17E1XI
10060 630 127X2.52 1 8000 54.7 63S R9 520 EPKT 17E1XI

Temperature limits: Should not be installed at


up to 90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 118.
15 x overall diameter.
Core identification:
Brown.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 26

FIXED WIRING AND MAINS CABLES


Plain annealed copper conductors, paper insulated, paper belted, semi-
conducting carbon paper tape bedding, lead sheathed, textile compound
bedding, galvanised steel wire armour, PVC outer sheath - Red. 6350/11000
volts grade to BS6480/88. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING No. OF WEIGHT OVERALL SINGLE RAYCHEM


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER CLEAT TERMINATION
(MM) REFERENCE
PILC3X25RD 25 7/2.14 3 5230 43.6 1.8 EPKT 17A3MIH2
PILC3X35RD 35 19/1.53 3 5890 42.3 2.0 EPKT 17B3MIH2
PILC3X50RD 50 19/1.78 3 6620 45.6 2.0 EPKT 17B3MIH2
PILC3X70RD 70 19/2.14 3 7820 49.7 2.0 EPKT 17B3MIH2
PILC3X95RD 95 19/2.52 3 9240 53.3 R9 EPKT 17C3MIH2
PILC3X120RD 120 37/2.03 3 10400 56.2 R9 EPKT 17C3MIH2
PILC3X150RD 150 37/2.25 3 11770 59.2 R10 EPKT 17C3MIH2
PILC3X185RD 185 37/2.52 3 13550 62.8 R10 EPKT 17C3MIH2
PILC3X240RD 240 61/2.25 3 16390 67.8 R11 EPKT 17C3MIH2
PILC3X300RD 300 61/2.52 3 19870 73.6 R12 EPKT 17D3MIH2
PILC3X400RD 400 61/2.85 3 23700 79.4 R14 EPKT 17D3MIH2

Temperature limits: Should not be installed at


up to 65°C. temperatures below 0°C.
Bending radius:
13 x overall diameter.
Core identification:
PAPER INSULATED White printed numbers on
insulating papers.
MEDIUM VOLTAGE
MAINS CABLE
Plain aluminium stranded conductors, paper insulated, paper belted, semi-
11000 VOLT conducting carbon paper tape bedding, lead sheathed, textile compound
(25MM2 TO 400MM2) bedding, galvanised steel wire armour, PVC outer sheath - Red. 6350/11000
volts grade to BS6480/88. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING No. OF WEIGHT OVERALL SINGLE RAYCHEM


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER CLEAT TERMINATION
(MM) REFERENCE
10100RD 95 19/2.52 3 7115 53.2 R9 EPKT 17C3MIH2
10103RD 185 37/2.52 3 9521 63.5 R11 EPKT 17C3MIH2
10105RD 300 61/2.52 3 13403 71.5 R12 EPKT 17D3MIH2

Temperature limits: Core identification:


up to 65°C. White printed numbers on
insulating papers.
Bending radius:
13 x overall diameter. Should not be installed at
temperatures below 0°C.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
27

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Stranded aluminium conductors, paper insulated, (mass impregnated, non-
draining type), carbon paper tape belted, corrugated aluminium sheathed, PVC
outer sheath. Red. 6350/11000 volts grade to ESI 09-12.

CCC CONDUCTOR STRANDING No. OF WEIGHT OVERALL SINGLE RAYCHEM


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER CLEAT TERMINATION
(MM) REFERENCE
PICAS3X95 95 19/2.52 3 3400 49.0 2.0 EPKT 17C3MIH2
PICAS3X120 120 37/2.03 3 4000 53.2 R9 EPKT 17C3MIH2
PICAS3X150 150 37/2.25 3 4500 56.6 R9 EPKT 17C3MIH2
PICAS3X185 185 37/2.52 3 5200 60.7 R10 EPKT 17C3MIH2
PICAS3X240 240 61/2.25 3 6400 66.8 R11 EPKT 17D3MIH2
PICAS3X300 300 61/2.52 3 7500 72.5 R12 EPKT 17D3MIH2

Temperature limits: Core identification:


up to 65°C. White numbers printed on
insulating papers.
Bending radius:
13 x overall diameter. Should not be installed at
temperatures below 0°C.

PAPER INSULATED
CORRUGATED
ALUMINIUM SHEATHED
MEDIUM VOLTAGE
MAINS CABLE
11000 VOLT
(95MM2 TO 300MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 28

FIXED WIRING AND MAINS CABLES


Plain annealed stranded copper conductors, XLPE insulated, PVC extruded
bedding, galvanised steel wire armour incorporating tinned copper wires to
provide 60% conductivity of any one phase, PVC outer sheath. Black. 600/1000
volts grade generally to BS5467 and BC295.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
NCB3X10/1 10 7/1.04 3 896 18.9 20 0.8
NCB4X10/1 10 7/1.04 4 1038 20.3 20 0.8
NCB3X16/1 16 7/1.70 3 1205 23.1 25 1.0
NCB4X16/1 16 7/1.70 4 1675 26.3 25 1.1
NCB3X25 25 7/2.14 3 1550 26.9 25 1.1
NCB4X25 25 7/2.14 4 1880 29.1 32 1.2
NCB3X35 35 7/2.52 3 1940 29.6 32 1.2
NCB4X35 35 7/2.52 4 2350 32.1 32 1.4
NCB3X50 50 19/1.78 3 2360 28.4 32 1.2
NCB4X50 50 19/1.78 4 2950 31.3 32 1.4
NCB3X70 70 19/2.14 3 3120 32.0 32 1.4
NCB4X70 70 19/2.14 4 4230 36.8 40 1.6
NCB3X95 95 19/2.52 3 4310 36.7 40 1.6
NCB4X95 95 19/2.52 4 5390 40.6 50S 1.6
NCB3X120 120 37/2.03 3 5160 40.0 50S 1.6
NCB4X120 120 37/2.03 4 6980 45.8 50S 2.0
NCB3X150 150 37/2.25 3 6610 45.1 50S 1.8
NCB4X150 150 37/2.25 4 8300 49.9 50 2.0
NCB3X185 185 37/2.52 3 7920 49.3 50 2.0
NCB4X185 185 37/2.52 4 10070 54.9 63S R9
NCB3X240 240 61/2.25 3 9930 54.5 63S R9
NCB4X240 240 61/2.25 4 12680 61.0 63 R10
NCB3X300 300 61/2.52 3 11970 59.5 63 R10
NCB4X300 300 61/2.52 4 15380 66.5 75S R11

Temperature limits: Core identification:


-15 to +70°C. 3 core - Brown, Black, Grey.
4 core - Brown, Black, Grey, Blue.
Bending radius:
up to 16mm2 - 6 x overall diameter. Should not be installed at
over 16mm2 - 8 x overall diameter. temperatures below 0°C.
Current ratings, see page 112.

Plain annealed stranded copper conductors, XLPE insulated, PVC extruded


bedding, galvanised steel wire armour incorporating tinned copper wires to
provide 60% conductivity of any one phase, PVC outer sheath. Black.
1900/3300 volts grade generally to BS5467 and BC295.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
NCB3X16/3 16 7/1.70 3 1600 29.5 32 1.2
NCB3X25/3 25 19/1.35 3 2060 32.3 32 1.4
NCB3X35/3 35 19/1.53 3 2330 35.0 40 1.4
NCB3X50/3 50 19/1.78 3 3040 34.9 40 1.4
NCB3X70/3 70 19/2.14 3 3800 38.0 40 1.6
NCB3X95/3 95 19/2.52 3 4730 41.4 50S 1.8
NCB3X120/3 120 37/2.03 3 6070 45.6 50S 1.8
NCB3X150/3 150 37/2.25 3 7010 48.3 50 2.0
NCB3X185/3 185 37/2.52 3 8270 51.6 50 R9
NCB3X240/3 240 61/2.25 3 10310 56.5 63S R9
XLPE INSULATED MAINS NCB3X300/3 300 61/2.25 3 12300 60.7 63 R10
CABLE WITH 60%
Temperature limits: Core identification:
CONDUCTIVITY
-15 to +90°C. Brown, Black, Grey.
IN ARMOUR.
(MINES & QUARRIES & Bending radius: Should not be installed at
up to 16mm2 - 6 x overall diameter. temperatures below 0°C.
BRITISH COAL) over 25mm2 - 8 x overall diameter.
(10MM2 TO 300MM2) Current ratings, see page 112.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
29

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Plain annealed stranded copper conductors, XLPE insulated, lead sheathed,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Cores White
with Black numbers. 600/1000 volts grade to BS5467 and EEMUA 133.
Flame propogation to BS 4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
EEMUA2X1/5 ESI 1.5 7/0.53 2 566 15.3 20S 0.6
EEMUA3X1/5 ESI 1.5 7/0.53 3 593 15.8 20 0.6
EEMUA4X1/5 ESI 1.5 7/0.53 4 813 16.64 20 0.7
EEMUA5X1/5 1.5 7/0.53 5 695 16.8 20 0.7
EEMUA7X1/5 1.5 7/0.53 7 1072 17.7 20 0.8
EEMUA12X1/5 1.5 7/0.53 12 1387 22.3 25 0.9
EEMUA19X1/5 1.5 7/0.53 19 1686 24.8 25 1.0
EEMUA27X1/5 1.5 7/0.53 27 2418 30.0 32 1.2
EEMUA37X1/5 1.5 7/0.53 37 2850 32.7 40 1.4
EEMUA2X2/5ESI 2.5 7/0.67 2 772 16.68 20 0.7
EEMUA3X2/5ESI 2.5 7/0.67 3 842 17.21 20 0.7
EEMUA4X2/5ESI 2.5 7/0.67 4 934 18.28 25 0.7
EEMUA5X2/5 2.5 7/0.67 5 1038 18.4 20 0.8
EEMUA7X2/5 2.5 7/0.67 7 1324 20.02 25 0.9
EEMUA12X2/5 2.5 7/0.67 12 1750 25.19 32 1.0
EEMUA19X2/5 2.5 7/0.67 19 2489 29.9 32 1.2
EEMUA27X2/5 2.5 7/0.67 27 3248 34.17 40 1.4
EEMUA37X2/5 2.5 7/0.67 37 3840 42.81 50S 1.6
EEMUA5X4 4.0 7/0.85 5 1014 20.6 25 0.9
EEMUA7X4 4.0 7/0.85 7 1110 21.5 25 0.9

Temperature limits:
-15 to +90°C.
Bending radius:
12 x overall diameter.
Core identification:
White with Black numbers.

XLPE INSULATED LEAD


SHEATHED CONTROL
CABLE FOR
PETRO-CHEMICAL
INDUSTRIES
(1.5MM2 TO 4MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 30

FIXED WIRING AND MAINS CABLES


Plain annealed stranded copper conductors, XLPE insulated, lead sheathed,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. 600/1000
volts grade to BS5467 and EEMUA 133 (formerly OCMA 4B). Flame
propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
EEMUA2X25 25 7/2.14 2 2094 27.5 32 1.1
EEMUA3X25 25 7/2.14 3 2673 30.5 32 1.2
EEMUA4X25 25 7/2.14 4 3204 32.5 40 1.4
EEMUA2X35 35 19/1.53 2 2868 27.5 32 1.4
EEMUA3X35 35 19/1.53 3 3338 31.0 32 1.4
EEMUA4X35 35 19/1.53 4 4043 33.5 40 1.4
EEMUA2X50 50 19/1.78 2 2783 28.1 32 1.2
EEMUA3X50 50 19/1.78 3 3572 34 40 1.4
EEMUA4X50 50 19/1.78 4 4456 37.5 40 1.4
EEMUA2X70 70 19/2.14 2 3566 31.1 32 1.4
EEMUA3X70 70 19/2.14 3 4639 37.5 40 1.4
EEMUA4X70 70 19/2.14 4 6160 43.5 50S 1.6
EEMUA2X95 95 19/2.52 2 4678 35.1 40 1.4
EEMUA3X95 95 19/2.52 3 6023 43 50S 1.6
EEMUA4X95 95 19/2.52 4 7592 47.5 50 1.8
EEMUA2X120 120 37/2.03 2 5641 38.5 50S 1.6
EEMUA3X120 120 37/2.03 3 7392 46.5 50S 1.8
EEMUA4X120 120 37/2.03 4 9802 53 63S 2.0
EEMUA2X150 150 37/2.25 2 6660 41.8 50S 1.8
EEMUA3X150 150 37/2.25 3 9242 52.5 50 2.0
EEMUA4X150 150 37/2.25 4 11757 58 63S R9
EEMUA2X185 185 37/2.52 2 8457 47.1 50 2.0
EEMUA3X185 185 37/2.52 3 11054 56.5 63S R9
EEMUA4X185 185 37/2.52 4 14117 63 63 R10
EEMUA2X240 240 61/2.25 2 10286 52.3 63S R9
EEMUA3X240 240 61/2.25 3 13792 55.9 63S R9
EEMUA4X240 240 61/2.25 4 17700 65.8 75S R11
EEMUA2X300 300 61/2.52 2 12245 56.7 63S R9
EEMUA3X300 300 61/2.52 3 16519 64.1 63 R11
EEMUA4X300 300 61/2.52 4 21173 71.5 75S R12

Temperature limits:
-15 to +90°C.
Bending radius:
12 x overall diameter.
Core identification:
2 core - Brown, Blue
3 core - Brown, Black, Grey.
4 core - Brown, Black, Grey, Blue.
Should not be installed at
temperatures below 0°C.

XLPE INSULATED
LEAD SHEATHED MAINS
CABLE FOR
PETRO-CHEMICAL
INDUSTRIES
(25MM2 TO 300MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
31

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
Plain annealed stranded copper conductors, XLPE insulated, lead sheathed,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. 600/1000
volts grade to BS5467 and EEMUA 133 (formerly OCMA 4B). Flame
propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
EEMUA2X1/5 1.5 7/0.53 2 690 15.32 20S 0.6
EEMUA3X1/5 1.5 7/0.53 3 744 15.76 20 0.6
EEMUA4X1/5 1.5 7/0.53 4 813 16.64 20 0.7
EEMUA2X2/5 2.5 7/0.67 2 772 16.68 20 0.7
EEMUA3X2/5 2.5 7/0.67 3 842 17.21 20 0.7
EEMUA4X2/5 2.5 7/0.67 4 934 18.28 25 0.7
EEMUA2X4 4.0 7/0.85 2 883 17.66 20 0.7
EEMUA3X4 4.0 7/0.85 3 1190 18.27 20 0.7
EEMUA4X4 4.0 7/0.85 4 1310 19.5 25 0.8
EEMUA2X6 6.0 7/1.04 2 1001 18.66 25 0.8
EEMUA3X6 6.0 7/1.04 3 1122 19.35 25 0.8
EEMUA4X6 6.0 7/1.04 4 1402 21.64 25 0.9
EEMUA2X10 10.0 7/1.35 2 1227 20.66 25 0.8
EEMUA3X10 10.0 7/1.35 3 1493 22.2 25 0.9
EEMUA4X10 10.0 7/1.35 4 1710 24.07 25 1.0
EEMUA2X16 16.0 7/1.70 2 1565 23.30 25 1.0
EEMUA3X16 16.0 7/1.70 3 1813 24.69 32 1.0
EEMUA4X16 16.0 7/1.70 4 2191 26.68 32 1.1

Temperature limits:
-15 to +90°C.
Bending radius:
12 x overall diameter.
Core identification:
2 core - Brown, Blue.
3 core - Brown, Black, Grey.
4 core - Brown, Black, Grey, Blue.
Should not be installed at
temperatures below 0°C.

XLPE INSULATED LEAD


SHEATHED MAINS CABLE
FOR PETRO-CHEMICAL
INDUSTRIES
(1.5MM2 TO 16MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIXED WIRING AND MAINS CABLES 32

FIXED WIRING AND MAINS CABLES


Plain annealed stranded copper conductors, XLPE insulated, lead sheathed,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black.
1900/3300 volts grade to BS5467 and EEMUA 133 (formerly OCMA 4B).
Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
EEMUA3X25/3 25 7/2.14 3 3400 32.5 32 1.4
EEMUA3X35/3 35 19/1.53 3 3560 38.4 40 1.6
EEMUA3X50/3 50 19/1.78 3 4520 38.1 40 1.6
EEMUA3X70/3 70 19/2.14 3 5550 41.4 50s 1.8
EEMUA3X95/3 95 19/2.52 3 6770 45.0 50s 2.0
EEMUA3X120/3 120 37/2.03 3 8390 49.4 50 2.0
EEMUA3X150/3 150 37/2.25 3 9630 52.3 50 R9
EEMUA3X185/3 185 37/2.52 3 11270 55.8 63s R9
EEMUA3X240/3 240 61/2.25 3 13720 60.9 63 R10
EEMUA3X300/3 300 61/2.52 3 16380 65.3 75s R11

Temperature limits: Core identification:


-15 to +90°C. Brown, Black, Grey.
Bending radius: Should not be installed at
12 x overall diameter. temperatures below 0°C.

XLPE INSULATED
LEAD SHEATHED MAINS
CABLE FOR
PETRO-CHEMICAL
INDUSTRIES
3300 VOLT
(25MM2 TO 300MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
33

FIXED WIRING AND MAINS CABLES


FIXED WIRING AND MAINS CABLES
SPLIT CONCENTRIC
Plain annealed stranded copper phase conductor, XLPE insulated surrounded
by a concentric layer of plain annealed solid copper neutral conductors. XLPE
insulated and plain annealed solid strand bare copper earth conductors, PVC
outer sheath. Black. 600/1000 volts grade to BS 4553/88.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE
(MM) (MM)
4 SPLITCON 4 7/0.85 206 9.6 20S
6 SPLITCON 6 7/1.04 281 11.4 20
10 SPLITCON 10 7/1.35 394 12.7 20
16 SPLITCON 16 7/1.70 583 14.6 25
25 SPLITCON 25 *7/2.14 843 18.7 32
35 SPLITCON 35 7/2.52 1300 23.0 40

* Stranding of neutral is the same as Should not be installed at


phase conductor except 25 sq mm temperatures below 0°C.
which has 11 x 1.70mm.
Also available in Violet outer sheath
Conductor identification: in 6mm, 10mm, 16mm & 25mm.
Brown Live/Blue Neutral.

Straight CONCENTRIC (CNE)


Plain annealed stranded copper phase conductor, PVC insulated surrounded by
a concentric layer of plain annealed solid copper neutral/earth conductors in
concentric layer, PVC outer sheath. Black. 600/1000 volts grade to BS 4553/88
& ESI 09-7.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE
(MM) (MM)
4 STRCON 4 7/0.85 180 9.0 20S
6 STRCON 6 7/1.04 230 10.0 20S
16 STRCON 16 7/1.70 440 12.0 20
25 STRCON 25 7/2.14 600 15.0 25
35 STRCON 35 7/2.25 850 16.0 25

Temperature limits: Should not be installed at


-15 to +70°C. temperatures below 0°C.
Bending radius:
10 x overall diameter.

XLPE INSULATED SINGLE


PHASE SPLIT AND
STRAIGHT CONCENTRIC
SERVICE CABLE
(4MM2 TO 35MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
34
35

FLEXIBLE CABLES
FLEXIBLE CABLES
FLEXIBLE CABLES 36

FLEXIBLE CABLES
PVC INSULATED FLEXIBLE CORDS TYPE 318*Y
Plain annealed flexible copper conductors, PVC insulated, PVC outer sheath.
Black or White. 300/500 volts grade to BS6500. (Harmonized code HO5VV-F).
Flame propagation to BS4066 PT1 and IEC 332 PT1. (*HO3VV-F)

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
2182Y/5 0.5 16/0.2 2 36 5.4 20/16
2182Y/75 0.75 24/0.2 2 45 5.8 20/16
2183Y/5 0.5 16/0.2 3 44 5.6 20/16
2183Y/75 0.75 24/0.2 3 55 6.1 20/16
3182Y/5 0.5 16/0.2 2 52 6.3 20/16
3183Y/5 0.5 16/0.2 3 5 6.3 20/16
3182Y/75 0.75 24/0.20 2 59 6.8 20/16
3183Y/75 0.75 24/0.20 3 70 7.2 20/16
3184Y/75 0.75 24/0.20 4 85 7.7 20/16
3185Y/75 0.75 24/0.20 5 110 8.5 20S
3182Y1 1.0 24/0.20 2 69 7.2 20/16
3183Y1 1.0 32/0.20 3 82 7.6 20/16
3184Y1 1.0 32/0.20 4 105 8.5 20S
3185Y1 1.0 32/0.20 5 130 9.1 20S
3182Y1/5 1.5 30/0.25 2 95 8.2 20/16
3183Y1/5 1.5 30/0.25 3 120 8.9 20S
3184Y1/5 1.5 30/0.25 4 150 10.0 20S
3185Y1/5 1.5 30/0.25 5 180 11.0 20
3182Y2/5 2.5 50/0.25 2 145 9.9 20S
3183Y2/5 2.5 50/0.25 3 180 10.8 20S
3184Y2/5 2.5 50/0.25 4 220 11.3 20
3185Y2/5 2.5 50/0.25 5 265 12.8 20

Temperature limits: 4 core - Blue, Brown, Black,


Fixed - -5 to +60°C. Green/Yellow.
Flexing - +5 to +60°C. 5 core - Blue, Brown, Black, Black,
Green/Yellow.
Bending radius:
Fixed 2 x overall diameter. Should not be installed at
Flexing 6 x overall diameter. temperatures below 0°C.
Core identification: Current ratings, see page 115.
2 core - Blue, Brown.
3 core - Blue, Brown, Green/Yellow.

PVC INSULATED
FLEXIBLE CORDS
TYPE 318*Y & 218*Y
(0.5MM2 TO 2.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
37

FLEXIBLE CABLES
FLEXIBLE CABLES
PVC INSULATED HEAT RESISTING FLEXIBLE CORDS TYPE 309*Y
Plain annealed flexible copper conductors heat resisting PVC outer sheath. White
300/500 volts grade to BS6141. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
3092Y/5 0.5 16/0.20 2 46 6.3 20/16
3093Y/5 0.5 16/0.20 3 66 6.5 20/16
3094Y/5 0.5 16/0.20 4 70 7.2 20/16
3092Y/75 0.75 24/0.20 2 56 6.8 20S
3093Y/75 0.75 24/0.20 3 68 7.2 20S
3094Y/75 0.75 24/0.20 4 85 7.7 20S
3092Y1 1.0 32/0.20 2 65 7.2 20S
3095Y/75 0.75 24/0.2 5 104 8.5 20S
3093Y1 1.0 32/0.20 3 77 7.6 20S
3094Y1 1.0 32/0.20 4 100 8.5 20S
3092Y1/5 1.5 30/0.25 2 80 8.2 20S
3093Y1/5 1.5 30/0.25 3 100 8.9 20S
3094Y1/5 1.5 30/0.25 4 130 10.0 20
3092Y2/5 2.5 50/0.25 2 135 10.0 20S
3093Y2/5 2.5 50/0.25 3 150 10.8 20
3094Y2/5 2.5 50/0.25 4 195 11.8 20

Temperature limits: Core identification:


Fixed - -5 to +90°C. 2 core - Blue, Brown.
Flexing - +5 to +90°C. 3 core - Blue, Brown, Green/Yellow.
Bending radius: 4 core - Blue, Brown, Black,
Fixed - 2 x overall diameter. Green/Yellow.
Flexing - 6 x overall diameter.
Should not be installed at
Current ratings, see page 115. temperatures below 0°C.

PVC INSULATED
FLEXIBLE CORDS
TYPE 309*Y
(0.5MM2 TO 2.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 38

FLEXIBLE CABLES
Plain annealed copper conductors, Low smoke and zero halogen (LS0H) insulated,
low smoke and zero halogen (LS0H) outer sheath. Black or white. 300/500 volts
grade (Generally to BS6500) flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
3182B/75 0.75 24/0.2 2 6.8 59 20/16
3183B/75 0.75 24/0.2 3 7.2 70 20/16
3184B/75 0.75 24/0.2 4 7.7 85 20/16
3185B/75 0.75 24/0.2 5 8.5 110 20S
3182B1 1.00 32/0.2 2 7.2 69 20/16
3183B1 1.00 32/0.2 3 7.6 82 20/16
3184B1 1.00 32/0.2 4 8.5 105 20S
3185B1 1.0 32/0.2 5 130 9.1 20S
3182B1/5 1.5 30/0.25 2 8.2 95 20/16
3183B1/5 1.5 30/0.25 3 8.9 120 20S
3184B1/5 1.5 30/0.25 4 10 150 20S
3185B1/5 1.5 30/0.25 5 11 180 20
3182B2/5 2.5 50/0.25 2 9.9 145 20S
3183B2/5 2.5 50/0.25 3 10.8 180 20S
3184B2/5 1.5 50/0.25 4 11.3 220 20
3185B2/5 2.5 50/0.25 5 265 12.8 20

Temperature limits: Core identification:


-15 to +70°c 2 core - Brown, Blue.
3 core - Blue, Brown, Green/Yellow.
Bending radius:
4 core - Blue, Brown, Black,
Fixed 4x overall diameter
Green/Yellow.
Flexing 6x overall diameter
5core - Blue, Brown, Black, Black,
Green/Yellow.

LOW SMOKE
ZERO HALOGEN FLEXIBLE
CORDS TYPE 318*B
(0.75MM2 TO 2.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
39

FLEXIBLE CABLES
FLEXIBLE CABLES
Plain annealed flexible copper conductors, PVC insulated, PVC sheathed. Grey.
300/500 volts grade, generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
YY2X/75 0.75 24/0.20 2 53 6.0 20/16
YY3X/75 0.75 24/0.20 3 63 6.3 20/16
YY4X/75 0.75 24/0.20 4 76 6.9 20/16
YY5X/75 0.75 24/0.20 5 93 7.5 20/16
YY7X/75 0.75 24/0.20 7 116 8.2 20/16
YY12X/75 0.75 24/0.20 12 194 11.1 20S
YY18X/75 0.75 24/0.20 18 278 13.0 20
YY25X/75 0.75 24/0.20 25 379 15.9 25
YY34X/75 0.75 24/0.20 34 516 18.2 25
YY50X/75 0.75 24/0.20 50 734 21.7 32
YY65X/75 0.75 24/0.20 65 912 24.3 32
YY2X1 1.0 32/0.20 2 60 6.2 20/16
YY3X1 1.0 32/0.20 3 73 6.5 20/16
YY4X1 1.0 32/0.20 4 89 7.1 20/16
YY5X1 1.0 32/0.20 5 109 7.8 20/16
YY7X1 1.0 32/0.20 7 137 8.5 20S
YY12X1 1.0 32/0.20 12 229 11.5 20
YY18X1 1.0 32/0.20 18 331 13.5 25
YY25X1 1.0 32/0.20 25 452 16.5 25
YY34X1 1.0 32/0.20 34 615 18.9 25
YY41X1 1.0 32/0.20 41 770 21.0 32
YY50X1 1.0 32/0.20 50 879 22.5 32
YY65X1 1.0 32/0.20 65 1171 26.5 40
YY2X1/5 1.5 30/0.25 2 77 6.8 20/16
YY3X1/5 1.5 30/0.25 3 95 7.2 20/16
YY4X1/5 1.5 30/0.25 4 117 7.8 20/16
YY5X1/5 1.5 30/0.25 5 144 8.6 20S
YY7X1/5 1.5 30/0.25 7 183 9.4 20S
YY8X1/5 1.5 30/0.25 8 232 12.5 20
YY10X1/5 1.5 30/0.25 10 265 12.4 20
YY12X1/5 1.5 30/0.25 12 307 12.8 20
YY18X1/5 1.5 30/0.25 18 461 15.4 25
YY25X1/5 1.5 30/0.25 25 627 18.8 25
YY34X1/5 1.5 30/0.25 34 850 21.4 32
YY50X1/5 1.5 30/0.25 50 1212 25.4 40
YY65X1/5 1.5 30/0.25 65 1602 29.5 40

Temperature limits: Core identification:


-5 to +70°C. 2 core - Black with White numbers.
3 core and above - Black with White
Bending radius:
numbers plus Green/Yellow.
Static - 6 x overall diameter.
Flexing - 15 x overall diameter. Should not be installed at
temperatures below -5°C.

PVC INSULATED FLEXIBLE


POWER AND CONTROL
CABLE TYPE “YY”
(0.75MM2 TO 1.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 40

FLEXIBLE CABLES
CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND
CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
YY2X2/5 2.5 50/0.25 2 114 8.0 20/16
YY3X2/5 2.5 50/0.25 3 143 8.5 20S
YY4X2/5 2.5 50/0.25 4 177 9.3 20S
YY5X2/5 2.5 50/0.25 5 229 10.6 20S
YY7X2/5 2.5 50/0.25 7 293 11.6 20
YY8X2/5 2.5 50/0.25 8 333 13.5 25
YY12X2/5 2.5 50/0.25 12 488 15.7 25
YY18X2/5 2.5 50/0.25 18 729 18.8 25
YY25X2/5 2.5 50/0.25 25 989 22.9 32
YY34X2/5 2.5 50/0.25 34 1338 26.0 40
YY3X4 4.0 56/0.30 3 230 11.6 20
YY4X4 4.0 56/0.30 4 289 12.0 20
YY5X4 4.0 56/0.30 5 357 13.2 20
YY7X4 4.0 56/0.30 7 457 14.4 25
YY3X6 6.0 84/0.30 3 326 13.2 20
YY4X6 6.0 84/0.30 4 480 14.4 25
YY5X6 6.0 84/0.30 5 583 16.6 25
YY7X6 6.0 84/0.30 7 782 18.6 25
YY3X10 10.0 80/0.40 3 610 16.7 25
YY4X10 10.0 80/0.40 4 737 18.8 25
YY5X10 10.0 80/0.40 5 914 20.9 32
YY3X16 16.0 126/0.40 3 812 18.5 25
YY4X16 16.0 126/0.40 4 1087 22.2 32
YY5X16 16.0 126/0.40 5 1370 25.0 32
YY4X25 25.0 196/0.40 4 960 25.8 32
YY5X25 25.0 196/0.40 5 1200 29.3 40
YY4X35 35.0 276/0.40 4 1344 28.9 40
YY5X35 35.0 276/0.40 5 1680 33.1 50S
YY4X50 50.0 396/0.40 4 1920 34.5 50S

Temperature limits: Should not be installed at


-5 to +70°C. temperatures below -5°C.
Bending radius:
Static - 6 x overall diameter.
Flexing - 15 x overall diameter.
Core identification:
2 core - Black with White numbers.
3 core and above - Black with White
numbers plus Green/Yellow.

PVC INSULATED FLEXIBLE


POWER AND CONTROL
CABLE TYPE “YY”
(2.5MM2 TO 50MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
41

FLEXIBLE CABLES
FLEXIBLE CABLES
Plain annealed flexible copper conductors, low smoke and zero halogen (LSOH)
insulated, low smoke and zero halogen (LSOH) sheathed. Grey. 300/500 volts
grade, generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
YY2X1/5LSF 1.5 30/0.25 2 77 6.80 20/16
YY3X1/5LSF 1.5 30/0.25 3 95 7.20 20/16
YY4X1/5LSF 1.5 30/0.25 4 117 7.80 20/16
YY5X1/5LSF 1.5 30/0.25 5 144 8.60 20S
YY7X1/5LSF 1.5 30/0.25 7 183 9.40 20S
YY12X1/5LSF 1.5 30/0.25 12 307 12.80 20
YY18X1/5LSF 1.5 30/0.25 18 461 15.40 25
YY25X1/5LSF 1.5 30/0.25 25 627 18.80 25
YY34X1/5LSF 1.5 30/0.25 34 850 21.40 32
YY2X2/5LSF 2.5 50/0.25 2 114 8.00 20/16
YY3X2/5LSF 2.5 50/0.25 3 143 8.50 20S
YY4X2/5LSF 2.5 50/0.25 4 177 9.30 20S
YY5X2/5LSF 2.5 50/0.25 5 229 10.60 20S
YY3X4LSF 4.0 56/0.30 3 230 11.60 20

Temperature limits: Core identification:


-5 to +70°C 2 Core - Black with white numbers
3 Core and above
Bending radius:
Black with white numbers plus
Static
Green/Yellow
6 x Overall Diameter
Should not be installed at
Flexing:
temperatures below -5°C.
15 x Overall Diameter

Plain annealed flexible copper conductors, low smoke and zero halogen (LSOH)
insulated, mylar taped, tinned copper wire braid, low smoke and zero halogen (LSOH)
outer sheath. Grey. 300/500 volts grade, generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
CY2X/75LSF 0.75 24/0.20 2 55 6.50 20S
CY3X/75LSF 0.75 24/0.20 3 77 7.00 20S
CY4X/75LSF 0.75 24/0.20 4 92 7.60 20S
CY2X1/5LSF 1.5 30/0.25 2 86 7.50 20S
CY3X1/5LSF 1.5 30/0.25 3 118 8.30 20S
CY4X1/5LSF 1.5 30/0.25 4 142 8.90 20S
CY5X1/5LSF 1.5 30/0.25 5 171 9.70 20S

Temperature limits: Core identification:


-5 to 70°C 2 Core - Black with White numbers
3 Core and above
Bending radius:
Black with White numbers plus
Static
Green/Yellow
6 x Overall Diameter
Should not be installed at
Flexible:
temperatures below -5°C.
15 x Overall Diameter

LSOH SHEATHED
FLEXIBLE POWER AND
CONTROL CABLE
TYPE ‘YY’
(1.5MM2 TO 4.0MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 42

FLEXIBLE CABLES
Plain annealed flexible copper conductors, PVC insulated, extruded PVC
bedding, galvanised steel wire braid armour, transparent PVC outer sheath.
300/500 volts grade generally to BS6500 and VDE 0250 class 5.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
SY2X/75 0.75 24/0.20 2 87 9.0 20/16
SY3X/75 0.75 24/0.20 3 121 9.1 20/16
SY4X/75 0.75 24/0.20 4 138 9.7 20/16
SY5X/75 0.75 24/0.20 5 164 10.3 20/16
SY7X/75 0.75 24/0.20 7 190 11.0 20/16
SY12X/75 0.75 24/0.20 12 302 14.3 20S
SY18X/75 0.75 24/0.20 18 433 16.8 20
SY25X/75 0.75 24/0.20 25 569 19.7 20
SY34X/75 0.75 24/0.20 34 684 21.8 25
SY2X1 1.0 32/0.20 2 101 9.2 20/16
SY3X1 1.0 32/0.20 3 133 9.3 20/16
SY4X1 1.0 32/0.20 4 152 9.9 20/16
SY5X1 1.0 32/0.20 5 181 10.6 20/16
SY7X1 1.0 32/0.20 7 213 11.3 20/16
SY12X1 1.0 32/0.20 12 361 14.7 20S
SY18X1 1.0 32/0.20 18 490 17.3 20
SY25X1 1.0 32/0.20 25 647 20.3 20
SY34X1 1.0 32/0.20 34 810 21.8 25
SY50X1 1.0 32/0.20 50 1112 23.9 25
SY2X1/5 1.5 30/0.25 2 114 9.8 20/16
SY3X1/5 1.5 30/0.25 3 159 10.0 20/16
SY4X1/5 1.5 30/0.25 4 189 10.6 20/16
SY5X1/5 1.5 30/0.25 5 220 11.4 20/16
SY7X1/5 1.5 30/0.25 7 273 12.6 20/16
SY12X1/5 1.5 30/0.25 12 460 16.6 20
SY18X1/5 1.5 30/0.25 18 633 19.2 20
SY25X1/5 1.5 30/0.25 25 882 23.2 25
SY34X1/5 1.5 30/0.25 34 1108 26.2 25
SY50X1/5 1.5 30/0.25 50 1583 32.8 32
SY2X2/5 2.5 50/0.25 2 143 11.0 20/16
SY3X2/5 2.5 50/0.25 3 218 11.3 20/16
SY4X2/5 2.5 50/0.25 4 267 12.5 20/16
SY5X2/5 2.5 50/0.25 5 334 13.8 20S
SY7X2/5 2.5 50/0.25 7 425 15.0 20S
SY12X2/5 2.5 50/0.25 12 738 22.1 25
SY18X2/5 2.5 50/0.25 18 1100 26.5 25
SY25X2/5 2.5 50/0.25 25 1450 31.5 32
SY34X2/5 2.5 50/0.25 34 1870 33.7 32

Temperature limits: Core identification:


-5 to +70°C. 2 core - Black with White numbers.
3 core and above - Black with White
Bending radius:
numbers plus Green/Yellow.
Static - 10 x overall diameter.
Flexing - 20 x overall diameter. Should not be installed at
temperatures below -5°C.

PVC INSULATED BRAIDED


FLEXIBLE CONTROL CABLE
TYPE “SY”
(0.75MM2 TO 2.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
43

FLEXIBLE CABLES
FLEXIBLE CABLES
CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND
CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
SY3X4 4.0 56/0.30 3 312 14.8 20S
SY4X4 4.0 56/0.30 4 384 15.8 20
SY5X4 4.0 56/0.30 5 556 18.1 20
SY7X4 4.0 56/0.30 7 685 19.6 20
SY3X6 6.0 84/0.30 3 407 16.2 20
SY4X6 6.0 84/0.30 4 508 17.9 20
SY5X6 6.0 84/0.30 5 663 19.3 20
SY7X6 6.0 84/0.30 7 789 21.4 25
SY3X10 10.0 80/0.40 3 621 17.2 20CX
SY4X10 10.0 80/0.40 4 779 21.9 25
SY5X10 10.0 80/0.40 5 1157 25.6 25
SY3X16 16.0 126/0.40 3 857 20.6 25CX
SY4X16 16.0 126/0.40 4 1384 27.5 32
SY5X16 16.0 126/0.40 5 1567 28.3 32
SY4X25 25.0 196/0.40 4 2021 33.8 40
SY5X25 25.0 196/0.40 5 2464 37.4 40
SY4X35 35.0 276/0.40 4 2500 34.5 40
SY5X35 35.0 276/0.40 5 3185 36.7 40
SY4X50 50.0 396/0.40 4 3518 40.3 505
SY4X70 70.0 356/0.50 4 4810 44.2 50SCX
SY4X95 95.0 485/0.5 4 6360 50.2 50CX

Temperature limits: Core identification:


-5 to +70°C. 2 core - Black with White numbers.
3 core and above - Black with White
Bending radius:
numbers plus Green/Yellow.
Static - 10 x overall diameter.
Flexing - 20 x overall diameter. Should not be installed at
temperatures below -5°C.

PVC INSULATED BRAIDED


FLEXIBLE CONTROL CABLE
TYPE “SY”
(4MM2 TO 95MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 44

FLEXIBLE CABLES
Plain annealed flexible copper conductors, PVC insulated, mylar taped, tinned
copper wire braid screen, PVC outer sheath. Grey. 300/500 volts grade
generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
CY2X/75 0.75 24/0.20 2 55 6.5 20S
CY3X/75 0.75 24/0.20 3 77 7.0 20S
CY4X/75 0.75 24/0.20 4 92 7.6 20S
CY5X/75 0.75 24/0.20 5 121 8.6 20S
CY7X/75 0.75 24/0.20 7 145 9.3 20S
CY12X/75 0.75 24/0.20 12 225 11.8 20
CY18X/75 0.75 24/0.20 18 328 14.1 25
CY25X/75 0.75 24/0.20 25 430 16.8 25
CY34X1 1 32/0.20 34 860 17.1 25
CY2X1 1.0 32/0.20 2 78 7.1 20S
CY3X1 1.0 32/0.20 3 87 7.2 20S
CY4X1 1.0 32/0.20 4 115 8.2 20S
CY5X1 1.0 32/0.20 5 136 8.9 20S
CY7X1 1.0 32/0.20 7 166 9.6 20S
CY12X1 1.0 32/0.20 12 271 12.6 20
CY18X1 1.0 32/0.20 18 381 14.6 25
CY25X1 1.0 32/0.20 25 532 17.8 25
CY34X1 1.0 32/0.20 34 735 21.1 32
CY2X1/5 1.5 30/0.25 2 86 7.5 20S
CY3X1/5 1.5 30/0.25 3 118 8.3 20S
CY4X1/5 1.5 30/0.25 4 142 8.9 20S
CY5X1/5 1.5 30/0.25 5 171 9.7 20S
CY7X1/5 1.5 30/0.25 7 217 10.5 20
CY12X1/5 1.5 30/0.25 12 354 13.9 25
CY18X1/5 1.5 30/0.25 18 534 16.7 25
CY25X1/5 1.5 30/0.25 25 704 19.7 32
CY34X1/5 1.5 30/0.25 34 896 22.4 32
CY42X1/5 1.5 30/0.25 42 1133 23.9 32
CY2X2/5 2.5 50/0.25 2 140 8.1 20/16
CY3X2/5 2.5 50/0.25 3 164 9.6 20S
CY4X2/5 2.5 50/0.25 4 206 10.4 20S
CY5X2/5 2.5 50/0.25 5 252 11.3 20
CY7X2/5 2.5 50/0.25 7 327 12.7 20
CY12X2/5 2.5 50/0.25 12 557 17.0 25
CY2X4 4.0 56/0.30 2 206 11.7 20
CY3X4 4.0 56/0.30 3 269 12.4 20
CY4X4 4.0 56/0.30 4 305 12.7 20
CY5X4 4.0 56/0.30 5 396 14.9 25
CY4X6 6.0 84/0.30 4 411 14.4 25
CY4X10 10.0 80/0.40 4 783 16.2 25

Temperature limits: Core identification:


Static - -20 to +80°C. 2 core - Black with White numbers.
Flexing - -5 to +70°C. 3 core and above - Black with White
numbers plus Green/Yellow.
Bending radius:
Static - 6 x overall diameter. Should not be installed at
Flexing - 15 x overall diameter. temperatures below -5°C.

PVC INSULATED BRAID


SCREENED FLEXIBLE
POWER AND CONTROL
CABLETYPE “CY”
(0.75MM2 TO 10MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
45

FLEXIBLE CABLES
FLEXIBLE CABLES
Plain annealed stranded circular copper conductors, circular high temperature
PVC outer sheath. UL & CSA approved also to BS6231. 600/1000 volts grade.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE
(MM) (MM)
TRI0/5 0.5 16/0.20 12 2.7 -
TRI/75 0.75 24/0.20 15 2.9 -
TRI1 1.0 32/0.20 18 3.1 -
TRI1/5 1.5 30/0.25 23 3.3 20/16
TRI2/5 2.5 50/0.25 34 3.7 20/16
TRI4 4.0 56/0.30 50 4.3 20/16
TRI6 6.0 84/0.30 71 4.9 20/16
TRI10 10.0 80/0.40 123 6.3 20/16
TRI16 16.0 126/0.40 207 9.0 20S
TRI25 25.0 196/0.40 303 10.4 20S
TRI35 35.0 276/0.40 412 11.9 20
TRI50 50.0 396/0.40 607 14.7 25
TRI70 70.0 360/0.50 837 16.8 25
TRI95 95.0 475/0.50 1079 18.8 25
TRI120 120.0 608/0.50 1280 19.9 32
BI150 150 756/0.50 1619 22.9 32
BI185 185 925/0.50 1948 24.1 32
BI240 240 1221/0.50 2518 28.6 40
BI300 300 1525.0.50 3112 32.2 505
BI400 400 2013/0.50 4051 36 50

Temperature limits: 4.0mm2 - 16mm2 - Brown, Black, Grey,


-30 to +105°C. Blue, Green/Yellow, Red, Yellow, White.
Should not be installed at 25.0mm2 - 120mm2 - Brown, Black,
temperatures below 0°C. Grey, Blue, Green/Yellow, Red, Yellow.
Standard colours available: 150-400 - Black.
0.5mm2 - 2.5mm2 - Brown, Black,
Current ratings on page 124
Grey, Blue, Green/Yellow, Red, Yellow,
White, Orange, Pink, Violet.

TRI-RATED SWITCHGEAR
AND CONTROL
PANEL WIRE
(0.5MM2 TO 400MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 46

FLEXIBLE CABLES
Tinned annealed flexible copper conductors, ethylene propylene rubber (EPR)
insulated, chlorosulphonated polyethylene (CSP) outer sheath. 300/500 volts
grade to BS6500.
Black or White. Flame propagation to BS4066 PT1 and IEC 332 PT1. Heat and
oil resistant and flame retardant (HOFR).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
3182TQ/75 0.75 24/0.20 2 58 6.3 20/16
3183TQ/75 0.75 24/0.20 3 72 6.8 20/16
3184TQ/75 0.75 24/0.20 4 86 7.4 20/16
3182TQ1 1.0 32/0.20 2 80 8.8 20S
3183TQ1 1.0 32/0.20 3 90 9.2 20S
3184TQ1 1.0 32/0.20 4 110 10.0 20S
3181TQ1/5 1.5 30/0.25 1 38 4.9 20/16
3182TQ1/5 1.5 30/0.25 2 115 10.5 20S
3183TQ1/5 1.5 30/0.25 3 135 11.0 20S
3184TQ1/5 1.5 30/0.25 4 170 12.5 20
3185TQ1/5 1.5 30/0.25 5 200 13.5 25
3186TQ1/5 1.5 30/0.25 6 335 12.2 20
3187TQ1/5 1.5 30/0.25 7 366 13.6 25
3180/12TQ1/5 1.5 30/0.25 12 410 17.1 25
3180/16TQ1/5 1.5 30/0.25 16 570 19.3 25
3180/20TQ1/5 1.5 30/0.25 20 710 21.8 32
3180/27TQ1/5 1.5 30/0.25 27 920 28.2 40
3180/37TQ1/5 1.5 30/0.25 37 1260 28.9 40
3181TQ2/5 2.5 50/0.25 1 41 5.5 20/16
3182TQ2/5 2.5 50/0.25 2 160 12.5 20
3183TQ2/5 2.5 50/0.25 3 195 13.0 20
3184TQ2/5 2.5 50/0.25 4 245 14.0 20
3185TQ2/5 2.5 50/0.25 5 300 15.5 25
3187TQ2/5 2.5 50/0.25 7 424 15.8 25
3180/12TQ2/5 2.5 50/0.25 12 600 20.0 32
3180/16TQ2/5 2.5 50/0.25 16 780 22.5 32
3180/20TQ2/5 2.5 50/0.25 20 1050 25.4 32
3180/27TQ2/5 2.5 50/0.25 27 1390 29.1 40
3180/37TQ2/5 2.5 50/0.25 37 1720 36.8 50S

Temperature limits: Should not be installed at


-25 to +90°C. temperatures below -25°C.
Bending radius: Current ratings, see page 115.
Fixed - 6 x overall diameter.
Flexing - 15 x overall diameter.
Core identification:
2 core - Blue, Brown.
3 core - Blue, Brown, Green/Yellow.
4 core - Grey, Black, Brown,
Green/Yellow.
5 core - Grey, Black, Brown, Blue,
Green/Yellow.
6 core and above - Black with White
numbers plus Green/Yellow.

EPR INSULATED HOFR


SHEATHED FLEXIBLE
POWER AND
CONTROL CABLE
(0.75MM2 TO 2.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
47

FLEXIBLE CABLES
FLEXIBLE CABLES
Tinned annealed flexible copper conductors, ethylene propylene rubber (EPR)
insulated, chlorosulphonated polyethylene (CSP) outer sheath. Black. 450/750
volts grade to BS6007.
Heat and oil resistant and flame retardant (HOFR). Flame propagation to
BS4066 PT1 and IEC 322 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6381TQ4 4.0 56/0.30 1 105 9.0 20S
6382TQ4 4.0 56/0.30 2 275 15.0 25
6383TQ4 4.0 56/0.30 3 335 16.0 25
6384TQ4 4.0 56/0.30 4 420 18.0 25
6385TQ4 4.0 56/0.30 5 515 19.5 32
6387TQ4 4.0 56/0.30 7 773 21.6 32
6380/12TQ4 4.0 56/0.30 12 1183 26.2 40

Temperature limits: Core identification:


-25 to +90°C. 2 core - Blue, Brown.
3 core - Blue, Brown, Green/Yellow.
Bending radius:
4 core - Grey, Black, Brown,
Fixed - 6 x overall diameter.
Green/Yellow.
Flexing - 7 x overall diameter.
5 core - Grey, Black, Brown, Blue,
Green/Yellow.
6 core and above - Black with White
numbers plus Green/Yellow.
Current ratings, see page 123.

EPR INSULATED
HEAVY DUTY
HOFR SHEATHED FLEXIBLE
MAINS CABLE (4MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 48

FLEXIBLE CABLES
Tinned annealed flexible copper conductors, ethylene propylene rubber (EPR)
insulated, chlorosulphonated polyethylene (CSP) outer sheath. Black. 450/750
volts grade to BS6007.
Heat and oil resistant and flame retardant (HOFR). Flame propagation to
BS4066 PT1 and IEC 322 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6381TQ6 6 84/0.30 1 130 11.0 20S
6382TQ6 6 84/0.30 2 370 15.6 25
6383TQ6 6 84/0.30 3 450 16.6 25
6384TQ6 6 84/0.30 4 565 18.5 25
6385TQ6 6 84/0.30 5 690 20.5 32
6387TQ6 6 84/0.30 7 904 25.7 40
6388TQ6 6 84/0.30 8 1040 27.2 40
6381TQ10 10 80/0.40 1 200 12.5 20
6382TQ10 10 80/0.40 2 690 20.6 32
6383TQ10 10 80/0.40 3 835 22.1 32
6384TQ10 10 80/0.40 4 1020 24.1 32
6385TQ10 10 80/0.40 5 1240 26.5 40
6381TQ16 16 126/0.40 1 275 14.5 25
6382TQ16 16 126/0.40 2 910 23.2 32
6383TQ16 16 126/0.40 3 1120 24.8 32
6384TQ16 16 126/0.40 4 1380 27.1 40
6385TQ16 16 126/0.40 5 1695 30.1 40
6381TQ25 25 196/0.40 1 400 16.5 25
6382TQ25 25 196/0.40 2 1290 27.4 40
6383TQ25 25 196/0.40 3 1600 29.3 40
6384TQ25 25 196/0.40 4 2140 32.5 50S
6385TQ25 25 196/0.40 5 2470 36.1 50S
6381TQ35 35 276/0.40 1 520 18.5 25
6382TQ35 35 276/0.40 2 1308 30.4 40
EPR INSULATED 6383TQ35 35 276/0.40 3 2080 32.9 50S
HOFR SHEATHED 6384TQ35
6385TQ35
35
35
276/0.40
276/0.40
4
5
2610
3187
36.5
40.5
50S
50
POWER AND 6381TQ50 50 396/0.40 1 730 21.0 32
6383TQ50 50 396/0.40 3 2890 38.5 50
CONTROL CABLE 6384TQ50 50 396/0.40 4 3650 42.6 50
(6MM2 TO 630MM2) 6385TQ50
6381TQ70
50
70
396/0.40
360/0.50
5
1
4450
980
47.3
23.5
63S
32
6383TQ70 70 360/0.50 3 3850 43.6 63S
6384TQ70 70 360/0.50 4 4880 48.6 63S
6385TQ70 70 360/0.50 5 5938 54.0 63
6381TQ95 95 475/0.50 1 1270 26.0 40
6383TQ95 95 475/0.50 3 4970 50.0 63
6384TQ95 95 475/0.50 4 6390 56.0 75S
6385TQ95 95 475/0.50 5 7924 62.0 75
6381TQ120 120 608/0.50 1 1570 28.5 40
6383TQ120 120 608/0.50 3 6350 56.8 75S
6384TQ120 120 608/0.50 4 7750 59.9 75S
6381TQ150 150 756/0.50 1 1960 31.5 40
6383TQ150 150 756/0.50 3 7700 59.9 75S
6384TQ150 150 756/0.50 4 9780 66.8 75
6381TQ185 185 925/0.50 1 2380 34.5 50S
6383TQ185 185 925/0.50 3 9350 65.9 75
6384TQ185 185 925/0.50 4 11900 73.5 90
6381TQ240 240 1221/0.50 1 3100 38.0 50
6383TQ240 240 1221/0.50 3 12000 74.7 90
6384TQ240 240 1221/0.50 4 15330 83.2
6381TQ300 300 1525/0.50 1 3790 41.5 50
6383TQ300 300 1525/0.50 3 14910 83.2
6384TQ300 300 1525/0.50 4 19030 92.8
6381TQ400 400 2013/0.50 1 4880 46.5 63S
6381TQ500 500 1769/0.60 1 6070 51.5 63
6381TQ630 630 2257/0.60 1 7460 56.5 75S

Temperature limits: 4 core - Grey, Black, Brown,


-25 to +90°C. Green/Yellow.
5 core - Grey, Black, Brown, Blue,
Bending radius:
Green/Yellow.
Fixed - 5 x overall diameter.
6 core and above - Black with White
Flexing - 7 x overall diameter.
numbers plus Green/Yellow.
Core identification:
Should not be installed at
2 core - Blue, Brown.
temperatures below -25°C.
3 core - Blue, Brown, Green/Yellow.
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
49

FLEXIBLE CABLES
FLEXIBLE CABLES
Plain annealed flexible copper conductors, rubber insulated, heavy duty
polychloroprene (PCP) outer sheath 450/750 volts grade. Black. Harmonized
code type HO7RN-F.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
3182P1/5 1.5 30/0.25 2 132 9.3 20
3183P1/5 1.5 30/0.25 3 165 10.3 20S
3184P1/5 1.5 30/0.25 4 200 11.2 20S
3185P1/5 1.5 30/0.25 5 240 12.3 20
3187P1/5 1.5 30/0.25 7 385 14.6 25
3180/12P1/5 1.5 30/0.25 12 520 20.3 32
3182P2/5 2.5 50/0.25 2 193 12.0 20
3183P2/5 2.5 50/0.25 3 235 11.8 20
3184P2/5 2.5 50/0.25 4 290 12.6 20
3185P2/5 2.5 50/0.25 5 345 14.3 25
3187P2/5 2.5 50/0.25 7 520 16.6 25
3180/12P2/5 2.5 50/0.25 12 810 22.0 32
3182P4 4.0 56/0.30 2 275 15.0 25
3183P4 4.0 56/0.30 3 320 13.7 25
3184P4 4.0 56/0.30 4 395 15.1 25
3185P4 4.0 56/0.30 5 485 16.9 25
6382P6 6.0 84/0.30 2 350 18.5 25
6383P6 6.0 84/0.30 3 495 15.2 25
6384P6 6.0 84/0.30 4 610 16.9 25
6385P6 6.0 84/0.30 5 760 18.8 25
6381P10 10 80/0.40 1 230 10.7 20S
6382P10 10 80/0.40 2 640 24.0 32
6383P10 10 80/0.40 3 880 21.9 32
6384P10 10 80/0.40 4 1060 24.0 32
6385P10 10 80/0.40 5 1300 25.5 32
6381P16 16 126/0.40 1 320 12.0 20
6382P16 16 126/0.40 2 850 27.5 40
6383P16 16 126/0.40 3 1090 24.7 32
6384P16 16 126/0.40 4 1345 27.0 40
6385P16 16 126/0.40 5 1680 30.0 40
6381P25 25 196/0.40 1 450 14.1 25
6382P25 25 196/0.40 2 1210 31.5 40
6383P25 25 196/0.40 3 1394 29.4 40
6384P25 25 196/0.40 4 1995 32.6 50S
6385P25 25 196/0.40 5 2470 36.1 50S
6381P35 35 276/0.40 1 605 15.8 25
6383P35 35 276/0.40 3 1850 32.8 50S
6384P35 35 276/0.40 4 2645 36.3 50S
6385P35 35 276/0.40 5 2930 39.8 50
6381P50 50 396/0.40 1 825 18.3 25
6384P50 50 396/0.40 4 3635 41.9 50
6381P70 70 360/0.50 1 1090 20.7 32
6384P70 70 360/0.50 4 4830 48.2 63S
6381P95 95 475/0.50 1 1405 23.4 32
6384P95 95 475/0.50 4 6320 55.0 75S
6381P120 120 608/0.50 1 1745 25.6 40
6381P150 150 756/0.50 1 1824 28.3 40
6381P185 185 925/0.50 1 2202 31.0 40
6381P240 240 1221/0.50 1 2847 34.5 50S
6381P300 300 1525/0.50 1 3495 37.7 50

Temperature limits: 4 core - Grey, Black, Brown,


-25 to +85°C. Green/Yellow.
5 core - Grey, Black, Brown, Blue,
Bending radius:
Green/Yellow.
RUBBER INSULATED Static - 6 x overall diameter.
6 core and above - Black with White
NEOPRENE SHEATHED Flexing - 15 x overall diameter.
numbers plus Green/Yellow.
FLEXIBLE Core identification:
Should not be installed at
POWER CABLE 2 core - Blue, Brown.
temperatures below 0°C.
(1.5MM2 TO 300MM2) 3 core - Blue, Brown, Green/Yellow.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 50

FLEXIBLE CABLES
Flexible tinned annealed copper conductors, ethylene propylene rubber
insulated, chlorosulphonated polyethylene bedding (CSP), tinned copper wire
braid screen, chlorosulphonated polyethylene (CSP) outer sheath. 300/500
volts grade to BS6500/75 and 450/750 Volts grade to BS6007/75 (where
applicable). Black. Flame propogation to BS 4066 PT1 and IEC 332 PT1.
Heat and oil resistant and flame retardant (HOFR).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
3802TQ1 1.0 32/0.20 2 170 11.1 20/16
3803TQ1 1.0 32/0.20 3 200 11.4 20/16
3804TQ1 1.0 32/0.20 4 230 12.1 20/16
3802TQ1/5 1.5 30/0.25 2 225 12.3 20/16
3803TQ1/5 1.5 30/0.25 3 270 13.1 20S
3804TQ1/5 1.5 30/0.25 4 320 14.2 20S
3802TQ2/5 2.5 50/0.25 2 300 14.8 20S
3803TQ2/5 2.5 50/0.25 3 350 15.6 20
3804TQ2/5 2.5 50/0.25 4 420 17.0 20
3803TQ4 4.0 56/0.30 3 715 21.3 25
3804TQ4 4.0 56/0.30 4 865 23.6 25
6803TQ6 6.0 84/0.30 3 973 24.8 25
6804TQ6 6.0 84/0.30 4 1166 27.1 32
6803TQ10 10.0 90/0.40 3 1592 30.7 32
6804TQ10 10.0 90/0.40 4 1878 33.3 40
6803TQ16 16.0 126/0.40 3 1992 33.8 40
6804TQ16 16.0 126/0.40 4 2452 37.2 40

Temperature limits: Should not be installed at


-25 to +90°C. temperatures below 0°C.
Bending radius: Current ratings, see page 122&123.
8 x overall diameter.
Core identification:
2 core - Blue, Brown.
3 core - Blue, Brown, Green/Yellow.
4 core - Grey, Black, Brown, Blue,
Green/Yellow.

EPR INSULATED BRAIDED


SCREEN FLEXIBLE MAINS
AND CONTROL CABLE
(1.0MM2 TO 16MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
51

FLEXIBLE CABLES
FLEXIBLE CABLES
Flexible tinned annealed copper conductors composite ethylene propylene rubber
chlorosulphonated polyethylene (EPR-CSP) insulation to BS6195/69 Type 4.
A. 300/500 volts grade E. 3800/6600 volts grade
C. 600/1000 volts grade F. 6350/11000 volts grade
D. 1900/3300 volts grade

CONDUCTOR RADIAL THICKNESS OF INSULATION


VOLTAGE CATEGORY
SIZE STRANDING MAX APPROX. A C D E F
CCC CODE (MM2) (MM2) DIA. OF DIA. OF (MM) (MM) (MM) (MM) (MM)
WIRES COND.
(MM) (MM)
0.5 16/0.20 0.21 0.93 0.8 1.4 - - -
0.75 24/0.20 0.21 1.14 0.8 1.4 - - -
1.0 32/0.20 0.21 1.32 0.8 1.4 - - -
TYPE 4 1/5 1.5 30/0.25 0.26 1.60 0.8 1.4 - - -
TYPE 4 2/5 2.5 50/0.25 0.26 2.00 0.9 1.4 2.8 - -
TYPE 4 4 4 56/0.30 0.31 2.6 1.0 1.4 - -
TYPE 4 6 6 84/0.30 0.31 3.6 1.0 1.5 - - -
TYPE 4 10 10 80/0.40 0.41 4.6 1.2 1.5 - - -
TYPE 4 16 16 126/0.40 0.41 5.7 - 1.5 2.8 5.0 7.6
TYPE 4 25 25 196/0.40 0.41 7.1 - 1.6 2.8 5.0 7.6
TYPE 4 35 35 276/0.40 0.41 8.5 - 1.6 2.8 5.0 7.6
TYPE 4 50 50 396/0.40 0.41 10.3 - 1.7 2.8 5.0 7.6
TYPE 4 70 70 360/0.50 0.51 12.4 - 1.8 2.8 5.0 7.6
TYPE 4 95 95 475/0.50 0.51 14.5 - 2.0 3.0 5.0 7.6
TYPE 4 120 120 608/0.50 0.51 16.0 - 2.2 3.0 5.0 7.6
TYPE 4 150 150 756/0.50 0.51 18.0 - 2.3 3.0 5.0 7.6
TYPE 4 185 185 925/0.50 0.51 20.0 - 2.4 3.0 5.0 7.6
TYPE 4 240 240 1221/0.50 0.51 23.0 - 2.4 3.0 5.0 7.6
TYPE 4 300 300 1525/0.50 0.51 26.0 - 2.6 3.0 - -
TYPE 4 400 400 2013/0.50 0.51 30.0 - 2.8 3.0 - -

MINIMUM OVERALL DIAMETER WEIGHT


VOLTAGE CATEGORY VOLTAGE CATEGORY
CCC CODE A C D E F A C D E F
(MM) (MM) (MM) (MM) (MM) KG/KM KG/KM KG/KM KG/KM KG/KM
3.3 4.5 - - - 12 17 - - -
3.5 4.7 - - - 16 21 - - -
3.7 4.9 - - - 19 24 - - -
TYPE 4 1/5 4.0 5.2 - - - 25 30 - - -
TYPE 4 2/5 4.6 5.6 8.5 - - 37 41 76 - -
TYPE 4 4 5.4 6.3 - - - 57 66 - - -
TYPE 4 6 6.5 7.5 - - - 80 93 - - -
TYPE 4 10 7.9 8.5 - - - 130 136 - - -
TYPE 4 16 - 9.6 12.4 17.2 22.9 - 206 255 384 566
TYPE 4 25 - 11.4 13.8 18.6 24.1 - 300 351 495 680
TYPE 4 35 - 12.8 15.2 20.0 25.5 - 406 458 613 810
TYPE 4 50 - 14.8 17.1 21.1 27.3 - 573 616 796 997
TYPE 4 70 - 17.2 19.2 24.2 29.4 - 793 820 1020 1237
TYPE 4 95 - 19.7 22.0 26.3 31.5 - 1028 1097 1287 1520
TYPE 4 120 - 21.9 23.5 27.8 33.3 - 1285 1340 1542 1804
TYPE 4 150 - 24.1 25.5 29.8 35.3 - 1562 1635 1853 2131
TYPE 4 185 - 26.3 27.5 32.1 37.3 - 1914 1973 2225 2503
TYPE 4 240 - 29.3 30.5 35.1 40.3 - 2431 2504 2782 3081
TYPE 4 300 - 33.0 33.8 - - - 3024 3098 - -
TYPE 4 400 - 37.4 37.8 - - - 3948 4045 -

Temperature limits: Should not be installed at


-20 to +90°C. temperatures below -25°C.
Bending radius:
EPR INSULATED FLEXIBLE 6 x overall diameter.
COIL LEAD
(0.5MM2 TO 400MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 52

FLEXIBLE CABLES
Tinned annealed flexible circular copper conductors, ethylene propylene
rubber (EPR) insulated, chlorosulphonated polyethylene (CSP) outer sheath.
Orange. Ref 0361TQ.
To BS638 Part 4.

CCC CONDUCTOR STRANDING WEIGHT OUTSIDE GLAND


CODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE
(MM) (MM)
0361TQ16OR 16 513/0.20 235 11.5 20S
0361TQ25OR 25 783/0.20 330 13.0 20
0361TQ35OR 35 1107/0.20 440 14.5 25
0361TQ50OR 50 1566/0.20 610 17.0 25
0361TQ70OR 70 2214/0.20 840 19.5 32
0361TQ95OR 95 2997/0.20 1120 22.0 32
0361TQ120OR 120 608/0.50 1410 24.0 32
0361TQ185OR 185 925/0.50 2100 29.0 40

Temperature limits: Bending radius:


-20 to +85°C. 6 x overall diameter.

EPR INSULATED FLEXIBLE


WELDING CABLE
TYPE 0361TQ
(16MM2 TO 185MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
53

FLEXIBLE CABLES
FLEXIBLE CABLES
RUBBER INSULATED FLAT CABLE
Flexible plain copper conductors, thermoplastic rubber insulated (TPR)
thermoplastic outer sheath (TPR). Black. 600/1000 volts grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL MAX CURRENT


CODE SIZE (MM2) (MM) CORES KG/KM DIMENSIONS RATINGS
(MM) (AMPS)
FLAT4X1/5R 1.5 30/0.25 4 110 16X5 22
FLAT12X1/5R 1.5 30/0.25 12 320 29X5 12
FLAT4X2/5R 2.5 50/0.25 4 170 19X6 30
FLAT7X2/5R 2.5 50/0.25 7 300 33X7 20
FLAT12X2/5R 2.5 50/0.25 12 490 51X6 20
FLAT4X4R 4 56/0.30 4 250 21X7 40
FLAT4X6R 6 84/0.30 4 330 24X7 52
FLAT4X10R 10 80/0.40 4 550 29X9 70
FLAT4X16R 16 126/0.40 4 800 35X10 95
FLAT4X25R 25 196/0.40 4 1350 46X14 127
FLAT4X35R 35 276/0.40 4 1800 51X15 157
FLAT4X50R 50 396/0.40 4 2400 56X17 190
FLAT4X70R 70 360/0.50 4 3250 63X18 242

Temperature limits: 7 and 12 core - Black cores with


-35 to +85°C. White numbers and one
Green/Yellow.
Bending radius:
10 x overall diameter. Should not be installed at
temperatures below 0°C.
Core identification:
4 core - Black, Grey, Brown,
Green/Yellow.

PVC INSULATED FLAT CABLE


Flexible plain copper conductors, PVC insulated, special PVC outer sheath. Black.
450/750 volts grade type H07VVH6-F. CENELEC HD 359 S2 IEC 227 part 6.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL MAX CURRENT


CODE SIZE (MM2) (MM) CORES KG/KM DIMENSIONS RATINGS
(MM) (AMPS)
FLAT4X1/5V 1.5 30/0.25 4 150 15X5 20
FLAT12X1/5V 1.5 30/0.25 12 420 41X5 11
FLAT4X2/5V 2.5 50/0.25 4 210 19X6 27
FLAT12X2/5V 2.5 50/0.25 12 620 51X6 16
FLAT4X4V 4 56/0.30 4 300 21X7 36
FLAT4X6V 6 84/0.30 4 385 23X7 48
FLAT4X10V 10 80/0.40 4 620 29X9 63
FLAT4X16V 16 126/0.40 4 990 37X11 85
FLAT4X25V 25 196/0.40 4 1550 46X14 112
FLAT4X35V 35 276/0.40 4 2030 51X15 138
FLAT4X50V 50 396/0.40 4 2650 56X17 168
FLAT4X70V 70 360/0.50 4 3650 63X18 213
FLAT4X95V 95 475/0.50 4 4550 73X21 258

Temperature limits: 12 core - Black cores with white


-25 to +70°C. numbers and one Green/Yellow.
Bending radius: Should not be installed at
RUBBER INSULATED 10 x overall diameter. temperatures below 0°C.
FLAT CABLE
Core identification:
(1.5MM2 TO 70MM2) 4 core - Black, Grey, Brown,
AND PVC INSULATED Green/Yellow.
FLAT CABLE
(1.5MM2 TO 95MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FLEXIBLE CABLES 54

FLEXIBLE CABLES
Flexible tinned annealed copper conductors, silicone insulated, silicone outer
sheath. 300/500 volts grade to VDE 0250 PT816.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
BIHF2X/75 0.75 24/0.20 2 53.4 6.5 20/16
BIHF3X/75 0.75 24/0.20 3 63.7 6.9 20/16
BIHF4X/75 0.75 24/0.20 4 83.6 7.9 20/16
BIHF5X/75 0.75 24/0.20 5 101.2 8.6 20S
BIHF7X/75 0.75 24/0.20 7 124.9 9.3 20S
BIHF2X1 1.0 32/0.20 2 59.9 6.7 20/16
BIHF3X1 1.0 32/0.20 3 78.3 7.5 20/16
BIHF4X1 1.0 32/0.20 4 94.6 8.1 20S
BIHF5X1 1.0 32/0.20 5 116.1 8.9 20S
BIHF7X1 1.0 32/0.20 7 144.3 9.6 20S
BIHF2X1/5 1.5 30/0.25 2 82.0 7.6 20/16
BIHF3X1/5 1.5 30/0.25 3 98.0 8.0 20/16
BIHF4X1/5 1.5 30/0.25 4 122.0 8.8 20S
BIHF5X1/5 1.5 30/0.25 5 148.0 9.6 20S
BIHF7X1/5 1.5 30/0.25 7 187.0 10.4 20S
BIHF2X2/5 2.5 50/0.25 2 135.0 8.9 20S
BIHF3X2/5 2.5 50/0.25 3 152.0 9.1 20S
BIHF4X2/5 2.5 50/0.25 4 188.0 10.1 20S
BIHF5X2/5 2.5 50/0.25 5 230.0 10.9 20S
BIHF7X2/5 2.5 50/0.25 7 293.0 13.1 20

Temperature limits: Core identification:


-60 to +180°C. 2 core - Blue, Brown.
3 core - Blue, Brown, Green/Yellow.
Bending radius:
4 core - Grey, Black, Brown,
Fixed - 5 x overall diameter.
Green/Yellow.
Flexing - 15 x overall diameter.
5 core and above - Grey, Black, Brown,
Blue, Green/Yellow
6 core and above - Black with White
numbers plus Green/Yellow.
Should not be installed at
temperatures below 0°C.

SILICONE INSULATED
FLEXIBLE CABLE
(0.75MM2 TO 2.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES
INSTRUMENTATION,

COMMUNICATION
CONTROL AND
55

CABLES
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 56

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
PART 1 CONSTRUCTION
Plain annealed flexible copper conductors, polyethylene insulated, laid up to
form pairs, collective aluminium/mylar tape screen complete with 0.5mm2
drain wire, PVC outer sheath reduced propagation, Blue or Black to BS5308
Part 1 Type 1. Flame propagation to BS4066 PT1 and IEC 332 PT1. (Bunched
cables to BS4066 PT3 and IEC 332 PT3).
PART 2 CONSTRUCTION
Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,
collective aluminium/mylar tape screen complete with 0.5mm2 drain wire,
PVC outer sheath reduced propagation. Blue or Black to BS5308 Part 2 Type1.
Flame propagation to BS4066 PT3 and IEC 332 PT3.

CCC CODE CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND


PT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE
(MM) (MM)
7100 7300 0.5 16/0.20 1 60 6.4 20/16
7101 7301 0.5 16/0.20 2 80 7.3 20/16
7102 7302 0.5 16/0.20 5 200 12.5 20
7103 7303 0.5 16/0.20 10 340 16.6 25
7104 7304 0.5 16/0.20 20 570 21.7 32
7105 7305 0.5 16/0.20 30 790 26.3 40
7106 7306 0.5 16/0.20 50 1270 33.3 50S
7107 7307 0.5 16/0.20 1 TRIPLE 69 6.6 20/16
7136 7336 0.75 24/0.20 1 75 6.7 20/16
7137 7337 0.75 24/0.20 2 100 7.7 20/16
7138 7338 0.75 24/0.20 5 250 13.7 25
7139 7339 0.75 24/0.20 10 450 18.1 25
7140 7340 0.75 24/0.20 20 800 23.9 32
7141 7341 0.75 24/0.20 30 1130 28.9 40
7142 7342 0.75 24/0.20 50 1840 36.8 50S
7143 7343 0.75 24/0.20 1 TRIPLE 88 6.9 20/16
7173 7373 1.5 7/0.53 1 100 7.7 20/16
7174 7374 1.5 7/0.53 2 150 9.1 20S
7175 7375 1.5 7/0.53 5 360 15.8 25
7176 7376 1.5 7/0.53 10 670 21.0 32
7177 7377 1.5 7/0.53 20 1230 27.9 40
N/A N/A 1.5 7/0.53 30 1720 33.7 50S
N/A N/A 1.5 7/0.53 50 2750 43.6 63S
7178 7378 1.5 7/0.53 1 TRIPLE 128 8.1 20/16

BS5308 PART 1, LSF


Plain annealed flexible copper conductors, polyethylene insulated, laid up to form
pairs, collective aluminium/mylar tape screen complete with 0.5mm2 drain wire,
low smoke and fume (LSF) sheath, Blue or Black, to BS5308 Part 1, Type 1 LSF.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
7246 0.75 24/0.20 1 75 6.7 20/16
7247 0.75 24/0.20 2 100 7.7 20/16
7248 0.75 24/0.20 5 250 13.7 25
7249 0.75 24/0.20 10 450 18.1 25
7250 0.75 24/0.20 20 800 23.9 32

CONTROL AND Temperature limits: Core identification:


-20 to +65°C. Part 1 colour code chart on page 62
INSTRUMENTATION CABLE
Part 2 colour code chart on page 63
NON-ARMOURED WITH Bending radius:
COLLECTIVE SCREEN 5 x overall diameter. Should not be installed at
temperatures below 0°C.
(0.5MM2 TO 1.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
57

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
BS5308 PART 1, TYPE 1
Plain annealed flexible copper conductors, polyethylene insulated, laid up to
form pairs, each pair individually aluminium/mylar foil tape screened,
complete with 0.5mm2 drain wire, collective aluminium/mylar foil tape screen
complete with 0.5mm2 drain wire, PVC outer sheath reduced propagation.
Blue or Black. Flame propagation to BS4066 PT1 and IEC 332 PT1. (Bunched
cables to BS4066 PT3 and IEC 332 PT3).
BS5308 PART 2, TYPE 1
Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,
each pair individually aluminium/mylar foil tape screened complete with
0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete with
0.5mm2 drain wire, PVC outer sheath reduced propagation. Blue or Black.
Flame propagation to BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066
PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND


PT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE
(MM) (MM)
7112 7312 0.5 16/0/20 2 160 11.4 20S
7113 7313 0.5 16/0/20 5 250 14.6 25
7114 7314 0.5 16/0/20 10 480 20.5 32
7115 7315 0.5 16/0/20 20 780 26.7 40
7116 7316 0.5 16/0/20 30 1100 31.7 40
7117 7317 0.5 16/0/20 50 1590 41.1 50
7149 7349 0.75 24/0/20 2 190 12.2 20
7150 7350 0.75 24/0/20 5 270 15.7 25
7151 7351 0.75 24/0/20 10 550 21.8 32
7152 7352 0.75 24/0/20 20 960 28.5 40
7153 7353 0.75 24/0/20 30 1320 33.7 50S
7154 7354 0.75 24/0/20 50 2120 44.0 63S
7185 7385 1.5 7/0.53 2 250 13.7 25
7186 7386 1.5 7/0.53 5 400 17.8 25
7187 7387 1.5 7/0.53 10 800 25.2 32
7188 7388 1.5 7/0.53 20 1400 33.8 50S
1.5 7/0.53 30 2040 40.4 50
1.5 7/0.53 50 3260 52.2 63

BS5308 PART 1, TYPE 1 LS0H


Plain annealed flexible copper conductors, polyethylene insulated, laid up to
form pairs, each pair individually aluminium/mylar tape screened. Complete
with 0.5mm2 drain wire, collective aluminium/mylar tape screen complete
with 0.5mm2 drain wire, low smoke zero halogen (LS0H) outer sheath, Black or
Blue, generally to BS5308 Part 1, Type 1 LS0H.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
71149 0.75 24/0.20 2 190 12.2 20
71150 0.75 24/0.20 5 270 15.7 25
71151 0.75 24/0.20 10 550 21.8 32
71152 0.75 24/0.20 20 960 28.5 40

CONTROL AND
INSTRUMENTATION CABLE Temperature limits: Core identification:
NON-ARMOURED WITH -20 to +65°C. Part 1 colour code chart on page 62.
INDIVIDUAL AND Part 2 colour code chart on page 63.
Bending radius:
COLLECTIVE SCREENS 5 x overall diameter. Should not be installed at
(0.5MM2 TO 1.5MM2) temperatures below 0°C.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 58

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
BS5308 PART 1, TYPE 2
Plain annealed flexible copper conductors, polyethylene insulated, laid up to
form pairs, collective aluminium/mylar foil tape screen, complete with
0.5mm2 drain wire, Polytheylene bedding, galvanised steel wire armour, PVC
outer sheath reduced propagation. Blue or Black. Flame propagation to
BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).
BS5308 PART 2, TYPE 2
Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,
collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,
Polytheylenebedding, galvanised steel wire armour, PVC outer sheath reduced
propagation. Blue or Black. Flame propagation to BS4066 PT1 and IEC 332 PT1.
(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEAT


PT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) (MM)
7118 7318 0.5 16/0/20 1 250 10.8 20/16 0.5
7119 7319 0.5 16/0/20 2 300 11.7 20/16 0.5
7120 7320 0.5 16/0/20 5 560 17.3 20 0.7
7121 7321 0.5 16/0/20 10 970 22.3 25 0.9
7122 7322 0.5 16/0/20 20 1640 28.5 32 1.2
7123 7323 0.5 16/0/20 30 2110 33.3 40 1.4
7124 7324 0.5 16/0/20 50 3270 41.5 50S 1.8
7125 7325 0.5 16/0/20 1 TRIPLE 276 11.0 20/16 0.5
7155 7355 0.75 24/0/20 1 280 11.1 20/16 0.5
7156 7356 0.75 24/0/20 2 330 12.3 20/16 0.5
7157 7357 0.75 24/0/20 5 750 19.2 20 0.8
7158 7358 0.75 24/0/20 10 1260 24.7 25 1.0
7159 7359 0.75 24/0/20 20 1890 30.7 32 1.4
7160 7360 0.75 24/0/20 30 2440 36.9 40 1.6
7161 7361 0.75 24/0/20 50 3890 46.4 50 2.0
7162 7362 0.75 24/0/20 1 TRIPLE 307 11.4 20/16 0.5
7189 7389 1.5 7/0/53 1 330 12.3 20/16 0.5
7190 7390 1.5 7/0/53 2 420 13.7 20S 0.6
7191 7391 1.5 7/0/53 5 940 21.5 25 0.9
7192 7392 1.5 7/0/53 10 1050 27.8 32 1.2
7193 7393 1.5 7/0/53 20 2400 35.1 40 1.4
7194 7394 1.5 7/0/53 30 3120 41.9 50S 1.8
7195 7395 1.5 7/0/53 50 5310 53.4 63S R9
7196 7396 1.5 7/0/53 1 TRIPLE 376 12.6 20/16 0.5
7208 7408 2.5 7/0/67 1 395 13.1 20S 0.6
7209 7409 2.5 7/0/67 2 490 15.9 20 0.6
7210 7410 2.5 7/0/67 5 1430 26.5 20 1.1
7211 7411 2.5 7/0/67 10 2235 35.1 40 1.4
7212 7412 2.5 7/0/67 20 3935 46.7 50 2.0
7213 7413 2.5 7/0/67 1 TRIPLE 407 13.7 20S 0.6

BS5308 PART 1, TYPE 2 LS0H


Plain annealed flexible copper conductors, polyethylene insulated, laid up to form
pairs, collective aluminium/mylar foil tape screen, complete with 0.5mm2 drain wire,
low smoke zero halogen bedding (LS0H), galvanised steel wire armour, low smoke
zero halogen (LS0H) sheath, Black or Blue, generally to BS5308 Part 1, Type 2 LS0H.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) (MM)
7255 0.75 24/0.20 1 280 11.1 20/16 0.5
7256 0.75 24/0.20 2 330 12.3 20/16 0.5
7257 0.75 24/0.20 5 750 19.2 20 0.8
7258 0.75 24/0.20 10 1260 24.7 25 1.0
7259 0.75 24/0.20 20 1890 30.7 32 1.4
7289 1.5 7/0.53 1 330 12.3 20/16 0.5
7290 1.5 7/0.53 2 420 13.7 205 0.6
7291 1.5 7/0.53 5 940 21.5 25 0.9
7292 1.5 7/0.53 10 1050 27.8 32 1.2
7293 1.5 7/0.53 20 2400 35.1 40 1.4

CONTROL AND
INSTRUMENTATION CABLE Temperature limits: Core identification:
-20 to +65°C. Part 1 colour code chart on page 62.
ARMOURED WITH Part 2 colour code chart on page 63.
COLLECTIVE SCREEN Bending radius:
6 x overall diameter.. Should not be installed at
(0.5MM2 TO 2.5MM2) temperatures below 0°C.
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
59

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
BS5308 PART 1, TYPE 2
Plain annealed flexible copper conductors, polyethylene insulated, laid up to
form pairs, each pair individually aluminium/mylar foil tape screened, complete
with 0.5mm2 drain wire, collective aluminium/mylar foil tape screen, complete
with 0.5mm2 drain wire, polyethylene bedding, galvanised steel wire armour,
PVC outer sheath reduced propagation. Blue or Black. Flame propagation to
BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).
BS5308 PART 2, TYPE 2
Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,
each pair individually aluminium/mylar foil tape screened, complete with
0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete with
0.5mm2 drain wire, PVC bedding, galvanised steel wire armour, PVC outer
sheath reduced propagation. Blue or Black. Flame propagation to BS4066 PT1
and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEAT


PT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) (MM)
7130 7330 0.5 16/0/20 2 460 16.8 20 0.7
7131 7331 0.5 16/0/20 5 760 20.9 25 0.9
7132 7332 0.5 16/0/20 10 1300 27.9 32 1.2
7133 7333 0.5 16/0/20 20 1870 34.3 40 1.4
7134 7334 0.5 16/0/20 30 2620 40.5 50S 1.6
7135 7335 0.5 16/0/20 50 4180 51.5 50 R9
7167 7367 0.75 24/0/20 2 500 17.6 20 0.7
7168 7368 0.75 24/0/20 5 920 22.0 25 0.9
7169 7369 0.75 24/0/20 10 1610 29.5 32 1.2
7170 7370 0.75 24/0/20 20 2420 37.8 40 1.6
7171 7371 0.75 24/0/20 30 3120 43.9 50S 1.8
7172 7372 0.75 24/0/20 50 4910 55.0 63S R9
7201 7401 1.5 7/0/53 2 730 20.4 20 0.9
7202 7402 1.5 7/0/53 5 1180 25.4 25 1.0
7203 7403 1.5 7/0/53 10 1820 33.5 40 1.4
7204 7404 1.5 7/0/53 20 3030 42.6 50S 1.8
7205 7405 1.5 7/0/53 30 3650 50.8 50 R9
7206 7406 1.5 7/0/53 50 5640 62.6 63 R10

BS5308 PART 1, TYPE 2 LS0H


Plain annealed flexible copper conductors, polyethylene insulated, laid up to form
pairs, each pair individually aluminium/mylar foil tape screened, complete with
0.5mm2 drain wire, collective aluminium/mylar foil tape screen, complete with
0.5mm2 drain wire, low smoke zero halogen (LS0H) bedding, galvanised steel wire
armour, low smoke zero halogen (LS0H) sheath, Blue or Black, generally to BS5308.

CCC CODE CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) (MM)
7267 0.75 24/0.20 2 500 17.6 20 0.7
7268 0.75 24/0.20 5 920 22.0 25 0.9
7269 0.75 24/0.20 10 1610 29.5 32 1.2
7270 0.75 24/0.20 20 2420 37.8 40 1.6
7298 1.5 7/0.53 2 730 20.4 20 0.9
7299 1.5 7/0.53 5 1180 25.4 25 1.0
7297 1.5 7/0.53 10 1820 33.5 40 1.4
7296 1.5 7/0.53 20 3030 42.6 505 1.8
CONTROL AND
INSTRUMENTATION CABLE Temperature limits: Core identification:
ARMOURED WITH -20 to +65°C. Part 1 colour code chart on page 62.
INDIVIDUAL AND Bending radius:
Part 2 colour code chart on page 63.
COLLECTIVE SCREEN 6 x overall diameter. Should not be installed at
(0.5MM2 TO 1.5MM2) temperatures below 0°C.
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 60

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
BS5308 PART 1, TYPE 3
Plain annealed copper conductors, polyethylene insulated, laid up to form
pairs, each pair individually aluminium/mylar foil tape screened complete
with 0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete
with 0.5mm2 drain wire, polyethylene bedding, lead sheathed, galvanised steel
wire armour, PVC outer sheath reduced propagation. Blue or Black. Flame
propagation to BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3
and IEC 332 PT3).
BS5308 PART 2, TYPE 3
Plain annealed flexible copper conductors, PVC insulated laid up to form pairs,
each pair individually aluminium/mylar foil tape screened complete with
0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete with
0.5mm2 drain wire, PVC bedding, lead sheathed, galvanised steel wire armour,
PVC outer sheath reduced propagation. Blue or Black. Flame propagation to
BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3.

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEAT


PT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) (MM)
7821 7921 0.75 24/0.20 1 700 15.7 20 0.7
7822 7922 0.75 24/0.20 2 795 16.8 20 0.7
7823 7923 0.75 24/0.20 5 1598 25.1 25 1.0
7824 7924 0.75 24/0.20 10 2280 29.4 32 1.2
7825 7925 0.75 24/0.20 20 3630 37.3 40 1.6
7826 7926 0.75 24/0.20 30 4385 43.1 50S 1.8
7827 7927 0.75 24/0.20 50 6895 53.1 63S R9
7971 - 1.0 1/1.13 1 710 15.8 20 0.7
7972 - 1.0 1/1.13 2 828 17.0 20 0.7
7973 - 1.0 1/1.13 5 1627 25.0 25 1.0
7974 - 1.0 1/1.13 10 2275 29.6 32 1.2
7975 - 1.0 1/1.13 20 3149 37.6 40 1.6
7976 - 1.0 1/1.13 30 4420 42.6 50S 1.8
7977 - 1.0 1/1.13 50 6964 53.5 63S R9
7851 7951 1.5 7/0.53 1 940 16.9 20 0.7
7852 7952 1.5 7/0.53 2 1051 19.0 20 0.8
7853 7953 1.5 7/0.53 5 1973 27.4 32 1.1
7854 7954 1.5 7/0.53 10 2823 33.2 32 1.4
7855 7955 1.5 7/0.53 20 4498 42.1 50S 1.8
7856 7956 1.5 7/0.53 30 6207 50.1 50 2.0
7857 7957 1.5 7/0.53 50 8961 61.0 63 R10

Temperature limits: Core identification:


-20 to +63°C. Part 1 colour code chart on page 62.
Part 2 colour code chart on page 63.
Bending radius:
5 x overall diameter. Should not be installed at
temperatures below 0°C.

CONTROL AND
INSTRUMENTATION CABLE
LEAD SHEATHED
ARMOURED WITH
COLLECTIVE SCREEN
(0.75MM2 TO 1.5MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
61

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
BS5308 PART 1, TYPE 3
Plain annealed flexible copper conductors, polyethylene insulated, laid up to
form pairs, collective aluminium/mylar tape screen, complete with 0.5mm2
drain wire, polyethylene bedding, lead sheathed, galvanised steel wire armour,
PVC outer sheath reduced propagation. Blue or Black. Flame propagation to
BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).
BS5308 PART 2, TYPE 3
Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,
collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,
PVC bedding, lead sheathed, galvanised steel wire armour, PVC outer sheath
reduced propagation. Blue or Black. Flame propagation to BS4066 PT1 and IEC
332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEAT


PT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) (MM)
7830 7930 0.75 24/0.20 2 1280 21.5 25 0.9
7831 7931 0.75 24/0.20 5 1810 26.0 25 1.1
7832 7932 0.75 24/0.20 10 2720 32.7 32 1.4
7833 7933 0.75 24/0.20 20 4270 40.9 50S 1.8
7834 7934 0.75 24/0.20 30 6000 46.3 50S 2.0
7835 7935 0.75 24/0.20 50 8330 58.5 63S R10
N/A N/A 1.0 1/1.13 2 1280 22.3 25 0.9
N/A N/A 1.0 1/1.13 5 1820 27.2 25 1.1
N/A N/A 1.0 1/1.13 10 2750 34.2 40 1.4
CONTROL AND N/A N/A 1.0 1/1.13 20 4350 43.8 50S 1.8
N/A N/A 1.0 1/1.13 30 6110 51.4 50 R9
INSTRUMENTATION CABLE N/A N/A 1.0 1/1.13 50 8350 62.5 63 R10
LEAD SHEATHED 7870 7970 1.5 7/0.53 2 1680 25.5 25 1.1
7871 7971 1.5 7/0.53 5 2300 30.0 32 1.2
ARMOURED WITH 7872 7972 1.5 7/0.53 10 4000 40.1 50S 1.6
INDIVIDUAL AND 7873 7973 1.5 7/0.53 20 6300 50.2 50 2.0
7874 7974 1.5 7/0.53 30 8110 57.6 63S R10
COLLECTIVE SCREENS 7875 7975 1.5 7/0.53 50 11160 70.6 75S R12
(0.75MM2 TO 1.5MM2)
Temperature limits: Core identification:
-20 to +65°C. Part 1 colour code chart on page 62.
Part 2 colour code chart on page 63.
Bending radius:
15 x overall diameter. Should not be installed at
temperatures below 0°C.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 62

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
BS5308 PART 1

PAIR A B PAIR A B
NUMBER WIRE WIRE NUMBER WIRE WIRE
1 BLACK BLUE 26 WHITE YELLOW
2 BLACK GREEN 27 RED YELLOW
3 BLUE GREEN 28 ORANGE YELLOW
4 BLACK BROWN 29 BLACK GREY
5 BLUE BROWN 30 BLUE GREY
6 GREEN BROWN 31 GREEN GREY
7 BLACK WHITE 32 BROWN GREY
8 BLUE WHITE 33 WHITE GREY
9 GREEN WHITE 34 RED GREY
10 BROWN WHITE 35 ORANGE GREY
11 BLACK RED 36 YELLOW GREY
12 BLUE RED 37 BLACK VIOLET
13 GREEN RED 38 BLUE VIOLET
14 BROWN RED 39 GREEN VIOLET
15 WHITE RED 40 BROWN VIOLET
16 BLACK ORANGE 41 WHITE VIOLET
17 BLUE ORANGE 42 RED VIOLET
18 GREEN ORANGE 43 ORANGE VIOLET
19 BROWN ORANGE 44 YELLOW VIOLET
20 WHITE ORANGE 45 GREY VIOLET
21 RED ORANGE 46 BLACK TURQUOISE
22 BLACK YELLOW 47 BLUE TURQUOISE
23 BLUE YELLOW 48 GREEN TURQUOISE
24 GREEN YELLOW 49 BROWN TURQUOISE
25 BROWN YELLOW 50 WHITE TURQUOISE

For individual screened pairs, identification will be Black/Blue numbered pairs.


Two pair collectively screened cables are in quad formation colour coded in
rotation, Black, Blue, Green, Brown.
Single triple will be Black, Blue, Turquoise.

BS5308 PART 1 CORE


IDENTIFICATION
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
63

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
BS5308 PART 2

PAIR A B PAIR A B
NUMBER WIRE WIRE NUMBER WIRE WIRE
1 WHITE BLUE 26 RED/BLUE BLUE
2 WHITE ORANGE 27 RED/BLUE ORANGE
3 WHITE GREEN 28 RED/BLUE GREEN
4 WHITE BROWN 29 RED/BLUE WHITE
5 WHITE GREY 30 RED/BLUE BROWN
6 RED BLUE 31 BLUE/BLACK BLUE
7 RED ORANGE 32 BLUE/BLACK ORANGE
8 RED GREEN 33 BLUE/BLACK GREEN
9 RED BROWN 34 BLUE/BLACK BROWN
10 RED GREY 35 BLUE/BLACK GREY
11 BLACK BLUE 36 YELLOW/BLUE BLUE
12 BLACK ORANGE 37 YELLOW/BLUE ORANGE
13 BLACK GREEN 38 YELLOW/BLUE GREEN
14 BLACK BROWN 39 YELLOW/BLUE BROWN
15 BLACK GREY 40 YELLOW/BLUE GREY
16 YELLOW BLUE 41 WHITE/ORANGE BLUE
17 YELLOW ORANGE 42 WHITE/ORANGE ORANGE
18 YELLOW GREEN 43 WHITE/ORANGE GREEN
19 YELLOW BROWN 44 WHITE/ORANGE BROWN
20 YELLOW GREY 45 WHITE/ORANGE GREY
21 WHITE/BLUE BLUE 46 ORANGE/RED BLUE
22 WHITE/BLUE ORANGE 47 ORANGE/RED ORANGE
23 WHITE/BLUE GREEN 48 ORANGE/RED GREEN
24 WHITE/BLUE BROWN 49 ORANGE/RED BROWN
25 WHITE/BLUE GREY 50 ORANGE/RED GREY

For individual screened pairs, identification will be White/Blue numbered pairs.


Two pair collectively screened cables are in quad formation colour coded in
rotation, Blue, Green, Orange, Brown.
Single triple will be Blue, White, Green.

BS5308 PART 2 CORE


IDENTIFICATION
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 64

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
Plain annealed flexible copper conductors, PVC bedding, tinned annealed
copper wire braid screen, PVC bedding, galvanised steel wire armour, PVC
outer sheath. Grey. 300/500 volts grade to British Steel specification CES 20
part 4, Type 134. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)

BSC1342C 0.75 24/0/2 2 420 13.4 20S 0.6


BSC1343C 0.75 24/0/2 3 452 13.8 20S 0.6
BSC1344C 0.75 24/0/2 4 490 14.4 20S 0.6
BSC1347C 0.75 24/0/2 7 579 15.9 20S 0.7
BSC13412C 0.75 24/0/2 12 906 19.5 20 0.8
BSC13419C 0.75 24/0/2 19 1091 21.5 20 0.9
BSC13427C 0.75 24/0/2 27 1562 25.5 25 1.1
BSC13437C 0.75 24/0/2 37 1872 28.1 32 1.2

Temperature limits: Should not be installed at


-20 to +70°C. temperatures below 0°C.
Bending radius:
6 x overall diameter.

CORE IDENTIFICATION:

NO. OF COLOUR
CORES
2 BROWN BLUE
3 BROWN BLUE GREEN/YLW
4 BROWN GREY GREEN/YLW BLACK
7 RED BLUE GREEN YELLOW WHITE BLACK BROWN
12 RED BLUE GREEN YELLOW WHITE BLACK BROWN
VIOLET ORANGE PINK TURQUOISE GREY
19 RED BLUE GREEN YELLOW WHITE BLACK BROWN
VIOLET ORANGE PINK TURQUOISE GREY
RED/BLUE RED/GREEN RED/YELLOW RED/WHITE RED/BLACK RED/BROWN BLUE/YELLOW
27 RED BLUE GREEN YELLOW WHITE BLACK BROWN
VIOLET ORANGE PINK TURQUOISE GREY RED/BLUE RED/GREEN
RED/YELLOW RED/WHITE RED/BLACK RED/BROWN BLUE/YELLOW BLUE/WHITE BLUE/BLACK
BLUE/ORANGE BLUE/GREEN BLUE./GREY GREEN/YLW GREEN/WHITE GREEN/BLACK
37 RED BLUE GREEN YELLOW WHITE BLACK BROWN
VIOLET ORANGE PINK TURQUOISE GREY RED/BLUE RED/GREEN
RED/YELLOW RED/WHITE RED/BLACK RED/BROWN BLUE/YELLOW BLUE/WHITE BLUE/BLACK
BLUE/ORANGE BLUE/GREEN BLUE./GREY GREEN/YLW GREEN/WHITE GREEN/BLACK GRN/ORANGE
GREEN/GREY BROWN/YLW BRN/WHITE BRN/BLACK BROWN/GREY VIOLET/YLW VIOLET/BLACK
VIOLET/WHT RED/GREY

INSTRUMENTATION CABLE
TO BRITISH STEEL
SPECIFICATION
CES20 TYPE 134
(0.75MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
65

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
Tinned annealed flexible copper conductors, PVC insulated and laid up to form
pairs, collective aluminium/mylar foil tape screen, complete with 0.5mm2
drain wire, PVC bedding, galvanised steel wire armour, PVC outer sheath.
Orange. 300/500 volts grade.
Type 143. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND SINGLE


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
BSC1431P 0.75 24/0.20 1 280 11.4 20/16 0.5
BSC1432P 0.75 24/0.20 2 400 14.1 20S 0.6
BSC1435P 0.75 24/0.20 5 630 18.0 20 0.8
BSC14310P 0.75 24/0.20 10 950 22.2 25 0.9
BSC14320P 0.75 24/0.20 20 1550 28.2 32 1.2
BSC14330P 0.75 24/0.20 30 2000 32.3 32 1.4
BSC14350P 0.75 24/0.20 50 3200 40.6 50S 1.6

Temperature limits: Should not be installed at


-20 to +70°C. temperatures below 0°C.
Bending radius:
6 x overall diameter.

CORE IDENTIFICATION:

PAIR A B PAIR A B
NUMBER WIRE WIRE NUMBER WIRE WIRE
1 BLACK BLUE 26 WHITE YELLOW
2 BLACK ORANGE 27 WHITE VIOLET
3 BLACK GREEN 28 BLUE RED
4 BLACK BROWN 29 BLUE YELLOW
5 BLACK GREY 30 BLUE VIOLET
6 BLUE WHITE 31 GREEN RED
7 BLUE ORANGE 32 GREEN YELLOW
8 BLUE GREEN 33 GREEN VIOLET
9 BLUE BROWN 34 RED GREY
10 BLUE GREY 35 RED ORANGE
11 ORANGE WHITE 36 RED YELLOW
12 ORANGE GREEN 37 RED BROWN
13 ORANGE BROWN 38 RED VIOLET
14 ORANGE GREY 39 GREY YELLOW
15 GREEN WHITE 40 GREY VIOLET
16 GREEN BROWN 41 ORANGE YELLOW
17 GREEN GREY 42 ORANGE VIOLET
18 BROWN WHITE 43 YELLOW BROWN
19 BROWN GREY 44 YELLOW VIOLET
20 GREY WHITE 45 BROWN VIOLET
21 BLACK WHITE 46 TURQUOISE BLACK
22 BLACK RED 47 TURQUOISE BLUE
23 BLACK YELLOW 48 TURQUOISE RED
24 BLACK VIOLET 49 TURQUOISE ORANGE
25 WHITE RED 50 TURQUOISE YELLOW

INSTRUMENTATION CABLE
TO BRITISH STEEL
SPECIFICATION
CES20 TYPE 143
(0.75MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 66

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
Solid tinned annealed copper conductors, PVC insulated, polyester taped, PVC
sheathed. To BPO CW(M) 1308. Sheath colour: White. Flame propagation to
BS4066 PT1 and IEC 332 PT1.

CCC STRANDING No. OF WEIGHT OVERALL GLAND


CODE (MM2) PAIRS KGS/KM DIAMETER SIZE
(MM) (MM)
13000 1/0.50 2 18 4.1 20/16
13001 1/0.50 3 24 4.8 20/16
13002 1/0.50 4 35 5.8 20/16
13003 1/0.50 6 46 6.8 20/16
13004 1/0.50 10 70 8.3 20/16
13005 1/0.50 10+E 90 8.6 20S
13006 1/0.50 12 80 9.1 20S
13007 1/0.50 15 95 9.8 20S
13008 1/0.50 20+E 146 12.0 20
13009 1/0.50 25+E 163 11.4 20
13010 1/0.50 30+E 200 12.2 20
13012 1/0.50 40+E 297 15.0 25
13014 1/0.50 50+E 356 17.8 25
13016 1/0.50 60+E 412 20.9 32
13018 1/0.50 80+E 552 22.5 32
13020 1/0.50 100+E 697 24.1 32
13022 1/0.50 160+E 1135 30.5 40
13023 1/0.50 320+E 2306 39.5 50

E. denotes earth core. Bending radius:


5 x overall diameter.
Temperature limits:
-20 to +70°C. Should not be installed at
temperatures below 0°C.

CORE IDENTIFICATION:

PAIR A B PAIR A B
NUMBER WIRE WIRE NUMBER WIRE WIRE
1 WHITE/BLUE BLUE/WHITE 16 YELLOW/BLUE BLUE/YELLOW
2 WHITE/ORANGE ORANGE/WHITE 17 YELLOW/ORANGE ORANGE/YELLOW
3 WHITE/GREEN GREEN/WHITE 18 YELLOW/GREEN GREEN/YELLOW
4 WHITE/BROWN BROWN/WHITE 19 YELLOW/BROWN BROWN/YELLOW
5 WHITE/GREY GREY/WHITE 20 YELLOW/GREY GREY/YELLOW
6 RED/BLUE BLUE/RED 21 VIOLET/BLUE BLUE/VIOLET
7 RED/ORANGE ORANGE/RED 22 VIOLET/ORANGE ORANGE/VIOLET
8 RED/GREEN GREEN/RED 23 VIOLET/GREEN GREEN/VIOLET
9 RED/BROWN BROWN/RED 24 VIOLET/BROWN BROWN/VIOLET
10 RED/GREY GREY/RED 25 VIOLET/GREY GREY/VIOLET
11 BLACK/BLUE BLUE/BLACK 26 PINK/BLUE BLUE/PINK
12 BLACK/ORANGE ORANGE/BLACK 27 PINK/ORANGE ORANGE/PINK
13 BLACK/GREEN GREEN/BLACK 28 PINK/GREEN GREEN/PINK
14 BLACK/BROWN BROWN/BLACK 29 PINK/BROWN BROWN/PINK
15 BLACK/GREY GREY/BLACK 30 PINK/GREY GREY/PINK

Solid plain annealed copper conductors, cellular polyethylene insulated,


Petroleum jelly filled, PE outer sheath. Black. To CW1128A. Flame propagation
to BS4066 PT1 and IEC 332 PT1.

CCC STRANDING No. OF WEIGHT OUTSIDE GLAND


CODE (MM) PAIRS KG/KM DIAMETER SIZE
(MM)
13030 1/0.50 5 76 7.8 20/16
13031 1/0.50 10 113 9.1 20S
13032 1/0.50 20 154 11.3 20
13034 1/0.50 50 381 15.5 25
INTERNAL TELEPHONE 13035 1/0.50 100 710 20.7 32
CABLE TYPE CW1308
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
67

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6:
Issue 5 Section 3.6. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13050 0.28 1/0.6 *2 145 8.0 20/16 0.4
13051 0.28 1/0.6 5 221 10.0 20/16 0.4
13052 0.28 1/0.6 10 314 12.3 20/16 0.6
13053 0.28 1/0.6 20 463 15.0 20S 0.6
13054 0.28 1/0.6 30 697 18.0 20 0.8
13055 0.28 1/0.6 50 977 21.8 25 0.9
13056 0.28 1/0.6 100 1793 29.9 32 1.2

* 2 pair laid up in quad formation. Core identification:


See colour chart on page 69.
Temperature limits:
-20 to +70°C. Should not be installed at
temperatures below 0°C.

Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs, PVC bedding,
galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6: Issue 5 Section 3.6.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13081 0.63 1/0.9 *2 250 10.1 20/16 0.5
13083 0.63 1/0.9 5 350 14.1 20S 0.6
13084 0.63 1/0.9 10 650 18.6 20 0.8
13085 0.63 1/0.9 15 800 21.0 25 0.9
13086 0.63 1/0.9 20 1000 22.7 25 0.9
13087 0.63 1/0.9 25 1250 25.4 25 1.0
13088 0.63 1/0.9 30 1400 26.7 25 1.1
13089 0.63 1/0.9 40 1700 29.3 32 1.2
13090 0.63 1/0.9 50 2000 32.6 32 1.4
- 0.63 1/0.9 60 2690 36.6 40 1.6
- 0.63 1/0.9 75 2900 38.4 40 1.6
13091 0.63 1/0.9 100 3650 44.1 50S 1.8

Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs,
collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6:
Issue 5 Section 3.6. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13101 0.63 1/0.9 *2 258 11.0 20/16 0.5
13103 0.63 1/0.9 5 445 15.3 20S 0.6
13104 0.63 1/0.9 10 735 19.2 20 0.8
13105 0.63 1/0.9 15 908 21.4 25 0.9
13106 0.63 1/0.9 20 1046 23.1 25 1.2
13107 0.63 1/0.9 25 1750 25.8 25 1.2
13108 0.63 1/0.9 30 1512 27.1 32 1.2
13109 0.63 1/0.9 40 1804 30.2 32 1.2
13110 0.63 1/0.9 50 2166 33.6 40 1.4
- 0.63 1/0.9 100 3870 45.4 50S 2.0

* 2 pair laid up in quad formation. Core identification:


PVC INSULATED See colour chart on page 69.
Temperature limits:
MULTIPAIR ARMOURED -20 to +70°C. Should not be installed at
CABLE TO ESI temperatures below 0°C.
Bending radius: 6 x overall diameter.
STANDARD
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 68

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-
6: Issue 6 Section 4.5. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13381 0.5 1/0.8 *2 200 9.5 20/16 0.5
13383 0.5 1/0.8 5 290 13.1 20S 0.6
13384 0.5 1/0.8 10 450 17.0 20 0.7
13385 0.5 1/0.8 15 630 18.9 20 0.8
13386 0.5 1/0.8 20 770 20.5 20 0.9
13387 0.5 1/0.8 25 1159 23.2 25 1.0
13388 0.5 1/0.8 30 1110 26.2 25 1.1
13389 0.5 1/0.8 40 1450 31.8 32 1.4
13390 0.5 1/0.8 50 1770 33.4 40 1.4
13391 0.5 1/0.8 100 3000 43.4 50S 1.8

Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs,
collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,
PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-
6: Section 4.5. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13401 0.5 1/0.8 *2 260 10.9 20/16 0.5
13403 0.5 1/0.8 5 380 14.1 20S 0.6
13404 0.5 1/0.8 10 660 17.8 20 0.7
13405 0.5 1/0.8 15 795 19.4 20 0.8
PVC INSULATED 13406 0.5 1/0.8 20 900 21.1 25 0.9
13407 0.5 1/0.8 25 1159 23.5 25 1.0
MULTIPAIR ARMOURED 13408 0.5 1/0.8 30 1380 27.1 32 1.1
13409 0.5 1/0.8 40 1800 33.0 32 1.4
CABLE TO ESI 13410 0.5 1/0.8 50 2220 34.9 40 1.4
STANDARD 13411 0.5 1/0.8 100 3041 44.7 50S 1.8

Solid tinned annealed copper, polyethylene insulated, low smoke and zero
halogen (LS0H) bedding, galvanised steel wire armour, low smoke and zero
halogen (LS0H) sheath. Black. Generally to ESI 09-6: Issue 6 Section 4.5.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13501 0.5 1/0.8 *2 200 9.5 20/16 0.5
13503 0.5 1/0.8 5 290 13.1 20S 0.6
13504 0.5 1/0.8 10 450 17.0 20 0.7
13506 0.5 1/0.8 20 770 20.5 20 0.9

Solid tinned, annealed copper conductors, polyethylene insulated, twisted to form


pairs, collective aluminium/mylar foil tape screen complete with 0.5mm2 drain, wire,
low smoke zero halogen (LS0H) bedding, galvanised steel wire armour, low smoke
and zero halogen (LS0H) sheath. Black. Generally to ESI 09-6: Issue 6 Section 4.5.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13601 0.5 1/0.8 *2 260 10.9 20/16 0.5
13603 0.5 1/0.8 5 380 14.1 20S 0.6
13604 0.5 1/0.8 10 660 17.8 20 0.7
13606 0.5 1/0.8 20 900 21.1 25 0.9

* 2 pair laid up in quad formation. Core identification:


See colour chart on page 70.
Temperature limits:
-20 to +70°C. Should not be installed at
temperatures below 0°C.
Bending radius: 8 x overall diameter.
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
69

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
ESI 09-6 SECTION 3

PAIR A B PAIR A B
NUMBER WIRE WIRE NUMBER WIRE WIRE
1 BLACK BLUE 26 WHITE YELLOW
2 BLACK ORANGE 27 WHITE VIOLET
3 BLACK GREEN 28 BLUE RED
4 BLACK BROWN 29 BLUE YELLOW
5 BLACK GREY 30 BLUE VIOLET
6 BLUE WHITE 31 GREEN RED
7 BLUE ORANGE 32 GREEN YELLOW
8 BLUE GREEN 33 GREEN VIOLET
9 BLUE BROWN 34 RED GREY
10 BLUE GREY 35 RED ORANGE
11 ORANGE WHITE 36 RED YELLOW
12 ORANGE GREEN 37 RED BROWN
13 ORANGE BROWN 38 RED VIOLET
14 ORANGE GREY 39 GREY YELLOW
15 GREEN WHITE 40 GREY VIOLET
16 GREEN BROWN 41 ORANGE YELLOW
17 GREEN GREY 42 ORANGE VIOLET
18 BROWN WHITE 43 YELLOW BROWN
19 BROWN GREY 44 YELLOW VIOLET
20 GREY WHITE 45 BROWN VIOLET
21 BLACK WHITE 46 TURQUOISE BLACK
22 BLACK RED 47 TURQUOISE BLUE
23 BLACK YELLOW 48 TURQUOISE RED
24 BLACK VIOLET 49 TURQUOISE ORANGE
25 WHITE RED 50 TURQUOISE YELLOW

All two pair cables are in quad formation and colour coded in rotation - Blue,
Orange, Green, Brown.

PAIR COLOUR
NUMBER WIRE A WIRE B
1 WHITE BLUE
2 WHITE ORANGE
3 WHITE GREEN
4 WHITE BROWN
5 WHITE GREY
6 RED BLUE
7 RED ORANGE
8 RED GREEN
9 RED BROWN
10 RED GREY
11 BLACK BLUE
12 BLACK ORANGE
13 BLACK GREEN
14 BLACK BROWN
15 BLACK GREY
16 YELLOW BLUE
17 YELLOW ORANGE
18 YELLOW GREEN
19 YELLOW BROWN
20 YELLOW GREY

2 pair (quad) cables - white, red, blue


and orange
(in order of rotation)

ESI 09-6
SECTION 3.6
CORE IDENTIFICATION
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 70

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
ESI 09-6 SECTION 4

PAIR A B
NUMBER WIRE WIRE
1 WHITE BLUE
2 WHITE ORANGE
3 WHITE GREEN
4 WHITE BROWN
5 WHITE GREY
6 RED BLUE
7 RED ORANGE
8 RED GREEN
9 RED BROWN
10 RED GREY
11 BLACK BLUE
12 BLACK ORANGE
13 BLACK GREEN
14 BLACK BROWN
15 BLACK GREY
16 YELLOW BLUE
17 YELLOW ORANGE
18 YELLOW GREEN
19 YELLOW BROWN
20 YELLOW GREY

All two pair cables are in quad For 40 pair cables the formation will be
formation and colour coded in 2 X 20 pair units numbered - 1 and 2.
rotation - White, Red, Blue, Orange.
For 50 pair cables the formation will
ESI 09-6 For 30 pair cables the formation will be 5 X 10 pair units numbered - 1, 2
SECTION 4.5 be 3 X 10 pair units numbered - 1, 2 3, 4 and 5.
CORE IDENTIFICATION and 3.

Each unit is lapped with coloured tape for identification as follows

UNIT 1 BLUE
UNIT 2 ORANGE
UNIT 3 GREEN
UNIT 4 BROWN
UNIT 5 GREY

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
71

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
Solid plain annealed copper conductors, cellular polyethylene insulated, petroleum
jelly filled, collective aluminium/mylar tape screen plus 0.5mm2 drain wire,
polyethylene bedding, galvanised steel wire armour, PVC outer sheath. Black. To
BS3573 and CW1128/1198. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13150 0.63 1/0.9 5 392 16.7 20 0.7
13151 0.63 1/0.9 10 620 19.9 20 0.8
13153 0.63 1/0.9 20 1078 24.8 25 1.0
13154 0.63 1/0.9 50 2155 34.5 40 1.6

Solid plain annealed copper conductors, cellular polyethylene insulated,


petroleum jelly filled solid polyethylene bedding, galvanised steel wire armour,
PE outer sheath. Black.
To BPO CW 1128A/1198A. (Concentric construction). Flame propagation to
BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEAT


CODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE
(MM) (MM) SINGLE
13040 0.196 1/0.5 5 470 11.78 20/16 0.5
13041 0.196 1/0.5 10 721 12.30 20S 0.5
13042 0.196 1/0.5 20 1204 14.78 20S 0.6
13043 0.196 1/0.5 50 2347 22.78 25 0.9
13044 0.196 1/0.5 100 3660 29.77 32 1.2

COLOUR SCHEME FOR BS3573 - UNIT CONSTRUCTION

PAIR A B UNIT 1 BLUE


NUMBER WIRE WIRE UNIT 2 ORANGE
1 WHITE BLUE UNIT 3 GREEN
2 WHITE ORANGE UNIT 4 BROWN
3 WHITE GREEN UNIT 5 GREY
4 WHITE BROWN
5 WHITE GREY
6 RED BLUE If sub-units are used binders for
7 RED ORANGE corresponding sub-units shall be the
8 RED GREEN
same colour.
9 RED BROWN
10 RED GREY

Cables may be manufactured using 5-


pair sub-units coloured as 1-5 and 6-10

PETROLEUM
JELLY FILLED TELEMETRY
CABLE TO BS3573 AND
CW1128/1198
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 72

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
Tinned annealed flexible copper conductors, PVC insulated, non-hygroscopic binder
tape, tinned annealed copper wire braid screen, PVC outer sheath. Black. 440 volts
grade. To Ministry of Defence Standard DEF 61-12 (Part 4 for 7/0.2 conductors, Part
5 for 16/0.2 conductors). Flame propogation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM2) CORES KG/KM DIAMETER SIZE
(MM) (MM)
722C 0.22 7/0.20 2 23 4.1 16
723C 0.22 7/0.20 3 27 4.3 16
724C 0.22 7/0.20 4 32 4.6 16
726C 0.22 7/0.20 6 55 5.9 16
728C 0.22 7/0.20 8 69 6.0 16
7212C 0.22 7/0.20 12 83 7.2 16
7218C 0.22 7/0.20 18 110 8.5 20
7225C 0.22 7/0.20 25 150 9.8 20
7236C 0.22 7/0.20 36 200 11.2 20
7250C 0.22 7/0.20 50 270 13.0 25
7260C 0.22 7/0.20 60 310 13.8 25
1622C 0.50 16/0.20 2 69 6.9 16
1623C 0.50 16/0.20 3 79 7.2 16
1624C 0.50 16/0.20 4 92 7.7 16
1626C 0.50 16/0.20 6 120 8.7 20
1628C 0.50 16/0.20 8 146 8.9 20
16210C 0.50 16/0.20 *10 190 11.8 20
16212C 0.50 16/0.20 12 198 11.0 20
16218C 0.50 16/0.20 18 250 12.5 20
16225C 0.50 16/0.20 25 320 14.6 25
16236C 0.50 16/0.20 36 450 16.7 25
16250C 0.50 16/0.20 50 564 18.5 32
16260C 0.50 16/0.20 60 670 20.3 32

Tinned annealed flexible copper conductors, low smoke and zero halogen
(LS0H) insulation, non-hygroscopic binder tape, tinned annealed copper wire
braid screen, low smoke and zero halogen (LS0H) outer sheath. Black. 440 volt
grade. Generally to ministry of Defence Standard DEF61-12 Part 5 LSF.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM2) CORES KG/KM DIAMETER SIZE
(MM) (MM)
LSF1622C 0.50 16/0.20 2 69 6.9 16
LSF1623C 0.5 16/0.20 3 79 7.2 16
LSF1624C 0.5 16/0.20 4 92 7.7 16
LSF1626C 0.5 16/0.20 6 120 8.7 20
LSF16212C 0.5 16/0.20 12 198 11.0 20
LSF16218C 0.5 16/0.20 18 250 12.5 20
LSF16225C 0.5 16/0.20 25 320 14.6 25

* Laid up in a pair configuration. Core identification:


See colour chart on page 73.
Temperature limits:
-55 to +70°C. Should not be installed at
temperatures below 0°C.
Bending radius:
6 x overall diameter.

DEFENCE
STANDARD SCREENED
MULTICORE
CABLE ‘C’ TYPE
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
73

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
COLOUR CODES

CORE COLOUR
NUMBER
1 RED
2 BLUE
3 GREEN
4 YELLOW
5 WHITE
6 BLACK
7 BROWN
8 VIOLET
9 ORANGE
10 PINK
11 TURQUOISE
12 GREY
13 RED/BLUE
14 GREEN/RED
15 YELLOW/RED
16 WHITE/RED
17 RED/BLACK
18 YELLOW/BLUE
19 YELLOW/BLUE
20 WHITE/BLUE
21 BLUE/BLACK
22 ORANGE/BLUE
23 GREEN/BLUE
24 GREY/BLUE
25 YELLOW/GREEN
26 WHITE/GREEN
27 GREEN/BLACK
28 ORANGE/GREEN
29 GREY/GREEN
30 YELLOW/BROWN
31 WHITE/BROWN
32 BROWN/BLACK
33 GREY/BROWN
34 YELLOW/VIOLET
35 VIOLET/BLACK
35 VIOLET/BLACK
36 WHITE/VIOLET

Where 2 colours are shown the core


is striped e.g. Red/Blue - the core is
striped Red with Blue.

DEFENCE
STANDARD 61-12
PARTS 4 & 5 CORE
IDENTIFICATION
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 74

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
NON-ARMOURED
Plain annealed flexible conductors, PVC insulated, laid up to form pairs,
collective aluminium mylar foil tape screen, complete with 0.5mm2 drain
wire, PVC outer sheath.
Thermocouple wires calibrated to BS4937, ANSI 96.1 and IEC 584.3.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

NO OF SIZE STRANDING OVERALL GLAND JX CCC KCB CCC KX CCC TX CCC


PAIRS (MM2) (MM) DIAMETER SIZE CODE CODE CODE CODE
(MM) (MM) (WAS VX)
1 0.75 24/0.20 6.7 20/16 7500 7530 7570 7550
2 0.75 24/0.20 7.7 20/16 7501 7531 7571 7551
5 0.75 24/0.20 13.7 25 7503 7533 7573 7553
10 0.75 24/0.20 18.1 25 7505 7537 7575 7557
20 0.75 24/0.20 23.9 32 7507 7539 7577 7559

Temperature limits: Core identification:


-30 to +105°C. See colour chart on page 77.
Bending radius: Should not be installed at
5 x overall diameter. temperatures below 0°C.

ARMOURED
Plain annealed flexible conductors, PVC insulated, laid up to form pairs,
collective aluminium mylar foil tape screen, complete with 0.5mm2 drain
wire, PVC bedding, galvanised steel wire armour, PVC outer sheath.
Thermocouple wires calibrated to BS4937, ANSI 96.1 and IEC 584.3.
Flame propagation to BS4066 PT1 and IEC 332 PT1.

NO OF SIZE STRANDING OVERALL GLAND JX CCC KCB CCC KX CCC TX CCC


PAIRS (MM2) (MM) DIAMETER SIZE CODE CODE CODE CODE
(MM) (MM) (WAS VX)
1 0.75 24/0.20 11.1 20/16 7600 7640 7700 7660
2 0.75 24/0.20 12.3 20/16 7601 7641 7701 7661
5 0.75 24/0.20 19.2 20 7603 7643 7703 7663
10 0.75 24/0.20 24.7 25 7605 7645 7705 7665
20 0.75 24/0.20 30.7 32 7607 7647 7707 7667

Temperature limits: Core identification:


-30 to +105°C. See colour chart on page 77.
Bending radius: Should not be installed at
6 x overall diameter. temperatures below 0°C.

PVC INSULATED
COLLECTIVE SCREENED
THERMOCOUPLE
EXTENSION AND
COMPENSATING CABLE
(0.75MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
75

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
TRAFFIC CONTROL CABLE
Plain annealed solid conductors, PVC insulated, PVC bedding, galvanised steel
wire armour, PVC outer sheath, colour orange, generally to BS6346/87

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
TRAF4X1 1.0 1/1.13 4 325 13.3 20S
TRAF8X1 1.0 1/1.13 8 413 15.6 20S
TRAF12X1 1.0 1/1.13 12 567 17.9 20
TRAF16X1 1.0 1/1.13 16 774 19.9 20
TRAF20X1 1.0 1/1.13 20 905 22.0 25
TRAF4X1/5 1.5 1/1.38 4 363 12.5 20S
TRAF8X1/5 1.5 1/1.38 8 534 15.8 20
TRAF12X1/5 1.5 1/1.38 12 704 18.5 20
TRAF16X1/5 1.5 1/1.38 16 836 20.0 20
TRAF20X1/5 1.5 1/1.38 20 1040 21.5 25
TRAF8X1E 1.0 1/1.13 8 533 16.3 20

Temperature limits: Violet, White/Red, Blue/Red,


-15 to +70°C. Black/Red, Grey/Red, Yellow/Red,
Brown/Red.
Core identification:
20 core - Red, White, Blue, Black,
4 core - Red, White, Blue, Black.
Green, Yellow, Brown, Orange, Grey,
8 core - Red, White, Blue, Black, Green,
Violet, White/Red, Blue/Red,
Yellow, Brown, Orange.
Black/Red, Grey/Red, Yellow/Red,
12 core - Red, White, Blue, Black,
PVC INSULATED Green, Yellow, Brown, Orange, Grey,
Brown/Red, Green/Red, Orange/Red,
ARMOURED Violet/Red, Blue/White.
Violet, White/Red, Blue/Red.
TRAFFIC SIGNAL CABLE, 16 core - Red, White, Blue, Black, Should not be installed at
LOOP FEEDER CABLE Green, Yellow, Brown, Orange, Grey, temperatures below 0°C.
AND LOOP
DETECTOR CABLE
TRAFFIC CONTROL CABLE UNARMOURED
Plain annealed solid conductors, PVC insulated, PVC sheathed, colour orange,
generally to BS6346/87, 600/1000v grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
TRAF8X1NA 1.0 1/1.13 8 218 12.6 20
TRAF12X1NA 1.0 1/1.13 12 305 13.5 25

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES 76

INSTRUMENTATION, CONTROL AND


COMMUNICATION CABLES
LOOP FEEDER ARMOURED CABLE
Plain annealed solid conductors, polythene insulated, polythene bedding,
galvanised steel wire armour, polythene outer sheath. Generally to BS6346/87.
Outer sheath colour: Orange. 600/1000 volts grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
LOOP2X1/5SWA 1.5 1/1.38 2 (1pr) 235 11.8 20S
LOOP4X1/5SWA 1.5 1/1.38 4 (2pr) 300 12.7 20S
LOOP2X2/5SWA 2.5 1/1.78 2 (1pr) 279 12.5 20S
LOOP4X2/5SWA 2.5 1/1.78 4 (2pr) 383 15.0 20

Temperature limits: Core identification:


-15 to +70°C. 2 core - Brown, Blue
4 core - Brown, Black, Grey, Blue.
Bending radius:
6 x overall diameter. Should not be installed at
temperatures below 0°C.

LOOP FEEDER CABLE


Plain annealed solid conductors, polyethylene insulated, polyethylene outer
sheath, colour orange, 600/1000v grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
LOOP2X2/5 2.5 1/1.78 2 (1pr) 10.4 9.3 20S
LOOP4X2/5 2.5 1/1.78 4 (2pr) 16.0 10.7 20S

Temperature limits: Core identification:


-15 to +70°C. 2 core - Brown, Blue
4 core - Brown, Black, Grey, Blue.
Bending radius:
6 x overall diameter. Should not be installed at
temperatures below 0°C.

LOOP DETECTOR CABLE


Tinned flexible copper conductor, ethylene propylene rubber insulated (EPR),
polychloroprene sheathed (PCP), 600/100v generally to BS6500 + BS6195,
sheath colour black.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
LOOP1/5 1.5 30/.025 1 53.8 7.0 20S
LOOP2/5 2.5 50/0.25 1 64.0 7.9 20S

Temperature limits: Should not be installed at


-30 to +85°C. temperatures below -25°C.
Bending radius: 6 x overall diameter.

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
77

INSTRUMENTATION, CONTROL AND COMMUNICATION CABLES


INSTRUMENTATION, CONTROL AND
COMMUNICATION CABLES
EX JX KX NX TX UX VX CODE
+- +- +- +- +- +- +-

BRITISH
BS1843: 1952

+- +- +- +- +- +- +-

AMERICAN
ANSI

+- +- +- +- +-

GERMAN
DIN

RC/SC KCB
+- +- +- +- +- +-

IEC 584-3

+- +- +- +- +- +-

COLOUR CODING OF
THERMOCOUPLE
IEC 584-3
EXTENSION AND
INTRINSICALLY
COMPENSATING CABLE SAFE
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
78
79

RAILWAY CABLES
RAILWAY CABLES
RAILWAY CABLES 80

RAILWAY CABLES
SIGNALLING CABLES
Stranded or flexible tinned copper conductors to BS6360, EPR insulated to BS7655 for
types B1, LSZH insulated for types A1, A2, A3. PCP sheath for types A1 & B1, LSZH
sheath for types A2 & A3. Manufactured to Railtrack specification RT/E/PS/00005.

CCC RAIL RAIL CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE CODE TYPE SIZE CORES (KG/KM) DIAMETER SIZE
(MM2)
A11X/75BR 6/120002 A1 Brown 0.75 7/0.37 1 16 2.95 N/A
A11X/75RD 6/120003 A1 Red 0.75 7/0.37 1 16 2.95 N/A
A11X/75OR 6/120004 A1 Orange 0.75 7/0.37 1 16 2.95 N/A
A11X/75GY 6/120005 A1 Grey 0.75 7/0.37 1 16 2.95 N/A
A11X/75VIR 6/120006 A1 Violet 0.75 7/0.37 1 16 2.95 N/A
A11X/75BK 6/120007 A1 Black 0.75 7/0.37 1 16 2.95 N/A
A11X115BK 6/120008 A1 Black 1.15 16/0.30 1 20 3.25 N/A
A21X/75 6/120020 A2 0.75 7/0.37 1 30 4.50 N/A
A21X115 6/120024 A2 1.15 16/0.30 1 35 4.80 20/16
A32X/75 6/120040 A3 0.75 7/0.37 2 67 7.75 20/16
A34X/75 6/120041 A3 0.75 7/0.37 4 108 9.20 20S
A36X/75 6/120042 A3 0.75 7/0.37 6 160 11.10 20S
A310X/75 6/120043 A3 0.75 7/0.37 10 259 14.35 25
A314X/75 6/120044 A3 0.75 7/0.37 14 495 15.75 25
A336X/75 6/120045 A3 0.75 7/0.37 36 752 24.20 32
A348X/75 6/120046 A3 0.75 7/0.37 48 963 27.50 40
B11X2/5 6/120061 B1 2.5 7/0.67 1 34 8.05 20/16
B11X10 6/120062 B1 10 7/1.35 1 205 10.60 20S
B11X35 6/120063 B1 35 19/1.53 1 495 14.50 25
B22X1/5 6/120081 B2 1.5 7/0.53 2 135 10.75 20S
B22X2/5 6/120082 B2 2.5 7/0.67 2 17 11.80 20
B22X10 6/120083 B2 10 7/1.35 2 443 16.85 25
B22X16 6/120113 B2 16 7/1.70 2 625 18.80 25
B22X35 6/120084 B2 35 19/1.53 2 1232 25.05 32
B22X70 6/120085 B2 70 19/2.14 2 2043 64.80 75
B22X95 6/120086 B2 95 19/2.52 2 2945 74.70 90
B24X/75 6/120087 B2 0.75 7/0.37 4 150 11.50 20S
B24X1/5 6/120088 B2 1.5 7/0.53 4 220 12.30 20
B24X2/5 6/120089 B2 2.5 7/0.67 4 295 13.35 20
B27X/75 6/120090 B2 0.75 7/0.37 7 225 13.25 20
B27X1/5 6/120091 B2 1.5 7/0.53 7 370 14.20 25
B27X2/5 6/120092 B2 2.5 7/0.67 7 500 15.50 25
B210X/75 6/120093 B2 0.75 7/0.37 10 280 16.20 25
B210X1/5 6/120094 B2 1.5 7/0.53 10 401 17.50 25
B210X2/5 6/120095 B2 2.5 7/0.67 10 680 19.20 25
B212X/75 6/120096 B2 0.75 7/0.37 12 321 16.65 25
B26PX/75 6/120111 B2 0.75 7/0.37 6pr 469 22.15 32
B212X1/5 6/120097 B2 1.5 7/0.53 12 410 18.00 25
B212X2/5 6/120098 B2 2.5 7/0.67 12 730 19.80 25
B219X/75 6/120099 B2 0.75 7/0.37 19 425 19.15 25
B219X1/5 6/120100 B2 1.5 7/0.53 19 615 20.80 32
B219X2/5 6/120101 B2 2.5 7/0.67 19 815 22.95 32
B227X/75 6/120102 B2 0.75 7/0.37 27 606 22.60 32
B227X1/5 6/120103 B2 1.5 7/0.53 27 897 25.00 32
B227X2/5 6/120104 B2 2.5 7/0.67 27 1200 27.65 40
B237X/75 6/120105 B2 0.75 7/0.37 37 786 22.60 32
B237X1/5 6/120106 B2 1.5 7/0.53 37 1126 28.25 40
B237X2/5 6/120107 B2 2.5 7/0.67 37 1600 31.25 40
B248X/75 6/120108 B2 0.75 7/0.37 48 972 28.95 40
B248X1/5 6/120109 B2 1.5 7/0.53 48 1280 31.60 40
B248X2/5 6/120110 B2 2.5 7/0.67 48 1960 35.10 50S

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
81

RAILWAY CABLES
RAILWAY CABLES
SIGNALLING CABLES

CCC RAIL RAIL CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE CODE TYPE SIZE CORES (KG/KM) DIAMETER SIZE
(MM2)
C1X2/5 6/120130 C1 2.5 50/0.25 1 174 12.60 25
C22X2/5 6/120140 C2 2.5 50/0.25 2 342 16.85 25
C24X2/5 6/120141 C2 2.5 50/0.25 4 445 18.65 25
C27X2/5 6/120142 C2 2.5 50/0.25 7 590 42.40 50
C210X2/5 6/120143 C2 2.5 50/0.25 10 784 25.55 40
C212X2/5 6/120144 C2 2.5 50/0.25 12 868 26.25 40
C216X2/5 6/160145 C2 2.5 50/0.25 16 980 28.65 40
C3TPWS 6/160086 C3TPWS 2.5 50/0.25 1pr 250 17.50 25
D11X/75 6/120211 D1 0.75 7/0.37 1 25 7.30 20/16
D11X1/5 6/120212 D1 1.5 7/0.53 1 30 7.65 20/16
D11X2/5 6/120213 D1 2.5 7/0.67 1 34 8.05 20/16
D11X10 6/120214 D1 10 7/1.35 1 205 10.60 20S
D11X35 6/120215 D1 35 19/1.53 1 495 14.50 25
D22X1/5 6/120216 D2 1.5 7/0.53 2 135 10.75 20S
D22X2/5 6/120217 D2 2.5 7/0.67 2 170 11.80 20
D22X10 6/120218 D2 10 7/1.35 2 443 16.85 25
D22X35 6/120219 D2 35 19/1.53 2 1232 25.05 40
D227X/75 6/120238 D2 0.75 7/0.37 27 606 22.60 32
D227X1/5 6/120239 D2 1.5 7/0.53 27 897 25.00 32
D227X2/5 D2 2.5 7/0.67 27 1200 27.65 40
D237X/75 6/120241 D2 0.75 7/0.37 37 786 25.55 32
D237X1/5 6/120242 D2 1.5 7/0.53 37 1126 28.25 40
D237X2/5 D2 2.5 7/0.67 37 1600 31.25 40
D248X/75 6/120244 D2 0.75 7/0.37 48 972 28.95 40
D248X1/5 6/120245 D2 1.5 7/0.53 48 1280 31.60 40
D248X2/5 6/120246 D2 2.5 7/0.67 48 1960 35.10 50S
E11X2/5 6/120172 E1 2.5 50/0.25 1 174 12.60 20
E22X2/5 6/120170 E2 2.5 50/0.25 2 342 16.85 25
E24X2/5 6/120171 E2 2.5 50/0.25 4 445 18.65 25
E27X2/5 6/120173 E2 2.5 50/0.25 7 590 21.20 32
E210X2/5 6/120174 E2 2.5 50/0.25 10 784 25.55 32
E212X2/5 6/120175 E2 2.5 50/0.25 12 868 26.25 40
E3TPWS 6/160090 E3TPWS 2.5 50/0.25 1pr 250 17.50 25

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
RAILWAY CABLES 82

RAILWAY CABLES
POWER CABLES
Solid plain aluminium sectoral conductors XLPE insulated, PVC outer sheath,
Black to BR800 06/142639. 600/1000 volts grade to BS 5467.

CCC RAIL CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE CODE SIZE CORES (KG/KM) DIAMETER SIZE
(MM2)
SAC2X16NA 6/142419 16 2 420 14.30 25
SAC2X25NA 6/142519 25 2 455 16.60 25
SAC2X35NA 6/142609 35 2 525 18.00 25
SAC2X50NA 6/142629 50 2 620 20.40 32
SAC2X70NA 6/142639 70 2 840 22.80 32
SAC2X95NA 6/142644 95 2 1020 26.20 40
SAC4X70NA 6/151469 70 4 1750 30.60 40

TRACK FEEDER CABLES


Uncompacted circular stranded aluminium to BS6360 or uncompacted circular
stranded tinned copper to BS6360. CSP sheathed type RS4 to BS6899, black.

CCC RAIL POLARITY CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE CODE SIZE CORES (KG/KM) DIAMETER SIZE
(MM2)
TRACK150 6/116601 NEGATIVE 150 AL 37/2.25 1 540 19.40 25
TRACK161 6/132340 NEGATIVE 161 CU 91/1.53 1 1887 24.80 32
TRACK240 6/132990 NEGATIVE 240 AL 61/2.25 1 1076 28.30 40
TRACK500 6/132840 POSITIVE 500 AL 61/3.20 1 2245 40.20 50
TRACK500CU 6/132992 NEGATIVE 500 CU 91/2.65 1 5291 40.60 50
TRACK630CU 6/116612 POSITIVE 630 CU 127/2.52 1 6692 44.20 63S
TRACK800 6/132991 NEGATIVE 800 AL 127/2.85 1 3255 48.50 63S
TRACK1000 6/116610 POSITIVE 1000 AL 127/3.20 1 3943 53.00 63

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
83

MARINE AND OFFSHORE CABLES


MARINE AND
OFFSHORE CABLES
MARINE AND OFFSHORE CABLES 84

MARINE AND OFFSHORE CABLES


Tinned annealed stranded copper conductors, ethylene propylene rubber (EPR)
insulated, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000 volts
grade to BS6883 and IEC 92-3.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6571TQ1/5 1.5 7/0.53 1 49 5.5 20/16
6572TQ1/5 1.5 7/0.53 2 125 8.9 20S
6573TQ1/5 1.5 7/0.53 3 150 9.4 20S
6574TQ1/5 1.5 7/0.53 4 180 10.3 20S
6575TQ1/5 1.5 7/0.53 5 190 11.0 20S
6576TQ1/5 1.5 7/0.53 6 240 12.2 20
6577TQ1/5 1.5 7/0.53 7 275 12.5 20
6578TQ1/5 1.5 7/0.53 8 295 13.3 25
6570/10TQ1/5 1.5 7/0.53 10 360 16.2 25
6570/12TQ1/5 1.5 7/0.53 12 440 16.4 25
6570/19TQ1/5 1.5 7/0.53 19 740 19.3 32
6570/27TQ1/5 1.5 7/0.53 27 970 23.5 32
6570/30TQ1/5 1.5 7/0.53 30 1015 24.3 32
6570/37TQ1/5 1.5 7/0.53 37 1220 26.0 40
6571TQ2/5 2.5 7/0.67 1 63 6.0 20/16
6572TQ2/5 2.5 7/0.67 2 160 9.8 20S
6573TQ2/5 2.5 7/0.67 3 190 10.4 20S
6574TQ2/5 2.5 7/0.67 4 240 11.4 20
6575TQ2/5 2.5 7/0.67 5 280 12.6 20
6576TQ2/5 2.5 7/0.67 6 470 16.9 25
6577TQ2/5 2.5 7/0.67 7 355 13.7 25
6578TQ2/5 2.5 7/0.67 8 398 15.3 25
6570/10TQ2/5 2.5 7/0.67 10 519 17.7 25
6570/12TQ2/5 2.5 7/0.67 12 650 18.3 25
6570/19TQ2/5 2.5 7/0.67 19 860 21.7 32
6570/27TQ2/5 2.5 7/0.67 27 1220 26.3 40
6570/30TQ2/5 2.5 7/0.67 30 1270 27.1 40
6570/37TQ2/5 2.5 7/0.67 37 1610 29.5 40
6571TQ4 4.0 7/0.85 1 90 6.9 20/16
6572TQ4 4.0 7/0.85 2 240 12.0 20
6573TQ4 4.0 7/0.85 3 280 12.7 20
6574TQ4 4.0 7/0.85 4 360 13.9 25
6575TQ4 4.0 7/0.85 5 425 15.3 25
6577TQ4 4.0 7/0.85 7 530 17.7 25
6571TQ6 6.0 7/1.04 1 115 7.5 20/16
6572TQ6 6.0 7/1.04 2 305 13.1 20
6573TQ6 6.0 7/1.04 3 370 13.9 25
6574TQ6 6.0 7/1.04 4 475 15.4 25

Core identification: Should not be installed at


White with Black numbers. temperatures below -15°C.
Single cores available in either Black
or Green/Yellow outer sheath.

EPR INSULATED
NON-ARMOURED
SHIPWIRING CABLE
(1.5MM2 TO 6MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
85

MARINE AND OFFSHORE CABLES


MARINE AND OFFSHORE CABLES
Tinned annealed stranded copper conductors, ethylene propylene rubber (EPR)
insulated, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000 volts
grade to BS6883 type SW4 and IEC 92-3.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6571TQ10 10 7/1.35 1 165 9.0 20S
6572TQ10 10 7/1.35 2 470 16.0 25
6573TQ10 10 7/1.35 3 595 17.2 25
6574TQ10 10 7/1.35 4 745 18.9 25
6571TQ16 16 7/1.70 1 230 10.1 20S
6572TQ16 16 7/1.70 2 655 18.3 25
6573TQ16 16 7/1.70 3 830 19.5 32
6574TQ16 16 7/1.70 4 1045 21.7 32
6571TQ25 25 19/1.35 1 380 12.4 20
6572TQ25 25 19/1.35 2 1090 22.9 32
6573TQ25 25 19/1.35 3 1340 24.4 32
6574TQ25 25 19/1.35 4 1680 27.1 40
6571TQ35 35 19/1.53 1 490 13.6 25
6572TQ35 35 19/1.53 2 1310 25.3 32
6573TQ35 35 19/1.53 3 1630 27.1 40
6574TQ35 35 19/1.53 4 2130 30.1 40
6571TQ50 50 19/1.78 1 640 15.5 25
6572TQ50 50 19/1.78 2 1720 29.0 40
6573TQ50 50 19/1.78 3 2210 30.9 40
6574TQ50 50 19/1.78 4 2840 34.6 50S
6571TQ70 70 19/2.14 1 870 17.5 25
6573TQ70 70 19/2.14 3 3080 35.3 50S
6574TQ70 70 19/2.14 4 3950 39.2 50
6571TQ95 95 37/1.78 1 1150 19.6 32
6573TQ95 95 37/1.78 3 4060 40.3 50
6574TQ95 95 37/1.78 4 5170 45.1 63S
6571TQ120 120 37/2.03 1 1440 21.4 32
6573TQ120 120 37/2.03 3 5130 44.4 63S
6571TQ150 150 37/2.25 1 1770 23.8 32
6571TQ185 185 37/2.52 1 2200 26.3 40
6571TQ240 240 61/2.25 1 2780 29.5 40
6571TQ300 300 61/2.52 1 3450 32.6 50S
6571TQ400 400 91/2.36 1 4400 36.7 50S
6571TQ500 500 91/2.65 1 5600 40.5 50
6571TQ630 630 127/2.52 1 6910 44.4 63S

Single core cables are available in Core identification:


Black or Green/Yellow outer sheath. White with Black numbers.
Temperature limits: Should not be installed at
-30 to +85°C. temperatures below -15°C.
Bending radius:
up to 25mm - 4 x overall diameter.
above 25mm - 6 x overall diameter.

EPR INSULATED
NON-ARMOURED
SHIPWIRING CABLE
(10MM2 TO 630MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
MARINE AND OFFSHORE CABLES 86

MARINE AND OFFSHORE CABLES


Tinned annealed stranded copper conductors, ethylene propylene rubber (EPR)
insulated, low smoke, zero halogen (LSOH) bedding, galvanised steel wire
braid armour, low smoke, zero halogen (LSOH) SW4 outer sheath. Black.
600/1000 volts grade to BS6883 IEE 92-3.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6582TQ1/5 1.5 7/0.53 2 300 13.3 20S
6583TQ1/5 1.5 7/0.53 3 325 13.8 20S
6584TQ1/5 1.5 7/0.53 4 395 15.0 20S
6585TQ1/5 1.5 7/0.53 5 407 15.2 20S
6586TQ1/5 1.5 7/0.53 6 425 16.5 20
6587TQ1/5 1.5 7/0.53 7 525 17.2 20
6580/12TQ1/5 1.5 7/0.53 12 790 21.7 25
6580/19TQ1/5 1.5 7/0.53 19 1090 24.7 25
6580/27TQ1/5 1.5 7/0.53 27 1515 29.3 32
6580/37TQ1/5 1.5 7/0.53 37 1870 33.2 32
6582TQ2/5 2.5 7/0.67 2 350 14.2 20S
6583TQ2/5 2.5 7/0.67 3 400 15.0 20S
6584TQ2/5 2.5 7/0.67 4 470 16.1 20
6585TQ2/5 2.5 7/0.67 5 485 16.9 20
6586TQ2/5 2.5 7/0.67 6 550 18.2 20
6587TQ2/5 2.5 7/0.67 7 635 18.5 20
6580/12TQ2/5 2.5 7/0.67 12 990 23.9 25
6580/19TQ2/5 2.5 7/0.67 19 1390 27.6 32
6580/27TQ2/5 2.5 7/0.67 27 1990 33.2 32
6580/37TQ2/5 2.5 7/0.67 37 2500 36.7 40
6582TQ4 4.0 7/0.85 2 480 16.6 20
6583TQ4 4.0 7/0.85 3 530 17.3 20
6584TQ4 4.0 7/0.85 4 585 18.4 20
6585TQ4 4.0 7/0.85 5 700 20.2 20
6587TQ4 4.0 7/0.85 7 897 22.7 25

Temperature limits: Core identification:


-30 to +85°C. White with Black numbers.
Bending radius: Should not be installed at
6 x overall diameter. temperatures below -15˚C.

EPR INSULATED
BRAIDED ARMOUR
SHIPWIRING CABLE
(1.5MM2 TO 4MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
87

MARINE AND OFFSHORE CABLES


MARINE AND OFFSHORE CABLES
Tinned annealed stranded copper conductors, ethylene propylene rubber (EPR)
insulated, low smoke, zero halogen (LSOH) bedding, galvanised steel wire
braid armour, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000
volts grade to BS6883 & IEE92-3 .

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6582TQ6 6 7/1.04 2 570 17.9 20
6583TQ6 6 7/1.04 3 635 18.7 20
6584TQ6 6 7/1.04 4 760 20.1 20
6582TQ10 10 7/1.35 2 750 21.0 25
6583TQ10 10 7/1.35 3 930 22.4 25
6584TQ10 10 7/1.35 4 1080 24.0 25
6582TQ16 16 7/1.70 2 1020 23.7 25
6583TQ16 16 7/1.70 3 1190 24.9 25
6584TQ16 16 7/1.70 4 1450 26.9 25
6582TQ25 25 19/1.35 2 1500 29.0 32
6583TQ25 25 19/1.35 3 1800 30.7 32
6584TQ25 25 19/1.35 4 2500 33.6 40
6582TQ35 35 19/1.53 2 1810 31.0 32
6583TQ35 35 19/1.53 3 2400 34.0 40
6584TQ35 35 19/1.53 4 2880 36.2 40
6582TQ50 50 19/1.78 2 2510 36.0 40
6583TQ50 50 19/1.78 3 3000 38.1 40
6584TQ50 50 19/1.78 4 3670 41.0 50S
6582TQ70 70 19/2.14 2 2940 36.0 40
6583TQ70 70 19/2.14 3 3980 42.8 50S
6584TQ70 70 19/2.14 4 4840 46.1 50
6582TQ95 95 37/1.78 2 3813 40.9 50S
6583TQ95 95 37/1.78 3 5290 48.5 50
6584TQ95 95 37/1.78 4 6310 52.6 63S
6582TQ120 120 37/2.03 2 4692 44.9 50S
6583TQ120 120 37/2.03 3 6480 52.9 63S
6584TQ120 120 37/2.03 4 7770 57.4 63S
6582TQ150 150 37/2.25 2 5634 48.9 50
6583TQ150 150 37/2.25 3 7700 57.9 63S
6584TQ150 150 37/2.25 4 9400 63.1 63
6582TQ185 185 37/2.52 3 9550 63.8 63
6583TQ185 185 37/2.52 4 11520 69.6 75S
6584TQ240 240 61/2.25 3 12300 71.5 75
6582TQ240 240 61/2.25 4 14840 78.3 90
6583TQ300 300 61/2.52 3 14850 78.8 90
6584TQ300 300 61/2.52 4 17938 84.9 90

Temperature limits: Core identification:


-30 TO +85°C. White with Black numbers.
Bending radius: Should not be installed at
6 x overall diameter temperatures below -15°C.

EPR INSULATED
BRAIDED ARMOURED
SHIPWIRING CABLE
(6MM2 TO 300MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
MARINE AND OFFSHORE CABLES 88

MARINE AND OFFSHORE CABLES


Tinned annealed stranded copper conductors, ethylene propylene rubber (EPR)
insulated, low smoke, zero halogen (LSOH) bedding tinned phosphor bronze
braid armour, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000
volts grade to BS6883 & IEE92-3 .

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE
(MM) (MM)
6591TQ6 6 7/1.04 1 245 11.7 20/16
6591TQ10 10 7/1.35 1 320 13.4 20S
6591TQ16 16 7/1.70 1 395 14.5 20S
6591TQ25 25 19/1.35 1 565 17.3 20
6591TQ35 35 19/1.53 1 740 18.4 20
6591TQ50 50 19/1.78 1 940 20.3 20
6591TQ70 70 19/2.14 1 1270 22.7 25
6591TQ95 95 37/1.78 1 1600 25.0 25
6591TQ120 120 37/2.03 1 1930 27.2 32
6591TQ150 150 37/2.25 1 2330 29.5 32
6591TQ185 185 37/2.52 1 3000 33.1 32
6591TQ240 240 61/2.25 1 3710 36.6 40
6591TQ300 300 61/2.52 1 4480 40.0 50S
6591TQ400 400 91/2.36 1 5340 43.9 50S
6591TQ500 500 91/2.65 1 6540 48.1 50
6591TQ630 630 127/2.52 1 8000 52.3 50

Temperature limits: Core identification:


-30 to +85°C. White.
Bending radius: Should not be installed at
6 x overall diameter. temperatures below -15°C.

EPR INSULATED SINGLE


CORE BRAIDED
SHIPWIRING CABLE
(6MM2 TO 630MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
89

FIREPROOF CABLES
FIREPROOF CABLES
FIREPROOF CABLES 90

FIREPROOF CABLES
Solid plain annealed copper conductors, magnesium oxide insulated, solid copper
sheath to BS6207, IEC 331 and BS 6387 CWZ. Available in the following options:
(a) Light Duty = 500 volts grade (b) Outer sheath finishes, bare copper,
Heavy Duty = 1000 volts grade PVC or LSF
(c) Outer sheath colours. Orange, Red
or White.

SIZE BARE SHEATHED OVERALL OVERALL GLAND SINGLE HOLE CLIP NOMINAL
REF. KG/KM KG/KM DIAMETER DIAMETER FOR USE REFERENCE STD DRUM
BARE SHEATHED WITH RPS BARE SHEATHED LTHS (MTS)
(MM) (MM) SEALS
2L1.0 105 126 5.1 6.4 20 20 26 500
2L1.5 131 154 5.7 7.0 20 20 28 500
2L2.5 180 206 6.6 7.9 20 26 32 500
2L4.0 262 322 7.7 9.2 20 30 37 500
3L1.0 136 159 5.8 7.1 20 22 28 500
3L1.5 168 194 6.4 7.7 20 24 30 500
3L2.5 222 272 7.3 8.8 20 28 34 500
4L1.0 162 187 6.3 7.6 20 24 30 500
4L1.5 203 231 7.0 8.3 20 28 34 500
4L2.5 286 336 8.1 9.6 20 32 37 500
7L1.5 310 351 8.4 9.9 25 32 40 380
7L2.5 433 475 9.7 11.2 25 37 43 285
1H6.0 173 213 6.4 7.7 20 24 34 650
1H10 233 273 7.3 8.8 20 28 34 510
1H16 321 361 8.3 9.8 20 32 37 400
1H25 456 506 9.6 11.1 20 37 43 275
1H35 600 650 10.7 12.2 20 40 47 222
1H50 782 842 12.1 13.6 25 47 54 170
1H70 1087 1147 13.7 15.2 25 54 59 190
1H95 1450 1520 15.4 17.4 25 59 67 155
1H120 1790 1870 16.8 18.8 32 63 75 135
1H150 2130 2230 18.4 20.4 32 71 79 110
1H240 3146 3312 23.3 26.1 40 88 101 67

Temperature limits: Bending radius: 6 x overall diameter.


PVC sheath -20 to +70°C.
Should not be installed at
LSF sheath -20 to +80C.
temperatures below 0°C.

SIZE BARE SHEATHED OVERALL OVERALL GLAND SINGLE HOLE CLIP NOMINAL
REF. KG/KM KG/KM DIAMETER DIAMETER FOR USE REFERENCE STD DRUM
BARE SHEATHED WITH RPS BARE SHEATHED LTHS (MTS)
(MM) (MM) SEALS
2H1.5 224 259 7.9 9.4 20 30 37 500
2H2.5 275 314 8.7 10.2 20 34 40 500
2H4.0 355 398 9.8 11.3 20 37 43 500
2H6.0 433 483 10.9 12.4 20 43 47 500
2H10 637 697 12.7 14.2 25 47 54 500
2H16 888 968 14.7 16.2 25 54 63 112
2H25 1175 1275 17.1 19.1 32 67 75 80
3H1.5 253 290 8.3 9.8 20 32 37 500
3H2.5 324 365 9.3 10.8 20 37 43 500
3H4.0 416 461 10.4 11.9 20 40 47 500
3H6.0 530 590 11.5 13.0 25 43 51 184
3H10 783 853 13.6 15.1 25 54 59 130
3H16 1000 1080 15.6 17.1 25 59 71 100
3H25 1442 1548 18.2 20.2 40 71 79 70
4H1.5 303 344 9.1 10.6 20 34 43 500
4H2.5 385 430 10.1 11.6 20 40 47 500
4H4.0 517 577 11.4 12.9 25 43 54 195
4H6.0 658 718 12.7 14.2 25 47 54 144
4H10 980 1050 14.8 16.3 25 54 63 110
4H16 1300 1390 17.3 19.3 32 67 75 89
4H25 1800 1943 20.1 22.3 40 79 88 60
7H1.5 431 478 10.8 12.3 25 43 47 245
7H2.5 561 614 12.1 13.6 25 47 54 195
12H2.5 875 970 15.6 17.9 32 59 71 148
19H1.5 989 1086 16.6 18.9 40 63 71 112

MINERAL Should not be installed at


INSULATED CABLE temperatures below 0°C.
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
91

FIREPROOF CABLES
FIREPROOF CABLES
Plain annealed copper conductor, silicon rubber insulated aluminium/polyester
tape screen, tinned annealed copper earth wire, low smoke halogen free (LSOH)
outer sheath. Red, White, Orange or Black. Fire resistant to IEC 331 and BS6387.
Flame retardant to BS5839-1:2003 and IEC 332 PT3 CAT CWZ.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND 1 HOLE GLAND


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLIP REF REF
(MM) (MM)
FP2X1 1.0 1/1.13 2+E 90 7.5 20 32 251
FP3X1 1.0 1/1.13 3+E 110 8.0 20 34 251
FP4X1 1.0 1/1.13 4+E 135 8.8 20 40 251
FP7X1 1.0 1/1.13 7+E 170 10.5 20 47 252
FP12X1 1.0 1/1.13 12+E 270 13.7 25 59 254
FP2X1/ 5 1.5 1/1.38 2+E 110 8.0 20 34 251
FP3X1/ 5 1.5 1/1.38 3+E 130 8.4 20 40 251
FP4X1/5 1.5 1/1.38 4+E 160 9.5 20 43 251
FP7X1/5 1.5 1/1.38 7+E 230 11.3 20 51 252
FP12X1/5 1.5 1/1.38 12+E 365 15.2 25 67 254
FP19X1/5 1.5 1/1.38 19+E 540 17.8 25 79 254
FP2X2/5 2.5 7/0.67 2+E 160 9.0 20 40 252
FP3X2/5 2.5 7/0.67 3+E 200 10.5 20 47 252
FP4X2/5 2.5 7/0.67 4+E 250 11.7 20 47 252
FP7X2/5 2.5 7/0.67 7+E 285 13.7 20 54 252
FP12X2/5 2.5 7/0.67 12+E 470 17.9 25 75 254
FP19X2/5 2.5 7/0.67 19+E 720 21.4 32 88 255
FP2X4 4.0 7/0.85 2+E 260 11.3 20 43 252
FP3X4 4.0 7/0.85 3+E 315 12.1 25 54 254
FP4X4 4.0 7/0.85 4+E 380 13.3 25 54 254

E= Earth conductor. Core identification:


2 core - Brown, Blue.
Temperature limits:
3 core - Brown, Black, Grey.
-10 to +80°C.
4 core - Brown, Black, Grey, Blue.
Bending radius: 7 core and above - White with Black
6 x overall diameter. numbers.
Should not be installed at
temperatures below 0°C.

FIRE RESISTANT
SECURITY CABLE
(1.0MM2 TO 4MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
FIREPROOF CABLES 92

FIREPROOF CABLES
Plain annealed stranded copper conductor, mica fire resistant tape, XLPE
insulated, low smoke halogen free (LSOH) bedding, galvanised steel wire
armour, low smoke halogen free (LSOH) outer sheath. Black. 600/1000 volts.
Fire resistant to IEC 331 & BS7846 / BS6387 & CWZ.
Flame propagation to BS4066 PT1 and IEC 332 PT1 (PT3 for bunched cables).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
6942F1/5 1.5 7/0.53 2 340 13.6 20S 0.6
6943F1/5 1.5 7/0.53 3 380 14.2 20S 0.6
6944F1/5 1.5 7/0.53 4 420 15.1 20S 0.6
6947F1/5 1.5 7/0.53 7 500 17.3 20 0.7
6940/12F1/5 1.5 7/0.53 12 820 22.1 25 0.9
6940/19F1/5 1.5 7/0.53 19 1080 25.8 25 1.1
6940/27F1/5 1.5 7/0.53 27 1550 30.4 32 1.2
6940/37F1/5 1.5 7/0.53 37 1850 33.4 32 1.4
6942F2/5 2.5 7/0.67 2 390 15.1 20S 0.6
6943F2/5 2.5 7/0.67 3 430 15.7 20S 0.7
6944F2/5 2.5 7/0.67 4 500 16.8 20 0.7
6947F2/5 2.5 7/0.67 7 730 19.8 20 0.8
6940/12F2/5 2.5 7/0.67 12 1020 24.9 25 1.0
6940/19F2/5 2.5 7/0.67 19 1530 29.5 32 1.2
6940/27F2/5 2.5 7/0.67 27 1950 34.4 40 1.4
6940/37F2/5 2.5 7/0.67 37 2440 37.8 40 1.6
6942F4 4 7/0.85 2 460 16.1 20 0.7
6943F4 4 7/0.85 3 530 16.9 20 0.7
6944F4 4 7/0.85 4 700 18.1 20 0.8
6947F4 4 7/0.85 7 840 21.6 25 0.9
6942F6 6 7/1.04 2 640 17.3 20 0.7
6943F6 6 7/1.04 3 730 18.1 20 0.8
6944F6 6 7/1.04 4 850 20.3 20 0.8
6942F10 10 7/1.35 2 820 20.0 20 0.8
6943F10 10 7/1.35 3 940 21.0 25 0.9
6944F10 10 7/1.35 4 1090 22.6 25 0.9
6942F16 16 7/1.70 2 1025 22.1 25 0.9
6943F16 16 7/1.70 3 1370 23.5 25 1.0
6944F16 16 7/1.70 4 1560 26.0 25 1.1

Temperature limits: Core identification:


-25 to +90°C. 2 core - Brown, Blue.
3 core - Brown, Black, Grey.
Bending radius:
4 core - Brown, Black, Grey, Blue.
8 x overall diameter.
7 core and above - White with
Black numbers.
Should not be installed at
temperatures below 0°C.

FIRE RESISTANT POWER


AND CONTROL CABLE
(1.5MM2 TO 16MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
93

FIREPROOF CABLES
FIREPROOF CABLES
Plain annealed stranded copper conductor, mica fire resistant tape, XLPE
insulated, low smoke, zero halogen (LSOH) bedding, galvanised steel wire
armour, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000 volts
grade. Fire resistant to BS6387/7846 & CWZ.
Flame propagation to BS4066 PT1 and IEC 332 PT1 (PT3 for bunched cables).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE


CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT
(MM) (MM)
FP 2X25 25 7/2.14 2 1200 22.0 25 0.9
FP 3X25 25 7/2.14 3 1800 27.4 25 1.1
FP 4X25 25 7/2.14 4 2100 29.1 32 1.2
FP 2X35 35 7/2.52 2 1600 24.8 25 1.0
FP 3X35 35 7/2.52 3 2100 29.2 32 1.2
FP 4X35 35 7/2.52 4 2500 32.2 32 1.4
FP 2X50 50 19/1.78 2 2000 28.0 32 1.2
FP 3X50 50 19/1.78 3 2600 33.0 32 1.4
FP 4X50 50 19/1.78 4 3200 35.0 40 1.4
FP 2X70 70 19/2.14 2 2400 30.7 40 1.4
FP 3X70 70 19/2.14 3 3400 37.0 40 1.6
FP 4X70 70 19/2.14 4 4500 40.2 50S 1.6
FP 2X95 95 19/2.52 2 3300 35.3 40 1.4
FP 3X95 95 19/2.52 3 4500 40.6 50S 2.0
FP 4X95 95 19/2.52 4 5600 44.0 50S 1.8
FP 2X120 120 37/2.03 2 3800 36.6 40 1.6
FP 3X120 120 37/2.03 3 5500 43.8 50S 1.8
FP 4X120 120 37/2.03 4 7200 48.4 50 2.0
FP 2X150 150 37/2.25 2 4400 39.3 40 1.6
FP 3X150 150 37/2.25 3 6900 48.0 50 2.0
FP 4X150 150 37/2.25 4 8500 52.5 50 R9
FP 2X185 185 37/2.52 2 5700 44.2 50S 1.8
FP 3X185 185 37/2.52 3 8200 52.0 50 R9
FP 4X185 185 37/2.52 4 10300 57.1 63S R10
FP 2X240 240 61/2.25 2 7200 48.0 50 2.0
FP 3X240 240 61/2.25 3 10200 57.1 63S R10
FP 4X240 240 61/2.25 4 12800 62.7 63 R10
FP 2X300 300 61/2.52 2 8300 51.8 63S R9
FP 3X300 300 61/2.52 3 12200 63.0 63 R10
FP 4X300 300 61/2.52 4 15600 69.6 75S R11
FP 3X400 400 61/2.85 3 15000 69.5 75S R11
FP 4X400 400 61/2.85 4 20400 78.0 75 R12

Temperature limits: Core identification:


-25 to +90°C. 2 core - Brown, Blue.
3 core - Brown, Black, Grey.
Bending radius:
4 core - Brown, Black, Grey, Blue.
8 x overall diameter.
Should not be installed at
temperatures below 0°C.

FIRE RESISTANT
POWER CABLE
(25MM2 TO 400MM2)
Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.
94
95

INSTALLATION ACCESSORIES
INSTALLATION
ACCESSORIES
97

LML

LML Products Limited


Since its inception in 1968, LML has designed, manufactured and supplied a
comprehensive range of copper tube terminals including bespoke specials.
With in-house tooling and electroplating facilities, LML will always provide a
solution for its quality focused customers in compliance with BS EN ISO
9001:2000
Copper Tube Terminals
LML terminals are manufactured from seamless copper tube to BS EN 12449
and feature bell mouth entry up to 400mm2 and chamfered entry from
500mm2 to 1000mm2. All terminals and splices (other than parallel splices)
are provided with an inspection hole to ensure the conductor is fully inserted
before crimping. Internal barrel diameters suit standard cables as defined in
BS EN 6360.
Standard finish is bright electro tin plating to BS EN 1872. Other finishes can
be provided, e.g. nickel or silver. Terminals are independently tested to comply
with BS EN 61238-1, and are also approved for military use and by London
Underground.
Crimp Tooling
LML Products also supply a large range of manual hydraulic tools for crimping
terminals from 1.5mm2 to 1000mm2. LML also supplies a range of hydraulic
crimping tools with rechargeable battery.
Med/High Voltage Crimp Terminals
LML Products manufactures a range of copper tube terminals to suit 11kv and
33kv. We also manufacture water blocked splices and terminals.
101

RAXTON LIMITED

Raxton products are designed to solve the fundamental difficulties which


exist due to the variety of thread forms currently in use within the electrical
industry. These thread forms are predominantly Isometric, Imperial, N.P.T., BSP
and PG.
Problems caused by dissimilar threads can occur in many environments
including industrial, EExd, EExe and mining. Raxton conversions are fully
approved to meet these requirements, being certified by leading test
authorities including BASEEFA, SIRA, ISSEP, KEMA, DET NORSKE VERITAS and
Standards Association of Australia. They are marked accordingly.
Standard material is brass and readily available alternatives include mild
steel, stainless steel and aluminium. Our EExe range is also available in glass
filled nylon.

ADAPTORS NYLON GLANDS


REDUCERS SCREWED NIPPLING
HEXAGON HEAD PLUGS COUPLERS
RIGHT ANGLE ADAPTORS BUSHES
MALE TO MALE ADAPTORS SHROUDS
UNIONS LOCKNUTS/LOCKRINGS
STOPPING PLUGS EARTH TAGS
EARTH LEAD ADAPTORS WASHERS
THREADED EARTH PLATES
104

W. J. FURSE & COMPANY LIMITED

E-Klips is a division of W J Furse & Co Ltd, a multi-disciplined engineering and


marketing company employing nearly 200 people worldwide.
We are the largest UK manufacturer of a comprehensive range of industrial
fasteners, which are made available to the electrical/mechanical industry.
They provide a quick, efficient method of fixing without drilling or bracket making.
Our commitment to quality has set industry standards while our new designs
bring you all the benefits of E-Klips continuous product development philosophy.
Wholly manufactured in the UK, E-Klips fasteners can be found throughout
Europe and in many other countries in the world where our unequalled
combination of speed and quality is properly appreciated.
This combination can give you savings of up to 60% over a complete
installation – a very significant competitive advantage!
E-Klips are available for every type of installation through our established
distributor network who are fully supported by our stocks and service.
So, if you would like to use the faster fastener, simply specify E-Klips and put
your opposition in the shade.
105

W. J. FURSE & COMPANY LIMITED

As a recognised world leader in the Earthing and Lightning Protection Industry,


W J Furse has a proven track record spanning over one hundred years.
The range complies with the requirements of relevant British and World
standards, and our design and manufacturing quality control systems are
independently assessed and approved to ISO9001. W J Furse can also offer a
level of competitiveness, service and technical support that is the envy of
competitors both in the UK and overseas.
Our extensive range includes the following:
Earth Rods
Copperbond, solid copper and stainless steel.
Earth Pits
Lightweight, high performance plastic and regular duty concrete pits.
Fittings
Clamps, bonds, clips and accessories in copper and aluminium alloys and
plastics suitable for flat tape and solid circular conductor systems.
Conductors
An extensive range of copper and aluminium conductors available bare and
PVC covered.
Specialist Products
Including weldable and adhesive conductor clips and earth rod seals.
Furseweld Process
An exothermic welding process with a simple self contained method of
forming high quality electrical connections which do not require external
power or heat source, making the process completely portable.
106

FRAMING AND SUPPORT SYSTEMS

CF1

CF28
CF2
CF14
CF21
CF9

CF29
CF3

CF22
CF15

CF34
CF4

CF10/1 CF16 CF23

CF5

CF35

CF11 CF17 CF24


CF6 CF36

CF18

CF37
CF25
CF7
CF12 CF38/1
CF38/2

CF19 CF26

CF8

CF13 CF27

CF20 CF39
107

Long Spring Channel Nuts


M6 ZL6
M8 ZL8
M10 ZL10
M12 ZL12
CF40 CF47
CCC1 41x21x2.5
Available in Both Plain and Slotted
Short Spring Channel Nuts
M6 ZS6
M8 ZS8
M10 ZS10
PL1 PVC M12 ZS12
GL1 Galv

CF41* Plain Channel Nuts


M6 ZN6
M8 ZN8
M10 ZN10
M12 ZN12 CCC2 41x21x2.5 Double

CF42* M10 x 40
Cone Pointed
CA1 Set Screws
Available in 150, 300,
450, 600, 750mm
M6 x 12, 16, 20, 25,
30, 35 40 and 50mm
Roofing Nuts CCC3 41x41x2.5
and Bolts Available in Both Plain and Slotted

M6 x 8, M10 and
M12 x 20, 25, 30,
35, 40 and 50mm
Hex Head
Set Screws
CA2
Available in 150, 300,
450, 600, 750mm
CF44

M6, M8, M10 and


M12
Hex Nuts, Flat
CF45* and Spring CCC4 41x41x2.5 Double
Washers Available Finishes
Pre Galvanised to BS 2989
HDG TO BS 729
CA3 Stainless Steel 316
Available in 150, 300,
450, 600, 750mm

M6, M8, M10


CF46 Pvc 2 M12 x 3MTR Lengths
FA1 of Threaded Rod

Pvc 1
108
109

CURRENT RATINGS
CURRENT RATINGS
CURRENT RATINGS 110

PVC AND LSF CONDUIT WIRING CABLES


PVC INSULATED ONLY, SINGLE CORE GENERAL PURPOSE WIRING CABLES TO BS6004
XL-LSF INSULATED ONLY, SINGLE CORE WIRING CABLES TO BS7211
Current Carrying Capacity (Amperes)

CONDUCTOR REFERENCE METHOD 4 REFERENCE METHOD 3 REFERENCE METHOD 1 REFERENCE METHOD 11 REFERENCE METHOD 12 (FREE AIR)
CROSS (ENCLOSED IN CONDUIT (ENCLOSED IN CONDUIT (CLIPPED DIRECT) (ON A PERFORATED
SECTIONAL IN THERMALLY ON A WALL OR IN CABLE TRAY HORIZONTAL VERTICAL TREFOIL
AREA INSULATING WALL ETC.) TRUNKING ETC.) HORIZONTAL OR FLAT SPACED FLAT SPACED
VERTICAL)
2 CABLES 3 OR 4 2 CABLES 3 OR 4 2 CABLES 3 OR 4 2 CABLES 3 OR 4 2 CABLES 2 CABLES 3 CABLES
SINGLE CABLES 3 SINGLE CABLES SINGLE CABLES SINGLE CABLES SINGLE SINGLE TREFOIL
PHASE PHASE A. C PHASE 3 PHASE PHASE 3 PHASE PHASE 3 PHASE PHASE PHASE 3 PHASE
A.C. or D.C A.C. OR D.C. A.C. A.C. OR D.C. A.C FLAT & A.C or D.C. A.C. FLAT & A.C. OR D.C. A.C. OR D.C. A.C.
FLAT & TOUCHING FLAT & TOUCHING OR 3 CABLES OR 3 CABLES
TOUCHING OR TREFOIL TOUCHING OR TREFOIL 3 PHASE 3 PHASE
1 2 3 4 5 6 7 8 9 10 11 12
MM2 AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP
1 14 13 17 15 19 17.5 - - - - -
1.5 18 17 22 19 25 23 - - - - -
2.5 24 23 30 26 34 31 - - - - -
4 33 30 40 35 46 41 - - - - -
6 43 39 51 45 59 54 - - - - -
10 58 53 71 63 81 74 - - - - -
16 76 70 95 85 109 99 - - - - -
25 100 91 126 111 143 130 158 140 183 163 138
35 124 111 156 138 176 161 195 176 226 203 171
50 149 135 189 168 228 209 293 215 274 246 209
70 189 170 240 214 293 268 308 279 351 318 270
95 228 205 290 259 355 326 375 341 426 389 330
120 263 235 336 299 413 379 436 398 495 453 385
150 300 270 375 328 476 436 505 461 570 524 445
185 341 306 426 370 545 500 579 530 651 600 511
240 400 358 500 433 644 590 686 630 769 711 606
300 459 410 513 493 743 681 794 730 886 824 701
400 - - 683 584 868 793 915 849 1065 984 820
500 - - 783 666 990 904 1044 973 1228 1150 936
630 - - 900 764 1130 1033 1191 1115 1423 1338 1069
800 - - - - 1288 1179 1358 1275 1581 1485 1214
1000 - - - - 1443 1323 1520 1436 1775 1671 1349

Note: Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface to
appendix 4 of BS7671, the 16th Edition of the IEE Wiring Regulations.
The current-carrying capacities in columns 2 to 5 are also applicable to flexible cables to BS 7211 Table 3(b) where the
cables are used in fixed installations.
For cable in rigid PVC conduit the values stated in Table 4D1 of BS 7671, the 16th Edition of the IEE Wiring Regulations
are applicable (See Regulations 521-05).
Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connected
to the conductor is suitable for the conductor operating temperature (See Regulation 512-02 of BS 7671, the 16th
Edition of the IEE Wiring Regulations).
Table derived from IEE copyright information.
BS 7671 - 16th Edition, IEE Wiring Regulations.
Ambient temperature: 30°C.
Conductor operating temperature: 90°C.
111

CURRENT RATINGS
SINGLE CORE CABLES HAVING THERMOSETTING INSULATION
(NON-MAGNETIC ARMOUR), COPPER CONDUCTORS BS5467 BS6724.
Current Carrying Capacity (Amperes)

CONDUCTOR REFERENCE METHOD 1 REFERENCE METHOD 2 REFERENCE METHOD 12 (FREE AIR)


CROSS (CLIPPED DIRECT) (ON A PERFORATED
SECTIONAL CABLE TRAY) 2 CABLES 2 CABLES D.C. 3 OR 4 CABLES, 3 PHASE A.C.
AREA SINGLE PHASE A.C.
2 CABLES 3 OR 4 2 CABLES 3 OR 4 HORIZONTAL VERTICAL HORIZONTAL VERTICAL HORIZONTAL VERTICAL 3 CABLES
SINGLE CABLES 3 SINGLE CABLES 3 FLAT FLAT SPACED SPACED FLAT FLAT TREFOIL
PHASE PHASE A.C. PHASE PHASE SPACED SPACED SPACED SPACED
A.C. OR D.C FLAT & A.C. FLAT & A.C. FLAT &
FLAT & TOUCHING TOUCHING TOUCHING
TOUCHING
2 3 4 5 6 7 8 9 10 11 12
MM2 AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP
50 237 220 253 232 282 266 284 270 288 266 222
70 303 277 322 293 357 337 356 349 358 331 285
95 367 333 389 352 436 412 446 426 425 393 346
120 425 383 449 405 504 477 519 497 485 449 402
150 488 437 516 462 566 539 600 575 549 510 463
185 557 496 587 524 643 614 688 660 618 574 529
240 656 579 689 612 749 714 815 782 715 666 625
300 755 662 792 700 842 805 943 906 810 755 720
400 853 717 899 767 929 889 1137 1094 848 797 815
500 962 791 1016 851 1032 989 1314 1266 923 871 918
630 1082 861 1146 935 1139 1092 1528 1474 992 940 1027
800 1170 904 1246 987 1204 1155 1809 1744 1042 978 1119
1000 1261 961 1345 1055 1289 1238 2100 2026 1110 1041 1214

Voltage Drop per Ampere per metre (mV)

CONDUCTOR 2 2 CABLES - SINGLE PHASE A.C. 3 OR 4 CABLES - 3 PHASE A.C.


CROSS CABLES
SECTIONAL D.C.
AREA
REFERENCE METHODS REFERENCE METHOD REFERENCE METHODS REFERENCE METHODS REFERENCE METHOD
1 & 11 (TOUCHING) 12 (SPACED) 1, 11 & 12 1 & 11 12
(IN TREFOIL TOUCHING) FLAT & TOUCHING) (FLAT SPACED)
1 2 3 4 5 6 7
MM2 MV MV MV MV MV MV
r x z r x z r x z r x z r x z
50 0.98 0.99 0.21 1.00 0.98 0.29 1.00 0.86 0.180 0.87 0.84 0.25 0.88 0.84 0.33 0.90
70 0.67 0.68 0.200 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.70
95 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58
120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.51
150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.45
185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41
240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37
300 0.155 0.170 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34
400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33
500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31
630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29
800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26
1000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

Note: Spacings larger than those specified in Method 12 (see Table 4A, BS7671 - 16th Edition, IEE Wiring Regulations)
will result in larger voltage drop.
Table derived from IEE copyright information.
Conductor operating temperature: 90°C.
CURRENT RATINGS 112

MULTICORE ARMOURED CABLES HAVING THERMOSETTING INSULATION


COPPER CONDUCTORS BS5467 BS6724.
Current Carrying Capacity (Amperes)

CONDUCTOR REFERENCE METHOD 1 REFERENCE METHOD 11


CROSS SECTIONAL (CLIPPED DIRECT) (ON A PERFORATED HORIZONTAL OR VERTICAL TRAY)
AREA OR REFERENCE METHOD 13 (FREE AIR)
2 CORE CABLE 3 OR 4 2 CORE CABLE 3 OR 4
SINGLE PHASE CORE CABLE, SINGLE PHASE CORE CABLE,
A.C. or D.C. 3 PHASE A.C. A.C. OR D.C. 3 PHASE A.C.
1 2 3 4 5
MM2 AMP AMP AMP AMP
1.5 27 23 29 25
2.5 36 31 39 33
4 49 42 52 44
6 62 53 66 56
10 85 73 90 78
16 110 94 115 99
25 146 124 152 131
35 180 154 188 162
50 219 187 228 197
70 279 238 291 251
95 338 289 354 304
120 392 335 410 353
150 451 386 472 406
185 515 441 539 463
240 607 520 636 546
300 698 599 732 628
400 787 673 847 728

Note: 1. Where the conductor is to be protected by a equipment connected to the conductor is suitable
semi-enclosed fuse to BS3036, see item 6.2 of the for the conductor operating temperature (see
preface to appendix 4 of BS7671, the IEE Wiring Regulation 512-02 of BS 7671, the IEE Wiring
Regulations, 16th Edition. Regulations, 16th Edition).
2. Where a conductor operates at a temperature Ambient temperature: 30°C.
exceeding 70°C it shall be ascertained that the
Conductor operating temperature: 70°C.

VoLtage Drop per Ampere per Metre (mV)

CONDUCTOR 2 CORE 2 CORE CABLE 3 OR 4 CABLE


CROSS SECTIONAL CABLE D.C SINGLE PHASE A.C. 3 PHASE A.C
AREA
1 2 3 4
MM2 MV MV MV
1.5 31 31 27
2.5 19 19 16
4 12 12 10
6 7.9 7.9 6.8
10 4.7 4.7 4.0
16 2.9 2.9 2.5

r x z r x z
25 1.85 1.85 0.160 1.90 1.60 0.140 1.65
35 1.35 1.35 0.155 1.35 1.15 0.135 1.15
50 0.98 0.99 0.155 1.00 0.86 0.135 0.87
70 0.67 0.67 0.150 0.69 0.59 0.130 0.60
95 0.49 0.50 0.150 0.52 0.43 0.130 0.45
120 0.39 0.40 0.145 0.42 0.34 0.130 0.37
150 0.31 0.32 0.145 0.35 0.28 0.125 0.30
185 0.25 0.26 0.145 0.29 0.22 0.125 0.26
240 0.195 0.20 0.140 0.24 0.175 0.125 0.21
300 0.155 0.16 0.140 0.21 0.140 0.120 0.185
400 0.120 0.13 0.145 0.195 0.115 0.125 0.170

Tables derived from IEE copyright information.


Conductor operating temperature: 90°C.
113

CURRENT RATINGS
SINGLE CORE CABLES HAVING THERMOSETTING INSULATION
COPPER CONDUCTORS BS5467 BS6724.
Current RATINGS (ac)

NOMINAL SINGLE CORE


AREA OF DIRECT IN GROUND IN SINGLE-WAY DUCTS IN FREE AIR
CONDUCTOR TREFOIL GROUP FLAT SPACED= TREFOIL GROUP FLAT TOUCHING TREFOIL GROUP FLAT SPACED=
UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D
MM2 AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP
25 - - - - - - - - - - - -
35 - - - - - - - - - - - -
50 220 220 230 230 225 220 220 220 235 250 295 300
70 270 270 280 280 270 260 270 270 285 310 370 370
95 320 320 335 335 320 305 325 325 360 375 455 460
120 360 360 380 380 360 340 370 370 415 430 520 530
150 410 410 430 430 400 375 415 410 470 490 600 600
185 460 455 485 485 440 410 465 460 540 550 690 690
240 530 520 560 560 505 470 540 540 640 650 820 820
300 600 580 640 640 560 500 610 610 740 740 940 940
400 680 650 730 730 610 530 690 690 840 840 1100 1100
500 750 710 830 830 680 570 790 780 990 930 1280 1280
630 830 760 940 940 750 620 890 890 1110 1040 1500 1480
800 920 810 1070 1060 830 660 1010 990 1270 1140 1720 1690
1000 1000 860 1180 1170 910 690 1100 1090 1400 1230 1950 1900

=Adjacent cable surfaces separated by one cable diameter.


CURRENT RATINGS 114

MULTICORE ARMOURED CABLES HAVING THERMOSETTING INSULATION,


ALUMINIUM CONDUCTORS BS5467 BS6724.
Current Carrying Capacity (Amperes)

CONDUCTOR REFERENCE METHOD 1 REFERENCE METHOD 2 (ON A PERFORATED CABLE TRAY)OR


CROSS SECTIONAL (CLIPPED DIRECT) REFERENCE METHOD 13 (FREE AIR)
AREA
2 CORE CABLE 3 OR FOUR 2 CORE CABLE 3 OR 4
SINGLE PHASE CORE CABLE, SINGLE PHASE CORE CABLE,
A.C. or D.C. 3 PHASE A.C. A.C. OR D.C. 3 PHASE A.C.
1 2 3 4 5
MM2 AMP AMP AMP AMP
16 82 71 85 74
25 108 92 112 98
35 132 113 138 120
50 159 137 166 145
70 201 174 211 185
95 242 214 254 224
120 - 249 - 264
150 - 284 - 305
185 - 328 - 350
240 - 386 - 418
300 - 441 - 488

Note: 1. Where the conductor is to be protected by a for the conductor operating temperature (see
semi-enclosed fuse to BS3036, see item 6.2 of the Regulation 512-02 of BS 7671, the IEE Wiring
preface to appendix 4 of BS7671, the IEE Wiring Regulations, 16th Edition).
Regulations, 16th Edition.
Ambient temperature: 30°C.
2. Where a conductor operates at a temperature
Conductor operating temperature: 90°C.
exceeding 70°C it shall be ascertained that the
equipment connected to the conductor is suitable

Voltage Drop per Ampere per Metre (mV)

ONDUCTOR 2 CORE 2 CORE CABLE 3 OR 4 CABLE


CROSS SECTIONAL CABLE D.C. SINGLE PHASE A.C. 3 PHASE A.C.
AREA 2 3 4
MM2 MV MV MV
16 4.8 4.8 4.2
r x z r x z
25 3.1 3.1 0.165 3.1 2.7 0.140 2.7
35 2.2 2.2 0.160 2.2 1.90 0.140 1.95
50 1.60 1.65 0.160 1.65 1.40 0.135 1.45
70 1.10 1.10 0.155 1.15 0.96 0.135 0.97
95 0.82 0.82 0.150 0.84 0.71 0.130 0.72
120 - - 0.56 0.130 0.58
150 - - 0.45 0.130 0.47
185 - - 0.37 0.130 0.39
240 - - 0.28 0.125 0.31
300 - - 0.23 0.125 0.26

Tables derived from IEE copyright information.


Conductor operating temperature: 90°C.
115

CURRENT RATINGS
CURRENT RATINGS FOR FLEXIBLE CORDS;
RATING FACTORS, MAXIMUM AMBIENT AND OPERATING TEMPERATURES FOR CABLES AND CORDS. COPPER CONDUCTORS

NOMINAL CURRENT CARRYING CAPACITY (AMPERES) VOLT DROP PER AMPERE PER METRE MAXIMUM MASS
CROSS SECTIONAL D.C. OR 3 PHASE D.C. OR 3 PHASE SUPPORTABLE BY TWIN
AREA OF CONDUCTOR SINGLE PHASE A.C. A.C. SINGLE PHASE A.C. A.C. FLEXIBLE CORD (SEE
REGULATION 522-8-06)
1 2 3 4 5 6
MM2 AMP AMP MV MV KG
0.5 3 3 93 80 2
0.75 6 6 62 54 3
1.0 10 10 46 40 5
1.25 13 - 37 - 5
1.5 16 16 32 27 5
2.5 25 20 19 16 5
4.0 32 25 12 10 5

Note: The tabulated voltage drop values above are for Table derived from IEE copyright information.
60°C PVC insulated flexible cords. For 85°C PVC
BS 7671 - 16th Edition, IEE Wiring Regulations.
insulated flexible cords they are to be multiplied
by a factor of 1.09. Conductor operating temperature: 60°C.

Correction factor for ambient temperature

AMBIENT TEMPERATURE 35°C 40°C 45°C 50°C 55°C


CORRECTION FACTOR 0.91 0.82 0.71 0.58 0.41

Maximum ambient and operating temperature for cables and cords

TYPE OF MAXIMUM AMBIENT TEMPERATURE MAXIMUM NORMAL OPERATING TEMPERATURE


INSULATION OF SURROUNDINGS OF CABLE INSULATION OR SHEATH
OR SHEATH NON FLEXIBLE CABLES LEXIBLE CABLES ALL FIXED OR FLEXIBLE CABLES PARTS OF FLEXIBLE CORDS
AND FLEXIBLE CORDS AND FLEXIBLE CORDS EXCEPT CONTAINED WITHIN A LIGHTING
AS PROVIDED IN FITTING, APPLIANCE OR
COLUMNS MARKED* ACCESSORY, AND NOT SUBJECT
TO FLEXING OR OTHER
MECHANICAL STRESS
°C °F °C °F °C °F °C °F
GENERAL 65 179 65 149 70 58 75 167
PURPOSE PVC
HEAT RESISTING 80 179 75 167 85 185 100 212
PVC
CURRENT RATINGS 116

XLPE INSULATED 600/1000 AND 1900/3300 VOLTS CABLES WITH COPPER


CONDUCTORS SUSTAINED CURRENT RATING (AMP)(50HZ) ERA PARAMETERS

NOMINAL 600/1000 VOLTS 3 SINGLE CORE CABLES 1900/3300 VOLTS 3 SINGLE CORE CABLES
CONDUCTOR IN TREFOIL ARRANGEMENT IN TREFOIL ARRANGEMENT
AREA DIRECT DUCT AIR AIR DIRECT DUCT AIR
MM2 ARMOURED ARMOURED UNARMOURED ARMOURED ARMOURED ARMOURED ARMOURED
50 231 231 223 231 222 219 240
70 284 278 284 295 271 264 300
95 340 327 352 362 324 310 368
120 386 366 412 420 366 342 428
150 431 396 475 483 409 376 487
185 485 437 551 555 460 414 556
240 558 489 658 654 528 464 656
300 623 534 761 745 589 506 747
400 691 567 887 851 651 535 851
500 765 615 1027 963 720 579 963
630 841 664 1186 1084 789 624 1084
800 888 692 1347 1178 831 650 1178
1000 942 735 1503 1278 880 689 1278

NOMINAL 600/1000 VOLTS TWIN CORE 600/1000 VOLTS 3 OR 4 CORE 1900/3300 VOLTS 3 CORE
CONDUCTOR ARMOURED CABLE ARMOURED CABLE ARMOURED CABLE
AREA DIRECT DUCT AIR DIRECT DUCT AIR DIRECT DUCT AIR
MM2
1.5 38 31 31 32 26 26 - - -
2.5 49 41 41 42 34 35 - - -
4 65 53 55 55 45 47 - - -
6 81 67 70 69 56 59 - - -
10 109 89 95 92 75 82 - - -
16 141 115 126 119 96 107 114 96 112
25 183 148 164 152 124 140 147 124 149
35 219 178 202 182 149 172 175 147 177
50 259 211 244 217 177 209 207 174 213
70 317 260 306 266 218 263 254 214 268
95 381 313 378 319 263 324 304 257 328
120 433 357 437 363 300 376 345 293 380
150 485 401 499 406 338 430 387 328 432
185 547 455 576 458 382 495 436 371 496
240 632 527 680 529 442 584 502 428 583
300 708 592 775 592 496 666 563 480 667
400 799 669 892 667 570 766 633 549 765

Cables shall only be continuously operated at their Standard depth of laying: 0.5m for 600/1000 volts
tabulated rating if the minimum current at which circuit cables.
protection is designed to operate does not exceed 1.45 0.8m for 1900/3300
times (in the case of cables in air or in ducts) or 1.3 times volts cables.
(in the case of cables laid direct in the ground) the values
Thermal resistivity of soil: 1.2K.m/W.
given above.
Standard ground temperature: 15°C.
Ambient air temperature: 25°C.
117

CURRENT RATINGS
REQUIREMENTS FOR INSTALLATION AND USE OF CABLES, FLEXIBLE
CABLES AND CORDS
Minimum bending radius for fixed wiring

INSULATION FINISH OVERALL DIAMETER FACTOR APPLIED TO O.D. OF CABLE TO


DETERMINE MINIMUM INTERNAL RADIUS OF BEND
PVC NON-ARMOURED NOT EXCEEDING 10mm 3
EXCEEDING 10mm BUT NOT EXCEEDING 25mm 4*
EXCEEDING 25mm 6*
ARMOURED ANY 6*

*For circular conductors only. For shaped conductor cables, the minimum bending radius factor is 8.

Suggested minimum bending radius for flexible cables and cords

DESCRIPTION OVERALL DIAMETER FACTOR APPLIED TO O.D. OF CABLE TO


DETERMINE MINIMUM INTERNAL RADIUS OF BEND
FIXED BENDS AND SETS MM
FLEXIBLE CORDS AND CABLES UP TO 10 2
10 TO 25 3
ABOVE 25 4

SUBJECT TO FLEXING
FLEXIBLE CORDS AND CABLES UP TO 25 6
ABOVE 25 8

WIRE ARMOURED, SCREENED


OR TEXTILE REINFORCED FLEXIBLE UP TO 8
CABLES AND CORDS ABOVE 25 10

Maximum spacing of supports for fixed wiring

OVERALL DIAMETER OF CABLES* MAXIMUM SPACING OF CLIPS


NON-ARMOURED PVC SHEATHED CABLES ARMOURED CABLES AND CORRUGATED
ALUMINIUM SHEATHED CABLES
HORIZONTAL ++ VERTICAL ++ HORIZONTAL ++ VERTICAL ++
1 2 3 4 5
MM MM MM MM MM
NOT EXCEEDING 9 250 400 - -
EXCEEDING 9 AND NOT EXCEEDING 15 300 400 350 450
EXCEEDING 15 AND NOT EXCEEDING 20 350 450 400 550
EXCEEDING 20 AND NOT EXCEEDING 40 400 550 450 600

*Taken as the measurement of the major axis, in the case of flat cables.
++The spacings stated for horizontal runs may be applied also to run at an angle of more than 30° from the vertical.
For runs at an angle of 30° or less from the vertical, the vertical spacings are applicable.

Suggested minimum bending radius for power distribution cables

CABLE TYPE FACTOR APPLIED TO O.D. OF CABLE TO


DETERMINE MINIMUM INTERNAL RADIUS OF BEND
XLPE & PVC INSULATED CABLES TO: 8
BS 6724 (INCLUDING FIRETUF POWER OHLS), BS 5467 & BS 6346. MULTICORE SINGLE CORE
PAPER INSULATED CABLES TO BS 6480: 12 16
Up to and including 8700/11000 volts
Above 8700/11000 volts up to and including 12700/22000 volts 15 18*
19000/33000 volts 18 21*
XLPE INSULATED CABLES TO BS 6622
Unarmoured 15 20
Armoured 12 15

*This also applies to individual cores of ‘SL’ cables.


CURRENT RATINGS 118

SINGLE CORE XLPE INSULATED 6350/11000 VOLT ARMOURED CABLES TO


BS6622 STRANDED COPPER CONDUCTORS

NOMINAL INSULATION ARMOUR APPROX. THICKNESS APPROX. APPROX. MINIMUM MAXIMUM MAXIMUM RESISTANCE
CONDUCTOR THICKNESS WIRE DIAMETER OF OVERALL CABLE BENDING ARMOUR OF CONDUCTOR
AREA DIAMETER OVER OVERSHEATH DIAMETER WEIGHT RADIUS RESISTANCE DC AT 20°C DC AT 20°C
ARMOUR AT 20°C
MM2 MM MM MM MM MM KG/KM MM OHMS/KM OHMS/KM OHMS/KM
50 3.4 1.6 24.9 1.8 28.5 1400 450 0.38 0.387 0.494
70 3.4 1.6 26.6 1.9 30.4 1500 500 0.35 0.268 0.341
95 3.4 1.6 28.3 1.9 32.1 1900 500 0.33 0.193 0.247
120 3.4 1.6 29.9 2.0 33.9 2100 550 0.32 0.153 0.196
150 3.4 2.0 32.1 2.1 36.3 2500 550 0.24 0.124 0.160
185 3.4 2.0 33.9 2.1 38.1 3000 600 0.22 0.0991 0.128
240 3.4 2.0 36.3 2.2 40.7 3700 650 0.21 0.0754 0.098
300 3.4 2.0 38.6 2.2 43.0 4300 650 0.20 0.0601 0.079
400 3.4 2.0 41.7 2.4 46.5 5300 700 0.19 0.0470 0.063
500 3.4 2.5 45.9 2.5 50.9 6500 800 0.14 0.0355 0.051
630 3.4 2.5 49.8 2.6 55.0 8000 850 0.13 0.0283 0.041

NOMINAL INDUCTANCE REACTANCE IMPEDANCE MAXIMUM MAXIMUM SUSTAINED CURRENT RATING MAXIMUM SYMMETRICAL SHORT MAXIMUM EARTH-FAULT
CONDUCTOR + AT 50HZ AT 90°C CAPACITANCECHARGING Ø CIRCUIT CURRENT RATING SHORT CURRENT RATING
AREA + + CURRENT AT
NORMAL
VOLTAGE & LAID IN SINGLE IN AIR FOR FOR FOR FOR FOR FOR
FREQUENCY DIRECT WAY DUCTS 0.2 SECS 1.0 SECS 3.0 SECS 0.2 SECS 1.0 SECS 3.0 SECS
MM2 MH/KM OHMS/KM OHMS/KM µF/KM AMP/KM AMP AMP AMP KA KA KA KA KA KA
50 0.430 0.134 0.512 0.24 0.49 221 220 251 15.2 6.8 3.9 15.2 6.8 3.9
70 0.400 0.127 0.364 0.28 0.56 270 261 310 21.9 9.8 5.6 17.2 7.7 4.4
95 0.380 0.120 0.274 0.32 0.64 321 306 376 30.4 13.6 7.8 18.3 8.2 4.7
120 0.370 0.115 0.227 0.36 0.71 363 341 431 38.5 17.2 9.9 19.5 8.7 5.0
150 0.360 0.113 0.195 0.39 0.77 410 375 490 47.3 21.1 12.2 25.7 11.5 6.6
185 0.350 0.108 0.167 0.43 0.85 455 410 562 59.3 26.5 15.3 27.3 12.2 7.0
240 0.330 0.104 0.143 0.48 0.96 520 460 650 78.1 34.9 20.1 29.3 13.1 7.6
300 0.320 0.100 0.128 0.53 1.06 580 500 740 98.0 43.7 25.2 31.5 14.1 8.7
400 0.310 0.097 0.116 0.59 1.18 650 531 840 >100 55.9 32.3 33.8 15.1 8.7
500 0.310 0.096 0.108 0.66 1.31 710 570 931 >100 70.6 40.7 46.5 20.8 12.0
630 0.290 0.092 0.101 0.74 1.47 761 620 1040 >100 90.8 52.6 50.3 22.5 13.0

+ Cables in touching trefoil arrangement.


ø Cables in touching trefoil or trefoil ducts.
Standard depth of laying: 0.8m.
Thermal resistivity of soil (g): 1.2K.m/W.
Standard ground temperature: 15°C.
Ambient air temperature: 25°C.
Maximum conductor temperature: 90°C.
Short circuit ratings have been calculated on the following:-
Symmetrical fault, conductor temperature rise of 90°C - 250°C.
Earth fault, armour temperature rise of 80°C - 200°C.
119

CURRENT RATINGS
THREE CORE XLPE INSULATED 6350/11000 VOLTS ARMOURED CABLES TO
BS6622 STRANDED COPPER CONDUCTORS

NOMINAL INSULATION THICKNESS THICKNESS ARMOUR THICKNESS APPROX. APPROX. MINIMUM MAXIMUM MAXIMUM RESISTANCE
CONDUCTOR THICKNESS OF COPPER OF WIRE OF OVERALL CABLE BENDING ARMOUR OF CONDUCTOR
AREA SCREEN EXTRUDED DIAMETER OVERSHEATH DIAMETER WEIGHT RADIUS RESISTANCE
TAPE BEDDING AT 20°C DC AT 20°C AC AT 20°C
MM MM MM MM MM MM MM KG/KM MM OHMS/KM OHMS/KM OHMS/KM
25 3.4 0.075 1.9 2.5 2.4 50.1 4400 650 0.64 0.727 0.926
35 3.4 0.075 1.9 2.5 2.5 52.9 4900 650 0.58 0.524 0.668
50 3.4 0.075 2.1 2.5 2.6 56.0 5600 700 0.56 0.387 0.494
70 3.4 0.075 2.1 2.5 2.7 59.9 6500 750 0.52 0.268 0.341
95 3.4 0.075 2.2 2.5 2.8 64.1 7800 800 0.48 0.193 0.247
120 3.4 0.075 2.4 2.5 3.0 68.2 8900 850 0.46 0.153 0.196
150 3.4 0.075 2.4 2.5 3.1 71.4 10000 900 0.44 0.124 0.160
185 3.4 0.075 2.5 2.5 3.2 75.7 11600 950 0.41 0.0991 0.128
240 3.4 0.075 2.5 3.15 3.4 82.6 14800 1000 0.30 0.0754 0.099
300 3.4 0.075 2.5 3.15 3.6 88.0 17300 1100 0.28 0.0601 0.080
400 3.4 0.075 2.5 3.15 3.8 95.1 20500 1150 0.26 0.0470 0.065

NOMINAL INDUCTANCE REACTANCEIMPEDANCEMAXIMUMMAXIMUM ARMOUR SUSTAINED CURRENT RATING MAXIMUM SYMMETRICAL SHORT MAXIMUM EARTH-FAULT
CONDUCTOR AT 50HZ AT 90°C CAPACITANCE CHARGING LOSS AT 50HZ CIRCUIT CURRENT RATING SHORT CURRENT RATING
AREA CURRENTAT AND AT MAX.
NORMAL CURRENT
VOLTAGE & RATING LAID IN SINGLE IN AIR FOR FOR FOR FOR FOR FOR
FREQUENCY LAID DIRECT DIRECT WAY DUCTS 0.2 SECS 1.0 SECS 3.0 SECS 0.2 SECS 1.0 SECS 3.0 SECS
MM2 MH/KM OHMS/KM OHMS/KM µF/KM AMP/KM KW/KM AMP AMP AMP KA KA KA KA KA KA
25 0.36 0.114 0.93 0.19 0.38 0.22 152 131 163 8.1 3.6 2.0 8.1 3.6 2.0
35 0.34 0.106 0.68 0.22 0.44 0.34 181 156 197 11.2 5.0 2.9 11.2 5.0 2.9
50 0.32 0.101 0.51 0.24 0.49 0.50 213 182 236 15.2 6.8 3.9 15.2 6.8 3.9
70 0.31 0.096 0.35 0.28 0.56 0.82 260 224 291 21.9 9.8 5.6 21.9 9.8 5.6
95 0.29 0.092 0.26 0.32 0.64 1.3 309 263 353 30.4 13.6 7.8 30.4 13.6 7.8
120 0.28 0.088 0.22 0.36 0.71 1.8 349 306 402 38.5 17.2 9.9 35.3 15.8 9.1
150 0.27 0.086 0.18 0.39 0.77 2.3 390 342 454 47.3 21.1 12.2 37.6 16.8 9.7
185 0.27 0.084 0.15 0.43 0.85 3.1 436 379 515 59.3 26.5 15.3 40.0 17.9 10.3
240 0.26 0.081 0.13 0.48 0.96 5.4 499 438 600 78.1 34.9 20.1 54.8 24.5 14.1
300 0.25 0.080 0.11 0.53 1.06 7.0 553 481 676 98.0 43.7 25.2 58.8 26.3 15.2
400 0.25 0.078 0.10 0.59 1.18 10.0 619 552 768 >100 55.9 32.3 63.7 28.5 16.5

Standard depth of laying: 0.8m.


Thermal resistivity of soil (g): 1.2K.m/W.
Standard ground temperature: 15°C.
Ambient air temperature: 25°C.
Maximum conductor temperature: 90°C.
Short circuit ratings have been calculated on the following:-
Symmetrical fault, conductor temperature rise of 90°C - 250°C.
Earth fault, armour temperature rise of 80°C - 200°C.
CURRENT RATINGS 120

THREE CORE XLPE INSULATED 6350/11000 VOLTS ARMOURED CABLES TO


BS6622 STRANDED ALUMINIUM CONDUCTORS

NOMINAL INSULATION THICKNESS THICKNESS ARMOUR THICKNESS APPROX. APPROX. MINIMUM MAXIMUM MAXIMUM RESISTANCE
CONDUCTOR THICKNESS OF COPPER OF WIRE OF OVERALL CABLE BENDING ARMOUR OF CONDUCTOR
AREA SCREEN EXTRUDED DIAMETER OVERSHEATH DIAMETER WEIGHT RADIUS RESISTANCE
TAPE BEDDING AT 20°C DC AT 20°C AC AT 20°C
MM MM MM MM MM MM MM KG/KM MM OHMS/KM OHMS/KM OHMS/KM
25 3.4 0.075 1.9 2.5 2.4 50.1 3800 650 0.64 1.20 1.540
35 3.4 0.075 1.9 2.5 2.5 52.9 4100 650 0.58 0.868 1.110
50 3.4 0.075 2.1 2.5 2.6 56.0 4500 700 0.56 0.641 0.822
70 3.4 0.075 2.1 2.5 2.7 59.9 5300 750 0.52 0.443 0.570
95 3.4 0.075 2.2 2.5 2.8 64.1 5800 800 0.48 0.320 0.410
120 3.4 0.075 2.4 2.5 3.0 68.2 6400 850 0.46 0.253 0.325
150 3.4 0.075 2.4 2.5 3.1 71.4 7000 900 0.44 0.206 0.265
185 3.4 0.075 2.5 2.5 3.2 75.7 7800 950 0.41 0.164 0.212
240 3.4 0.075 2.5 3.15 3.4 82.6 9800 1000 0.30 0.125 0.161
300 3.4 0.075 2.5 3.15 3.6 88.0 11000 1100 0.28 0.100 0.130
400 3.4 0.075 2.5 3.15 3.8 95.1 13400 1150 0.26 0.0778 0.103

NOMINAL INDUCTANCE REACTANCEIMPEDANCEMAXIMUMMAXIMUM ARMOUR SUSTAINED CURRENT RATING MAXIMUM SYMMETRICAL SHORT MAXIMUM EARTH-FAULT
CONDUCTOR AT 50HZ AT 90°C CAPACITANCE CHARGING LOSS AT 50HZ CIRCUIT CURRENT RATING SHORT CURRENT RATING
AREA CURRENTAT AND AT MAX.
NORMAL CURRENT
VOLTAGE & RATING LAID IN SINGLE IN AIR FOR FOR FOR FOR FOR FOR
FREQUENCY LAID DIRECT DIRECT WAY DUCTS 0.2 SECS 1.0 SECS 3.0 SECS 0.2 SECS 1.0 SECS 3.0 SECS
MM2 MH/KM OHMS/KM OHMS/KM µF/KM AMP/KM KW/KM AMP AMP AMP KA KA KA KA KA KA
25 0.36 0.114 1.54 0.19 0.38 0.14 118 101 127 5.2 2.3 1.3 5.2 2.3 1.3
35 0.34 0.106 1.12 0.22 0.44 0.21 141 121 153 7.2 3.2 1.8 7.2 3.2 1.8
50 0.32 0.101 0.83 0.24 0.49 0.31 166 141 183 9.7 4.3 2.5 9.7 4.6 2.5
70 0.31 0.096 0.58 0.28 0.56 0.50 202 174 226 14.1 6.3 3.6 14.1 6.3 3.6
95 0.29 0.092 0.42 0.32 0.64 0.77 241 205 274 19.5 8.7 5.0 19.5 8.1 5.0
120 0.28 0.088 0.34 0.36 0.71 1.1 272 239 314 24.7 11.0 6.3 24.7 11.0 6.3
150 0.27 0.086 0.28 0.39 0.77 1.4 304 267 354 30.3 13.5 7.8 30.3 13.5 7.8
185 0.27 0.084 0.23 0.43 0.85 1.9 343 297 404 38.1 17.0 9.8 38.1 17.0 9.8
240 0.26 0.081 0.18 0.48 0.96 3.3 395 347 473 50.1 22.4 12.9 50.1 22.4 12.9
300 0.25 0.080 0.15 0.53 1.06 4.4 440 383 536 62.8 28.1 16.2 58.8 26.3 15.2
400 0.25 0.078 0.13 0.59 1.18 6.5 500 446 618 80.1 35.9 20.7 63.7 28.5 16.5

Standard depth of laying: 0.8m.


Thermal resistivity of soil (g): 1.2K.m/W.
Standard ground temperature: 15°C.
Ambient air temperature: 25°C.
Maximum conductor temperature: 90°C.
Short circuit ratings have been calculated on the following:-
Symmetrical fault, conductor temperature rise of 90°C - 250°C.
Earth fault, armour temperature rise of 80°C - 200°C.
121

CURRENT RATINGS
TECHNICAL SPECIFICATIONS FOR 6381TQ

Single core, EPR insulated, HOFR sheathed. BS6007 - 6381TQ

AMBIENT TEMPERATURE 25 30 35 40 45 50 55 60 65 70 75 80
RATING FACTOR 1.02 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60 0.52 0.43 0.30

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.


For further guidance refer to the 16th Edition IEE Wiring Regulations.
For ambient air temperatures other than 30°C, the above factors should be applied.
Ambient temperature: 30°C.
Conductor operating temperature: 85°C.

Current Carrying Capacity (Amperes)

CONDUCTOR REFERENCE METHOD 3 REFERENCE METHOD 1 REFERENCE METHOD 11 REFERENCE METHOD 12


CROSS SECTIONAL (ENCLOSED IN CONDUIT ETC. (CLIPPED DIRECT) (ON A PERFORATED CABLE TRAY) (FREE AIR)
AREA IN OR ON A WALL) HORIZONTAL OR VERTICAL
2 CABLES 3 OR 4 CABLES 2 CABLES 3 OR 4 CABLES 2 CABLES 3 OR 4 CABLES SINGLE PHASE 3 CABLES
SINGLE PHASE 3 PHASE A.C. SINGLE PHASE 3 PHASE A.C. SINGLE PHASE 3 PHASE A.C. A.C. OR D.C. OR TREFOIL
A.C. OR D.C. A.C. OR D.C. FLAT & A.C. OR D.C. FLAT & 3 OR 4 CABLES 3 PHASE A.C.
FLAT & TOUCHING OR FLAT & TOUCHING 3 PHASE A.C.
TOUCHING TREFOIL TOUCHING OR TREFOIL FLAT SPACED
HORIZONTAL
OR VERTICAL
1 2 3 4 5 6 7 8 9
MM2 AMP AMP AMP AMP AMP AMP AMP AMP
4 40 36 45 42 - - - -
6 52 46 59 54 - - - -
10 72 63 81 75 - - - -
16 96 85 108 100 - - - -
25 127 112 143 133 153 140 154 134
35 157 138 177 164 189 174 192 167
50 190 167 215 199 229 211 235 204
70 242 213 274 254 293 269 303 262
95 293 258 332 308 356 327 370 320
120 339 298 384 357 412 379 431 373
150 372 334 442 411 475 437 499 432
185 428 379 519 469 542 499 573 495
240 510 443 607 553 639 589 679 587
300 593 506 695 636 735 679 786 680
400 719 602 827 755 860 798 929 799
500 835 689 946 865 989 918 1081 919
600 975 791 1088 996 1143 162 1263 1060
CURRENT RATINGS 122

FLEXIBLE CABLES AND CORDS TECHNICAL SPECIFICATIONS FOR 638*TQ


CURRENT CARRYING CAPACITY (Amperes)

AMBIENT TEMPERATURE 25 30 35 40 45 50 55 60 65 70 75 80
RATING FACTOR 1.02 1.02 0.95 0.90 0.85 0.80 0.74 0.67 0.60 0.52 0.43 0.30

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.


For further guidance refer to the 16th Edition IEE Wiring Regulations.
For ambient air temperatures other than 30°C, the above factors should be applied.

Current Carrying Capacity (Amperes)

CONDUCTOR CROSS D.C. OR SINGLE PHASE A.C. 3 PHASE A.C. SINGLE PHASE A.C. OR D.C.
SECTIONAL AREA (2 CORE CABLE, WITH OR WITHOUT (3 CORE, 4 CORE OR 2 SINGLE CORE CABLES TOUCHING
PROTECTIVE CONDUCTOR) 5 CORE CABLE)
MM2 AMP AMP AMP
4 41 36 -
6 53 47 -
10 73 64 -
16 99 86 -
25 131 114 -
35 - 140 192
50 - 170 240
70 - 216 297
95 - 262 354
120 - 303 414
150 - 348 476
185 - 397 540
240 - 467 645
300 - 537 741
400 - - 885
500 - - 1017
630 - - 1190

Ambient temperature: 30°C.


Conductor operating temperature: 85°C.
Note: The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface.
123

CURRENT RATINGS
TECHNICAL SPECIFICATIONS FOR FLEXIBLE CORDS
Applicable to: 318*Y, 218*Y, 2491YX, 309*Y, 318*P/TQ, 398*P, 380*Y, 380*P, 380*TQ, 219*Y.

Correction Factor for Ambient Temperature 60°C rubber and PVC cords

AMBIENT TEMPERATURE 35 40 45 50 55
RATING FACTOR 0.91 0.82 0.71 0.58 0.41

85°C rubber cords having a HOFR sheath or heat-resisting PVC sheath and for 90°C heat resisting and PVC cords

AMBIENT TEMPERATURE 35-50 55 60 65 70


RATING FACTOR 1.0 0.96 0.83 0.67 0.47

180°C rubber cords

AMBIENT TEMPERATURE 35-150 155 160 165 170 175


RATING FACTOR 1.0 0.92 0.82 0.71 0.57 0.40

BS6141 BS6500 Current Carrying Capacity (Amperes)

CONDUCTOR CROSS SECTIONAL AREA CURRENT CARRYING CAPACITY (Amperes)


SINGLE PHASE A.C. 3 PHASE A.C.
1 2 3
MM2 AMP AMP
0.5 3 3
0.75 6 6
1 10 10
1.25 13 -
1.5 16 16
2.5 25 20
4 32 25

Voltage Drop (per ampere per metre)

CONDUCTOR CROSS SECTIONAL AREA D.C. SINGLE PHASE A.C. 3 PHASE A.C.
1 2 3
MM2 MV MV
0.5 93 80
0.75 62 54
1 46 40
1.25 37 -
1.5 32 27
2.5 19 16
4 12 10

Note: The tabulated values above are for 60°C rubber insulated and PVC insulated flexible cords and for other types
of flexible cords they are to be multiplied by the following factors:
For 85°C rubber or PVC insulated: 1.09
180°C rubber insulated: 1.31
CURRENT RATINGS 124

TRI-RATED - SWITCHGEAR WIRING CABLE

NO. OF CORES CURRENT RATING MIXIMUM DC


& NOMINAL SINGLE CABLE 2 CABLES BUNCHED 3 CABLES BUNCHED CONDUCTOR
CROSS SECTIONAL RESISTANCE@
AREA OF CONDUCTOR 20˚C
NO X MM2 AMP AMP AMP ΩKM
1 x 0.50 11.50 10.00 7.00 39.00
1 x 0.75 16.00 14.00 10.50 26.00
1 x 1.00 19.00 16.50 12.50 19.50
1 x 1.50 24.00 20.00 16.00 13.30
1 x 2.50 32.00 28.00 22.00 7.98
1 x 4.00 43.00 37.00 29.00 4.95
1 x 6.00 56.00 49.00 39.00 3.30
1 x 10.00 79.00 69.00 57.00 1.91
1 x 16.00 105.00 91.00 76.00 1.12
1 x 25.00 141.00 123.00 104.00 0.780
1 x 35.00 178.00 154.00 131.00 0.554
1 x 50.00 217.00 188.00 162.00 0.386
1 x 70.00 276.00 239.00 208.00 0.272
1 x 95.00 337.00 292.00 257.00 0.206
1 x 120.00 400.00 347.00 305.00 0.161
1 x 150.00 457.00 396.00 350.00 0.129
1 x 185.00 526.00 454.00 405.00 0.106
1 x 240.00 634.00 546.00 489.00 0.0801
1 x 300.00 730.00 610.00 560.00 0.0641
NOTES
NOTES