Guaranteed Technical Particulars

1 a) b) c) d) e) f) g) i. ii. h) i) j) i. ii. k) l) m) n) 2 a) i. ii. iii. iv. v. b) i. ii. c) i. ii. GENERAL Name of the Manufacturer Country of Manufacture Type of Circuit Breaker Manufacturer's type designation Standard applicable Rated Voltage Rated Current under normal condition at 40 degree C ambient under site condition at 50 degree C ambient Rated Frequency Number of poles Whether gang operated Electrically Mechanically Whether dead tank or live tank Type of installation Number of breaks per pole Latching current GUARANTEED RATINGS Rated short circuit breaking currents Symmetrical component at rated voltage DC component Asymmetrical breaking current at rated voltage Rated symmetrical breaking capacity Rated asymmetrical breaking capacity Rated short circuit making current OR Short circuit peak withstand current at higher rated voltage at lower rated voltage Break time Rated Break time Maximum total break time under any duty condition for any current up to rated breaking current with limiting conditions of voltage and pressure Rated Closing time Rated Opening time Rated maximum Opening time under any condition with limiting voltage and pressure Rated Arcing time First pole to clear factor Rated Close open time Rated Short-time withstand current 1 second 3 second Rated operating duty Unit Crompton Greaves Ltd India SF6 Gas Insulated 120-SFM-32B IEC-62271-100 / IS 13118 145 Upto 3150 Upto 3150 50 / 60 3 Yes Yes Live tank Outddor 1 100

kV (rms) A A Hz No.

No kAp

kA % kA MVA MVA

40 45.00% 47.4 10046 11907

kA (peak) kA (peak) ms ms ms ms ms ms ms kA kA

100 100 </=60 </=60 </=130 </=30 </=34 </=30 1.5 </=40 ms 40 40 O-0.3s-CO-3min-CO L90 & L75 As per IEC-62271-100

d) e) f) g) h) i) j) i. ii. k) l)

m) Rated out-of-phase breaking current OR Rated breaking capacity under asynchronous condition n) Rated line charging breaking current . Rated cable charging breaking current p) Rated single capacitor bank breaking current q) Corresponding over voltage during breaking capacitive current

kA A A A p.u.

10 50 160 400 < 2.3

Guaranteed Technical Particulars


r) Rated shunt reactor breaking current s) Maximum arc duration and corresponding breaking current under lockout pressure t) Rated Small fault current breaking capacity u) Maximum temperature rise for main contacts over an ambient temperature of 50 degree C v) Rated supply voltage and pick up range for i. Trip coil ii. Close coil w) Normal power consumption at rated supply voltage of i. Trip Coil ii. Close Coil x) Rated pressure and limits of operation for extinguishing medium at 20 deg.C y) Minimum dead time for i. Three phase reclosing ii. Single phase reclosing z) Data on Restriking voltage i. Rated Breaking currents ii. TRV Peak v. Rate of rise of restriking voltage aa) No. of breaker operations before maintenance i. at rated interrupting capacity ii. at 50% of rated interrupting capacity iii. at rated normal current iv. at 50% of rated normal current bb) Maximum pole descrepancy during i. Opening ii. Closing cc) Minimum time interval between each make / break operations 3 DIELECTRIC WITHSTANDS OF COMPLETE BREAKER a) One minute dry and wet power withstand voltage i. Between live terminal ii. Between terminal with breaker contacts open & ground b)
1.2/50 micro second impulse withstand voltage

A ms, kA
O

315 kA 30, 4 < 55 degree C 110 or 125 or 220,(70 to 110%) 110 or 125 or 220, (85 to 110%) 40

V DC V DC

W W (kg/cm2) ms ms % kV (peak) kV/S

2x635W at 110 VDC 605W at 110 VDC

7; 6 to 7 300 NA 100% 249 2 10 20 1000 3000 60% 266 3 30% 266 5 10% 272 6

ms ms ms

</=3.3 </=5 Suitable for Operating seq. O-0.3sec-CO-3min-CO

kV (rms) kV (rms)

275 275

i. Between live terminal ii. Between terminal with breaker contacts open & ground c) Creeapage distance i. To earth ii. Across interruptor 4 4.1 a) i. ii. b) c) OPERATING MECHANISM SPRING CHARGNING MECHANISM Type of operating mechanism Closing Opening Type Designation No. of operations possible with stored energy

kV (peak) kV (peak) mm mm

650( on demand 700kVp is available) 650( on demand 700kVp is available) 3625 3625

Motorised Spring charged mechanism Spring Spring BM O-C-O

4.2 DETAILS OF SPRING CHARGNING MOTOR a) Type of Motor b) Type of Mounting

Universal Neck Mounted

Guaranteed Technical Particulars


c) Direction of rotation as viewed from non-driving end d) Rated supply voltage and operating range e) Motor Wattage f) Rated speed at rated voltage and frequency on no load g) Full load current at rated voltage and frequency h) Efficiency of motor at rated voltage and frequency 'i) Starting current j) Stator winding insulation class k) Weight l) Maximum time for charging the spring m) Whether indication of spring charged condition provided in control cabinet n) Make of Motor 5 DATA ON SF6 GAS a) Quantity of SF6 per pole b) Guaranteed maximum leakage rate c) Rated pressure of SF6 gas in operating chamber at 20OC d) Operating pressure range f) Capacity of SF6 gas cylinder g) Spare gas provided h) Whether breakers are dispatched filled with gas V AC W rpm A % Clockwise 1 Ph, 240, 85-110% 650 850 3.6 at 240V, 50Hz AC 50 < 600% at full load current B 3 approx. 15 Yes KPT

kg sec.

kg %/annum kg/cm2 kg/cm2 kg

2.5 Less than 1% per annum 7 6.0 - 7.0 11 20% Partially filled to 0.5 to 1 kg/cm2 dispatched filled with gas for transportation & storage to be topped at site As per IEC-600376

i) j) i. ii.

Parameters of SF6 gas Gas pressure settings at 20OC) Low pressure alarm at Lockout pressure for a) Opening b) Closing GENERAL DIMENSIONS Over all Dimensions Length Width Height Weight of complete breaker for foundation design Weight of each pole Weight of Mechanism + Housing + Base frame Weight of the heaviest part of the breaker Impact loading for foundation design Downwords Upwords

kg/cm2 kg/cm2 kg/cm2

6.5 +/- 0.3 6.0 6.0 +/- 0.3


+/- 0.3

6 a) i. ii. iii. b) c) d) e) f) i. ii. g) h) i) i. ii. iii. iv.

mm mm mm kg kg kg kg kg kg g mm mm mm mm db db

4000 800 5450 1450 335 560 560 2000 2000 0.5 1280 1700 1200 3790 < 140 < 140

Seismic level Minimum clearance in air Between live parts Between phases (Centre to Centre) Live parts to earth Live parts to ground level including plinth of 300 mm j) Noise level distance of i. 0M from the breaker ii. 50 M from the breaker

Guaranteed Technical Particulars


iii. iv. k) i. ii. iii. 100M from the breaker 150M from the breaker Packing Dimensions Pole Unit Assy (2 nos in one case) Pole Unit Assy (1 no in one case) Mechanism Housing Assy.(1 no in one case) db db mm mm mm mm < 140 < 140 3300 X 1260 X 810(H) 3300 X 800 X 810(H) 4040x900x1470(H) NA

iv. Marshalling box (Total 1 no) 7 a) b) c) d) e) f) g) h) i) i. ii. k) l) i. ii. m) n) o) p) q) r) s) i. ii. t) u) CONSTRUCTIONAL DETAILS Weight of absorbant per pole Whether arcing contacts are provided Type and material of arcing contacts Type and Material of main contacts Whether main contacts are silver plated / Silver plating thickness Contact pressure on main contacts Length of contact separation Length of contact travel Rate of contact travel Opening Closing Wheather the making & breaking contacts are hermatically sealed No. of spare auxiliary contacts provided for Owner's use Normally Open when breaker is open Normally Closed when breaker is open Rated voltage of auxiliary contacts Type of auxiliary contacts Continuous Current Carrying Capacity DC breaking current with 20 ms time constant Whether auxiliary contacts are sliver plated Finish of exposed ferrous parts Finish paint Offered to Domestic Customer's Offered to International Customer's Finish for Support Structure OR Columns

gm

300 Yes Tulip, Copper-Tungsten Finger, Copper-Chromium Yes / 25 microns

kg/mm mm mm m/s m/s

0.3 120 150 4.2 - 5.0 1.8 -2.2 Yes

V DC A A

Make of support porcelains

8/9/10 8/9/10 250 Rotary 20 7.5 A at 264 VDC Yes Hardware are HDG/SS As per customer requirement Shade 631 of IS 5 Shade RAL 7032 Hot Dip Galvanised ARGILONGERMANY/SARVANA(SIL)/LIAONING SHUANGLING/FUSHUN HIGH TECH ELECTRIC/ LILING HUAXIN/LILING PUKOU INSULATORS/PRATHAMESH CERAMICS/IEC/ MODERN

9 a) b) c) d) e) f) g) h) i) i. ii. j) k)

VALIDATED OPERATING CONDITIONS Maximum ambient air temperature Minimum ambient air temperature Maximum relative humidity Wind load / Wind velocity Seismic Level Altitude Maximum annual rain fall Average thunder storms days per year Maximum DC supply voltage variation Closing Opening Maximum AC supply voltage variation Degree of pollution as per IEC 815

O O

C C %

50 -20 100% 0.5 1000 3000 80 +/-20 -30, +20 +/-10 CL-III, Heavily polluted

kg/cm2/m/sec. 260/80

g m mm No. % % %

Guaranteed Technical Particulars


l) Wheather breaker is suitable for tripping at 50% of DC supply voltage m) Wheather breaker is suitable to work under hot humid climate, chemically polluted atomsphere, fumes, fungus and salt spray conductive rust. VALIDATED MULTIPLE USES: EHV/HV SUBSTATIONS (IN INDIA AS WELL AS IN OTHER COUNTRIES) INDUSTRIAL PROJECTS STEEL PLANT LINE APPLICATIONS GENERATOR APPLICATIONS HILLY AREAS/HIGHER ALTITUDE IN EXCESS OF 1000M NOTE: 1) THE BREAKERS ARE VALIDATED FOR OPERATING CONDITIONS AND MULTIPLE USES AS ABOVE . FOR OPERATING CONDITIONS DIFFERENT THAN ABOVE PLEASE REFER TO DESIGN DEPARTMENT Yes Yes