Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz
1. Introduction
Physical Effects of Fault Currents
1. 2. 3. 4. 5. High temperatures may be reached by elements conducting excessive currents. This may cause deterioration, melting and burning of the electrical insulation, and melting of conductors. Large magnetic forces act on conductors with large currents. As a result, distortion and breakage of the mechanical structure of electrical equipment may take place. High conductor temperatures and arcs due to damaged insulation may result in fires that cause destruction of equipment, buildings and surroundings. During fault conditions, elevated levels of electrical potential may exist on surfaces that are at the earth potential during normal operation. The voltage in parts of the power system may be reduced. Stability of the power system may be at risk.
Fault
Large (magnetic) forces on conductors Damaged insulation Arcs Damage/destruction Damage/destruction of of equipment/buildings equipment/buildings /surroundings /surroundings
Excessive current
Voltage supplied to Voltage supplied to users reduced. users reduced. Power system Power system stability at risk. stability at risk.
1.
3.
2.
2
1.
To minimise the damage and repair cost resulting from power system faults.
Achieved by using circuit breakers and fuses to stop (break) fault currents.
2.
To reduce safety hazards associated with fault conditions. Achieved by using circuit breakers and other switchgear to isolate the faulty circuits from the rest of the power system.
3.
3
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz
1.
Fuses. Fuses break the fault current once and require manual replacement. The time of fuse operation cannot be controlled. Circuit breakers. Circuit breakers can break fault currents repeatedly and are also used as switching and isolating devices. The instant of operation is determined by an internal tripping system, or an external tripping device: a protection relay. Protection relays. Relays monitor currents and voltages at a given point of the power system. If they detect a faulty condition or receive an external command, they trip the circuit breakers to which they are connected. The faulty conditions that relays are designed to detect include fault currents, overload currents, under/overvoltage, phase sequence, thermal overload, etc. Voltage transformers and current transformers. These measurement transformers are connected to protection relays and produce isolated signals representing the actual currents and voltages in the power system. Reserve power sources (batteries and UPS units). Circuit breaker tripping circuits and electronic relays require a power source that is independent from the power system being protected.
4
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz
2.
3.
4.
5.
Circuit breakers are mechanical switching devices whose main purpose is to break fault currents. In addition to the protective function, the circuit breakers are also applied for normal operation switching of power system components. For maintenance or repair of electrical equipment and transmission lines, the circuit breakers, together with other switching devices will ensure personnel safety.
Circuit breaker
Signals representing the state of the power system (currents, voltages, states of other relays)
Processor
Protective relay
Arc chute
Contact in air
i i i i i
. . . . .
Arc
6
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz
SF6 gas
Sulphur-hexafluoride
SF6
Puffer volume
Fixed contact
SF6
SF6
SF6 SF6
SF6 SF6
C/B operates
Current transformer
Rated continuous current: 3000 A Rated voltage: 245 kV Interrupting capability: 40 kA Spring-hydraulic mechanism
Rated continuous current: 4000 A Rated voltage: 800kV Interrupting capability: 63 kA Three serially connected, 2-cycle puffer interrupters Spring-hydraulic mechanism
145 kV
Vacuum
Vacuum bottle
Vacuum
Fixed contact
Moving contact
Bellows
To operating mechanism
were typical insulating and extinguishing media in the older designs. Nowadays, they have been almost entirely replaced by SF6 gas. 10
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz
2.3 Moulded-case Circuit Breakers (MCCB) and Miniature Circuit Breakers (MCB)
For low-voltage distribution systems (Max. ratings about 1 kV, 1.5 kA). Air at atmospheric pressure is the interrupting medium. Compact and economic design. Hand-operated (remote control mechanisms possible on bigger units) Protection mechanisms are an integral part of the c/b. The most common ones are: -magnetic trip. -thermal trip. Magnetic trip: The fault current passing through a coil of one or two turns actuates the trip mechanism. Thermal trip: In small circuit breakers, a bimetallic strip is deflected by the heat generated by the current flowing through it directly, or through a heating element wrapped around it. After a delay, which is inversely proportional to current, the device trips the circuit breaker. Electronic protection: In bigger units, the trip functions are provided by an electronic system.
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz
Typical tripping characteristic of a moulded-case circuit breaker (MCCB) Both parts of the characteristic (thermal and electromagnetic) are adjustable in a certain range.
12
Power Engineering 2 Part 1: Power System Protection by Dr Peter Graszkiewicz