Technical Data

GB

a-eberle

Issue 04/2006

Measuring and monitoring unit


for insulation resistance
MU-ISO-04
1

Input

9 Output 10
+

0,7 1
0,3

1,5
2,5

0,2

MU-ISO-04

5
0,1

Auxiliary

11

Application
The unit is measuring the insulation resistance
of not grounded medium-voltage power
stations.
A special application is the monitoring of
insulation resistance of induction furnaces or
arc furnaces.
Special advantages:
 Separate installation of indicating and
recording instruments is possible, due to the
galvanic isolated DC current separated from
the high voltage section (measuring signal).
 Low-resistance DC power source,
therefore parasitic external voltages are
largely eliminated.
 High resistance AC bleeder due to series
reactor.

Function
The measuring unit consists of the following
components:
 Series reactor
 Measuring transducer with galvanic
isolated DC power source and a limit
detector with relay contact signal.

18 19 20

12

100

18

19

20

The DC power source (U) produces via series


reactor (Dr) low-resistance phase conductor,
back to the bleeder RISO a measuring current
on ground, which is reverse proportional to the
insulation resistance RISO.
Dr

RISO

UH

Block diagram

Technical Data
Series reactor EI 130a
DC resistance
AC resistance (50Hz)
Operating voltage
Operating frequency
range

440 , +/-10
45 k, +/- 5 k
3000 V
451000 Hz

A. Eberle GmbH & Co. KG

Technical Data
Operating DC current
Type
Protection

Connection
Test voltage

MU-ISO-04
25 mA
EI 130 open
IP 00, impregnated
with protecting
varnish
flat-pin plug
6.3 x 0.8
Winding
Ground: 7kV

Limits of error (RISON 5k) 1% v. EW


Temperature effect
25 / 10K
Influence of
0.2% / 10% UH
auxiliary supply
Limit detector
Adjustment range
... 0
Accuracy of adjustment 2.5% RISON
Adjustment element SE potentiometer,
front panel
Operating delay
1s
Switching contact
250V, 2A
Mechanical life
50 x 106
operating cycles
Relay function
maximum detecor,
zero signal current
principle changeover contact

Measuring transducer with


limit detector
Input:
Measured quantity
Measuring range
Measuring voltage
Resistance
(via series reactor)
Operational voltage
Output:
Output quantity Y
Measuring range

Load
Response time
Response

Insulation
resistance
... 0
12 V=
250

Auxiliary power
AC

3000 V

DC current
(galvanic isolation)
2.....20 mA=
RISO ... 0
< 2 mA signals
malfunction in the
metering unit
20
0.1 s

Ambience
Climate class
Temperature range

3z / -10 / +60
-10 ... +60C

Security
Class of protection
Overvoltage category
Pollution degree
Degree of protection
Inside
Terminal compartment

 K

9 = 9.    +
 K + 2)3/

Test voltages

Frequency range
Power input

115 V or 230 V,
5%
45 ... 65 Hz
4 VA

II, EN 61010-1
2
2
IP43
IP00

Input

Output

Relay

Auxiliary

7 kV

2.3 kV

2.3 kV

7 kV

2.3 kV

2.3 kV

Relay

2.3 kV

2.3 kV

2.3 kV

Auxiliary

2.3 kV

2.3 kV

2.3 kV

Input
Output

A. Eberle GmbH & Co. KG

Technical Data
L1

MU-ISO-04

L2
1

DR

RE

Display

RISO

10
P10
P8
18

SE

19

XW

20

11

UH

12

Terminal connections
Input
Output 20 mA
Test socket 100 mV
Auxiliary 115 / 230 V~
Relay contact, Switch-over contact

Terminal
Terminal
Socket
Terminal
Terminal

1
-9
+10
+P8 -P10
~11 ~12
18
19

Flat-pin plug 6.3 x 0.8


Solid conductor 2.5
2mm

20

Solid conductor 2.5


Solid conductor 2.5

Connection diagram
110

104
5

Input

9 Output 10
+

0,7 1
0,3

1,5
2,5

0,2

MU-ISO-04

5
0,1
18 19 20

12

100
0

19

20

60

47

7.6

18

5.1

Auxiliary

11

68

35
37.5
5.1

Dimension diagram transducer


3

A. Eberle GmbH & Co. KG

Technical Data

MU-ISO-04

Operating instructions:

Operating test
Furnace operating system is switched off
Auxiliary supply is connected.

 Operation of the transducer MU-ISO-04


without series reactor (Dr) is not permissible.
 Always connect the high-voltage supply
with terminal 1 of the series reactor.
 The output circuit terminal 9- / 10+ is
galvanically isolated from the high voltage
circuit. In the case of malfunction extra-low
voltages occur.
 The metering unit including the installation
is to be tested for function prior to the
commissioning of the system.
 Attention:
When testing an entire induction furnace
system disconnet the insulation resistance metre (series reactor and transducer) first. Possibly a test can cause an
occurrence of DC voltage potential (e,g.
partial opening of the DC link)
 Trouble shooting:
In the case of malfunction at first only
the transducer is to be exchanged. If this
action does not lead to the repair, the series reactor needs to be exchanged too.
If the second action does not eliminate
the malfunction, the system needs to be
checked for the cause of the defect.

Control of the indication of


insulation resistance RISO =

 Disconnect the terminal lead of terminal 1


of the series reactor.
Check:
 Indicator in position and/or output current
= 2mA
 Limit value relay is on contact between
terminal 19 20 is closed
Condition:
 Set point adjuster > 0

Control of the indication of


insulation resistance RISO = 0

 connect terminal lead to terminal 1 of the


series reactor
 Simulate a short circuit of the furnace.
Check:
 Indicator in position 0 and/or output
current = 20mA
 Limit value relay is off contact between
19 18 is closed.

Control of an
insulation resistance RISO

Possible reasons for malfunction:


DC voltage potential caused by converter
system. Earth shunt in the furnace circuit.

 Connect the reference resistance (e.g.


0,7k) between terminal 1 of the series
reactor and terminal 3 of the transducer.
Check:
 Conformance of the indicator and/or output
current with the calibration curve.
 Turn off the limit value relay by turning the
set point adjuster to (......0).

Defective devices are solely


to be repaired by
A. Eberle GmbH & Co. KG

A. Eberle GmbH & Co. KG

Technical Data

MU-ISO-04

Note:
The small tolerance of the copper resistance
of the reactor causes a maximum measuring
error of 10 . If necessary, a local calibration
is possible.

Adjustment of the limit detector


The adjustment of the switching point is carried
out via the calibration table or the reference resistance. The set point adjuster is set to and
returned slowly until the limit value relay is off
(contact 18 19 are closed). Its at 0.7k with
the quoted reference resistance.

Adjustment of an insulation
resistance RISO

 Connect the reference resistance (e.g.


0.7k) between terminal 1 of the series
reactor and terminal 3 of the transducer.
 By means of a trimming resistance RE (accessible by the opening on the front plate
of the transducer between clamp 1 and 3)
the scale interval indicator is to be aligned
with the measuring shunt.

I m/mA

Calibration curve MU-ISO-04


20.0
18.0

17.4

16.0
14.0
12.0

10.3

10.0
8.0

6.4

6.0

3.9

4.0

3.0

2.0
0.0

0,1

0,7

1,5

10

2.5

20

2.1
100

2.0

Riso/k

A. Eberle GmbH & Co. KG

Technical Data

MU-ISO-04

Analogue indicator (96 x 96 mm) with coloured scale

Series reactor EI 130a


A. Eberle GmbH & Co. KG

Technical Data

MU-ISO-04

Notes: ..........................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
.....................................................................................................................
7

A. Eberle GmbH & Co. KG

Technical Data

MU-ISO-04

A. Eberle GmbH & Co. KG


Aalener Str. 30/32
D-90441 Nrnberg
Tel.: +49 (0) 911 / 62 81 08-0
Fax: +49 (0)911 / 62 81 08 96
www.a-eberle.de
info@a-eberle.de
A. Eberle GmbH & Co. KG

T612D201A00
8