Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
90
or 270
yoarg
_
U
1
_
I
1
o360
y 4
and, for a backward fault,
yoarg
_
U
1
_
I
1
o180
y 5
where y is called the blocking angle. Obviously, if y is 01,
the criteria will have highest sensitivity or largest operating
region, but may fail to identify the fault direction when the
phase difference between
_
U
1
and
_
I
1
is near 01 or 1801. To
prevent the relay from maloperation, the blocking angle is
set as 0
oyo30
_
I
1
Z
c
6
where Z
c
is a compensation impedance in phase with Z
M1
.
For a forward fault with small Z
M1
, the compensated
voltage is
_
U
0
1
_
I
1
Z
M1
Z
c
7
If Z
c
is sufciently large,
_
U
0
1
can hold a phase angle which is
approximately 2701 leading
_
I
1
, i.e. it ensures correct phase
Operating region
for
backward faults
Operating region
for
forward faults
2
2
+ j
1
I
.
Fig. 3 Operating characteristic of the directional criteria
1
F
1 M
Z
1 L
xZ
1 N
Z
1
Z
1
) 1 (
L
Z x
1 M
E
1 N
E
1 M
Z
1
F
1 N
Z
1
Z
1
) 1 (
L
Z x
1 M
E
1 N
E
F
U
.
F
U
.
1 L
xZ
1 M
Z
1 N
Z
1
U
.
.
1
I
.
1
F
1
) 1 (
L
Z x
1 L
xZ
1
Z
F
U
2
F
F
U
.
1
U
.
1
I
.
1 M
Z
1 L
Z
1 N
Z
1
Z
a
b
c
d
Fig. 2 Decomposition of positive sequence network
712 IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 6, November 2006
comparison. For a backward fault, the compensated
voltage is
_
U
0
1
_
I
1
Z
L1
Z
N1
Z
c
8
To ensure correct directional detection in this case, Z
c
must
satisfy
Z
c
oZ
L1
Z
N1
9
Hence, to ensure appropriate relay sensitivity for both
forward and backward faults, Z
c
is taken as 0.5 Z
L1
. So (6)
becomes
_
U
0
1
_
U
1
0:5
_
I
1
Z
L1
10
The phase relationship between
_
U
1
,
_
U
0
1
and
_
I
1
is shown as
Fig. 4a. Figure 4b shows how the method operates correctly
when
_
U
1
has a small magnitude and the wrong phase
relationship with
_
I
1
for a forward fault.
To cope with problems (ii) and (iii), we use magnitude
comparison instead of phase comparison. The compensated
voltage
_
U
00
1
is dened as
_
U
00
1
_
U
1
_
I
1
Z
0
c
11
where Z
0
c
is a compensation impedance in phase with Z
M1
.
For a forward fault, the compensated voltage is
_
U
00
1
_
I
1
Z
M1
Z
0
c
12
If Z
0
c
is sufciently large, the magnitude relationship
between
_
U
00
1
and
_
U
1
is
j
_
U
00
1
j4j
_
U
1
j 13
For a backward fault, the compensated voltage is
_
U
00
1
_
I
1
Z
L1
Z
N1
Z
0
c
14
Comparing (14) with (2), if Z
0
c
is less than 2Z
L1
Z
N1
,
then
j
_
U
00
1
joj
_
U
1
j 15
To meet the requirements of both (13) and (15), Z
0
c
is taken
as Z
L1
. Hence (11) becomes
_
U
00
1
_
U
1
_
I
1
Z
L1
16
The magnitude relationship between
_
U
1
and
_
U
00
1
is shown as
Fig. 5a. Figure 5b shows that the method works well when
_
I
1
has small magnitude and the wrong phase relationship
with
_
U
1
for a forward fault.
3.3 Practical operating logic and criteria
Combining the basic criteria with the techniques to solve the
problems created by inadequate voltage and/or current, the
practical operating logic and the corresponding directional
criteria for the proposed relay are shown in Table 1.
Here U
min1
, I
min1
are the minimum thresholds (start-up
values) of
_
U
1
and
_
I
1
, and U
min 2
, I
min 2
are the second
thresholds of
_
U
1
and
_
I
1
, at which
_
U
1
and
_
I
1
are just able to
perform correct phase comparison. Basically, the settings
for U
min 2
and I
min 2
are based on the resolutions of the CT,
the PT and the A/D used in the relay scheme. The settings
for the minimum thresholds are based on the random
outputs from the extracting process of the fault components
(discussed in Section 4) seen during frequency variations or
power-system normal operating conditions. According to
our test results and the data analysis for the trial
maloperation, the practical settings for these thresholds
are selected as U
min 1
0:5 $ 1:5 V, I
min 1
0:1 $ 0:2I
n
,
U
min 2
2 $ 3U
min1
and I
min2
3 $ 5I
min 1
, where I
n
is
the rated secondary current of the CT.
4 Extraction of fault components
The fault component is dened as the fault-generated
voltage or current. This is the difference between the voltage
or current during the fault and the prefault voltage or
current, respectively. The signal-processing procedure for
the proposed algorithm is as follows.
1
I
1
U
1
U
1
U
1
U
.
'
'
'
.
1
I
.
.
.
.
.
.
.
1
5 . 0
+ j
forward fault forward faults
backward faults
I Z
L
1
U
1
U
a b
Fig. 4 The phasor diagrams for
_
U
1
and
_
U
0
1
a Phase relationships
b Method operating correctly
1
+1
I
1
U
.
.
.
.
.
.
.
.
.
1
U
1
U
backward faults
forward faults
forward fault
1
U
1
U
1
U
1
I
1
I Z
L
a b
Fig. 5 The phasor diagrams for
_
U
1
and
_
U
00
1
a Magnitude relationship
b Method operating correctly
Table 1: Practical operating logic and corresponding criteria
Conditions
j
_
U
1
j ! U
min2
and j
_
I
1
j ! I
min2
U
min1
j
_
U
1
joU
min2
and j
_
I
1
j ! I
min 2
I
min1
j
_
I
1
jI
min2
and j
_
U
1
j !
U
min1
Directional
criteria
180
y arg
_
U
1
_
I
1
360
y arg
_
U
0
1
_
I
1
360
y !forward fault
j
_
U
00
1
j4j
_
U
1
j !forward fault
y arg
_
U
1
_
I1
180
y ! backward fault
y arg
_
U
0
1
_
I
1
180
y !backward fault
j
_
U
00
1
joj
_
U
1
j !backward fault
Notes 0
oyo30
oyo30
_
U
0
1
_
U
1
0:5
_
I
1
Z
L1
_
U
00
1
_
U
1
_
I
1
Z
L1
IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 6, November 2006 713
Step 1:
Equation (17) is used to extract the fault component
samples for each phase:
x
fk
x
k
x
k2N
x
k2N
x
k4N
17
where x
k
is the present voltage or current sample; N is the
number of samples in one power-frequency cycle; x
fk
is the
extracted fault component sample; and k is the sample
number, 0,1,2yetc.
After fault inception, this algorithm is able to provide
two cycles of fault component data, which includes the DC
offset, harmonics and the steady-state fault component. In
addition, it can reduce the unbalanced output efciently
during a frequency disturbance or power swing; this is
particularly benecial if a fault instigates a power swing or
occurs during one.
Step 2:
The full-cycle DFT algorithm is used to extract the steady-
state fault components for each phase, this can be described
mathematically as:
_
X
f
2
p
N
N1
k0
x
fk
cos
2p
N
k
j
N1
k0
x
fk
sin
2p
N
k
18
where,
_
X
f
is the estimated fundamental-frequency fault
components of voltage or current during the present data
window.
Step 3:
Equation (19) is used to calculate the required positive
sequence fault components,
_
U
1
and
_
I
1
_
X
1
1
3
_
X
fa
e
j120
_
X
fb
e
j240
_
X
fc
19
where,
_
X
fa
;
_
X
fb
and
_
X
fc
are the fundamental frequency
fault components of the phase a, b and c voltage or current
obtained from step 2.
5 Simulation results and analysis
To evaluate the performance of the proposed algorithm,
many simulations were carried out using the EMTDC
package. The simulated model is a typical Chinese 500kV
transmission line, as shown in Fig. 6, and the relay was
applied at bus M.
The power frequency of the model system is 50Hz, the
phase difference between source M and N is 201 and the
ratios of the PTs and CTs are 500kV/100V and 1250A/5A
respectively. The secondary data from the PTs and CTs are
used to perform the simulation. An analogue antialiasing
lter (low-pass Butterworth lter) with a cut-off frequency
of 300Hz is applied to each signal channel used in the
model. The sampling frequency is 800Hz and a full-cycle
DFT is used to estimate the fundamental-frequency
components. In all the simulation studies, fault inception
was set at t 0.2s. The required parameters used in the
directional criteria are: y201, U
min1
0.5V, I
min1
0.2A,
U
min2
1.5V, I
min 2
1A.
5.1 Responses for forward faults
Figure 7 shows a typical operating response for a forward
AG fault at F
1
with 15O resistance in the fault path. The
primary voltage and current waveforms of the faulted phase
are shown in Fig. 7a. The fault-component voltage and
current extracted using (17) are shown in Fig. 7b. Figure 7c
and d show the magnitudes of
_
U
1
and
_
I
1
and their phase
difference based on a full-cycle DFT algorithm for two
cycles after fault inception. As expected, one cycle is
required for the estimated magnitudes and phases to reach a
stable value, but the phase difference begins to satisfy the
operating condition (4) half a cycle after fault inception.
Simulation results for various forward faults show that the
relay detects all types of forward fault successfully within
811ms.
5.2 Responses for backward faults
Figure 8 shows a typical operating response for a backward
AG fault at F
3
with 15O fault resistance. The phase
difference between
_
U
1
and
_
I
1
begins to satisfy operation
condition (5) half a cycle after fault inception. Other
simulation results show that the backward looking relay
detects all types of backward fault successfully within
812ms.
5.3 Responses for high-resistance-faults
Figure 9 shows the operating response for a forward
BG fault at F
1
with 300O fault resistance. When Fig. 9a is
compared with Fig. 7c, the magnitudes of both
_
U
1
and
_
I
1
can be seen to have decreased signicantly. Since j
_
I
1
j is less
than 1A, the directional criterion based on magnitude
comparison is applied to the decision process. According to
Table 1, the relay provides a correct and fast forward
response for this high-resistance fault (see Fig. 9b).
The response to a backward BG fault at F
3
with 300O
fault resistance is shown in Fig. 10. The relay also provides
a correct and fast reverse response.
5.4 Responses for different system
conditions
This simulation study was used to investigate the inuence
of source impedance on the relay. Figure 11 shows the
response to a remote forward AG fault at F
2
with Z
M1
of
10O (i.e. source M is relatively strong). In this case, the
magnitude of
_
U
1
is smaller than 1.5V half a cycle after fault
inception, so the phase difference between
_
U
0
1
and
_
I
1
is used
to make the directional decision. As shown in Fig. 11b,
the phase difference satises the forward-fault criterion
correctly [200
oarg
_
U
0
1
=
_
I
1
o340
_
I
B
D
_
I
C
_
I
A
D
_
I
B
_
I
C
21
For a case of phase earth fault, the comparison result will be
D
_
I
A
_
I
B
D
_
I
C
_
I
A
; D
_
I
B
_
I
C
0 22
The three increments shown in (21) can be extracted by (18).
This algorithm has been proved very effective [6].
6.3 Negative and zero-sequence
components
Negative- and zero-sequence components have been used in
traditional directional relays for many years. Each of them
can identify fault directions for certain types of faults. To
enhance the reliability of the directional-protection scheme
on asymmetrical phasephase or earth faults, both negative-
and zero sequence component-based schemes could be used
as a back up for the PSFC-based scheme.
7 Conclusions
The design and operating performance of a directional
algorithm based on the PSFC have been described in
this paper. Combining the basic principle of this algorithm
with the operating experience on several real networks,
the paper provides an integrated solution for detecting the
direction to a fault. Theoretical analysis and simulation
results conrm that the proposed relay algorithm has
signicant advantages over more traditional directional-
relaying techniques.
First, it is suitable for all types of fault, including high-
resistance faults, and is not affected by the load or the low-
voltage dead zone seen with close-up faults. Secondly, it
has an operating time of typically half a cycle though the
full-cycle DFT is used to estimate fundamental frequency
components. Thirdly, it has adequate sensitivity and
reasonable immunity to the effect of power swings.
Moreover, it can detect all types of faults reliably on long
or short lines and is not affected by the strength of the
sources.
Consequently, the proposed algorithm is inherently
suitable for use in a directional-comparison pilot-protection
scheme for EHV transmission lines.
8 Acknowledgments
This research was funded by the Scientist Research
Foundation of Shandong Province, China. The authors
thank Shandong University and Queens University Belfast
for their support.
Fig. 13 Response for a forward AG fault at F
1
with power swing
(Df 1Hz)
a Primary current
b Secondary-fault component currents
c Magnitudes of PSFC
d Phase difference
Fig. 14 Phase-difference responses for non-single phase-to-earth
faults at F
1
and F
2
a Forward AB fault
b Forward ABC fault
c Backward ABG fault
IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 6, November 2006 717
9 References
1 He, J.L, Zhang, Y.H., and Yang, N.C.: New type power line carrier
relaying system with directional comparison for EHV transmission
lines, IEEE Trans. Power Appar. Syst., 1984, 103, (2), pp. 429436
2 Xia, Y.Q., He, J.L., and Li, K.K.: A reliable directional relay based
on compensated voltage comparison for EHV transmission lines,
IEEE Trans. Power Deliv., 1992, 7, (4), pp. 19551962
3 Johns, A.T.: New ultra-high-speed directional comparison technique
for the protection of EHV transmission lines, IEE Proc. C, Gener.
Power Trasns. Distrib., 1980, 127, pp. 228239
4 Johns, A.T., Barker, A., Martin, M.A., Walker, E.P., and Crossley,
P.A.: A new approach to EHV directional comparison protection
using a digital signal processor, IEEE Trans. Power Deliv., 1986, 1,
(2), pp. 2434
5 Lyonette, D.R.M., Bo, Z.Q., Weller, G., and Jiang, F.: A new
directional relay for the protection of EHV transmission lines based
on the detection of transient voltage signals . IEEE PES 2000 Winter
Meeting, pp. 18271831
6 Ge, Y.Z.: New typed of protective relaying and fault Location: their
theory and techniques (Xian Jiaotong University Press, 1996),
pp. 7981 (in Chinese)
7 Crossley, P.A., Elson, S.F., Rose, S.J., and Williams, A.: The design
of a superimposed component directional comparison protection. Int.
Conf. Developments in Power System Protection, IEE Conf. Publ.
302, 1989, pp. 151155
8 Rose, S.J., Crossley, P.A., Walker, E.P., Johns, A.T., Martin, M.A.,
and Peck, D.: Disturbance monitoring/fault test evaluation of a
directional comparison protection on the UK transmission system,
IEEE Trans. Power Deliv., 1988, 3, (4), pp. 14101418
9 Su, B., Dong, X.Z., Sun, Y.Z., Bo, Z.Q., and He J., L.: New principle
of high-speed directional relay. IEEE PES 2002 Summer Meeting,
pp. 387392
10 Suonan, J.L., Xu, Q.Q., Song, G.B., and Wu, Y.: A reliable
directional relay based on positive sequence compensated voltage and
current components. Int. Conf. Developments in Power System
Protection, IEE Conf. Pub. 500, 2004, pp. 104107
11 XuJi Electric Co. Ltd.: WXH-801/802 digital microprocessor-based
line protection relays, 2003 (in Chinese)
12 NARI Relay Co. Ltd.: RCS-901A/B protection relays for extra high
voltage, 2002 (in Chinese)
13 Xu, Z.Y: New type distance protection of power lines
(China Electrical Power Press, 2002), pp. 353359, 499502 (in
Chinese)
718 IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 6, November 2006