Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Release
X 2 3 4
New Digital Output Module Available The S7--300 Digital Output Module SM 322; DO 8 X 48--125 VDC/1.5A has been added to the S7--300 family. The order number for this module is 6ES7 322-1CF00-0AA0. This product information includes details about the characteristics and technical specifications of the SM 322; DO 8 X 48--125 VDC/1.5A Module. Refer to the S7-300 Installation and Hardware Manual for more information about the S7-300 product family.
Additional Assistance For assistance in answering technical questions, for training on this product, or for ordering, contact your Siemens distributor or sales office.
Characteristics The SM 322; DO 8 48--125 VDC/1.5A features the following characteristics: ! 8 outputs, reverse polarity protection and isolated in groups of 4 ! 1.5 A output current ! Rated load voltage 48 to 125 VDC ! Suitable for solenoid valves, DC contactors and indicator lights ! Group error display Using the module with high-speed counters Please take note of the following information on the use of the module in connection with high-speed counters:
Note When connecting the power supply via a mechanical contact, the outputs of the SM 322; DO 8 48-125 VDC/1.5 A carry a 1 signal for approximately 50 !s for reasons associated with the circuitry.
Product Information S7-300 Digital Output Module SM 322 DO 8 x 48-125 VDC/1.5 A A5E00262196-01
+5V SF
1 L+
11 13
2 L+
Figure 1
Product Information S7-300 Digital Output Module SM 322 DO 32 x 48-125 VDC/1.5 A A5E00262196-01
! !
At 1 signal
min. L + (-1.2 V)
Output current At 1 signal Rated value Permitted range 1.5 A 10 mA to 1.5 A max. 3 A for 10 ms max. 0.5 mA
! !
! !
Unshielded Shielded
Voltages, Currents, Potentials Rated load voltage L+ 48 VDC to 125 VDC Yes, by means of fuse1)
! !
At 0 to 1 At 1 to 0
!
max. 6 A max. 4 A max. 3 A
Isolation
! ! !
! !
Yes Yes 4
Limit (internal) of the in ductive circuit interruption voltage up Short-circuit protection of the output
Yes, electronic3) typ. 4.4 A Fuse 6.3 A/250 V, quick blow, 5 x 20 mm SP0001.1012 194-1630-0
Threshold on
Replacement fuses
! !
From the backplane bus From the load voltage L+ (no load)
! ! !
1)
Schurter Wickmann
Status, Interrupts, Diagnostics Status display Interrupts Diagnostic functions Green LED per channel None Red LED (SF)2)
3) 2)
The fuses on this module are merely supplementary fuses. External overcurrent protection (suitable for branch circuits conforming to the local regulations for electrical engineering) is required in the supply cables of the load circuit. Potential errors are: - No load voltage - Fuse defective - Output overloaded If an overload condition is detected, the output is inhibited for approximately 2.4 s.
Product Information S7-300 Digital Output Module SM 322 DO 8 x 48-125 VDC/1.5 A A5E00262196-01