Sei sulla pagina 1di 17

NoDispVolPartSectionPageRevised SpecificationReferenceSMC CommentConclusionME 1CC-14aUnder schedule guarantee table Note ; 1.

Performance corrections to the following parameters shall be applied to corre ct the measured performance to the referenced condition. - Generator(s) power factor(s) - Ambient conditions at cooling tower - Auxiliary loads - Measured power different than specified (Part Load) - Ambient temperature - Ambient pressure - Ambient humidity - Fuel analysis - Power grid frequency - Inlet pressure drop - Unit degradation - Condensate preheater inlet temperature 2. The correction for ambient conditions at cooling tower inlet shall not be app lied in case of no difference between cooling tower inlet air temperature and th e CT inlet air temperature. 3. The correction for auxiliary loads, all equipments supplied in the scope of w ork that are permanently required during the normal operation shall be included in the performance test. 4. The correction factor for condensate preheater inlet temperature shall be app lied in case of sulfur content in fuel gas higher than the fuel gas specificatio n as specified in table 1B.3.9-1.Deviation No. G1 ME11D.3.11D-3Design of pipe hanger systems for all piping 65 mm (2-1/2 inches) i n diameter and larger and for all 50 mm (2 inch) and smaller pipe having operati ng temperatures of 150? C (300? F) or higher shall be according to the results of the pipe stress analysis. For cold lines, which are not subject to stress ana lysis hanger systems will be designed for 80 mm and larger compliant to ANSI sta ndards.Deviation No. S-015ME 21 1B.3.9.1 1B-4 The combined cycle unit shall be designed to operate safety and continuously wit hout load limitation per based on gas composition according to table 1B.3.9-1 be low. The combustion turbines shall be designed to operate continuously without l oad limitation based on fuel gas Wobbe index range of +/-5%. In case of fuel gas properties are beyond the range of +/-5% Wobbe index properties, the Contractor shall perform the retuning work on the combustion turbines to a new range in or der to meet the emission requirements without hardware modification, additional permanent equipment nor instruments.Deviation No. G7, S-024, S-025 ME 21 1D.2.31D-4 All piping except interconnection and internal piping of GTG package, HRSG, bypa ss dump line and STG package shall be designed, selected, and fabricated in acco rdance with the following criteria and the Process Piping Materials Guide attach ed at the end of this section.Deviation No. S-038 ME211D.2.3.31D-63. Sample piping outside sample panel shall be 15 mm nominal inn er diameter stainless steel.Deviation No. S-040ME211D.2.3.41D-6c. HRSG feedwater - 32 mm Socket Weld. Butt Weld.

Deviation No. S-041 ME211D.2.3.51D-7Drain connections shall be provided at all control valve station s between the inlet isolation valve and the control valve, except for steam bypa ss valves, drain valves may not be provided. Deviation No. M-011ME211D.2.3.8 1D-9Unless otherwise specified, steel fittings 65 mm and larger shall be butt we lding type and steel fittings 50 mm and smaller shall be socket welding type or butt weld with X-ray test.Deviation No. S-044ME211D.2.3.81D-9Specially designed adapters shall be Weldolets or Sweepolets. integrally reinforced branch fittings .Deviation No. M-013ME211D.2.3.9 1D-11All nuts and bolts shall be metric.Deviation No. S-045ME211D.2.4.31D-13Clas s 150, 300, and 400 and 600 valves 65 mm and larger shall be constructed as fol lows: * Bonnet joints shall be of the bolted flanged type having flat face flange faci ngs for Class 150 valves and male and female facings for Class 300 and 400, 400 and 600 valves. * Body ends will be butt weld type unless otherwise required. Class 600, 900, 1500, and 2500 valves 65 mm and larger shall be constructed as f ollows: * Bonnet joints shall be of the pressure seal or breechlock type. * Valves shall have grease-lubricated antifriction bearing yoke sleeves. * Body ends shall be butt weld type unless otherwise required.Deviation No. M-01 4ME211D.2.8.21D-211D.2.8.2 Design Codes and Standards The code and standard shall be according to the item 1B.3.11, Volume 2. Codes an d standards unique to chemical engineering design to be used in design and const ruction are summarized below: DIN standard shall also be acceptable for the QC Chemical Dosing System.Deviatio n No. S-048ME 2 1 1D.2.8.4 1D-24 The cycle condition chemicals shall consist of Phosphate feed to HRSG drum, Oxyg en scavenger (non-hydrazine) feed to feedwater and Ammonia feed to maintain the desired condensate pH.Deviation No. S-049ME211D.2.8.41D-24c) Closed cycle cooli ng system chemical conditioning Pot feeder shall be provided to feed Sodium Nitrite Carbohydrazide as a conditio ning chemical to the closed cycle cooling system to minimize corrosion and to co ntrol pH of the system.Deviation No. S-050ME211D.2.9.21D-25All piping and equipm ent having an actual operating temperature greater than 54 o C unless directed o therwise by EGAT 60oC where after insulation installation, the outer surface tem perature shall not exceed 60oC based on the design conditions of 0.5 m/s wind ve locity and 35oC ambient temperature.Deviation No. S-051ME211D.2.9.21D-25All pipi ng accessories such as valves, strainers, and expansion joints in piping that th e areas or equipment where personnel can be access to be insulated.Deviation No. M-019ME 21 Table 1D.2-31D-49: HP /IP Bypass Conditioning Valve Outlet A335, P5 : IP Bypass Conditioning Valve Outlet A335, P22Deviation No. S-057ME 21 Table 1D.2-31D-49 : LP Bypass Conditioning Valve to Condenser A335, P5 P22Deviation No. S-058ME21T able 1D.2-41D-54, 1D-55Building/Area Redundancy Required Electrical Equipment rooms 2 x 100%

Switchgear equipment areas Power Control Centers N+1 Power Control Centers with I&C cubicle installation 2 x 100% Critical equipment 2x100% N+1 Inverter and charging equipment 2 x 100% N+1 ,Excitation board, and electronic equipment Battery rooms 2 x 100% N+1 Deviation No. S-047 and S-062ME 222B.42B-3The Contractor shall propose as an option the inlet cooling system for increasing the output of combustion turbine. The space, connection points and necessary accessories sh all be designed and provided to install the inlet cooling system.Deviation No. S-150 ME222B.52B-3Other vent valves for startup shall also be provided at the steam dr um, and other necessary parts as designed by the Contractor. All startup vent an d drain valves shall be motorized valves All vent and drain valves for automatic start up of the plant shall be motorized valves. Deviation No. S-151ME222B.62B-4The ST shall be designed suitable for sliding pre ssure operation between 100% and approx. 60% load (fixed pressure operation belo w 60% load) and frequent startup requirements with minimum startup and shutdown time and capable of achieving the specified service life of the unit 200,000 EOH or 5,000 starts.Deviation No. S-152 ME222B.62B-4Any system that has a potential for allowing water to enter the ST s hall be designed in accordance with the latest edition of ANSIIASME TDP-I 2006 " Recommended Practices for the Prevention of Water Damage to Steam Turbines Used for Electric Power Generation." The system shall protect the ST against water da mage by removing moisture produced by condensation of steam in the main steam pi ping.Deviation No. S-153 ME222B.6.12B-4Condensed steam collected in the drain pots shall be drained to th e steam blowdown tank condenser.Deviation No. S-154ME222B.6.12B-5The main seal s team from steam turbine system shall supply steam seal to the ST seals and drain system for normal operation.Deviation No. S-155ME222B.6.3.12B-5To minimize stea m/metal temperature differential during startup, the system shall include a desu perheater between the main steam pipework and turbine glands, if necessary.Devia tion No. S-158 ME222B.6.3.22B-6Drains shall be provided at the low points of the steam pipework to drain the condensate in piping between the main steam stop valve and the ST. Deviation No. S-160 ME222B.6.42B-6The ST lube oil purification and storage equipment shall include t he ST lube oil conditioner, lube oil transfer pump, lube oil dump tank, separate lube oil purif ier, piping, valves, and accessories as required.Deviation No. S-163 ME222B.6.42B-6The ST lube oil reservoir shall drain to the lube oil conditioner or to the lube oil dump tank by gravity. A suction pump in the lube oil purifier may also be used. The lube oil conditioner shall return purified oil to the res ervoir. A lube oil transfer pump shall be provided to transfer oil from the lube oil dump tank to the conditioner or the dump connection. The lube oil lines sha ll be valved to provide other modes of lube oil transfer if required.Deviation N o. S-164 ME222B.72B-7Steam exhaust from the ST will be condensed in a single shell two shell, two passes horizontal surface type, divid ed water box with internal air cooling sections and a deaerating-reheating hot w ellDeviation No. S-166ME222B.72B-7The condensate pumps shall be supplied to tran sport the condensate from condenser hotwell through gland steam condenser, HRSG last stage coil and then to deaerato r.Deviation No. S-167ME222B.72B-7The IP and LP steam turbine bypass desuperheate

rDeviation No. S-168ME222B.72B-7* Condensate letdown to one day condensate stora ge tank for dumping the condensate into the tank when condenser hotwell water le vel is high * The gland steam desuperheaterDeviation No. S-169ME222B.72B-7The minimum flow r equirement of the condensate pump shall be maintained by a minimum recirculation flow valve, located downstream of gland steam condenser, which shall simultaneo usly ensure a constant flow of condensate through the gland steam condenser. eac h pump. A common minimum flow recirculation of condensate pump shall be provided and sha ll be located at downstream of gland steam condenser.Deviation No. S-171ME222B.7 2B-7The makeup condensate shall be supplied from one day condensate storage tank located outside generation building by condensate transfer pump. The tank receives demin eralized water from site demineralized water storage tank by demineralized water transfer pumps.Deviation No. S-172 and M-85ME222B.7.12B-8The steam supply to th e deaerating condenser shall normally be taken from the LP steam supply system. Deviation No. S-173ME222B.7.22B-8The cooling water extracted from main cooling w ater closed cooling water system shall be supplied for seal water heat exchanger .Deviation No. S-174ME222B.7.42B-9Transient analysis shall be provided to show t he sizing philosophy of the deaerator. The deaerator storage capacity shall be considered at maximum electric output power between normal water level and low a larm level. The Contractor shall provide adequate over pressure protection and h igh and low water level protection for the deaerator. The bypass deaerator storage capacity shall be considered to have 1.5 minutes re tention time for the deaerated condensate mass flow of the deaerator pump.Deviat ion No. S-177, M-86ME222B.82B-9The condensate from steam piping system shall be drained to main steam blowdown tank and then to blowdown sump the condenser.Devi ation No. S-178ME222B.8.12B-10The HP steam system shall also provide steam to th e ST and the gland steam system pressure regulating valve for sealing the ST during startup and low load operati on and bypass operation.Deviation No. S-179ME222B.92B-10Two 100 percent or three 50 per cent capacity pumps shall circulate the closed cycle cooling water through the c ooling water heat exchangers and the various plant equipment heat exchangers.Dev iation No. S-180ME222B.92B-10The CCCW system makeup shall be supplied by condens ate demineralized water system.Deviation No. S-181ME222B.92B-10, 2B-11The except ions will be equipment requiring more precise temperature control, such as the e xciter coolers, and the ST lube oil coolers, etc. These coolers shall be control led by local pneumatic loops. These coolers shall have temperature sensing devic es included as part of their respective systems to provide information for remot e monitoring. The temperature control shall be ensured by electrical-driven temperature contro l mixing valves, other cooling system (lube oil cooling system) is controlled by local control. Information regarding to temperature shall be transmitted to DCS .Deviation No. S-182ME222B.92B-11? GT, ST and generator lube oil coolers ? ST hydraulic power unit coolers (if required) ? GT, ST generator hydrogen air coolers, if required ? HRSG circulating pump oil coolers ? Air Compressor after coolers (if required) ? HRSG feedwater pump oil coolers ? Sample coolers. ? Vacuum pump coolers ? Gland steam condenser Flow through the CCCW heat exchanger shall be controlled by a bypass so as to ma intain a constant CCCW cold water temperature.Deviation No. S-183ME 2

2 2B.102B-11Circulating water pumps shall be installed to supply water from coolin g tower to the ST condenser, HRSG blowdown purposes (as backup) and other CCCW h eat exchangers.Deviation No. S-184ME 222B.102B-11Circulating water piping to HRSG blowdown tanksDeviation No. S-186ME 222B.102B-12The circulating water system shall supply sufficient cooling water t o the condenser, CCCW heat exchangers, HRSG blowdown under all steam turbine ope rating loads and under steam turbine bypass valve operation at all ambient condi tions. Deviation No. S-187ME222B.102B-13The circulating water (as backup) for HR SG blowdown purpose shall be bled from discharge pump header. The regulating con trol valve set installed at each HRSG blowdown tank inlet shall be provided and sized properly in order to maintain and control blowdown water temperature not t o exceed 60 o C before delivery to the existing blowdown sump. Deviation No. S-188ME222B.112B-13Fuel gas preheater shall be supplied to keep th e fuel gas temperature 28?C 10?C above dew point of hydrocarbon/water and hydrat e formation temperature water and 15?C above dew point of hydrocarbon and hydrat es as per CT requirements.Deviation No. S-189 ME222B.112B-14The fuel gas filter and filter separator shall be pressure vessels containing multiple tube filters made of high efficiency molded fiberglass. The vessel will have a quick opening flanged type closure, blowdown and vent connec tions, and differential pressure gauge. Deviation No. S-190 ME222B.112B-14The gas filter shall be carbon steel with fiberglass cellulose fil ter elements as required by CT.Deviation No. S-191 ME222B.13.22B-15Steam Turbine Generator Bearing Area and HRSG Feed Pump Lube Oil System The ST generator bearings shall be protected by pre-action spray / sprinkle syst ems using closed spray nozzles and installed to NFPA 13 and 15 requirements. The detectors shall be flame or heat detectors. HRSG feed water pumps shall be protected by Electrical heat detector with manual call point, and alarm (horn/siren) of Fire detection, fire extinction shall be performed by portable dry chemical and portable CO2 fire extinguisher in combina tion with indoor hydrant for fire suppression. Deviation No. M-088ME 2 2 2B.13.22B-16Electrical Cable Spreading Room These areas shall be protected by pre-action systems using closed spray nozzle w ith an early warning fire detection system in accordance with NFPA 15 requiremen ts. deluge water systemDeviation No. M-089, S-195ME222B.13.22B-16Steam Turbine L ube Oil Reservoir, Coolers, Storage and Conditioning Area Foam water sprinkle installed to NFPA 11A, 16 and 25 complete with cross zone fi xed heat detector shall be providedDeviation No. M-047ME222B.13.22B-16Emergency Diesel Generator Area Emergency diesel generator area shall be protected by a wet pipe sprinkle system in accordance with NFPA 13 requirements automatically actuated CO2 system.Devia tion No. M-049, S-196ME222B.14 2B-18The control air and station air system shal l supply compressed air at the required pressure and capacity for control air, g eneral plant use, and for operation of other plant equipment except for gas turb ine package. Deviation No. S-197ME222B.142B-18Two 100 percent capacity air compr essors, each compressor shall supply technically oil free air at the compressor aftercooler outlet and complete with intake air filter-silencer, moisture separa tor, and other accessories required.Deviation No. S-198ME222B.142B-19The two 100 percent capacity refrigerant air dryers shall dry all of the control air to a d ew point of +2 o C 3?C for service air and -40?C for instrument air or lower at outlet pressure conditions.Deviation No. S-199ME

2 2 2B.20.12B-23 The chemical feed system shall consist of phosphate feed system (to HRSG drums), and ammonia feed system (to condensate pump discharge). and oxygen scavenger (n on-hydrazine) feed system (to condensate pump discharge).Deviation No. S-201ME22 2B.212B-24HRSG blowdown shall be discharged to the blowdown tank where it shall be quenched with RO rejection water and circulating water as backup to reduce te mperature. Then the wastewater is diverted to the existing blowdown sump. Servi ce cooling waterDeviation No. S-202ME222B.222B-25The contractor shall provide th e following major components for cycle makeup and storage system. One condensate storage tank (for demineralized water) 2 x 100% cycle makeup requirement of horizontal centrifugal demineralized water transfer pumps. Capacity for each pump shall be determined by the Contractor Interconnecting piping and valves. The demineralized water transfer pumps shall pump demineralized water from the e xisting site demineralized water tank at water treatment plant to the condensate tank for storage of demineralized water. The condensate storage tank shall be u sed to store both condensate dump water and demineralized water. This arrangeme nt assures a high quality makeup water supply regardless of condensate dump qual ity and provides greater flexibility of operation and maintenance of the cycle m akeup and storage system. for condenser to make up. Deviation No. S-203 and M91ME233B.13B-2The combustion turbine and auxiliary equi pment shall be compact and self-contained, with acoustic enclosures, where neces sary to meet the requirements of equipment noise level as specified in Volume 2, Section 1D.1.3.Deviation No. S-231 ME233B.1.13B-2Where variable inlet guide vanes or bleed valves are incorporated into the compressor, limit switches the continuous position monitoring system sh all be provided to inform the operator that these devices have operated at the c orrect compressor speed, discharge pressure, gas turbine load and exhaust temper ature as appropriate.Deviation No. S-233 ME233B.1.33B-3The combustion turbine and its auxiliary systems fuel gas system s hall be contained within an acoustic enclosure. The other auxiliaries system whi ch locate outside the enclosure shall be meet requirements of equipment noise le vel.Deviation No. S-235 ME233B.1.43B-3There shall be no critical speed within the range of ? 10% of norm al running speed. The Contractor shall base on 1% proof stress to state the mini mum factor of safety existing in the rotor discs.Deviation No. S-240 ME233B.1.43B-3After balancing of each individual compressor and turbine rotor, t he complete rotor subassemblies shall be dynamically balanced again after the co mpressor and turbine rotor are mating The complete rotor shall be statically and dynamically balanced prior to assembly into the stator. Deviation No. S-241 ME233B.1.53B-4The blading shall be designed to withstand all vibration, thermal shock, gas and mechanical loads that may be experienced during service which are within the boundaries of contractors released design.Deviation No. S-244 ME233B.1.53B-4Both compressor and turbine bladings shall not suffer damage from resonant vibrations within 5% -5% / +3% of the normal operating speed whether sy nchronized or not.Deviation No. S-245 ME233B.1.103B-6The load fluctuation expected during the transition between one m odes of combustion to the next shall be provided. Curves for emissions levels ag ainst all loading shall also be provided.Deviation No. S-255 ME233B.1.103B-6The igniters shall be designed for maximum reliability and their operation shall be automatic. Provisions shall be made for purging to prevent ac cumulation of carbon deposits on the burner tips.Deviation No. S-256 ME233B.1.11.13B-7sealing oil supply of generator (if required)Deviation No. S-25 7ME233B.1.11.13B-7The capacity of the emergency pump and DC power supply shall b e sufficient to allow safe run-down of the machine, turning gear operation and s tart-up.Deviation No. S-258ME233B.1.11.53B-7The speed at which the overspeed gov ernors will operate shall be set to trip at 10% 8% above normal synchronous spee d.

Equipment shall be provided to allow the testing of the overspeed protective dev ices. The overspeed protection system shall be equipped with a self-test device, which is normally actuated every hour. The system shall allow the operator to s tart the self-test.Deviation No. S-260 ME233B.1.11.63B-8The turning device shall be motor hydraulically operated and sh all engage and start automatically. A mechanical interlock or overrun between th e engine starting and turbine turning mechanisms shall be provided to prevent si multaneous operation.Deviation No. S-261 ME233B.1.133B-22 ., bird and small animals. An additional protection screen for t he air intake duct shall be provided after the final filters.Deviation No. S-306 ME233B.1.133B-22An additional protection screen for the air intake duct shall be provided after the final filters. Filter shall be cylindrical cartridge type an d shall be installed horizontal parallel with the inlet air flow to the inlet ai r filtration system.Deviation No. S-307 ME233B.1.133B-22The filter unit housing shall be equipped with re-usable implosi on doors The re-usable implosion door shall be provided as option. It shall be d esigned to prevent collapse of the inlet filter housing due to high differential pressure across the filter elements. The implosion doors shall be furnished wit h gaskets or seals to prevent entry of unfiltered air.Deviation No. S-308 ME233B.1.133B-22The design of the filter and air intake structural shall allow f or the quick and convenient replacement of the filters and shall able to replace the pre-filter during combustion turbine in operation. The Bidder shall provide maintenance facilities as required for online replaceme nt. The Bidder shall propose the maintenance procedure for replacement of prefil ter during plant in operation.Deviation No. S-311 ME233B.1.153B-23The sound attenuators fitted in the inlet plenum before the comp ressor and in the exhaust duct from the turbine (if required, to meet the specif ied noise criteria) shall comprise absorbent material suitably cladded between p erforated metal sheets or shall be of other acceptable type, subject to EGAT's a cceptance.Deviation No. S-312 ME233B.1.16.33B-23The steady-state speed droop shall be capable of adjustment wi thin the range of 2 to 6 3 to 8 percent at the rated speed.Deviation No. S-314ME 233B.1.18.13B-26The fuel gas heater shall raise the temperature of the natural g as to 28 ?C above the hydrocarbon dew point 10?C above dew point of water and 15 ?C above dew point of hydrocarbon and hydrates as per CT requirements. Deviation No. S-320 ME233B.1.233B-28, 3B-293B.1.23 Inlet Air Cooling System (Option) Not Applicable The fog cooling system shall be proposed for inlet air cooling system as option.

Including of the local/remote selection shall be selected from CT contr 23 ME2 33B.1.31.43B-32The compressor, drive motor, and all accessories shall be com pletely factory assembled on a common or several skids, fabricated steel base so as to comprise a complete compressor package ready for installation.Deviation N o. S-330 ME233B.1.31.43B-32The compressor, drive motor, and all accessories shall be comp letely factory assembled on a common, fabricated steel base so as to comprise a complete compressor package ready for installation. Internal piping shall be such that only single point connections for gas inlet, gas outlet, drains, and vents are located indoors.Deviation No. S-331 ME233B.1.31.63B-32The discharge pressure control systems shall use recirculation , as necessary, to supply the required flow rate at a constant pressure. Gas sha ll be recirculated to point upstream of the inlet gas scrubber.Deviation No. S-3 32 ME233B.1.31.63B-32The Compressors shall be designed for a life of 30 25 years.De viation No. S-333ME 233B.1.31.63B-32The following data and curves shall be submitted with the propos al in engineering stage:Deviation No. S-334ME233B.2.13B-37Materials from which t

he various components of the steam turbine are manufactured shall be suitable to withstand the loading and environmental effects imposed during th e stipulated service life of the plant design life time of the steam turbine.Dev iation No. S-336ME233B.2.13B-37Full details of the materials proposed used for t he casing, rotors, blades, diaphragms, or blade carrier and connecting pipework, including chemical composition, mechanical properties shall be provided within the quality documentation, according to Contractors factory quality and inspecti on plan. , heat Heat treatment procedures, fabrication and repair welding proced ures, shall be supplied. inspection Inspection procedures and defect acceptable standards shall be provided during the bidding stage may be reviewed at contrac tors manufacturing facility.Deviation No. S-337ME233B.2.13B-37The casing shall b e horizontally split and supported at the center line, with flexible supports at the high pressure end.Deviation No. S-338ME233B.2.13B-37The design and material s of construction of the casings shall be such that there will be no leakage, gr owth or deterioration of ?any part under all operation conditions which may affe ct the efficiency and reliability of the Unit steam turbine, except of these res ulting from normal wear and tear and assuming operation according to offered loa d regime.Deviation No. S-339ME233B.2.13B-37The casings shall be divided on the h orizontal centerline and the joint joints shall preferably be of metal to metal design.Deviation No. S-340ME233B.2.13B-37Dovetailed Appropriate grooves shall be turned in the wheels or rotor to securely hold the individual blades.Deviation No. S-341ME233B.2.13B-37The completed turbine rotor shall be balanced and test a t 15% 25% overspeed for a minimum of 2 minutes in the manufacturer's plant in or der to ensure that all amplitudes of vibration are within acceptable limits.Devi ation No. S-343ME233B.2.13B-38The steam turbine and generator coupling shall int egral with the shaft or shrinked-on and amply strong to withstand shocks during operation, including generator short circuit conditions and synchronizing out of phase.Deviation No. S-345ME233B.2.13B-38The coupling shall be designed with hyd raulic radial fit solid bolts type so as to permit easy and rapid disconnection, reassembly and alignment.Deviation No. S-346ME233B.2.13B-38Each diaphragm or st ationary blade shall be split along the horizontal centerline and a doweled tong ue and groove joint taper pins and/or dowel pins shall be provided to ensure cor rect alignment and prevent interstage leakage.Deviation No. S-347ME233B.2.13B-38 To minimize blade erosion from the moisture, the leading edges of the blades in the later stages are induction hardened or covered with satellite, or protected by other s uitable measures according to Contractors standard.Deviation No. S-348ME233B.2.1 3B-39Suitable monitors of shaft eccentricity and position, shaft vibration level s, differential thermal expansion between rotor and casing, bearing oil temperat ure shall also be provided to ensure that these are well within the design limit s.Deviation No. S-350ME233B.2.13B-39Motor or Pneumatically operated vacuum break er valves with inlet filter shall be provided at the condenser.Deviation No. S-3 51ME233B.2.13B-39The steam valves shall have actuator driven by an electro-hydra ulic control governing system. For LP steam stop and control valve shall be elec tro-pneumatic actuator with additional 12 months extended warranty, however elec tro-hydraulic as option. Deviation No. S-352ME233B.2.13B-39The valves shall be equipped with both coars e and fine strainers. A removable corrosion-resistant integral strainer shall be furnished with the turbine stop valve for commissioning. Separate strainer may be used for LP valves. All screens shall be removable without disturbing the inl et piping. A temporary fine mesh strainer shall be furnished for using during st artup in commissioning.Deviation No. S-353ME233B.2.23B-39The cover and internal blinking fixtures shall be used at Blow-off inserts shall be supplied for each H P and IP stop valve to allow bypassing the steam turbine during steam blowout cl eaning of the steam piping.Deviation No. S-355ME233B.2.33B-39Complete gland seal ing system for each steam turbine, including gland steam condenser, attemperator , two full size gland steam exhaust fans, etc. shall be provided to prevent infi ltration of air into the main steam system and leakage of steam into the turbine hall through the steam turbine chests and steam turbine casing.Deviation No. S356ME233B.2.33B-39A steam strainer shall be provided in the auxiliary steam supp

ly line header to the glands and mounted as close as practicable to the glands g land sealing system.Deviation No. S-357ME233B.2.33B-40Arrangements shall be made where possible to enable the steam turbine glands to be examined without the ne ed to lift the cylinder covers.Deviation No. S-358ME233B.2.53B-43All main bearin gs shall be provided with a positive visual check for oil flow through the beari ngs via sight flow indicators or inspection openings on the oil return lines.Dev iation No. S-366ME233B.2.63B-44For shipment and storage, the interior of reservo ir shall be lined or coated preserved with a rust preventive coating oil which w ill be compatible with the turbine lubricating oil and all openings tightly seal ed for protection during shipment.Deviation No. S-368ME233B.2.63B-44k. A portabl e fixed vacuum type purifier for steam turbine lube oil.Deviation No. S-370ME233 B.2.73B-45c. Soleplates are to be furnished under turbine and generator, where n ecessary according to Contractor s standard.Deviation No. S-371ME233B.2.7.3B-45f. An overspeed governor exerciser shall be furnished to permit testing without tr ipping the unit.Deviation No. S-372ME233B.2.93B-45Cladding and, if necessary, a suitable acoustic enclosure shall be furnished for the steam turbine generator u nit. If an enclosure will be supplied, access doors, ventilation and lighting fa cilities shall be included.Deviation No. S-374ME233B.2.123B-46The steam turbine and generator couplings shall be integral shrinked on with the shaft and amply s trong to withstand shocks during operation including generator short circuit con ditions and synchronizing out of phase. The couplings with hydraulic radial fit solid bolt type shall be designed so as to permit easy and rapid disconnection, reassembly and alignment.Deviation No. S-376ME233B.2.133B-46All piping for steam , oil and water shall be seamless steel. Exceptions are allowed for the cross-ov er pipe from HP/IP to LP turbine.Deviation No. S-377ME233B.33B-47Silencers shall be provided at safety valves outlet, start-up vent stack, and the HRSG blowdown tank vent pipes.Deviation No. M-104ME233B.3.2 3B-47, 3B-48* Internally insulate d HRSG casing and duct work with a stainless steel liner throughout from combust ion turbine outlet to the end of superheater bank where gas temperatures exceed 400 oC.Deviation No. M-107ME233B.3.3.13B-50The heating surface shall be directly accessible for inspection, cleaning and replacement of tube elements.Deviation No. M-112ME233B.3.3.13B-50Each attemperator station shall consist of a pneumatic motor actuated block valve and of a pneumatic motor actuated control valve for automatically quick response.Deviation No. S-379, M-113ME233B.3.3.23B-50The inte rior of the drum shall be blast cleaned with steel or other nonsilica-bearing gr it, and shall be coated with a water soluble corrosion preventive material be ap plied with the preventive measure for drum corrosion protection before shipment. Deviation No. M-115ME233B.3.3.23B-50The equipment shall at least consist of prim ary separators and secondary separators.Deviation No. M-116ME233B.3.3.33B-51Mani fold or headers design temperature shall be the same as those of the tube unless they are situated outside the gas path. For manifold located outside the gas pa th and the piping between the superheater and attemperator, the design temperatu re shall be the same as maximum fluid operating temperature plus 16 ?C oF.Deviat ion No. M-117ME233B.3.3.43B-51To ensure adequate separation between tube banks na tural frequency and the frequency of vibrations induced by gas flow, the arrange ment of the tube banks, supports and spacers shall be verified considered by mat hematical and/or physical models by the supplier prior to installation. The typi cal analysis on the natural frequency of vibration shall be submitted.Deviation No. M-102ME233B.3.3.53B-52The exterior surfaces of expansion joints shall be ins ulated to prevent corrosion of components in the vicinity of the expansion joint . The expansion joint at the inlet/outlet duct shall be internally insulated. The personal protection for the surface temperature when it exceeds 60 oC shall be p rovided for expansion joint at the inlet/outlet duct.Deviation No. M-121ME233B.3 .3.63B-52The damper including actuator and all accessories shall be provided at each HRSG stacks. to prevent rainwater entering stack during shutdown.Deviation No. M-122ME233B.3.3.93B-54HRSG casing and ductwork shall be designed to limit su rface temperature of 55 60 oC maximum based on ambient temperature of 27 oC and an air velocity of 15 meters per minute. The temperature at the penetration area on casing surface (roof and bottom), excluding bellow, shall not exceed 200 oC

average over each module bay.Deviation No. M-128, 129ME233B.3.73B-54Test procedu res shall be in accordance with the ANSI ASME code for pressure piping.Deviation No. M-131ME233B.3.83B-54One HRSG blowdown tank shall be provided for each HRSG. The HRSG blowdown tank shall be sized for 5 minutes storage time (LWL to HWL) b ased on the startup period and then vent to the atmosphere. Deviation No. M-132M E233B.3.83B-55The spray water, completed with the control valve and manual bypas s valve, shall be provided to cool down water in the HRSG blowdown tank to maint ain blowdown water temperature not to exceed 60?C before delivery to the blowdow n sump. Continuous blowdown will flow from LP/IP/HP steam drums via the angle type contr ol valve to the HRSG blowdown tanks. Intermittent blowdown from each drum and all other HRSG startup drains shall be directed to each HRSG blowdown tank. The intermittent blowdown system flow rate shall be based on the worst-case conditions for starting of the combustion turbi ne and shall be directed to each HRSG blowdown tank via the motorized valve. HRSG blowdown shall be routed by pumps of 2x100% redundant design to the service cooling water return line, which joins the circulating water line downstream of the condenser. Continuous blowdown will flow from IP/HP steam drums via the control valve to th e blowdown flash pipe. Intermittent blowdown from each drum and all other HRSG startup drains shall be directed to the start up flash tank. The intermittent blowdown system flow rate shall be based on the worst-case conditions for starting of the combustion turbi ne.Deviation No. S-380ME233B.3.93B-55Flow nozzles and orifices in low pressure l ines (lower than 100 BarG) shall be flanged for easy removal. Deviation No. M-134ME233B.4.13B-58One steam surface condenser shall be of single pressure design, downward or Two condensers with undivided waterboxes, one on e ach side of the LP Turbine, lateral type, consisting of horizontal shell with di vided waterbox arranged for two water pass through shell the cooling waterside o f the plant is of the divided configuration.Deviation No. S-383ME233B.4.13B-586. Steam duct and expansion joint from steam turbine to condenser.Deviation No. S384ME233B.4.43B-583B.4.4 Condenser Shell Expansion Element Not applicable The diaphragm plate shall be made of suitable grade of steel and shall accommoda te the differential expansion of the shell and tubes. Deviation No. S-385ME233B. 4.63B-59Tube sheet material shall be made of stainless steel Type 304. carbon st eel with a stainless steel cladding Type 316L or equivalent on the waterside.Dev iation No. S-386ME233B.4.73B-59Tube material shall be made of seamless stainless steel Type 304. longitudinal welded stainless steel tubes ASTM A249 Type 316 or equivalent.Deviation No. S-387ME233B.4.83B-59The hotwell storage capacity from norma level to low-low level shall not be less than five (5) minutes of the desi gn flow.Deviation No. S-388ME233B.4.83B-59The leak detection baffles shall be pr ovided to divide the hot well into two sections parallel with the tubes.Deviatio n No. S-389ME233B.4.93B-59Circulating water nozzles shall be located as specifie d at the time the award is made. Waterboxes shall be constructed of suitable grade of steel with rubber lining ep oxy coating with minimum of 1.0 mm internal coating thickness. Each condenser w aterbox shall be provided with ferrous anode for a sacrificial anode cathodic pr otection system. Each condenser waterbox shall be provided with two 500 mm one 6 00 mm. diameter, quick opening hinged type manhole.Deviation No. S-390ME233B.4.1 13B-605. A silencer shall be used to reduce the noise level of the discharge. T he internal parts shall be made of stainless steel which is suitable for the ope rating condition.Deviation No. S-391ME233B.4.133B-617. Transient analysis shall be provided to show the sizing philosophy of the deaerator and height of deaerat or to avoid the cavitation of HRSG feed pump during turbine trip and load reject ion.Deviation No. M-86ME233B.4.143B-61Circulating water inlet and outlet valves and expansion joint shall be flanged rated for 150 lb Raised Flat Face (ASA AWWA ) flange.Deviation No. M-136ME233B.5.23B-62Additional equipment and services to be furnished by the Contractor shall include, but are not limited to, the follow ing:

- Water sprinkle fire protection system for protection of cooling tower. - Manual pull station 2 points with alarm horn and outdoor hydrant nearby area f or fire protection of cooling tower. Deviation No. M-144ME 233B.5.23B-62a ## Add. No.2The material of sound mat shall be polypropylene with high chemical resistan ce and ultraviolet light stabilized polyethelene. Mounting support, wire rod and other accessories shall be made of stainless steel type 316L for corrosion resi stance. The supporting structure will be made of FRP structural element which ar e assemble with 316 stainless steel hardware.Deviation No. M-146ME233B.5.83B-63F ill shall be of polypropylene Polyvinyl chloride (PVC) or Polypropylene.Deviatio n No. M-150ME233B.5.93B-63Drift eliminators shall be of polypropylene Polyvinyl chloride (PVC) or Polypropylene.Deviation No. M-151ME233B.5.12.13B-64Fans shall be of the single-speed, multi-blade propeller type, designed for low noise level and vibration free operation acceptable vibration levels operation.Deviation No . M-138ME233B.5.12.23B-64Oil fill and drain piping shall be 25 mm welded 316 mad e of 316L stainless steel pipe or 316 SS of nitrile armoured pipe. Deviation No . M-139ME 233B.5.12.43B-65 ## Add. No.2The sound enclosures for fan drive motors shall be a rigid complete enclosur e, fabricated from SS type 316L and shall be lined with sound absorbing material in accordance with ASTM C423-84A. galvanized steel with coating and the absorbi ng material will be designed equivalent to ASTM C423-84A. Testing shall be in ac cordance with ASTM E90.Deviation No. M-140ME233B.6.13B-677. Main Steam Blowdown TankDeviation No. S-394ME233B.6.13B-679. CCW expansion tankDeviation No. S-398ME 23Table 3B.6-13B-701. Clean Turbine Lube oil Tanks 2x Lube Oil Reservoir Capacity UL 142 - 9 N/R In Accordance with UL 142Deviation No. S-396ME23Table 3B.6-13B-706.Main Steam Blowdown Tanks 5-minute Storage Capacity ASME 3 Note 1 Spot Note 2Deviation No. S-397ME233B.73B-713B.7 Field-Erect ed Tanks Not ApplicableDeviation No. S-398ME233B.73B-713B.7 Field-Erected Tan ks Not ApplicableDeviation No. S-399 and M-152ME233B.9.13B-79The HP steam bypas s station shall consist of the following equipment: 1. Emergency isolation valve 2. Bypass control valve with integral or separate desuperheater 3. Spray water control valve 4. Spray water pressure reducing/isolation valve with bypass valveDeviation No. M-156 and M-157ME233B.9.23B-804.Spray water pressure reducing/isolation valve w ith bypass valveDeviation No. S-403ME233B.9.33B-803. Spray water control shut-o ff valve 4.Spray water pressure reducing/isolation valve with bypass valve Deviation No. S-404ME233B.9.43B-81The design and construction of bypass control valves shall conform to ANSI requirements for valve construction based on the de sign pressure and temperature conditions. All materials shall be in accordance w ith the applicable ASTM standards and the selection of materials shall be approv ed by EGAT.Deviation No. S-407ME233B.9.43B-81All HP and IP bypass control valves shall be provided with taps in the body upstream at the seat to a prewarming fl ow path. All necessary piping, valves and orifices shall be supplied to provide prewarming capability for each HP and IP bypass system.Deviation No. S-409ME233B .9.43B-81The Contractor may design a common oil hydraulic fluid supply unit to s ervice all of the bypass valves associated with power block.Deviation No. S-410M E233B.9.43B-81A single hydraulic oil supply unit may be used to supply oil to al l accumulators. Each oil supply unit shall be equipped with two 100 percent, mot or driven pumps and associated instruments, valving, piping, tubing and one (1) oil reservoir. Oil supply units and accumulators shall be mounted on a common base.Deviation No. S-411ME233B.9. 43B-81Each IP desuperheater shall be designed to maintain a constant outlet stea

m temperature over the full range of steam conditions by modulating spray water flow through the spray water control valve.Deviation No. S-412ME233B.11.13B-823B .11.1 Scope of Work The Contractor shall supply several general service type pumps for the Facility. The scope of supply shall include, but is not limited to, supply of the followi ng pumps and accessories: * Demineralized water transfer pumps (2x50 %) * Closed cycle cooling water pumps (2x100% or 3x50%)Deviation No. S-413, S-415ME 233B.11.13B-82* Condensate transfer pump (lx100%)Deviation No. S-414, M-161 and M-162ME233B.11.33B-82The pumps and motors, when running as a single unit at the site, the amplitude of vibration in any plane measured at the pump shaft and th e upper drive bearing shall be satisfied with Zone A on ISO 7919 and ISO 10816 s tandard, latest edition over the pump operating range. Deviation No. S-417ME233B.123B-854. For each pump, a flow meter minimum flow va lve shall be provided to control the individual modulating control valve in the recirculation line to the deaerator to maintain the minimum design flow quantity of the pump.Deviation No. S-423ME233B.12.13B-85* Monitor bearing temperature an d seal water temperature and alarm when high.Deviation No. S-425ME233B.12.13B-85 9. The isolated suction valve, discharge non-return valve and motorized manual discharge valve of approved design and Deviation No. S-426ME233B.12.13B-859. the HP HRSG feed pump discharge non-return valve shall be air operated, non slam sw ing check valve type.Deviation No. S-427ME233B.13.13B-873. The pump shall be ra ted such that one pump can supply 110% of the flow to the deaerator for standard deaerator and integral deaerator HP/IP feedwater pump or LP steam drum (for int egral condenser deaerator type located in condenser) for deaerating condenser at the HRSG MCR condition (normal operation) with 15% design flow frictional head loss margin.Deviation No. S-431ME233B.13.13B-874. The Net Positive Suction Head (NPSH) available shall be equal to or greater than the manufacturer's required NPSH (without any damaging pump parts even at run-out point) plus minimum 20% s afety margin.Deviation No. S-432ME233B.13.13B-887. Suction strainers with isola tion valves, expansion joint, differential switches and indicators with water fl ush/drain pipeline for cleaning purpose shall be provided.Deviation No. S-434ME2 33B.13.13B-888. Condensate control valve station shall include one (1) two (2) x100% condensate control valve plus a low flow start-up bypass valve. The conden sate control valves shall be pneumatically operated operated by electric actuato rs.Deviation No. S-435ME233B.14.3.23B-89Pump materials Impeller : SS ASTM A743 Type 304 CA6NM Type 316L or SS ASTM A743 CF3. Shaft : SS ASTM A743 Type 420 SS ASTM A276 or SS ASTM A240 Shaft sleeves: SS ASTM A743 Type 420 SS ASTM A276 or SS ASTM A240 Casing: CS ASTM A48 A36 or EN 10025-S275JR Deviation No. M-166ME233B.17.13B-941. Two 100 percent or three 50 percent capaci ty, horizontal, centrifugal type CCCW pumps 2. One carbon steel CCCW storage tank with interior protective coating. One expa nsion tankDeviation No. S-437ME233B.17.23B-943B.17.2 CCCW Heat Exchangers (Shell and Tube Type) Not Applicable The design, construction and performance shall comply with the following criteri a:

.as specified Item 3B.4.12, Volume 2, Condenser Tube Cleaning System.D 3B-96The plate and tubes running through the clamping plates shall be of austeni tic stainless steel material or equivalent Titanium.Deviation No. S-440ME233B.17 .3.63B-98Screen size: 300 2000 micron filtrationDeviation No. S-446ME23 3B.17.3.63B-98Body: Carbon steel 400 micron epoxy coated or rubberlined insideDe viation No. S-447ME23 3B.19.13B-1003B.19.1 Cycle Chemical Feed System The Cycle chemical feed system shall consist of phosphate feed system (to HRSG d rums), and ammonia feed system (to condensate pump discharge). and oxygen scave nger (non-hydrazine) feed system (to condensate pump discharge).Deviation No. S-

449ME23 3B.19.1.23B-1003B.19.1.2 Oxygen Scavenger Feed System Not used The oxygen scavenger (non-hydrazine) feed system shall consist of the skid, stra iner, 2x100% chemical feed pumps, dilution tank, measuring tank, calibration col umn and mixer. The injection rate of the chemical feed pumps shall be controlle d by automatically adjusting the pump stroke. One air or electric operatedDeviat ion No. S-451ME 233B.19.1.33B-100This chemical feed system shall consist of the skid, strainer, 2x100% chemical feed pumps, dilution tank, measuring tank, calibration column an d mixer.Deviation No. S-452ME 233B.19.1.33B-100The injection rate of the chemical feed pumps shall be controll ed by automatically adjusting the pump stroke frequency controlled pumps based .. Deviation No. S-453ME233B.19.4.13B-103The water/steam samples shall be extracted from the following points. * Condensate Demineralized makeup water * Condensate pump discharge * Condensate after chemical feed * Final feedwater or economizer inlet * HRSG water * Saturated steam * Superheated steam and reheat steam * Deaerator inlet and outlet * Closed cycle cooling water. Deviation No. S-460, S-461ME233B.19.4.23B-104The sampling system shall consist o f freestanding panels be mounted on panels fixed to the inside walls of the samp ling container housing conditioning and analysis equipment. All sampling equipme nt shall be mounted on the frontside of in these panels . e. Piping, tubing, fittings valves, and brackets per ANSI B31.1 or DIN g. Panel fabrication by welding. No welding, bolts or bolt holes shall show fro m the front of the panels Panel shall mounted to wall with screw/bolts at front side of the panelDeviation No. S-462, S-464, S-465ME233B.19.4.33B-104Sampling Panel shall be installed in air condition room container. All material construction shall be submitted to EGAT for review duri ng engineering phase. Furthermore, contractor will provide the rain protection f or the pre-fabricated sampling container. The roof shall be extended at least 1. 50m from the edge of container. In addition, the 1.50m siding shade and the rain gutter with downspout shall be provided. Air condition system shall be supplied and shall be spilt type, 2 x 100% capacity. Air conditioning shall be 2x50% cap acity, sizing according to heat load requirements. Sampling panel installed in t he container is not acceptable.Deviation No. S-466ME233B.19.4.43B-105h. Back pre ssure relief valves for each common line Deviation No. S-467ME233B.19.4.53B-10512. If shared sampling is used, maximum an d minimum delay times for sample switching stated including analyzer response ti me and time required to obtain representative sample from point being analyzed o nly one sampling flow will be passed through in normal operation.Deviation No. S -470ME233B.19.5.3B-105Certified calibration curves shall be provided for analyze rs on site.Deviation No. S-471ME233B.24.13B-125One turbine room supplemental cra ne for both combustion turbines. (Option)Deviation No. M-176ME233B.24.33B-125The crane shall be designed and constructed in accordance with the latest applicabl e requirements of the standard specifications and codes of CMAA Specification No .70, ANSIB30.2, AGMA, AISC, ASTM, AWS, IEEE, NEC, NEMA, FEM 1.001, and other such regular published and accepted standards except where modified or supplemented b y these specifications.Deviation No. M-173ME233B.24.73B-127Auxiliary hoist 5 spe ed magnetic variable speed (stepless).Deviation No. M-178ME233B.24.15.43B-131Hyd raulic Brakes Hydraulic brakes shall be of the pressurized-fluid operating disc or shoe type a ttached to the driving motor shaft. The brakes shall be activated by pressurizi

ng the hydraulic system through a foot pedal in the operating cab. The foot ped al shall be conveniently located adjacent to the operator's chair and shall be l imited to a 200 mm stroke and 34 kilograms of pedal force to develop required br aking torque. Hydraulic brakes requiring an excess of 34 kilograms of pedal for ce shall be equipped with a power operated hydraulic booster system. Power oper ated hydraulic brake systems shall be equipped with a remotely con-trolled bleed er with the control button located in the operator's cab. Deviation No. M-179ME233B.25.13B-134This item covers the design, performance, an d construction of hoists, trolleys, and accessory items. except for the maintena nce hoist at the air intake filter house. Deviation No. S-475ME233B.25.13B-134All rotating equipment over 100 kg except fo r CW Pumps shall be provided with monorails, hoists and trolleys, maintenance or supporting beam or lifting lug to permit the equipment to be removed. Deviation No. M-175ME233B.26 3B-138The Specification applies to the seamles s ferrous cylindrical containers and accessories intended for handling compresse d gases for general uses in power stations and their ancillary plants except for CO2 cylinders for the fire fighting systems of the GT enclosure and PCC's.Devia tion No. S-476ME2Change filtration concept for service cooling water booster lin e to provide 2X100% Duplex strainer without bypass lineFlow diagram: COOLING WAT ER SYSTEMME2Site fire protection piping shall be kept to fire main ring loop con cept.Flow diagram: Site fire protectionME 2Drawing No. WNCC4-UUU-M002DRAWING NUMBER/TITLE WNCC4-UUU-M2000 INDEX WNCC4-UUU-M2001 LEGEND WNCC4-APK-M2002 EMEGENCY GENERATOR WNCC4-CAA-M2003 STATION AIR WNCC4-CAB-M2004 CONTROL AIR NOT USED NOT USED NOT USED NOT USED NOT USED

WNCC4-DPA-M2005 NOT USED BUILDING DRAINS AND EQUIPMENT DRAINS WNCC4-ECB-M2007A NOT USED CLOSED CYCLE COOLING WATER WNCC4-ECB-M2007B CLOSED CYCLE COOLING WATER WNCC4-FGA-M2008A FUEL GAS SUPPLY WNCC4-FGA-M2008B FUEL GAS SUPPLY NOT USED NOT USED

NOT USED

WNCC4-FPA-M2010 NOT USED GENERATION BUILDING FIRE PROTECTION WNCC4-FWA-M2011A HRSG FEED NOT USED

WNCC4-FWA-M2011B HRSG FEED WNCC4-FWA-M2011C HRSG FEED WNCC4-FWC-M2012A CONDENSATE WNCC4-FWE-M2013 CYCLE CHEMICAL FEED WNCC4-FWF-M2014 CYCLE MAKEUP AND STORAGE WNCC4-HRB-M2015 CONDENSATE AIR EXTRACTION

NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED

WNCC4-HRC-M2016A CIRCULATING WATER WNCC4-HRC-M2016B CIRCULATING WATER

NOT USED NOT USED

WNCC4-HRE-M2018A NOT USED CIRCULATING WATER CHEMICAL FEED WNCC4-HRE-M2018B NOT USED CIRCULATING WATER CHEMICAL FEED WNCC4-HRF-M2019 CONDENSER CLEANING NOT USED

WNCC4-PMB-M2022 NOT USED SHUTDOWN CORROSION PROTECTION WNCC4-SAC-M2024A SAMPLING AND ANALYSIS WNCC4-SAC-M2024B SAMPLING AND ANALYSIS WNCC4-SAC-M2024C SAMPLING AND ANALYSIS WNCC4-SGF-M2025A HRSG#1 LP SYSTEM WNCC4-SGF-M2025B HRSG#1 IP SYSTEM WNCC4-SGF-M2025C HRSG#1 HP SYSTEM WNCC4-SGF-M2025D HRSG#1 BLOWDOWN NOT USED NOT USED NOT USED

NOT USED NOT USED NOT USED NOT USED

WNCC4-SGF-M2025E HRSG#2 LP SYSTEM WNCC4-SGF-M2025F HRSG#2 IP SYSTEM WNCC4-SGF-M2025G HRSG#2 HP SYSTEM WNCC4-SGF-M2025H HRSG#2 BLOWDOWN WNCC4-SGG-M2026A MAIN STEAM WNCC4-SGG-M2026B MAIN STEAM

NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED

WNCC4-SGG-M2026C NOT USED INTERMEDIATE PRESSURE STEAM WNCC4-SGH-M2027A LOW PRESSURE STEAM WNCC4-SGH-M2027B LOW PRESSURE STEAM WNCC4-STG-M2030 SITE FIRE PROTECTION WNCC4-TEF-M2031 MISCELLANEOUS DRAINS NOT USED NOT USED NOT USED NOT USED

WNCC4-TGC-M2032 NOT USED STEAM TURBINE SEALS AND DRAINS WNCC4-TGD-M2033 STEAM TURBINE LUBE OIL NOT USED

WNCC4-TGD-M2034A NOT USED STEAM TURBINE GENERATOR COOLING AND PURGE WNCC4-TGD-M2034B NOT USED STEAM TURBINE GENERATOR COOLING AND PURGE WNCC4-WSC-M2037 SERVICE WATER SUPPLY NOT USED

WNCC4-WWB-M2042 NOT USED SANITARY DRAINAGE & TREATMENT WNCC4-WWA-M2407 NOT USED CHEMICAL AND OILY WASTE DISPOSAL SYSTEMMinute of Clarification Meeting No.003

WNCC4 Project 24 May 2011

List of Contract Document Preparation

Potrebbero piacerti anche