Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Electrical. Recommendation on checking of each motor and the control panel as below: -Motor current operating current not exceeding full load current as rated at the motor nameplate. Every 2 weeks -Motor insulation within permissible operating range of 1M ohm and above. Every 3 months. -Motor winding resistance balance reading among phases. Every 3 months. -Control panel operation sequence, light indicators, Thermal overload trip simulation and emergency on operation. Components and inlet air filter should be cleaned to prevent dust accumulation that will reduce air flow through the filter and maximized components life span. Every 6 months * Soft vacuuming is possible. * Please note that electrical test and checking should only be carried out by trained personel with proper safety equipment. ** The recommended time is just a guide depending on site condition. More frequent checking is more encourage to enable system to operate smoothly. *** Grundfos shall not bear any responsibility for the above recommendation.
GRUNDFOS INSTRUCTIONS
DESCRIPTION
General The description covers the standard unit with functions for Grundfos Hydro Pneumatic DC Booster system, incorporating Grundfos Hydro Control Pneumatic DC and all accessories. Grundfos Hydro Pneumatic Booster System is designed for pressure boosting in system supplying consumption water to dwellings, office buildings, hotels, hospitals, departmental stores, manufacturing plants and etc. Pumps, motors and starter panel The Grundfos Hydro Pneumatic system is built with all Grundfos components, except where all applicable, certain non-Grundfos accessories are supplied. Users are not encouraged to install any equipment or connection into the system where not approved by Grundfos. The introduction of foreign equipment or connection into the system may affect the operation of the system, and may result in damage of pumps, components or the control panel. In this respect, Grundfos shall not be liable for the damage all standard warranty will be declared null and void. Pneumatic vessel One or more pneumatic vessel is supplied with the booster system. The vessel is supplied with a certain precharge air depending on the maximum operating pressure range. The pneumatic vessel forms part and parcel of the booster system operation and the system shall not be operated without a it integrally fitted into the system. The vessel shall conform to local authority rules and regulations and where applicable, it shall be inspected annually for defects. Users are encourage to read the accompanying manuals on the pneumatic vessel to ensure proper working and maintenance knowledge. In general, Grundfos supply the following sizes of standard pneumatic vessel: Type: Actual volume Pressure range Max liquid temp CT300V 270 litres 100-200psi 70 deg.celsius CT500V 527 litres 100-200psi 70 deg.celsius CT1000V 1000 litres 100-200psi 70 deg.celsius CT1500V 1526 litres 100-200psi 70 deg.celsius CT2000V 2017 litres 100-200psi 70 deg.celsius Please refer to Grundfos for optional pneumatic tank sizes and operating pressure. For optimum system operation, ensure a precharge air pressure of 70% of the setpoint. Accessories Depending on system design, Grundfos is able to supply other accessories to enhance the operation of the booster system. Users are encouraged to check with Grundfos for more details.
BENEFITS
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. One touch easy operation. User friendly with discharge pressure monitoring readout with indication light for the operation of the pump at the controller. Standard protection feature with front indication lights and read out at the controller. First in first out starting and stopping sequence and lead lag change over feature built in the controller. Password protected for settings of controller. Hour run meter for individual pump built in controller Clock program up to 3 start and stop setting for each day of the week Over pressure, under pressure, sensor failure, dry run protection and excessive start/stop in the controller. Easy setting of setpoint pressure (cut in) and differential settings (cut off) Phase failure protection during operation as standard. High quality components.
OPERATION
Auto mode Depending on the performance required the selected setpoint will be retained via automatic start/stop of mains operation of the pumps. The pressure range in which the pump will supply are controlled by the settings of the controller as supplied in the system. The pneumatic vessel in the system acts as a pressure holding unit to prevent frequent start/stop in intermittent demand and to provide for the system pressure to be retained for a longer time before the pumps are started again. All control, operation and protection features are activated in accordance with the set parameters To activate auto mode Press the start/stop button. The pump will operate automatically base on the setting of the controller until the start/stop button is pressed again.
Setpoint The system pressure settings is set via the controller. The setpoint is set according to the pressure range curve of the pump used as recommended in the above diagram. This is to ensure system will operate in optimum condition and supply the pressure required according to the consumption demand. Allow for minimum pressure differential of 10 meters between the setpoint and differential setting at the controller. Alternation of pumps The system is incorporated with a leadlag feature via the controller to allow alternation of pumps in automatic mode. In the condition where more than one duty pump is required, e.g consumption exceeds one duty pump capacity and where pressure falls below the setpoint, the next pump will come into operation to supply the pressure required. Where the first pump has finished a cycle, the second pump will start. First in first out function The system is incorporated with first in first out function via the controller to allow the operating time of the pump to be equally shared. In the condition where more than one duty pump is required, e.g consumption exceeds one duty pump capacity and where pressure falls below the setpoint, the next pump will come into operation to supply the pressure required. When the differential setpoint is reached, the pump that been operating the longest time will cut-off first. Emergency mode ** Operate only if the Hydro Pneumatic DC controller is faulty. During emergency operation, pump operation must be monitored to prevent the pump from dry running and operating at no flow. All protection is not applicable with this mode. Switch Off the isolator and unscrew the latch anti-clockwise to open the panel door. Switch On the isolator by turning the knob of the isolator clockwise to 900 to power on the starter panel. Switch On the emergency switch by turning it clockwise to 450. The pump will run until the emergency switch is manually switched off. * Refer to Fig 1.
1 10 9 3 2
8 7 6 5
1 Pump indicator On indicates the specific pump is running. Flashing indicates specific pump is on standby mode. Off indicates no pump or power supply not on. 2 Status indicator On indicates that the specific pump tripped via Manual Motor Starter(Refer MMS for protection) Status Indicator 1 flashing indicates Overpressure alarm Status Indicator 2 flashing indicates Underpressure alarm Status Indicator 3 flashing indicates Pressure transmitter failure alarm Status Indicator 4 flashing indicates Dry run protection alarm 3 Alpha numeric indicator Read out of the parameter and actual monitoring pressure and parameter settings. 4 Start/stop button To activate or shut down the system in auto mode. 5 Select (Enter) button To enter into specific parameter, to change and enter a value of the parameter. 6 Scroll right buttton To scroll forward into the parameter or increase the value of settings. 7 Scroll left button To scroll back into the parameter or decrease the value of settings. 8 Individual pump controller manual mode indicator * On indicates that the specific pump is set to operate to manual mode at n01 to n04 settings. 9 Clock program indicator *Flashing indicates the clock program of the controller is activated. 10 Auto restart (after power failure) * On indicates system will automatically operate after power resume. * Flashing indicates system will restart to previous state after power resume. * Off indicates system will not restart after power resume. Manual activation required.
10
Settings description
EPS CPS NP PC PD SP B TD HL ENTER PASSWORD CHANGE PASSWORD NUMBERS OF PUMP PUMP CONTROL START/STOP TIME GAB SETPOINT PRESSURE DIFFERENTIAL TIME DELAY HIGH LIMIT ENTER A PASSWORD FOR SETTING ACCESS CHANGE THE USER PASSWORD TOTAL PUMPS CONTROL BY CONTROLLER SET TO FIFO (FIXED) OTHERS NOT USED DELAY TIME BETWEEN PUMPS WHEN START STOP (S) PREVENT ALL PUMPS TO START STOP SIMULTANEOSLY PRESSURE SETTING (BAR) EXAMPLE: 6.5 BAR = 065 CUT OFF PRESSURE BAND (BAR) EXAMPLE: 015 = PUMP STOP AT SETPOINT + 1.5BAR DELAY START/STOP WHEN SP1 AND B REACHED (S) MAXIMUM PRESSURE CUT OUT SETPOINT (BAR) STOP SYSTEM WITH FAULT INDICATION WHEN PRESSURE REACHED HL SETPOINT AFTER THE HLT TIME ALARM DELAY FOR HIGH LIMIT (S) MINIMUM PRESSURE CUT OUT LIMIT SETPOINT (BAR) STOP SYSTEM WITH FAULT INDICATION WHEN PRESSURE REACHED LL SETPOINT AFTER THE LLT TIME ALARM DELAY FOR LOW LIMIT (MIN) SET TO C-CURRENT (FIXED) OTHERS NOT USED LOWEST RANGE OF SENSOR (BAR) HIGHEST RANGE OF SENSOR (BAR) 0 (FIXED) OTHERS NOT USED
HLT LL
LOW LIMIT DELAY ANALOGUE INPUT AITY LOWEST RANGE AITY HIGHEST RANGE AITY COMPENSATION
11
T11S TO T73E IS THE CLOCK PROGRAM FUNCTION FOR SYSTEM OPERATION AT SPECIFIC TIME AND DAY. PLEASE REFER TO GRUNDFOS FOR FURTHER INFORMATION. * THE DATE, CLOCK SETTINGS AND CLOCK PROGRAM FUNCTION ARE RESET UPON POWER ON/OFF.
12
13
Status indicator light for specific pump on (specific pump trip) Step B1 Check the MMS Trip position
Normal position Status indicator 1 light flashing (overpressure) Controller read out "PHL" Step C1 Check the high pressure setting at the controller Pressure reading is higher than HL limit Pressure reading is lower than HL limit Step C2 Check the Pneumatic tank Tank is faulty Tank is functional
Check pump and motor outgoing cable Reset the MMS once only If fault repeat, call Grundfos for assistance Reset. If fault repeat, call Grundfos.
Reset. If fault repeat, call Grundfos. Go to step C2 Call Grundfos for assistance Reset. If fault repeat, call Grundfos.
Status indicator 2 light flashing (under pressure) Controller read out "PLL" Step D1 Check the pressure reading on pressure gauge Pressure reading is higher than LL limit Pressure reading is lower than LL limit Step D2 Check the discharge pipe for major leakage Leakage detected No leakage detected
Reset. If fault repeat, call Grundfos. Go to step D2 Rectify the leakage Reset. If fault repeat, call Grundfos.
Status indicator 3 light flashing (pressure transmitter faulty) Controller read out "SEnF" Step E1 Check the pressure reading on pressure gauge Pressure reading is same as at controller Pressure reading is at 0 at the controller Step E2 Check the connection to the pressure transmitter Disconnected Connection correct
Reset. If fault repeat, call Grundfos. Go to step E2 Rectify the connection Reset. If fault repeat, call Grundfos.
Status indicator 4 light flashing (dry run protection) Controller read out "LSS" Step F1 Check the suction tank water level Water below electrode start level Water above electrode start level Step F2 Check the connection of the electrode Disconnected Connection correct
Auto reset when reach start level Go to step F2 Rectify the connection Reset. If fault repeat, call Grundfos.
Pump does not run when the pressure is lower than the setpoint in Auto Mode Step G1 Check the pressure reading on controller Pressure reading is lower than setpoint Pressure reading is higher than setpoint Step G2 Check the indicators at controller Status indicator light on/flashing Status indicator light not activated Settings incorrect Settings correct
Go to step B2 Go to step G2 Refer to light description and reset fault Go to step G3 Reset the settings at the controller Reset. If fault repeat, call Grundfos.
Pump does not run when emergency switch is activated Step H1 Check incoming power supply Power supply down Power supply on Step H2 Check control MCB OFF position ON position OFF position ON position OFF position ON position Activated Not activated
Rectify the source Go to step H2 Switch to ON position Go to step H3 Switch to ON position Go to step H4 Switch to ON position Go to step H5 Check outgoing motor cable Reset. If fault repeat, call Grundfos.
Pump start/stop too frequent or ESSF indicate at display Step I1 Check controller settings Settings incorrect Settings correct Step I2 Check tank precharge air (system off without pressure) Precharge air less than 70% of setpoint Precharge air at 70 to 80% of setpoint
Reset all settings Go to step I2 Check for leakage, and chrage air to 70% of setpoint Reset. If fault repeat, call Grundfos.
14
STANDARD SPECIFICATIONS
Ambient temperature: +5 to 45 deg.Celsius. Operating voltage: 3 X 380-440 V Operating frequency: 50-60 HZ Operating current: Depends on model Enclosure class: IP50 (Optional IP54 for weather proof upon requested) Motor starting: Direct on lin starting: 0.37 kW to 2.2kW Star/Delta starting: 3kW to 7.5kW Autotrans starting: 11kW and above. Please refer to Grundfos for optional forms of starting e.g soft staring, variable speed starting and etc. Material of panel: 1.5 mm Mild steel Colour of panel: Epoxy coat light grey as per Grundfos standard
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41