This symbol indicates the presence of dangerous voltage within and outside the product enclosure that may constitute a risk of electric shock, serious injury or death to persons if proper precautions are not followed.
Caution
This symbol alerts the user to the presence of hazards that may cause minor or moderate injury to persons, damage to property or damage to the device itself, if proper precautions are not followed.
Note
This symbol directs the users attention to important installation, operating and maintenance instructions.
Installation Considerations
Installation and maintenance of the ION 7500 / ION 7600 meter should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. The meter must be installed in accordance with all Local and National Electrical Codes.
DANGER
Failure to observe the following instructions may result in severe injury or death. During normal operation of the ION 7500 / ION 7600 meter, hazardous voltages are present on its terminal strips, and throughout the connected potential transformer (PT), current transformer (CT), digital (status) input, control power and external I/O circuits. PT and CT secondary circuits are capable of generating lethal voltages and currents with their primary circuit energized. Follow standard safety precautions while performing any installation or service work (i.e. removing PT fuses, shorting CT secondaries, etc). The terminal strips on the meter base should not be user-accessible after installation. Do not use digital output devices for primary protection functions. These include applications where the devices perform energy limiting functions or provide protection of people from injury. Do not use the ION 7500 / ION 7600 in situations where failure of the devices can cause injury or death, or cause sufficient energy to be released that can start a fire. The meter can be used for secondary protection functions. Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or communications terminals. Refer to the label on the ION 7500 / ION 7600 meter for the maximum voltage level the device can withstand.
CAUTION
Observe the following instructions, or permanent damage to the meter may occur.
The ION 7500 / ION 7600 meter offers a range of hardware options that affect input ratings. The ION 7500 / ION 7600 meters serial number label lists all equipped options. Applying current levels
incompatible with the current inputs will permanently damage the meter. This document provides installation instructions applicable to each hardware option. The ION 7500 / ION 7600 meters chassis ground must be properly connected to the switchgear earth ground for the noise and surge protection circuitry to function correctly. Failure to do so will void the warranty. Terminal screw torque: Barrier-type (current, voltage, and relay terminal screws: 1.35 Nm (1.00 ft-lbf) max. Captured-wire type (digital inputs/outputs, communications, power supply: 0.90 Nm (0.66 ft.lbf) max.
FCC Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
The Ringer Equivalence Number (REN) for the ION 7500 / ION 7600 optional internal modem is 0.6. Connection to the ION 7500 / ION 7600 internal modem should be made via an FCC Part 68 compliant telephone cord (not supplied). The ION 7500 / ION 7600 cannot be used on a public coin phone service or party line services.
Standards Compliance
CE: approved
Limitation of Liability
Power Measurement Ltd. (Power Measurement) reserves the right to make changes in the device or its specifications identified in this document without notice. Power Measurement advises customers to obtain the latest version of the device specifications before placing orders to verify that the information being relied upon by the customer is current. Regardless of whether any remedy set forth herein fails of its essential purpose, except to the extent the following limitation is prohibited by applicable law, Power Measurement shall not, in any event or under any legal claim or theory (whether based on contract, indemnity, warranty, tort (including negligence and strict liability) or otherwise), be liable to the original purchaser or any other person or entity for special, indirect, incidental, punitive, liquidated, special or consequential damages whatsoever with respect to any purchased product, including, without limitation, business interruption, loss of use, profit or revenue, even if Power Measurement has been advised of the possibility of such damages. To the extent that a limitation or exclusion of consequential damages are prohibited by applicable law, then Power Measurements liability shall be limited to twice the amount of the relevant purchased product. Not to limit the foregoing, a) Power Measurement shall not be liable for any claim (other than a claim solely for the breach of one of the above Warranties that is made in accordance with the above described procedures) made by the original purchaser, its employees, agents, or contractors for any loss, damage, or expense incurred due to, caused by, or related to any purchased product; and b) the above Warranties are the original purchaser's exclusive remedy and Power Measurement hereby expressly disclaims all other warranties, express or implied, including, without limitation, warranties of non-infringement and the implied warranties of merchantability and fitness for a particular purpose. These limited Warranties shall not apply to any product that has been subject to alteration, accident, misuse, abuse, neglect or failure to exactly follow Power Measurement's instructions for operation and maintenance. Any technical assistance provided by Power Measurement's personnel or representatives in system design shall be deemed to be a proposal and not a recommendation. The responsibility for determining the feasibility of such proposals rests with the original purchaser and should be tested by the original purchaser. It is the original purchasers responsibility to determine the suitability of any product and associated documentation for its purposes. The original purchaser acknowledges that 100% "up" time is not realizable because of possible hardware or software defects. The original purchaser recognizes that such defects and failures may cause inaccuracies or malfunctions. Only the terms expressed in these limited Warranties shall apply and no distributor, corporation or other entity, individual or employee of Power Measurement or any other entity is authorized to amend, modify or extend the Warranties in any way. The information contained in this document is believed to be accurate at the time of publication, however, Power Measurement assumes no responsibility for any errors which may appear here and reserves the right to make changes without notice. Power Measurement, ION, ION Enterprise, MeterM@il, WebMeter and smart energy everywhere are either registered trademarks or trademarks of Power Measurement. All other trademarks are property of their respective owners. Covered by one or more of the following patents: U.S. Patent No's 6792364, 6792337, 6751562, 6745138, 6737855, 6694270, 6671654, 6671635, 6687627, 6615147, 6611922, 6611773, 6563697, 6493644, 6397155, 6186842, 6185508, 6000034, 5995911, 5828576, 5736847, 5650936, D459259, D458863, D443541, D439535, D435471, D432934, D429655, D429533, D427533.
RMICAN Model
RMICAN-certified for revenue metering in Canada. RMICAN meters have different security options available (including a factory-sealed version), and can only be ordered with the 60 Hz system frequency option.
Available Options
Option
Form Factor
Integ. Display TRAN
Current Inputs
Standard (5 Amp) 1 Amp
COM
Standard (RS-232 and RS-485) Ethernet RJ45 Ethernet Fiber Modem
I/O
Standard (8 digital inputs, 3 Form C relays, 4 Form A outputs) Extra 8 digital inputs Four 0-1mA analog inputs Four 0-20 mA analog inputs Four -1 to 1mA analog outputs Four 0-20 mA analog outputs Same as ION 7500
Security
Standard1 RMANSI2
ION 7500
Model
Notes
1 2 3 4
Standard = password protected, no locking or sealing. RMANSI = ANSI C12.16 approved; meets ANSI C12.20 class 0.2 accuracy standards. Meets Industry Canada Locking Requirements. Meets Industry Canada Locking Requirements and Factory Sealed (only for delivery to Canada).
DANGER
Do not power up the meter until the current and voltage wiring is completed.
Recommended Tools
Phillips screwdriver Precision flat-head screwdriver Wire cutters / stripper
Meter Overview
Meter Front Meter Back
Voltage and Current Inputs
Digital Inputs
Analog Inputs
AI4 AI3 AI2
Analog Outputs
AI1 AO4 A03 A02 AO1
Softkeys
ESC
Button
DCD
TXD
TXD
RXD
COM CARD
IrDA Port
Power Supply
Communications Card
Ground Terminal
Operational LEDs
Navigation Buttons
PROG/SELECT
Button
Digital Inputs
PROG/SELECT: Press the PROG/SELECT (program or select) button to enter Setup mode. In Setup mode, press the PROG/SELECT button to accept changes. ESC:
ESC
Press the ESC (Escape) button to return to a higher menu or discontinue a configuration change.
NAVIGATION:
Press the UP / DOWN arrow buttons to highlight menu items, or increment / decrement numbers. Press the LEFT or RIGHT arrow buttons to move to an adjacent digit.
SOFTKEY: Press a SOFTKEY button to select the parameter that you want to configure from the sub-menus.
Unit Dimensions
Basic Model Rear View
59.0 mm [2.322] 31.9 mm [1.23] 18.3 mm [0.72] 11.1 mm [0.44] 14.2 mm [0.56] 43.9 mm [1.73] 110.4 mm [4.35] 80.9 mm [3.19] 43.3 mm [1.71]
192.0 mm [7.56]
81.1mm [3.19] 60.7 mm [2.39] 14.2 mm [0.56] 9.5 mm [0.38] 11.5 mm [0.45] 56.1 mm [2.21] 5.1 mm [0.20] 8.48 mm [0.33]
82.5 mm [3.25]
192.0 mm [7.56]
192.0 mm [7.56]
183.9 mm [7.24]
192.0 mm [7.56]
12.6 mm [0.50]
159.2 mm [6.27]
Bracket
CAUTION
Do not use metal door hinges as a grounding point.
R11 R12
R13
Type Contacts Wire Connector Voltage Rating Rated Load @ Rated Voltage Max. Voltage MOV Protection Max. Load @ Max. Voltage Turn-On Time Isolation Turn-Off Time Lifetime Update time
Form C (R1, R2, R3) NO, K, NC Use wiring that is appropriate for the application Ring or split ring connector 250 VAC / 30 VDC Resistive: 10 A (AC/DC) Inductive (PF=0.4): 7.5 A (AC) / 5 A (DC) 380 VAC / 125 VDC between K and NO/NC 300 V max. between NO and NC 3 A (AC) / 0.2 A (DC) 15 ms max. 5,000 VAC for 60 s 5 ms max. No load = 10,000,000 operations Rated voltage and load = 100,000 operations cycle or 1 s NO K NC
Meter
Alarm Lamp
Load
External Supply
Form A (D1, D2, D3, D4) 1.3 to 0.1 mm2 (16 to 28 AWG) Continuous or pulse 30 VDC 80 mA per channel Optically isolated; max. 5,000 V RMS isolation (UL-E91231) cycle or 1 s Meter
D3 D2 D1
Wire Signal Type Max. Load Voltage Max. Load Current Isolation
D1
DIGITAL OUTPUTS
D4 D3 D2 D1 - + - + - + - +
External Supply 30VDC max D4 output is factory-configured to pulse once every 1.8 Wh for Class 20 meters, or once every 0.18Wh for Class 2 meters (for calibration testing purposes).
9
External Relays
1.8 Wh
Scan Time
Digital Inputs: S1 - S8
DIGITAL INPUTS
S C O M S S 8 7 S 6 S S 5 4 S 3 S 2 S 1
Type Application Wire Min. Pulse Width Max. Pulse Rate Timing Resolution Updated Isolation to Ground Max. External Voltage
Self-excited (internal 30 VDC supply) Dry contact sensing, or with external excitation 1.3 to 0.1 mm2 (16 to 28 AWG) 1 ms 20 pulses per second 1 ms cycle (after timing resolution) max. 200 VDC for 10s 130 VDC continuous External Excitation Meter
_
S7
S7
S8
External Supply
DI8
External Supply
50 VDC max
10
DICOM
DICOM
Opticallycoupled switch
30 VDC
SCOM
Opticallycoupled switch
SCOM
DI8
30 VDC
30 VDC
+ +
+ +
+ +
_
_
S8
30 VDC
Opticallycoupled switch
Opticallycoupled switch
Captured wire connector 1.3 to 0.1 mm2 (16 to 28 AWG) DC current 0 to 20 mA (scalable 4-20 mA) or 0 to 1 mA 24 (0-20 mA option) or 475 (0-1 mA option) +/ 0.3% of full scale 1s 750 V max 400 k (channel/channel) Meter
+ AI1
AI3
Signal Type Available Options Input Impedance Accuracy Update Rate Isolation to Ground Isolation Impedance
AI4
AI3
AI2 AI1
mV
mA
Thermocoupler
Voltage-toCurrent Transducer
NOTE
Do not connect the analog inputs of the I/O card to the analog outputs on the same I/O card.
Captured wire connector 1.3 to 0.1 mm2 (16 to 28 AWG) DC current 0 to 20 mA (scalable 4-20 mA) or -1 to 1 mA (scalable 0-1 mA) 500 (0-20 mA option) or 10 k (-1 to 1 mA option) +/ 0.30% of full scale cycle or 1 s min. 1 cycle for measurement + cycle for ION + 1 s delay for hardware 750 V Meter
AO3
Analog Meter
OUT
AO1
COM
NOTE
Do not connect the analog outputs of the I/O card to the analog inputs on the same I/O card.
11
I51 I52
3~ VOLTAGE INPUTS
Voltage Inputs
Connector Type Wire Gauge Rated Inputs Fault Capture Overload Dielectric Withstand Input Impedance Ring or split ring connector 3.3 to 2.1 mm2 (12 to 14 AWG) 347 V L-N RMS /600 V L-L RMS 1400 V L-N peak 1500 VAC RMS continuous 2500 VAC RMS at 60 Hz for 60 s 5 M per phase
NOTE
The appropriate Volts Mode setting is included with each wiring diagram. Refer to Step 8 to learn how to configure Volts Mode on the meter.
12
LINE
347 V L-N / 600 V L-L max. VOLTS MODE = 4W-Wye
LOAD LOAD
Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source
LINE LINE
I4 Optional 2A 3A
V1
V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52
L / + N/-
Use PTs for voltages over 347 V L-N / 600 V L-L. Wye (Star) wiring for PT primaries and secondaries. VOLTS MODE = 4W-Wye
Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source
I4 Optional 2A 3A
V1
V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52
Phase B voltage (V2) displayed by meter is derived from phase A and phase C, not measured. V2 will display a value even if no voltage is present on Phase B. V2 values are only accurate for balanced loads. VOLTS MODE = 3W-Wye
LOAD
L / + N/-
13
Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source
When the common or star point of a 3-wire Wye system is grounded, the meter may be connected directly without using PTs, provided that the phase voltages are within the meters range. VOLTS MODE = 4W-Wye
LOAD
LINE LINE
2A
Do not connect
3A
V1
V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52
L / + N/-
Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source
LOAD
2A
3A
V1
V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52
L / + N/-
Use PTs for voltages over 600 V L-L. VOLTS MODE = Delta
14
Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source
LOAD
LINE
2A
3A
V1
V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52
L / + N/-
Use PTs for voltages over 600 V L-L VOLTS MODE = Delta
LINE
277 V L-N / 554 V L-L max. Use PTs for higher voltages. VOLTS MODE = Single
LOAD
15
DCE (computer)
2 3 4 5 6 7 8
2 3 4 5 6 7 8
DTE (meter)
Null modem cable pinout Pin 3 - Transmit Data - Pin 2 Pin 2 - Receive Data - Pin 3 Pin 7 - Request to Send- Pin 8 Pin 8 - Clear to Send- Pin 7 Pin 5 - Signal Ground- Pin 5 Pin 6 - Data Set Ready- Pin 4 Pin 4 - Data Terminal Ready- Pin 6
Connector Type Wire Maximum Cable Length Data Rate Isolation Duplex Compliance
DB9 female end for mating with male connector on the meter Null modem cable 15.2 m (50 ft) 300 115,200 bps Optical Full ANSI/IEEE C37.90-1989 surge withstand and fast transient tests
Connector Type Wire Maximum Cable Length Data Rate Maximum Devices (per bus) Isolation Duplex
Connect SH at one end only
Compliance
NOTE
IrDA port is located on front of meter
The IrDA port is multiplexed with the internal modem on the COM3 port. These ports cannot be used simultaneously.
16
Wire Type Connector Type Maximum Length Type Data Rate Isolation
High quality Category 3 or 5 unshielded twisted pair cable RJ45 modular 100 m (328 ft) IEEE 802.3 10Base-T for 10 Mbps base band CSMA/CD LANs 10 Mbps Transformer isolated to 1500 VAC/2250 VDC RMS
10Base-FL (Fiber)
Wire Type Connector Type Maximum Length Data Rate Isolation 62.5/125 micrometer multimode fiber optic cable ST 2000 m (6562 ft) 10 Mbps Optical
NOTE
ST type fiber cables
Connector Type Wire Type Data Rate Error Correction Data Compression
RJ11 FCC Part 68 compliant telephone cord (two male RJ11 ends) 300 bps 33.6 kbps V.42 LAPM, MNP 2-4, MNP 10 V.42 bis/MNP 5
17
G L+ N_
Use the PROG/SELECT, ESC, softkeys and arrow buttons to configure settings. The following example shows Volts Mode setup using the meter front panel.
Use arrow buttons to move up and down in list. Press PROG/SELECT to select Basic Setup.
Use arrow buttons to move up and down in list. Press PROG/SELECT to select PT/CT Setup.
Press Mode softkey. Use arrow buttons to move up and down in list. Press PROG/SELECT to select Delta.
18
The following table lists all settings that can be configured via the front panel. Menu Setting Description Range (Values) Default
VOLTS MODE
4W-WYE DELTA The power systems configuration 3W-WYE WYE, DELTA, etc. SINGLE DEMO The Potential Transformers primary 1 to 999,999.99 winding voltage rating The Potential Transformers secondary winding voltage rating The Current Transformers primary winding current rating The Current Transformers secondary winding current rating 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99
4W-WYE
120.00 120.00 5.00 5.00 120.00 120.00 5.00 5.00 5.00 5.00 Normal Normal Normal Normal Normal Normal Normal Normal Normal
The Potential Transformers primary 1 to 999,999.99 winding voltage rating on V4 The Potential Transformers secondary winding voltage rating on V4 The Current Transformers primary winding current rating on I4 The Current Transformers secondary winding current rating on I4 The Current Transformers primary winding current rating on I5 The Current Transformers secondary winding current rating on I5 The polarity of the Potential Transformer on Va The polarity of the Potential Transformer on Vb The polarity of the Potential Transformer on Vc The polarity of the Potential Transformer on V4 The polarity of the Current Transformer on Ia The polarity of the Current Transformer on Ib The polarity of the Current Transformer on Ic The polarity of the Current Transformer on I4 The polarity of the Current Transformer on I5 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99 Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted
BASIC SETUP
I5 PRIMARY I5 SECONDARY Va POLARITY Vb POLARITY Vc POLARITY V4 POLARITY Ia POLARITY Ib POLARITY Ic POLARITY I4 POLARITY I5 POLARITY
CURRENT PROBE The type of current probes being TYPE used with the meter
19
Menu
Setting
Description
Range (Values)
Default
PROTOCOL
COM1 SETUP
ION, Modbus RTU, Modbus Master, DNP V3.00, GPS:Truetime/Datum,GPS: ION Arbiter, GPS:Arbiter-Vorne, Factory, Ethergate, ModemGate 300, 1200, 2400, 4800, 9600, 9600 19200, 38400, 57600, 115200 0 to 1 0.010 From serial number1 RS232 RTS + DELAY
The data rate, in bits per second The transmit delay in seconds
Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number Hardware mode for port RS232 or RS485 RTS + DELAY or RTS/CTS
Specifies the handshake mode FLOW CONTROL when COM1 is set to RS232
COM2 SETUP
PROTOCOL
ION, Modbus RTU, Modbus Master, DNP V3.00, GPS:Truetime/Datum,GPS: ION Arbiter, GPS:Arbiter-Vorne, Factory, Ethergate, ModemGate 300, 1200, 2400, 4800, 9600, 9600 19200, 38400, 57600, 115200 0 to 1 0.010 101
The data rate, in bits per second The transmit delay in seconds
Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number ION, Modbus RTU, Modbus Master, DNP V3.00, GPS:Truetime/Datum,GPS: Arbiter, GPS:Arbiter-Vorne, Factory
PROTOCOL
ION
COM3 SETUP
BAUD RATE TRAN DELAY UNIT ID MODE ANSWER HR RINGS NON-ANSWER HR RINGS IP ADDRESS
The data rate, in bits per second The transmit delay in seconds
300, 1200, 2400, 4800, 9600, 9600 19200, 38400, 57600, 115200 0 to 1 0.010 102 Modem 1 5 none none none none
Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number The communications mode IRDA or Modem The number of rings during defined 0 to 255 answer hours The number of rings during defined 0 to 255 non-answer hours Sets the IP address for the meter Used if subnetting applies to your network Used in multiple network configurations Sets the address for the primary DNS Server that is configured to resolve domain names Sets the address for the secondary DNS Server that is configured to resolve domain names 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999
NETWORK SETUP
none
20
Menu
Setting
SWELL LIMIT
Description
Specifies the magnitude above which a power system input must rise for a swell to be recorded Specifies the magnitude below which a power system input must fall for a sag to be recorded
Range (Values)
100 to 1000
Default
106
SAG LIMIT
0 to 100
88
PQ SETUP
CHANGE CRITERIA NOMINAL VOLTAGE2 EVENT PRIORITY DIGIT GROUP VOLTS DECIMAL
Specifies the amount by which an input must change during a 0 to 100 disturbance to be considered a new sub-disturbance Specifies the nominal voltage of the 0 to 1,000,000 power system Assigns a priority level to sag/swell events Specifies symbols used to delimit thousands and decimal place holder Number of decimal places displayed for voltages Number of decimal places displayed for currents 0 to 255 1000.0 or 1,000.0 or 1000,0 1. to 123456789.XXX 1. to 123456789.XXX
10
0 200 1000.0 1.XX 1.XXX 1.XXX ABC LD/LG MM/DD/ YYYY Yes 1 5 300 +00:00 +00:00 COM1 UTC Line Freq
FORMAT SETUP
CURRNT DECIMAL POWER DECIMAL PHASE LABEL PF SYMBOL DATE FORMAT DISPLAY DST
Number of decimal places 1. to 123456789.XXX displayed for power measurements Specifies how phases are labelled LD (leading)/LG (lagging) Specifies how dates are displayed Specifies whether or not DST is displayed Sets when the display updates (in seconds) Higher numbers are sharper ABC, RST, XYZ, RYB, RWB, 123 LD/LG, +/-, CAP/IND MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD Yes or No 1 to 6 0 to 9
DISPLAY SETUP
Specifies when the displays dims (in 0 to 7200 (two hours) seconds) Sets the time zone of the meters location, relative to UTC - 12:00 to +13:00
Sets the daylight savings time offset -3:00 to +3:00 of the meters location Sets the port to receive time synchronization signals Specifies whether time sync signals are received in local time or UTC Ethernet, COM1, COM2, COM3 Local Time or UTC Line Freq, Internal or COMM Same format as specified in Date Format setting
TIME SETUP
CLOCK SOURCE Specifies time sync source LOCAL DATE LOCAL TIME Sets the local date Sets the local time
21
Menu
Setting
PASSWORD ENABLED WEB CONFIG WEB ACTIVE
1 2
Description
Sets the meter password Enables or disables security on the meter Enables or disables web browser configuration of the meter Enables or disables internal web server on the meter
Range (Values)
00000000 to 99999999 Yes or No Enabled or Disabled Yes or No
Default
00000000 No Enabled Yes
SECURITY SETUP
Serial number = PA-0302B222-01, Unit ID = 2222 NOMINAL VOLTAGE must be set to your systems nominal voltage to activate the meters power quality features.
Phasor Diagrams
DELTA phasors for UNITY Power Factor (resistive load)
Applicable Volts Mode = DELTA
VCA IC ABC Rotation IB ACB Rotation IA VAB VBC
VAB IB IA
IC VBC VCA
22
+kVAR
Reactive Power
Rotation IA VB IC IA Rotation VB IC
Rotation
VA
VA IB VB IA
IC
Reactive Power
Rotation
-kVAR
VB
IB
+kVAR
Reactive Power
Rotation IA VC IB IA IC Rotation VC IB
Rotation
VA
VA IC VC IA
IA VA
Rotation
Reactive Power
VA
-kVAR
IC VC
23
VAB IA IC VBC
+kVAR
Reactive Power
IA VBC
IA VAB
Reactive Power
VAB IB
-kVAR
IB VBC
+kVAR
Reactive Power
IB VAB
VAB IA IC
IA VCA VCA
Reactive Power
VAB
IB IC VCA
VAB
-kVAR
IB
24
Display Screens
Softkey V,I,PF Volts Amps Power Energy1 Demand1 Pk Dmd1 V Bar, I Bar, P Bar Summary1, Summary2 V-Trend, I-Trend, P-Trend D Inputs DI - I/O D-Output Anlg - I/O Phasors Name Plt Events Setpoint Energy2 Demand2 Pk Dmd2 THD V1 Harm, V2 Harm,... I1 Harm, I2 Harm,... TOU TOU Egy TOU Dmd1 & TOU Dmd2 Contents Volts, Amps, Power Factor Volts Amps Total Power Energy delivered Demand delivered Peak Demand delivered Voltage, Current and Power Bar Graphs Volts/Amps Summary, Power Summary Voltage, Current, Power Trends (ION 7500) Digital Inputs Digital I/O on expansion I/O card Digital Outputs Analog In and Out Phasors Nameplate information Events Setpoint Energy received Demand received Peak Demand received Volts and Amps Total Harmonic Distortion V1, V2, V3, V4 harmonics I1, I2, I3, I4, I5 harmonics Time Of Use Active Rate / Season TOU Energy delivered TOU Peak Demand 1 and 2
Additional display screens for the ION 7600: Softkey PQ Freq PQ Vmag1 PQ Vmag2 PQ Flk1 PQ Flk2 PQ Vdist PQ Vunb PQ Vhrm1 PQ Vhrm2 Avblty Contents Power Quality Power Frequency PQ Supply Voltage 1 PQ Supply Voltage 2 PQ Flicker 1 PQ Flicker 2 PQ Voltage Disturbance PQ Voltage Unbalance PQ Voltage Harmonics 1 PQ Voltage Harmonics 2 Power Availability