SM6 24 kV
Catalogue
2004
SM6 range 3 to 24 kV
Contents
2 3 4 5
SM6 range Field of application Units for all functions Operating conditions Main characteristics Factory-built cubicles description Compartments description Safety of people Telecontrol of power distribution networks A range of FPIs for underground networks Description of the control/monitoring and protection functions Characteristics of the functional units Functional units selection Automatic switching controls Operating mechanisms Auxiliaries Motor option and releases for Evolis circuit breakers Current transformers Voltage transformers Protection transformers Motors protection with CRM units Interlocks Connections Connections selection table Cable-connection from below
Cable-connection height Trenches depth Trench diagrams example
6 8 14 15 16 18 20 24 25 26
29 43 44 47 48 49 51 53 54 55
58 59
59 60 61
Installation Dimensions and weights Units dimensions Layout examples Protecting the environment A full range of services Appendices Trip curves for VIP 300 LL or LH relays Trip curves for VIP 200 and VIP 201 relays Trip curves for VIP 35 relays Fusarc CF fuses - Fuse and limitation curves Solefuse fuses - Fuse and limitation curves Order form
63 64 66 67 68
69 70 71 72 73 74
Appendices
Installation
Connections
SM6 range
Presentation
Presentation The experience of a world leader The ranges advantages The references of a leader Quality assurance
Presentation
The Schneider Electric groups experience extends over forty years in factory-built cubicles and over twenty five years in SF6 technology for Medium Voltage switchgear. This experience means that today Schneider Electric can propose a complementary range: DMV-A, DMV-D, DMV-S vacuum type circuit breaker cubicles and internal arc cubicles 16 kA.1 s to reinforced the safety of people. This gives you the advantage of unique experience, that of a world leader, with over half a million SF6 Medium Voltage units installed throughout the world. Putting this experience at your service and remaining attentive to your requirements is the spirit of active partnership that we want to develop in offering you the SM6 range. The modular SM6 range is a range of harmonised cubicles equipped with SF6 or vacuum air breaking technology switchgear. These cubicles allow you to produce all your Medium Voltage substation requirements up to 24 kV by superposing their various functions. The result of in-depth analysis of your requirements, both now and in the future, SM6 cubicles mean that you can take advantage of all the features of both a modern and proven technology.
MT20141
MT20140
1975: innovation Sulphur hexafluoride (SF6) is first used in an MV switch for an MV/LV transformer substation, with the VM6. 1989: experience Over 300,000 VM6 cubicles equipped networks throughout the world. 1991: innovation and experience Cumulated with the second generation of SM6 modular SF6 cubicles. 2003: a leading position b with over 600,000 SM6 cubicles installed around the world, Schneider Electric consolidates its position as uncontested leader in the Medium Voltage field. b development of the offer with the arrival of a range of vacuum type circuit breaker cubicles.
Presentation
SM6, a comprehensive range b a comprehensive offer covering your current and future requirements; b a design adapted to the extension of your installations; b a catalogue of functions for all your applications; b a product designed to be in compliance with standards constraints; b options to anticipate the telecontrol of your installations.
Compactness
MT20143
SM6, an optimised range b compact units, with low increment cubicles; b rationalised space requirement for switchboard installation; b reduction of civil works costs; b easy integration in factory-built outdoor substations for which the SM6 is particularly well designed.
Maintenance
MT20144
SM6, a range with reduced maintenance b the active parts (breaking and earthing) are integrated in an SF6-filled, sealed for life unit; b the control mechanisms, are intented to function with reduced maintenance under normal operating conditions; b enhanced electrical endurance when breaking.
Ease of installation
MT20145
SM6, a simple range to incorporate b reduced dimensions and weights; b only one civil works layout; b a solution adapted to cable connection; b simplified switchboard busbar design.
SM6, a proven range b a three position switch to block incorrect switching; b the earthing disconnector has full closing capacity; b positive breaking of position indicators; b internal arcing withstand in the cable and switchgear compartments; b clear and animated display diagrams; b switching lever with an anti-reflex function; b compartmented cubicles.
SM6 switchgear is perfectly adapted to telecontrol applications. Motorised, either when installed or at a later date on-site without any interruption in service, SM6 combines with the Easergy T200 remote control interface. You therefore benefit from a ready-to connect unit that is easy to incorporate providing guaranteed switchgear operation.
With the SM6, Schneider Electric proposes solutions for protection and energy management; the Sepam and VIP or relay ranges protect installations, providing continuity of electrical supply and reducing downtime.
Presentation
Upgradability
MT20142
Presentation
Asia/Middle East
b Pasteur Institute, Cambodia b Tian he City, China b Sanya Airport, China b Bank of China, Beijing, Jv Yanta, China b Jing Guang Hotel, JGH, China b Plaza Hotel, Jakarta, Indonesia b Bali Airport, Indonesia b Wakasa Control Center, Japan b Otaru Shopping center, Japan b New City of Muang, Thong Than, Kanjanapas, Thailand b Danang and Quinhon Airport, Vanad, Vietnam b British Embassy, Oman b KBF Palace Riyadh, Saudi Arabia b Raka Stadium, Saudi Arabia b Bilkent University, Turkey b TADCO, BABOIL development, United Arab Emirates
61001N
Africa
b ONAFEX, Hilton Hotel, Algeria b Yaounde University, Cameroon b Karoua Airport, Cameroon b Libreville Airport, Gabon b Ivarto Hospital, CORIF, Madagascar b Central Bank of Abuja, ADEFEMI, Nigeria b OCI Dakar, Oger international, CGE, Senegal b Bamburi cement Ltd, Kenya b Ivory Electricity Company, Ivory Coast
South America/Pacific
b Lamentin Airport, CCIM, Martinique b Space Centre, Kourou, Guyana b Mexico City Underground System, Mexico b Santiago Underground System, Chile b Cohiba Hotel, Havana, Cuba b Iberostar Hotel, Bavaro, Dominican Republic b Aluminio Argentino Saic SA, Argentina
Europe
b EDF, France b Eurotunnel, France b Futuroscope, Poitiers, France b Franois Mitterrand Library, France b Nestl company headquarters, France b Stade de France, Paris, France b Kronofrance, France b TLM Terminal , Folkestone, Great Britain b Zaventem Airport, Belgium b Krediebank Computer Centre, Belgium b Bucarest Pumping station, Rumania b Prague Airport, Czech Republic b Philipp Morris St Petersburg, Russia b Ligget Ducatt Tobacco Factory, Russia b Kremlin Moscow, Russia b Allibert Tarazona, Spain
Presentation
Quality assurance
Quality certified to ISO 9001
Schneider Electric has integrated a functional organisation into each of its units. The main mission of this organisation is to check the quality and the compliance with standards. This procedure is: b uniform throughout all departments; b recognised by many customers and approved organisations. But it is above all its strict application that has enabled recognition to be obtained by an independent organisation: The French Quality Assurance Association (FQAA). The quality system for the design and manufacture of SM6 units has been certified in conformity with the requirements of the ISO 9001: 2000 quality assurance model.
MT55054
MT55055
ISO
900 1
ISO
9002
During manufacture, each SM6 is subject to systematic routine testing which aims to check the quality and conformity: b sealing testing; b filling pressure testing; b opening and closing rate testing; b switching torque measurement; b dielectric testing; b conformity with drawings and plans. The results obtained are written and reported on the test certificate for each device by the quality control department. The environmental management system adopted by Schneider Electric production sites that produce the SM6 have been assessed and judged to be in conformity with requirements in the ISO 14001 standard.
61003N
MT55145
01 ISO 140
Presentation
A major advantage
SM6 range
Field of application
The SM6 range is made up of modular units containing fixed or withdrawable metal-enclosed SF6 switchgear, using sulphur hexafluoride (SF6) or vacuum: b switch-disconnector; b SF1, SFset or Evolis circuit breaker; b Rollarc 400 or 400 D contactor; b disconnector. SM6 units are used for the MV section in MV/LV transformer substations in public distribution systems and MV consumer or distribution substations up to 24 kV.
UTE standard
MV consumer substation (MV metering) IM IM CM DM2 QM PM IM
Substation GAM QM
Unit definitions
Below is the list of SM6 range units used in MV/LV transformer substations and industrial distribution substations: b IM, IMC, IMB switch; b PM fused switch; b QM, QMC, QMB fuse-switch combination; b CRM contactor and contactor with fuses; b DM1-A, DM1-D, DM1-S single-isolation SF6 type circuit breaker; b DMV-A, DMV-D, DMV-S single-isolation vacuum type circuit breaker; b DM1-W, DM1-Z withdrawable single-isolation SF6 type circuit breaker; b DM2 double-isolation SF6 type circuit breaker; b CM, CM2 voltage transformers; b GBC-A, GBC-B current and/or voltage measurements; b NSM-cables for main incoming and standby; b NSM-busbars for main incoming and cables for standby; b GIM intermediate bus unit; b GEM extension unit; b GBM connection unit; b GAM2, GAM incoming cable connection unit; b SM disconnector; b TM MV/LV transformer unit for auxiliaries; b other units, consult us; b special function EMB busbar earthing.
Other standards
MV consumer substations (MV metering) IM IM DM1-D GBC-A QM DM1-S
outgoing line toward other ring substations incoming line of the main distribution switchboard
SM6 range
Field of application
SM6 range
SM6 range
29
Switch unit with or without earthing disconnector right or left outgoing line IMB (375 mm)
Fuse-switch protection
DE55806 DE55807 DE55808
30
Fuse-switch combination unit right or left outgoing line QMB (375 mm)
31
DE55809
SM6 range
Contactor protection
page
DE55810 DE55811
32
33
Single-isolation circuit breaker unit right or left outgoing line DM1-D (750 mm)
DE55814
34
Single-isolation circuit breaker unit with autonomous protection DM1-S (750 mm)
DE55815
Double-isolation circuit breaker unit right or left outgoing line DM2 (750 mm)
SM6 range
SM6 range
35
Withdrawable single-isolation circuit breaker unit right outgoing line DM1-Z (750 mm)
36
Single-isolation circuit breaker unit right outgoing line DMV-D (625 mm)
36
DE55820
Single-isolation circuit breaker unit with autonomous protection DMV-S (625 mm)
10
SM6 range
MV metering
page
DE55821 DE55822
37
Voltage transformers for mains with earthed neutral system CM (375 mm)
Voltage transformers for mains with insulated neutral system CM2 (500 mm)
DE55823
38
Current and/or voltage measurement unit right or left outgoing line GBC-A (750 mm)
DE55824
11
SM6 range
SM6 range
Casings
page
DE55825 DE55825 DE55826
39
DE55827
40
DE55828
12
SM6 range
Other functions
page
DE55829 DE55830 DE55831
41
DE55832
42
Cables power supply for main incoming line and standby line NSM-cables (750 mm)
DE55833
Busbars power supply for main incoming line on right or left and cables for standby line NSM-busbars (750 mm)
13
SM6 range
SM6 range
Operating conditions
In addition to its technical characteristics, SM6 meets requirements concerning protection of life and property as well as ease of installation, operation and protecting the environment.
61000N
SM6 units are designed for indoor installations (IP2XC). Their compact dimensions are: b 375 mm to 750 mm wide; b 1600 mm high; b 840 mm deep this makes for easy installation in small rooms or prefabricated substations. Cables are connected via the front. All control functions are centralised on a front plate, thus simplifying operation. The units may be equipped with a number of accessories (relays, toroids, instrument transformers, surge arrestor, telecontrol, etc.).
Standards
SM6 units meet all the following recommendations, standards and specifications: b recommendations IEC: 60694: Common specifications for high-voltage switchgear and controlgear standards. 60271-200: A.C. metal-enclosed switchgear and controlgear for rated voltage above 1kV and up to including 52 kV. 60265: High voltage switches for rated voltages of 52 kV and above. 60420: High voltage alternating current switch-fuse combinations. 60255: Electrical relays. 62271-100: High-voltage alternating current circuit breakers. 62271-102: High-voltage alternating current disconnectors and earthing switches. b UTE standards: NFC 13.100: Consumer substation installed inside a building and fed by a second category voltage public distribution system. NFC 13.200: High voltage electrical installations requirements. NFC 64.130: High voltage switches for rated voltage above 1kV and less than 52 kV. NFC 64.160: Alternating current disconnectors and earthing switches. b EDF specifications: HN 64-S-41: A.C. metal-enclosed swichgear and controlgear for rated voltages above 1kV and up to and including 24 kV. HN 64-S-43: Electrical independent-operating mechanism for switch 24 kV - 400 A.
Designation
SM6 units are identified by a code including: b an indication of the function, i.e. the electrical diagram code: IM, QM, DM1, CM, DM2, etc. b the rated current: 400 - 630 - 1250 A; b the rated voltage: 7.2 - 12 - 17.5 - 24 kV; b the maximum short-time withstand current values: 12.5 - 16 - 20 - 25 kA.1 s; b the colour is of RAL 9002 type (frosted satin white). Example for a unit designated: IM 400 - 24 - 12.5 b IM indicates an incoming or outgoing unit; b 400 indicates the rated current is 400 A; b 24 indicates the rated voltage is 24 kV; b 12.5 indicates the short-time withstand current is 12.5 kA.1 s.
14
SM6 range
Main characteristics
The hereunder values are for working temperatures from -5C up to +40C and for a setting up at an altitude below 1000 m.
Rated voltage (kV) Insulation level 50 Hz, 1 mn insulation (kV rms) isolation 1.2/50 s insulation (kV peak) isolation Breaking capacity transformer off load (A) cables off load (A) short-time withstand current (kA.1 s)
7.2 20 23 60 70
12 28 32 75* 85
17.5 38 45 95 110
24 50 60 125 145
61005N
The making capacity is equal to 2.5 times the short-time withstand current. * 60 kV peak for the CRM unit.
General characteristics
Maximum breaking capacity Rated voltage (kV) Units IM, IMC, IMB, NSM-cables, NSM-busbars PM, QM, QMC, QMB CRM CRM with fuses SF6 circuit breaker range: DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 vacuum circuit breaker range: DMV-A, DMV-D, DMV-S
* in 800 A consult us.
7.2
12
17.5
24
630 A - 800 A* 25 kA 10 kA 25 kA 25 kA 20 kA 8 kA
Internal arc withstand: b standard:12.5 kA. 0.7 s; b enhanced:16 kA. 1 s. Protection index: b units: IP2XC (IP3X consult us); b between compartments: IP2x.
20 kA
25 kA
20 kA
Endurance
Units IM, IMC, IMB, PM, QM*, QMC*, QMB*, NSM-cables, NSM-busbars CRM Disconnector Electro-magnetic compatibility: b relays: 4 kV withstand capacity, as per recommendation IEC 60801.4; b compartments: v electrical field: - 40 dB attenuation at 100 MHz, - 20 dB attenuation at 200 MHz; v magnetic field: 20 dB attenuation below 30 MHz. Temperatures: The cubicles must be stored in a dry area free from dust and with limited temperature variations. b for stocking: from 40C to +70C, b for working: from 5C to +40C, b other temperatures, consult us. Rollarc 400 mechanical endurance IEC 60265 1000 operations class M1 IEC 62271-102 1000 operations IEC 62470 300 000 operations 100 000 operations IEC 62271-102 1000 operations IEC 62271-100 10 000 operations electrical endurance IEC 60265 100 breaks at In, p.f. = 0.7 class E3
Rollarc 400D SF6 circuit breaker range: DM1-A, Disconnector DM1-D, DM1-W, Circuit breaker SF DM1-Z, DM1-S, DM2 vacuum circuit breaker range: DMV-A, Disconnector DMV-D, Circuit breaker DMV-S Evolis
IEC 62470 100 000 breaks at 320 A 300 000 breaks at 250 A 100 000 breaks at 200 A
* as per recommendation IEC 60420, three breakings at p.f. = 0.2 b 1730 A under 12 kV, b 1400 A under 24 kV, b 2600 A under 5.5 kV.
15
SM6 range
16 31.5 25 630 - 1250 A 630 - 1250 A 20 16 630 - 1250 A 12.5 400 - 630 - 1250 A
SM6 range
2 1 5 4
1 switchgear: switch-disconnector and earthing switch in an enclosure filled with SF6 and satisfying sealed pressure system requirements. 2 busbars: all in the same horizontal plane, thus enabling later switchboard extensions and connection to existing equipment. 3 connection: accessible through front, connection to the lower switch-disconnector
and earthing switch terminals (IM cubicles) or the lower fuse-holders (PM and QM cubicles). This compartment is also equipped with an earthing switch downstream from the MV fuses for the protection units.
5 low voltage: installation of a terminal block (if motor option installed), LV fuses and compact relay devices. If more space is required, an additional enclosure may be added on top of the cubicle.
Optional, switch cubicles (IM) can also be fitted with: b control motorisation; b surge arrestors.
2 1 5
2 busbars: all in the same horizontal plane, thus enabling later switchboard extensions and connection to existing equipment. 3 connection and switchgear: accessible through front, connection to the downstream
terminals of the circuit breaker. Two circuit breaker offers are possible: b SF1: combined with an electronic relay and standard sensors (with or without an auxiliary power supply; b SFset: autonomous set equipped with an electronic protection system and special sensors (requiring no auxiliary power supply).
4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (Statimax) and test terminal boxes. If more space is required, an additional enclosure may be added on top of the cubicle.
Optional, cubicles may be fitted with: b current and voltage transformers; b circuit breaker control motorisation; b surge arrestors.
16
SM6 range
1 switchgear: disconnector(s) and earthing switch(es), in enclosure filled with SF6 and satisfying and one vacuum circuit breaker, sealed pressure system requirements. 2 1 5 4 2 busbars: all in the same horizontal plane, thus enabling later switchboard extensions and connection to existing equipment. 3 connection and switchgear: accessible through front, connection to the downstream terminals of the circuit breaker. b Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source); 4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes. If more space is required, an additional enclosure may be added on top of the cubicle.
Optional, cubicles may be fitted with: b current and voltage transformers; b circuit breaker control motorisation; b surge arrestors.
Contactor cubicles
61056N
1 switchgear: disconnector and earthing switch and contactor in enclosures filled with SF6 and satisfying sealed pressure system requirements. 2 1 5 2 busbars: all in the same horizontal plane, thus enabling later switchboard extensions and connection to existing equipment. 3 connection and switchgear: accessible through front.
This compartment is also equipped with an earthing switch downstream. The Rollarc contactor may be equipped with fuses. Two types may be used: b R400 with magnetic holding; b R400D with mechanical latching.
4 operating mechanism: contains the elements used to operate the disconnector(s), the contactor 400 or 400D and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices and test terminal boxes. With basic equipment, an additional enclosure is added on top of the cubicle.
Optional, cubicles may be fitted with current and voltage transformers.
17
SM6 range
SM6 range
Compartments description
Switchgear compartment
This compartment is separated from the busbar compartment and the connection compartment by the enclosure surrounding the switch, the disconnector and the earthing switch.
DE55834 61006N
Busbar compartment
The three insulated busbars are parallel-mounted. Connection is made to the upper pads of the enclosure using a field distributor with integrated captive screws. Ratings 400 - 630 - 1250 A.
DE55835 61007N
DE55837
18
SM6 range
Compartments description
Operating-mechanism compartments
These compartments contain the various operating functions for the: b switch and earthing switch; b disconnector(s); b circuit breaker; b contactor; and the voltage indicators. The operating-mechanism compartment may be accessed with the cables and busbars energised and without isolating the substation. It also enables easy installation of padlocks, locks and standard LV accessories (auxiliary contacts, trip units, motors, etc.).
DE55838 61008N
DE55839
C B A
C - Housing h = 2050 mm
In all cases, these volumes are accessible, with cables and busbars energised, without de-energising the substation.
19
SM6 range
SM6 range
Safety of people
By switchgear
Switch-disconnector
Contacts closed
Contacts open
Contacts earthed
Rollarc contactor
Contacts closed
Arcing period
Contacts open
20
SM6 range
Safety of people
By switchgear
Contacts closed
Precompression
Arcing period
Contacts open
21
SM6 range
SM6 range
Safety of people
By operating mechanism safety
22
SM6 range
Safety of people
By internal arc protection
Standard IEC 60271-200 appendix AA indicates a method for testing switchgear in metal enclosures under internal arcing conditions. The aim of this test is to show that an operator present in front of a switchboard would be protected against the effects of an internal fault.
To enhance the safety of people, it is desirable to provide as high a degree of protection as possible by evacuating the effects of internal arcing using: b evacuation systems which direct gases towards the top or the bottom of the switchboard enabling over pressure to be limited in the case of an internal fault in the compartments; b channelling and evacuating hot gases towards an external area, which is not hazardous for the operator; b materials which are non-inflammable for the cubicle; b reinforced panels.
Case of an SM6 switchboard installed against the wall upwards exhaust: 3-sides internal arc protection
DE55554
SM6 internal arc (in conformity with IEC 60271-200 appendix AA)
In its internal arc version, the SM6 range has successfully passed all of the type testing relative to standard IEC 60271-200 (6 acceptance criteria). The materials used meet the constraints for which the SM6 is designed. The thermal and mechanical forces that an internal arc can produce are perfectly absorbed by the enclosure. An operator present in the front of the SM6 switchboard during an internal fault will not be exposed to the effects of arcing.
Case of an SM6 switchboard installed in the middle of a room downwards exhaust: 4-sides internal arc protection
Choice of exhaust
The choice depends on the civil engineering: b Upwards exhaust: A ceiling height greater than 2200 mm is necessary. b Downwards exhaust: Civil engineering with an adequate volume is necessary.
23
SM6 range
DE55553
SM6 range
SM6 switchgear is perfectly suited to a telecontrol environment due to options such as: b Easergy T200 S telecontrol interface; b independent power supply of electrical controls; b auxiliary contacts for position and fault signalling; b current sensors for fault detection.
61015N
T200 S
b Easergy T200 S is installed inside the low voltage control cabinet of an IM and NSM SM6 for the telecontrol of one or two switches. b For switchboards up to 16 switches, the wall mounted version Easergy T200 I could be installed in the substation, and it is directly connected to the switches without any interface and converters. b It has a simple facia layout for local operation, allowing local control (local/remote) and enables visualisation of switchgear status. b It integrates a fault current detector (overcurrent and zero sequence) with detection thresholds that are configurable per channel (threshold and fault duration).
T200 I
PE150078
Control command
Local information
Power unit
PE150079
61017N
61018N
61020N
24
SM6 range
The Easergy earth fault current indicator range, the largest in the market, covers all MV network types. Merlin Gerin offers ammetric fault detectors for neutral impedant system and direct earthing distribution networks and for insulated and compensated neutral distribution networks.
Usage
Bright outdoor
61022N
All of the indicators offer multiphased (overload) fault and earth fault detection. For MV/LV substations 230 Vac powers the indicators. In MV/MV substations a lithium battery powers the indicators.
Equipped with microprocessors, they offer a broad range of corresponding controls for the majority of the protection plans and operating modes. A dry contact allows connection to a telecontrol system.
Characteristics
b Microswitch adjustment, b Overload current threshold, b Earth fault threshold, b Time to take the fault into account, b Reset delay, b Inrush, b Integrated and external warning light, b SCADA contact, b Phased current measurement by opening core, b Unbalanced current measurement by mean of 3 phase CTs or 1 zero-sequence split core CT.
MV/LV substation
MT20183EN
MV/LV substation
MV/LV substation
Flashing
Not flashing
25
SM6 range
Advantages
SM6 range
The Sepam range of protection and metering is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations for all levels of voltage. It consists of complete, simple and reliable solutions, suited to following 3 families: b Sepam series 20, b Sepam series 40, b Sepam series 80.
PE20081
Simplicity
Easy to install b Light, compact base unit. b Optional modules fitted on a DIN rail, connected using prefabricated cords. b User friendly and powerful PC parameter and protection setting software to utilize all of Sepams possibilities. User-friendly b Intuitive User Machine Interface, with direct data access. b Local operating data in the users language.
Sepam
Characteristics Basic
Protections
Applications
Transformer
Specific Substation
generator
Rotation
S20
T20
b 10 logic inputs b 8 relay outputs b 1 Modbus communication port b Logic equations editor
Current voltage and frequency protection Directional earth fault Directional earth fault and phase overcurrent
S40
T40
G40
M41
b 42 logic inputs and 23 relay Current voltage and frequency outputs protection b 2 Modbus communication Directional earth fault port b Logic equations editor Directional earth fault and b Removal memory cartridge phase overcurrent b Battery to save event logging data
M81 G82
26
Busbars
SM6 range
VIP 35
VIP 300 LL
PE55650
27
SM6 range
SM6 range
Statimax
General protection of MV consumer substations (MV metering). Statimax ensures, without an auxiliary source, against phase and zero-sequence faults. Statimax is made up of an electronic setting device, three toroid voltage-matching transformers, a zero-sequence transformer and a regulation device that supplies the power for the electronics and the low-energy Mitop release.
Statimax
Selection table
Protection type Protection units Sepam 2000 series 20 b b 50 - 51 50N - 51N b b 67N b 27 b b 59 49 b b 59N b 46 b b b b 51LR 66 b b 37 b b Code series 40 b b b b b b b b b b b Statimax series 80 b b b b b b b b b b b b b VIP 35 b (2) b (3) 200 b (1) b (1) 300 b(1) b (1)
Three-phase overcurrent Zero-sequence overcurrent Directional zero-sequence current Undervoltage Overvoltage Thermal image Zero-sequence overvoltage Negative sequence overcurrent Long start-up and rotor blocking Maximum number of start-ups Single-phase undercurrent
(1) DT, EI, SI, VI and RI trip curves. (2) Inverse curve suited to transformer protection. (3) DT trip curve.
28
IMB (375 mm) Switch with earthing switch Right or left outgoing
DE55843 DE55844
DE55841
Electrical characteristics
kA
DE55891
DE55842
25
20 630 A 16
12.5 7.2
Basic equipment:
b switch and earthing switch b three-phase busbars b CIT operating mechanism b voltage indicators b connection pads for dry-type cables b one to three CTs b three-phase bottom busbars for outgoing lines (right or left)
Versions:
b CI2 operating mechanism b CI1 operating mechanism b 630 A or 1250 A three-phase busbars b in 800 A version consult us
Optional accessories:
b motor for operating mechanism b auxiliary contacts b additional enclosure or connection enclosure for cabling from above b key-type interlocks b 50 W heating element b stands footing b release units b phase comparator b fault indicators b surge arrestors (for 500 mm cubicle)
29
QMB (750 mm) Fuse-switch combination unit Outgoing line right or left
DE55848
DE55846
Electrical characteristics
kA
DE55892
25
20 200 A 16
Basic equipment:
b switch and earthing switch b three-phase busbars b CI1 operating mechanism b voltage indicators b equipment for three UTE or DIN striker fuses b mechanical indication system for blown fuses b connection pads for dry-type cables b downstream earthing switch b one to three CTs b three-phase bottom busbars for outgoing lines (right or left)
Versions:
b 630 A or 1250 A three-phase busbars b CI2 operating mechanism
Optional accessories:
b motor for operating mechanism b auxiliary contacts b additional enclosure or connection enclosure for cabling from above b key-type interlocks b 50 W heating element b stands footing b indication contact for blown fuses b UTE or DIN striker fuses b release units
30
DE55847
DE55850
Electrical characteristics
kA 25
20 200 A 16
Basic equipment:
b switch and earthing switch b three-phase busbars b CIT operating mechanism b voltage indicators b connection pads for dry-type cables b downstream earthing switch b equipment for three UTE or DIN fuses
Versions:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b motor for operating mechanism b auxiliary contacts b enlarged low-voltage control cabinet b additional enclosure or connection enclosure for cabling from above b key-type interlocks b 50 W heating element b stands footing b mechanical indication system for blown fuses b UTE or DIN fuses
31
DE55892
DE55851
Electrical characteristics
kA
DE55893 DE55894
DE55852
kA 25
10 8 400 A
20 250 A 16
Basic equipment:
b Rollarc 400 or 400D contactor b disconnector and earthing switch b three-phase busbars b contactor operating mechanism R400 with magnetic holding or contactor R400D with mechanical latching b disconnector operating mechanism CS b one to three current transformers b auxiliary contacts on contactor b connection pads for dry-type cables b voltage indicators b downstream earthing switch b additional enclosure b operation counter b equipment for three DIN fuses
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle: v auxiliary contacts on the disconnector v protection using Sepam programmable electronic unit v one to three voltage transformers v key-type interlocks v 50 W heating element v stands footing b contactor: v mechanical interlocking b DIN fuses
32
DE55856
Electrical characteristics
kA
DE55895
25
20 630 - 1250 A 16
12.5 7.2
Basic equipment:
b SF1or SFset circuit breaker (only for the 400-630 A performances) b disconnector and earthing switch b three-phase busbars b circuit breaker operating mechanism RI b disconnector operating mechanism CS b voltage indicators b three CTs for SF1 circuit breaker b auxiliary contacts on circuit breaker b connection pads for dry-type cables b downstream earthing switch b three-phase bottom busbars
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle: v auxiliary contacts on the disconnector v additional enclosure or connection enclosure for cabling from above v protection using Statimax relays, or Sepam programable electronic unit for SF1 circuit breaker v three voltage transformers for SF1 circuit breaker v key-type interlocks v 50 W heating element v stands footing v surge arrestors b circuit breaker: v motor for operating mechanism v release units v operation counter on manual operating mechanism
33
Electrical characteristics
kA
DE55891
25
20 630 A 16
12.5 7.2
Basic equipment:
b SF1 circuit breaker b disconnector and earthing switch b three-phase busbars b circuit breaker operating mechanism RI b disconnector operating mechanism CS b auxiliary contacts on circuit breaker b VIP relay protection b three CR sensors for VIP relay protection b voltage indicators b connection pads for dry-type cables b downstream earthing switch b three CTs
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle: v auxiliary contacts on disconnectors v additional enclosure or connection enclosure for cabling from above v three voltage transformers v key-type interlocks v 50 W heating element v stands footing b circuit breaker: v motor for operating mechanism v release units v operation counter on manual operating mechanism
34
DM1-Z (750 mm) Withdrawable single-isolation circuit breaker Outgoing line on right
DE55863
DE55862
Electrical characteristics
kA
DE55895 DE55896
kA 25
25
20 630 - 1250 A 16
20 1250 A 16
12.5 7.2
Basic equipment:
b SF1 circuit breaker b disconnector and earthing switch b three-phase busbars b circuit breaker operating mechanism RI b disconnector operating mechanism CS b voltage indicators b three CTs b auxiliary contacts on circuit breaker b earthing switch operating mechanism CC b connection pads for dry-type cables b downstream earthing switch b three-phase busbars
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle: v auxiliary contacts on the disconnector v additional enclosure or connection enclosure for cabling from above v protection using Statimax relays or Sepam programable electronic unit v three voltage transformers v key-type interlocks v 50 W heating element v stands footing v withdrawable circuit breaker cradle v surge arrestors b circuit breaker: v motor for operating mechanism v release units v operation counter on manual operating mechanism
35
DE55865
Electrical characteristics
kA
DE55898
kA
DE55899
25
25
20 630 1250 A
20 630 A 16
16
12.5
12.5
Basic equipment:
b Evolis circuit breaker b disconnector and earthing switch for 400 - 630 A b disconnector and earthing switch for 1250 A b three-phase busbars b circuit breaker operating mechanism Proxima b disconnector operating mechanism CIT b voltage indicators b auxiliary contacts on circuit breaker b three CTs b Sepam programmable electronic unit b connection pads for dry-type cables b downstream earthing switch b 3 Cr sensors for VIP relay protection b protection by VIP relays
Version:
b 630 A or 1250 A three-phase busbars b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle: v auxiliary contacts on the disconnector v additional enclosure or connection enclosure for cabling from above v three voltage transformers v key-type interlocks v stands footing b circuit breaker: v motor for operating mechanism v release units v operation counter on manual operating mechanism
36
CM (375 mm) Voltage transformers for mains with earthed neutral system
DE55870 DE55871
CM2 (500 mm) Voltage transformers for mains with insulated neutral system
Electrical characteristics
kA
DE55890
25
20 50 A 16
Basic equipment:
b disconnector and earthing switch b three-phase busbars b operating mechanism CS b LV circuit isolation switch b LV fuses b three 6.3 A UTE or DIN type fuses b three-voltage transformers (phase-to-earth) b two voltage transformers (phase-to-phase)
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b auxiliary contacts b additional enclosure or connection enclosure for cabling from above b 50 W heating element b stands footing b indication contact for blown fuses
37
GBC-A (750 mm) Current and/or voltage measurements Outgoing line on right
DE55873 DE55874
GBC-A (750 mm) Current and/or voltage measurements Outgoing line on left
DE55875
Electrical characteristics
kA
DE55895
25
20 630 - 1250 A 16
12.5 7.2
Basic equipment:
b one to three CTs b connection bars b three-phase busbars
Optional accessories:
b additional enclosure b three voltage transformers (phase-to-earth), or two voltage transformers (phase-to-phase) b stands footing
38
DE55876
DE55876
Electrical characteristics
kA
DE55891 DE55895
DE55877
kA 25
25
20 630 A 16
20 630 - 1250 A 16
12.5 7.2
12.5 7.2
Basic equipment:
b three-phase busbars b three-phase busbars b connection bars b three-phase busbars for outgoing lines right or left
Optional accessories:
b stands footing b additional enclosure
39
DE55878
Electrical characteristics
kA
DE55891
DE55879
kA
DE55895
25
25
20 630 A 16
20 630 - 1250 A 16
12.5 7.2
12.5 7.2
Basic equipment:
b three-phase busbars b voltage indicators b connection pads for dry-type cables b connection bars b operating mechanism CC b earthing switch
Optional accessories:
b enlarged low-voltage control cabinet b stands footing b 50 W heating element b auxiliary contacts b surge arrestors b key-type interlocks
40
DE55880
DE55881
Electrical characteristics
kA
DE55895 DE55890
DE55882
kA
DE55891
kA 25
25
25
20 630 - 1250 A 16
20 50 A 16
20 630 A 16
12.5 7.2
12.5 7.2
Basic equipment:
b disconnector and earthing switch b three-phase busbars b operating mechanism CS b connection pads for dry-type cables b voltage indicators b two 6.3 A fuses, UTE or DIN type b LV circuit isolating switch b one voltage transformer (phase-to-phase) b disconnector and earthing switch b connection bars b operating mechanism CIT b installation on 630 A IM 375 mm or DM1-A units (except additional enclosure or connection enclosure for cabling from above) b require an key-type interlocks adapted to the switchboard network
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b auxiliary contacts b additional enclosure b key-type interlocks b stands footing b 50 W heating element b connection enclosure for cabling from above b mechanical indication system for blown fuses b connection enclosure for cabling from above b auxiliary contacts
41
NSM-cables (750 mm) Cables power supply for main incoming line (N) and standby line (S)
NSM-busbars (750 mm) Busbars power supply for main incoming line on right and cables (N) for standby line (S)
DE55884 DE55885
NSM-busbars (750 mm) Busbars power supply for main incoming line on left and cables (N) for standby line (S)
DE55883
Electrical characteristics
kA
DE55891
25
20 630 A 16
12.5 7.2
Basic equipment:
b switches and earthing switches b three-phase busbars b connection pads for dry-type cables b voltage indicators b mechanical interlocking b motorised operating mechanism CI2 with shunt trips b additional enclosure b automatic-control equipment
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b auxiliary contacts b key-type interlocks b 50 W heating element b stands footing b telecontrol
42
NSM-type SM6 cubicles include an automatic switching control installed in the low voltage control cabinet. There is both an automatic control for network switching and an automatic control for the back-up generator switching. Both of these automatic controls are based on the Easergy T200 S interface range and can consequently be optionally equipped with remote control functions. The system includes voltage presence detectors, fault current detectors, a back-up power supply and a local operation interface.
Ua
Network switch
b Setting of time delay before switching: 0.1s to 2 s (T1) b Setting the time delay for return to the initial state: 5 s to 120 s (T2).
t Us Us t
t U T1 tr U T2
t tr
Fig. 2
Fig. 3
Ua
MT20251
Ua
t Us Us
t U T1 T2 tr U tr T3
t T4
Fig. 4
Fig. 5
43
Operating mechanisms
The control devices required for the unit operating mechanisms are centralised on the front panel. The different types of operating mechanism are presented in the table opposite. Operating speeds do not depend on the operator, except for the CS. For the interlocks, consult the table pages 53/54 according to concerned cubicles.
Type of operating mechanism switch/disconnector circuit breaker CIT CI1 CI2 CS CC RI Proxima IM, IMB, IMC b v v PM b QM, QMC, QMB b v CM, CM2, CRM b DM1-A, DM1-D, DM1-S, DM1-Z, DM2 b b DM1-A(*), DM1-W b b b DMV-A, DMV-D, DMV-S b b NSM-cables, NSM-busbars b GAM b SM, TM b EMB b
b provided as standard v other possibility (*) 1250 A version
Units
44
Operating mechanisms
Operating mechanisms
61034N
SFset combinations 1 2 3 b b b b
61035N
46
Auxiliaries
The operating mechanisms CIT, CI1 and CI2 may be motorised. Un power supply Motor option DC 24 200 1 to 2 (s) 4 to 7 (s) 200 1 to 2 (s) 4 to 7 (s) AC (50 Hz)* 120 230
48
110
125
220
arming time CIT or for working CI1, CI2 Opening releases shunt trip (W) (VA) (ms) (W) (VA) (W) (VA) (ms)
200 35 160
250
300
300
response time undervoltage pick-up hold response time Closing release shunt trip
280 4 45 50 45
550 40
response time
200 55
250
300
300
(V) (W) (VA) (s) (W) (ms) (W) (VA) (ms) (W) (VA) (W) (VA) (ms)
48
110
125
220
arming time Opening releases Mitop (low energy) response time shunt trip
30
response time undervoltage pick-up hold response time Closing release shunt trip
response time
85 180 65 65
47
48/60 100/130 200/240 24/30 48/60 100/125 200/250 0.85 to 1.1 Un 180 2 to 3 In during 0.1 s 4 s max. 3 cycles per minute max. 10000 remote controlled opening operations Evolis P1 10 A at 240 V
This specific coil actuates the opening mechanism of the poles to trip the circuit breaker. It comprises a low energy consumption electromagnet. Characteristics power supply direct current threshold 0.6 A < I < 3 A response time of the circuit breaker at Un 11 ms Any tripping caused by the Mitop release is indicated momentarily by an SDE type changeover contact. This release unit also includes a coil enabling the remote rearming of the SDE contact.
Comment: to use the MITOP release requires the adjustment of a time delay to be set by the protection relay in order to ensure a circuit breaker operating time of 45-50 ms.
This causes instant opening of the circuit breaker when energised. Permanent energising of the MX locks the circuit breaker in the open position. Characteristics power supply Vac 50/60 Hz Vdc threshold consumption (VA or W) response time of the circuit breaker at Un
24/30 48/60 24/30 48/60 0.7 to 1.1 Un pick-up: 200 hold: 4.5 50 ms 10
100/130 100/130
200/250 200/250
48
Current transformers
150
200
61041N
For 400 - 630 A units DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B
Transformer ARM3/N2F b double primary winding; b single secondary winding for measurement and protection. Short-time withstand current Ith (kA) I1n (A) 10/20 20/40 Ith (kA) 5 12.5 t (s) 1 0.8 measurement 5 A 7.5 VA - class 0.5 and protection 1 A 1 VA - 10P30 5 A 5 VA - 5P10
* for 5 A protection
5 VA - 5P15
b double primary winding; b double secondary winding for measurement and protection. Short-time withstand current Ith (kA) I1n (A) 50/100 Ith (kA) 14.5 t (s) 1 measurement 5A 30 VA - class 0.5 and protection 5A 5 VA - 5P15 5A 7.5 VA - 5P10 100/200 200/400 300/600 25 25 25
49
Current transformers
61042N
For 1250 A units DM1-A, DM1-D, DM1-W, DM1-Z, GBC-A, GBC-B DMV-A, DMV-D
Transformer ARJP3/N2F b single primary winding; b double secondary winding for measurement and protection. Short-time withstand current Ith (kA) I1n (A) 1000 1250 Ith (kA) 25 t (s) 1 measurement 1 A 30 VA - class 0.5 and protection 1 A 10 VA - 5P20 measurement 5 A 30 VA - class 0.5 and protection 5 A 10 VA - 5P20
61044N
50
Voltage transformers
Transformers VRQ2-n/S1 (phase-to-earth) 50 or 60 Hz rated voltage (kV) primary voltage (kV) secondary voltage (V) thermal power (VA) accuracy class rated output for single primary winding (VA) rated output for double primary winding (VA) 24 10/3 100/3 250 0.5 30
15/3
15-20/3 20/3
30 30-50
30
15/3
Transformers VRC2/S1 (phase-to-phase) 50 or 60 Hz rated voltage (kV) primary voltage (kV) secondary voltage (V) thermal power (VA) accuracy class rated output for single primary winding (VA) 24 10 100 500 0.5 50
15
20
Transformers VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz rated voltage (kV) primary voltage (kV) secondary voltage (V) thermal power (VA) accuracy class rated output for single primary (VA) thermal power (VA) accuracy class rated output 12 17.5 10/3 15/3 100/3 - 100/3 200 0.5 30-50 100 3P 50 24 20/3
First secondary
Second secondary
51
Voltage transformers
For unit TM
61047N
Transformers RV9 (phase-to-phase) 50 or 60 Hz rated voltage (kV) primary voltage (kV) secondary voltage (V) output (VA) 24 10 220 2500
15 2500 4000
20 2500 4000
Note: the above mentioned voltage transformers are grounded neutral. For other characteristics, please consult us.
Surge arrestor
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMV-S*
In (A) (unit) Un (kV) (unit) 400/630 7.2 10 12 17.5 24
Note: the rated voltage of the surge arrestor is according to units rated voltage. (*) limited up to 17.5 kV for DMV-A and DMV-S circuit breaker cubicles.
52
Protection transformers
Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend, among other things, on the following criteria: b service voltage; b transformer rating; b fuse technology (manufacturer); Different types of fuses with medium loaded striker may be installed: b Solefuse fuses as per standard UTE NCF 64.210; b Fusarc CF fuses as per IEC recommendation 60.282.1 and DIN dimensions 43.625. Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse fuses rated 43 A or Fusarc CF fuses rated 50 A.
By fused switch
35
DE55901
55
450
Solefuse (UTE standards) rated rating L voltage (kV) (A) (mm) 7.2 6.3 to 125 450 12 100 17.5 80 24 6.3 to 63 Fusarc CF (DIN standards) rated rating L voltage (kV) (A) (mm) 7.2 125 292 12 6.3 to 20 292 25 to 40 292 50 to 100 292 24 6.3 to 20 442 25 to 40 442 50 to 63 442 80 442 Others (DIN standards) rated rating voltage (kV) (A) 7.2 160 200 12 125 160 200 17.5 125 24 100 125 L (mm) 292 292 292 292 292 442 442 442
(mm) 55
weight (kg) 2
35 6 23
33
45
weight (kg) 3.3 1.2 1.5 2.8 1.6 2.2 4.1 5.3 weight (kg) 3.8 3.8 2 3.8 3.8 5.4 5.4 5.4
33 6
23
Selection table
The color code is linked to the rated voltage of the fuse. Rating in A - no overload at -5C < t < 40C. Please consult us for overloads and operation over 40C. Service Transformer rating (kVA) voltage 25 50 100 125 160 (kV) Solefuse (UTE NFC standards 13.100, 64.210) 5.5 6.3 16 31.5 31.5 63 10 6.3 6.3 16 16 31.5 15 6.3 6.3 16 16 16 20 6.3 6.3 6.3 6.3 16 Solefuse (general case, UTE NFC standard 13.200) 3.3 16 16 31.5 31.5 31.5 5.5 6.3 16 16 31.5 31.5 6.6 6.3 16 16 16 31.5 10 6.3 6.3 16 16 16 13.8 6.3 6.3 6.3 16 16 15 6.3 6.3 16 16 16 20 6.3 6.3 6.3 6.3 16 6.3 6.3 6.3 6.3 16 22 Fusarc CF (DIN standards) 3.3 16 25 40 50 50 5.5 10 16 31.5 31.5 40 10 16 25 31.5 40 6.6 10 6.3 10 16 20 25 13.8 6.3 10 16 16 20 6.3 10 10 16 16 15 20 6.3 6.3 10 10 16 22 6.3 6.3 10 10 10 Type of fuse 200 250 315 400 500 630 800 Rated 1000 1250 1600 2000 2500 voltage (kV) 7.2 63 43 43 63 43 43 43 43 63 43
63
24 7.2
125 80 63 63 43 43
100 80 80 63 63
12 17.5 24 63 7.2
* please consult us
53
The current rating of fuses installed in CRM units depends on: b motor current rating In; b starting current Id; b frequency of starts. The fuses rating is calculated such that a current equal to twice the starting current does not blow the fuse within period equal to the starting time. The adjacent table indicated the ratings which should be used, based on the following assumptions: b direct on-line startup; b Id/In 6; b pf = 0.8 (P 500 kW) or 0.9 (P > 500 kW); b = 0.9 (P 500 kW) or 0.94 (P > 500 kW). The indicated values are for Fusarc fuses (to DIN standard 43-625). Example: Consider a 950 kW motor at 5 kV. P In = -------------------------------- = 130 A 3 U pf Id = 6 x In = 780 A Then select the next higher value, i.e. 790 A. For six 5-second starts per hour, select fuses rated 200 A.
Note: the same motor could not be protected for 12 starts per hour since the maximum service voltage for the required 250 A rated fuses is 3.3 kV.
Selection of fuses
The color code is linked to the rated voltage of the fuse. Starting current (A) Starting time (s) 5 10 Maximum service voltage (kV)
20
Number of starts per hour 6 12 6 12 6 1410 1290 1140 1030 890 790 710 640 610 540 480 440 310 280 250 240 230 210 180 170 250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 125 100 100 100
12
250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 125 100 100
250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 125 100 100
250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100 100
250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100 100
250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100
3.3
6.6
11
Maximum switchable power (kW) (direct on-line startup, six 5 sec. starts per hour) service voltage (kV) 3.3 4.16 5 without fuses 1550 1960 2360 with fuses 100 A 140 180 215 200 A 625 800 960 250 A 1135
Access to fuses
Access is via the front with the front panel removed. Fuses may be removed without tools by simply pulling them forward. The field deflector pivots and automatically returns to its position.
Replacement of fuses
When fault clearance results in one or two blown fuses, it is still common practice to replace only the blown fuses. However, though the remaining fuse(s) may apparently be in good condition, their operating characteristics are generally reduced due to the short-circuit. If non-blown fuses remain in service, they may blow even at very low over-current values. In systems where continuity of service is of importance, it is recommended to replace all three fuses, in compliance with IEC recommendation 60282.1. Please note: all three fuses must come from the same range: Solefuse or Fusarc CF (they have different fusion curves).
54
Interlocks
Switch units
b the switch can be closed only if the earthing switch is open and the access panel is in position. b the earthing switch can be closed only if the switch is open. b the access panel for connections can be opened only if the earthing switch is closed. b the switch is locked in the open position when the access panel is removed. The earthing switch may be operated for tests.
Functional interlocks
These comply with IEC recommendation 60271-200 and EDF specification HN 64-S-41. In addition to the functional interlocks, each disconnector and switch include: b built-in padlocking capacities (padlocks not supplied); b four knock-outs that may be used for keylocks (supplied on request) for mechanism locking functions.
Unit interlock
units IM, IMB, IMC PM, QM, QMB, QMC, DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DMV-A, DMV-D, DMV-S CRM NSM GAM SM interlock A1 C1 C4 A3 b b b b A4 b A5 50 b P1 b P2 P3 P5
Circuit-breaker units
b the disconnector(s) can be closed only if the circuit breaker is open and the access panel is in position interlock type 50. b the earth switch(es) can be closed only if the disconnector(s) is/are open. b the access panel for connections can be opened only if: v the circuit breaker is locked open, v the disconnector(s) is/are open, v the earth switch(es) is/are closed.
Note: it is possible to lock the disconnector(s) in the open position for no-load operations with the circuit breaker.
b b b b b b b b
A1 type
DE55902
Key-type interlocks
O
Outgoing units
Aim: b to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position.
C1 type
De55903
b to prevent the access to the transformer if the earthing switch for transformer protection has not first been closed.
S
C4 type
DE55904
S O
b to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position. b to prevent the access to the transformer if the earthing switch for transformer protection has not first been closed.
no key
free key
captive key
panel or door
55
Interlocks
A3 type
DE55905
Ring units
O
Aim: b to prevent the closing of the earthing switch of a load-side cubicle unless the line-side switch is locked open.
O
A4 type
DE55906
A5 type
DE55907
b to prevent the closing of the earthing switch of the casing unit unless the downstream and the upstream switches are locked in the open position.
S O S
50 type
DE55908
O O
Prevents b on-load switching of the disconnectors. Allows b off-load operation of the circuit breaker with the disconnectors open (double isolation). b off-load operation of the circuit breaker with the disconnector open (single isolation).
no key
free key
captive key
panel or door
56
Interlocks
P1 type
DE55909
b to prevent the closing of an earthing switch if the switch of the other unit has not been locked in the open position.
P2 type
DE55910
b to prevent on-load operation of the disconnector unless the switch is locked open; b to prevent the closing of the earthing switches unless the disconnector and the switch are locked open.
P3 type
DE55911
AX
P5 type
De55912
b to prevent the closing of the earthing switch of the incoming unit unless the disconnector and the switch is locked open.
no key
free key
captive key
panel or door
57
b to prevent on-load operation of the disconnector unless the switch is locked open; b to prevent the closing of the earthing switches with the unit energised, unless the disconnector and the switch are locked open; b to allow off-load operation of the switch.
Connections
61048N
The ageing resistance of the equipment in an MV/LV substation depends on three key factors:
b the need to make connections correctly New cold fitted connection technologies offer ease of installation that favours resistance over time. Their design enables operation in polluted environments under severe conditions. b the impact of the relative humidity factor The inclusion of a heating element is essential in climates with high humidity levels and with high temperature differentials. b ventilation control The dimension of the grills must be appropriate for the power dissipated in the substation. They must only traverse the transformer area. Network cables are connected: b on the switch terminals; b on the lower fuse holders; b on the circuit breakers connectors. The bimetallic lugs are: b round connection and shank for cables 300 mm2; b square connection round shank for cables > 300 mm 2 only. Crimping of lugs to cables must be carried out by stamping. The end connectors are of cold fitted type Schneider Electrics experience has led it to favour this technology wherever possible for better resistance over time. The maximum admissible cable cross section: b 630 mm2 for 1250 A incomer and feeder cables; b 300 mm2 for 400 - 630 A incomer and feeder cables ; b 95 mm2 for transformer protection cubicles with fuses. Access to the compartment is interlocked with the closing of the earthing disconnector. The reduced cubicle depth makes it easier to connect all phases. A 12 mm pin integrated with the field distributor enables the cable end lug to be positioned and attached with one hand. Use a torque wrench set to 50 mN.
50 to 630 mm2
1 or 2 per phase 400 mm2 400 < 1 630 mm2 per phase
round connector
50 to 630 mm2
1 per phase
Note: b The lugs, covered by a field distributor, can be square; b PM/QM type cubicle, round end connections 30 mm max.
58
Connections
IM,NSM-cables, NSM-busbars SM IMC PM, QM QMC CRM DM1-A SF1 DM1-A SFset, DM1-S DMV-A, DMV-S DM1-W GAM2 GAM
630 A 950 950 450 400 340 430 370 430 324 360 760 470
1250 A 950
H H
CRM
DE55917 DE55918
GAM2
DE55919
GAM
59
Connections
Connections
370 400 440 470 500 540 590 692 800 940
P4
P5
1000 1000
1350 1350
(2) must be installed with a 100 mm deep pan. (3) must be installed with a 350 mm deep pan, in a floor void.
Height: 450 mm
187.5
Note: the unit and the cables requiring the greatest depth must be taken into account when determining the depth P for single-trench installations. In double-trench installations, depth P must be taken into account for each type of unit and cable orientations.
630 A units
DMV-A for single and tri-core cables
DE55933
100
100
140 60
100
50 740
50 740
50 740
50 740
P4 480
350 P5 P5
250 P4
600
600
840
600
60
Connections
140 60
140 60 100
P1 P2 P2 P3
P1
600
20
20
20
IM
70
IM
DM1
Note: for connection with conduits, the bevel C must correspond to the following trench dimensions: P1 = 75 mm or P2/P3 = 150 mm.
61
Connections
Connections
220
100
200
P1
20
20
200 IM 200 IM IM IM
DM1-A
DM1-A
Note: to evacuate gases through the bottom, the technical pit volume must be over or equal to 2 m3.
62
Installation
Add to height: (1) 450 mm for low-voltage enclosures for control/ monitoring and protection functions. To ensure uniform presentation, all units (except GIM and GEM) may be equipped with low-voltage enclosures. (2) depending on the busbar configuration in the VM6 unit, two types of extension units may be used: b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm; b for all other VM6 units, a depth of 920 mm is required. (3) for the 1250 A unit.
height (mm) IM,IMB 1600(1) IMC 1600(1) PM, QM, QMB 1600(1) QMC 1600(1) CRM 2050 DM1-A, DM1-D, DM1-W, DM1-Z, 1600(1) DM2 DM1-S 1600(1) DMV-A, DMV-D 1600(1) DMV-S 1600(1) CM 1600(1) CM2 1600(1) GBC-A, GBC-B 1600 NSM-cables, NSM-busbars 2050 GIM 1600 GEM(2) 1600 GBM 1600 GAM2 1600 GAM 1600 SM 1600(1) TM 1600
Type of unit
width (mm) 375 500 375 625 750 750 750 625 625 375 500 750 750 125 125 375 375 500 375/500(3) 375
depth (mm) 940 940 940 940 940 1220 1220 940 940 940 940 1020 940 840 920/1060 940 940 1020 940 940
weight (kg) 120 200 130 230 390 400 260 320 260 190 210 290 260 30 30/35 120 120 120 120 190
Floor preparation
Units may be installed on ordinary concrete floors, with or without trenches depending on the type and cross-section of cables. Required civil works are identical for all 400 - 630 A units. To reduce the depth of trenches by 400 mm (for the 400 - 630 A units), which in many cases is sufficient to eliminate trenches altogether, units may be installed on a concrete footing prepared when pouring the floor. Installation of 400 - 630 A units on a footing: b enables installation in rooms where trenches are not possible; b in no way affects substation switching operation; b for the 1250 A units DM1-A and DM1-W, a floor void must be foreseen.
a
DE55940
Fixing of units
15 50
15
740
840
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the floor b for switchboards comprising up to three units, the four corners of the switchboard must be secured to the floor using: v M8 bolts (not supplied) screwed into nuts set into the floor using a sealing pistol, v screw rods grouted into the floor. b for switchboards comprising more than three units, the number and position of fixing points depends on local criteria (earthquake withstand capacities, etc.), each unit may be fixed as necessary. b position of fixing holes b depends on the width a of units:
12.3 x 12.3 Note: in circuit-breaker or contactor units, fixing devices are installed on the side opposite the switchgear.
a (mm) b (mm)
125 95
375 345
500 470
625 595
750 720
63
Installation
Installation
Units dimensions
CRM
450 450
450
1600
1600
1600
840
30 70
840
30 70
840
30 70
NSM-cables, NSM-busbars
DE55944 DE55945
GBM, GAM2
DE55946
GAM
450
1600
1600
1600
840
30 70
840
30 70
80
840
30 70
GIM
DE55947 DE55948
GEM
DE55949
GBC-A, GBC-B
1600
1600
1600
840
140
920
80
840
100
64
Installation
Units dimensions
450
1600
1600
80
840
80
DMV-A
DE55952 DE55953
DMV-D
DE55954
DMV-S
1680
1680
1600
100 85 100
450
600
450 25
1600
1600
220
220
65
Installation
Installation
Layout examples
940
200 20
1200 (*)
1160
200
1200 (*)
66
Installation
Schneider Electric is committed to a long term environmental approach. As part of this, the SM6 range has been designed to be environmentally friendly, notably in terms of the products recycleability. The materials used, both conductors and insulators, are identified and easily separable. At the end of its life, SM6 can be processed, recycled and its materials recovered in conformity with the draft European regulations on the end-of-life of electronic and electrical products, and in particular without any gas being released to the atmosphere nor any polluting fluids being discharged.
61016N
Ferrous metal
71%
b The environmental management system adopted by Schneider Electric production sites that produce the SM6 have been assessed and judged to be in conformity with requirements in the ISO 14001 standard.
MT55145
01 ISO 140
67
Installation
Installation
61052N
Schneider Electric is capable of offering a full range of services either associated or not with the supply of the SM6 unit. To improve the quality of your electrical power: b network study, harmonics study, etc.; b reactive energy compensation; b consumption monitoring; b optimisation of your electrical power supply contracts. To accompany the purchase and installation of your SM6 equipment: b adaptation of our equipment to provide a better response to your requirements; b on site assembly, testing and commissioning of your equipment; b customised financing solutions; b warranty extension; b operator training. To accompany your installation throughout its life and upgrading your equipment: b upgrading your existing equipment: functional adaptation, control motorisation, renovation of protections units, etc.; b on site work; b supply of replacement parts; b maintenance contracts; b end of life processing. Fore more information on all the services proposed by Schneider Electric, please contact your Schneider Electric Sales Office.
68
61053N
Appendices
DE55970
t>
t>
t >>
t >>
Is 1.2 Is
10 Is
I >>
Is 1.2 Is 10 Is
I >>
VI curve
t (s) 100
100
10
10
1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100
0.1
0.1
0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100
0.01
0.01
EI curve
t (s)
DE55972
RI curve
t (s) 10
1000
100
1 10 0.6
1 0.1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 1 1.2 10
0.1
0.01
I/Is 100
0.01 1 10
I/Is 100
69
Appendices
0.4 0.3
Appendices
td (s) 1000 500 200 100 50 20 10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.5 1 1.2 2 3 4 5 7 10 20 30 50 60
td (s) 1000 500 200 100 50 20 10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.5 1 1.2 2 3 4 5 7 10 20 30 50 60
td (s) 1000 500 200 100 50 20 10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.5 1 1.2 2 3 4 5 7 10 20 30 50 60 14 I/Is 13
70
Appendices
100
The trip curve shows the time before the relay acts, to which must be added 70 ms to obtain the breaking time.
10
0.1
type
0.01 0 1.2 5 10 15 20 25 30 I/Is
71
Appendices
Appendices
Fusarc CF fuses
Fuse and limitation curves
250 A
4A
Current (A)
8 6 4
Ia
2
8 1.
Ik
Is
Ik
10 8 6 4
1 8 6 4
4A
0.1
0.1
10
100
72
Appendices
Solefuse fuses
Fuse and limitation curves
100 A 125 A
4 6
100
8 1000
8 10000
Current (A)
8 6 4
Ia
2
8 1.
Ik
Is
Ik
2
125 A 100 A 80 A 63 A 43 A 31.5 A 25 A 20 A 16 A 10 A 6.3 A
10 8 6 4
1 8 6 4
0.1 0.1
10
100
73
Appendices
Modular switchboard
Order form
SM6 24 Connection to the network
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Short-circuit current Isc Rated current Ir Type of cubicle SM 375 IM 375 IMB 375 SM 500 IM 500 IMC 500 Position number in the switchboard (from left to right) Direction of lower busbars for IMB left (impossible as first cubicle of switchboard)
right
Options
Replacement of CIT by Electrical driving motorization 24 Vdc 32 Vdc 48 Vdc 60 Vdc CI1 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc CI2 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)
Remote control signalling 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V 220 V Signalling contact 1 C on SW and 1O & 1C on ES (not applicable on SM cubicle) 2 O & 2 C on SW 2 O & 3 C on SW and 1O & 1C on ES Roof configuration (A, B or C only one choice possible) A - Top incomer (cable maxi 240 mm2 with voltage indicator) 3/7.2 kV single core 2 x single core 10/24 kV single core 2 x single core B - Low voltage control cabinet (h = 450 mm) with unpunched door C - Wiring duct Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2) three core single core 2 x single core Heating element Interlocking (with key) Ronis Profalux For all cubicle (except SM) A4 A3 SM6-SM6 P1 SM6-SM6 Localisation of 2nd lock for A3 on switch on earthing switch Localisation of 2nd lock for A4 cubicle no. SM cubicle only P2 SM6-SM6 P3 SM6-SM6 Surge arrestors for IM 500 7.2 kV 10 kV 12 kV 17.5 kV 24 kV Operating counter CTs for IMC (quantity) 1 2 3 Replacement of 630 A busbar by 1250 A (not possible for IMB) Internal arc version 16 kA 1s (not possible with top incomer option) Telecontrol (48 Vdc electrical motorization compulsory) Cubicle with relay without relay Communication Modbus IEC DNP protocol Modem type RS232 RS485 Not for DNP PSTN GSM FSK 3 core balance current transformers
74
Modular switchboard
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Short-circuit current Isc Rated current Ir Type of cubicle QM 375 QMB 375 QMC 625 Position number in the switchboard (from left to right) Current transformers for QMC (to see price structure) Quantity of CTs 1 2 Direction of lower busbars for QMB left
3 right
Options
Fuses (see fuse price structure) Replacement of mechanism CIT by CI1 (only for PM) Electrical driving motorization 24 Vdc 32 Vdc 48 Vdc 60 Vdc 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc service voltage 12 kV CI1 by CI2 (only for QM) 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)
Shunt trip
closing & opening (on CI2) 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz) 380 Vac (50/60 Hz)
Remote control signalling (not applicable on PM, QMC and QMB) 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V 220 V Auxiliary contact signalling 1C on SW and 1O & 1C on ES 2 O & 2 C on SW 2 O & 3 C on SW and 1O & 1C on ES Blown fuse signalling contact (mechanical indication PM, electrical for the other cubicles) Roof configuration (A, B or C only one choice possible) A - Top incomer (cable maxi 240 mm2 with voltage indicator) 3/7.2 kV single core 2 x single core 10/24 kV single core 2 x single core B - Low voltage control cabinet (h = 450 mm) with unpunched door C - Wiring duct Interlocking C4 Ronis A1 Profalux C1
Heating element Operation counter Replacement of 630 A busbar by 1250 A (not possible for QMB) Internal arc version 16 kA 1s (not possible with top incomer option)
75
Modular switchboard
Order form
SM6 24 Circuit breaker protection
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Basic cubicle
Rated voltage Ur (maxi 17.5 kV for Evolis CB) Short-circuit current Isc Rated current Ir Type of cubicle For SF1 circuit breaker
DM1-S 750 DM2 left 750 DM2 right 750 DM1-W 750 DM1-Z 750 For SFset circuit breaker DM1-A 750 DM1-D left 750 DM1-D right 750 For Evolis circuit breaker DMV-A DMV-S DMV-D right Position number in the switchboard (from left to right) Busbar (Ir Ir cubicle) For DM1-A, DM1-S, DM1-W 400 A 630 A 1250 A For DM1-D, DM2 400 A 630 A For DM1-A, DM1-D, DM1-W, DM1-Z 1250 A For DMV-A, DMV-D, DMV-S 630 A 1250 A Protection For DM1-S, DMV-S VIP35 with CRc VIP300LL with CRa VIP300LL with CRb For DM2, DM1-Z, DM1-W Statimax 5 A, 2 s Statimax 1 A, 2 s Control for DMV-A and DMV-D Local (shunt trip coil compulsory) Remote (opening coil and closing coil compulsory) Local and remote (opening coil and closing coil compulsory) Voltage of the auxiliaries 48/60 Vdc 110/125 or 220/250 Vdc 110/130 or 220/240 Vac (50 Hz) Voltage of signalling 48/60 Vdc 110/125 Vdc 220/250 Vdc 110/130 Vac (50 Hz) 220/240 Vac (50 Hz) Cable connection by the bottom For DM1-A, DM1-W 6 x single core cable maxi 240 mm2 3 x single core cable maxi 240 mm2
Options
Roof configuration (not applicable on DMV-A, DMV-S, DMV-D) (A, B or C only one choice possible) A - Top incomer (cable maxi 240 mm2 with voltage indicator) 3/7.2 kV single core 10/24 kV single core DM2 1 set B - Low voltage control cabinet DM2 1 cabinet C - Wiring duct DM2 Other cubicles 1 set 1 set
Interlocking Ronis Profalux Not applicable on DM2 C4 A1 C1 CTs and VTs (not applicable for DM1-S, DMV-S) See specific order form Surge arrestor (for DM1-W 630 A without VTs) Signalling contact 2 O & 2 C on SW (not applicable with VTs) 2 O & 3 C on SW and 1 O & 1 C on ES (not applicable with VTs) 1 O & 2 C on SW (available only on cubicle with VTs) Heating element Circuit breaker See specific order form Internal arc version 16 kA 1s
76
Modular switchboard
Order form
SM6 24 MV metering
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Short-circuit current Isc Rated current Ir Type of cubicle In = 630 A, In busbar = 400 A In = 630 A, In busbar = 630 A In = 630 A, In busbar = 1250 A In = 1250 A, In busbar = 1250 A Direction of lower busbars for GBC-A
Quantity (kV) (kA) (A) CM CM CM CM2 CM2 CM2 TM TM TM GBC-A GBC-A GBC-A GBC-A GBC-B GBC-B GBC-B GBC-B right phase/earth 3
left VTs for GBC (to see price structure) CTs for GBC (to see price structure) Ratio choice for GBC Protections 1 secondary 2 secondaries Signalling contact phase/phase Quantity 1
1 O and 1 C on SW (CM, CM2, TM) blown fuse mechanical indication (CM, CM2, TM) Fuses for CM, CM2 and TM only (see fuse price structure)
Options
Roof configuration (A, B or C only one choice possible) A - Top incomer (cable maxi 240 mm2 with voltage indicator) 3/7.2 kV single core 2 x single core 10/24 kV single core 2 x single core B - Low voltage control cabinet (h = 450 mm) with unpunched door C - Wiring duct Heating element for CM, CM2, TM Internal arc version 16 kA 1s
77
Modular switchboard
Order form
SM6 24 Casing
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Short-circuit current Isc Rated current Ir Type of cubicle In = 630 A, In busbar = 400 A In = 630 A, In busbar = 630 A In = 1250 A, In busbar = 1250 A
Quantity (kV) (kA) (A) GAM 500 GAM 500 GAM 500 GAM2 375 GAM2 375 GBM 375 GBM 375 GBM 375
Position number in the switchboard (from left to right) Direction of lower busbars for GBM left (impossible on the first cubicle of the switchboard)
right
Options
Roof configuration (A, B or C only one choice possible) A - Top incomer (cable maxi 240 mm2 with voltage indicator) 3/7.2 kV single core 2 x single core 10/24 kV single core 2 x single core B - Low voltage control cabinet (h = 450 mm) with unpunched door C - Wiring duct Wiring duct for GBM ES auxiliary contact (only on GAM 500) Surge arrestors for GAM 500, 630 A 7.2 kV 10 kV 12 kV Interlocking on GAM 500 Localisation of 2nd lock for P5 Heating element (on GAM 500 630 A and on GAM2) Internal arc version 16 kA 1s 1 O and 1 C 17.5 kV Ronis A3 SM6-SM6 24 kV Profalux P5 SM6-SM6 cubicle no.
78
Modular switchboard
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Short-circuit current Isc Rated current Ir Type of cubicle In = 630 A, In busbar = 400 A In = 630 A, In busbar = 630 A In = 630 A, In busbar = 1250 A
Quantity (kV) (kA) (A) NSM busbar NSM busbar NSM cable NSM cable NSM cable
Position number in the switchboard (from left to right) Way of the busbars for NSM left right Cable connection by the bottom (cable maxi 240 mm2) three core on both single core on both 2 x single core on both 3 x single core on one cubicle and 2 x three core on the other one Stand by source Utility with paralleling generator without paralleling
Options
Signalling contact on earthing switch Operation counter Interlocking SM6-SM6 1 x P1 2 x P1 1 x A3 2 x A3 right cubicle left cubicle 2 heating elements (set) Telecontrol (only with utility stand by source) Communication Modbus protocol Modem type Not for DNP PSTN Ronis right cubicle right cubicle on switch on switch on switch Profalux left cubicle right and left cubicle left cubicle on earthing switch on earthing switch on earthing switch 1C on SW and 1O & 1C on ES
79
Order form
SF1 lateral fixed or withdrawable for SM6 24
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Colour for push buttons and indicators Push buttons open/close Indicator open/close Operating mechanism charged/discharged
green/red charge/discharge
Remote control
Electric motor - MCH Shunt closing release 24 Vdc 60 Vdc 30 Vdc 110 Vdc 48 Vdc 125 Vdc Leaflets language French 2432 Vdc 4860 Vdc/ac 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) English 110127 Vdc/ac 220250 Vdc/ac 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) Spanish
(*) Different releases combinations 2 Shunt opening release 1 Undervoltage release 1 1 MITOP
1 1
1 1 1 1
80
Order form
SFset lateral withdrawable for SM6 24
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
green/red charge/discharge
Is = 62.5 to 630 A Is = 200 to 630 A Is = 630 to 1250 A Is = 40 to 200 A Is = 250 to 1250 A Is = 40 to 200 A Is = 250 to 1250 A
VIP 200 Available in 2005 VIP 300P (not available for all CSa 200/1 electrical characteristics) CSb 1250/1 VIP 300LL CSa 200/1 CSb 1250/1
Remote control
Electric motor - MCH Shunt closing release 24 Vdc 60 Vdc 30 Vdc 110 Vdc 48 Vdc 125 Vdc Test box (VAP 6) Leaflets language 2432 Vdc 4860 Vdc/ac 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 110127 Vdc/ac 220250 Vdc/ac 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz)
French
English
Spanish
(*) Different releases combinations MITOP 1 1 1 1 Shunt opening release Undervoltage release 1
81
Order form
Evolis frontal fixed for SM6 up to 17.5 kV
Only one of the boxes (ticked or filled by the needed value) have to be considered between each horizontal line. Orange box corresponds to none priced functions.
Operation counter CDM Additional auxiliary contacts OF (4 AC) 1 Ready to close contact PF (1 AC) Locking of the circuit breaker in the open position By padlock or by locks and keys Profalux If locks 1 lock 2 identical locks Disabling of O/C circuit breaker push buttons
82