BW Series Fuji Molded Case Circuit Breakers are more compact (especially 100A, 125A, 250A frames) than any breakers on the market, so control panels take up less space than ever before. This product group maintains conformity to all Worldwide standards, including cULus / IEC / CE Marking / JIS (Japan) / CCC (China). Suitable for branch circuit protection 5 frame sizes, rated current of 15 to 800A, max 600V Standard type and high-interrupting capacities are available in identically sized breakers Shunt Trip, Undervoltage Release and other accessories are available Auxiliary Switch and Shunt Trip can be installed in the field
Circuit
starting at
$166.00
begin on page 31-5
starting at
$172.25
begin on page 31-31
NO
NO
NO NO
NO
UL 98
MOTOR CIRCUIT
NO NO NO NO NO
NO
NO
NO
NO
NO NO NO NO
UL 508
Motor overload protection (NEC 430.21-430.44) OSHA Lockout/tagout disconnect (NEC 430.81430.91)
YES YES
NO YES
Motor
1 - 80 0 - 633 - 0405
Volume 13
e31-2
Circuit Protection
Protection
Ferraz Shawmut UL 98 Rated Disconnect Switches
Heavy-duty fusible and non-fusible disconnects meet all the requirements of the UL 98 standard. These switches can be used as a motor disconnecting means to meet NEC 430.109; meets NEC 430.111 as a motor controller.
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors
SIRCO series
Non-fusible rotary disconnect switches Makes/breaks loads up to 800 amps Front operated Visible blade contacts Line-side shrouding comes standard with switch
FUSERBLOC series
Fusible rotary disconnect switches Makes/breaks loads up to 200 amps Front operated Uses Class CC and Class J fuses Line side shrouding comes standard with switch Touch-safe fuse covers standard with switch
starting at
$75.00
begin on page 31-62
Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection
starting at
$31.50
begin on page 31-95
for 10-pack
starting at
$22.50
begin on page 31-86
Volume 13
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
e31-3
Circuit Protection
Supplementary Protection Selection
Supplementary Protectors UL 1077
(continued)
Circuit Protection
from
CONTROL CIRCUIT
PLC I/O
General
Fuses UL 248-14
Control Transformer
page 31-54
page 31-92
YES
Contactor Coils Relays
YES
starting at
$1.75
begin on page 31-92
for 5-pack
$9.50
begin on page 31-54
Volume 13
e31-4
Circuit Protection
1 - 80 0 - 633 - 0405
UL489 or UL1077?
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors
Branch Protection
UL489
Supplementary Protection
UL1077
Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Branch Protection
UL489 Listed or Recognized CSA C22.2 No. 5 International ratings available depending on breaker type
UL489
Supplementary Protection
UL Recognized under UL1077 CSA 22.2 No. 285 IEC 60947-2 or IEC 898
UL1077
Function
Opens automatically on Overload and Short Circuit Opens automatically on Overload and Short Circuit when properly applied with Provides additional equipment protection where branch circuit protection is in its ratings already provided or not required Protects wire and cable against Overload and Short Circuit Not suitable for the protection of branch circuit conductors
Applications
Branch circuit protection in control panels, panelboards, switchboards and motor control centers Motor overload and motor short circuit protection (UL489 Recognized motor circuit protectors) for control panels and motor control centers Used within appliances or other electrical equipment such as control circuits, control power transformers, relays, PLC I/O points and lighting circuits Ideal replacement for fuses that are applied as supplementary protection
Features
Bolted down or DIN-rail mounted External handle mechanisms available Field mounted accessories Stand alone branch circuit protection Various levels of protection (curve type) High voltage and interruption levels (up to 100 kAIC @ 480V) DIN-Rail mounted Field mounted accessories Current limiting Various levels of protection (curve type) 10 kAIC @ 240 VAC 6 kAIC @ 277 VAC and 5 kAIC @ 480 VAC 10 kAIC @ 65 VDC kAIC = thousands of Amps interrupt capacity
Summary
A Supplementary Protector cant Be used for Branch Circuit Protection. Understanding the difference between Branch Circuit Protection and Supplementary Protection helps to ensure their proper use.
Volume 13
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
e31-5
Features
Thermal-magnetic 15A through 800A Suitable for branch circuit protection Rated current of 15 to 800A, max 600V Standard type and high-interrupting capacities available in identically sized breakers Shunt Trip, Undervoltage Release and other accessories available Line & load lug terminals included on all MCCBs Auxiliary switch, Alarm switch and Shunt Trip can be installed in the field Door-mounted or flange-mounted, flex shaft operating handles All frame sizes suitable for reverse-feed use All breakers include mounting hardware Terminal covers included for BW125 and BW250 frames. Terminal covers available for BW400, BW630 and BW800 frames.
Programmable Controllers
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors
Agency Approvals
UL listed, MCCB, File: E90584 UL listed, Accessories, File E93289 CE marked CCC marked TUV certified
Standards
UL 489 CSA C22.2 No.5 IEC 60947-2 EN 60947-2 GB 14048.2 JIS C8201-2-1, 2 (ANN.1, 2)
Fuji Electric Molded Case Circuit Breakers Technical Specifications Circuit Ampere Rating No. Breaker Type at 40C Poles
BW125JAGU BW250JAGU BW400SAGU BW630RAGU BW800RAGU
15-125 125-250 250-400 500-600 700-800 3 3 3 3 3
Volts AC
600 600 480 480 480
DC
250 250 250 250 250
Type of Trip*
N.I.T.U N.I.T.U N.I.T.U N.I.T.U N.I.T.U
UL 489 Interrupting Ratings (rms Symmetrical Amperes) (kA) Volts AC (50/60 Hz) Volts DC
240
50 50 50 100 100
Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power
480
30 30 35 50 50
600
10 10
250**
10 10 10 10 10
*Note: N.I.T.U denotes non-interchangeable trip unit. **Note: For DC or 1-phase AC applications, use the two outside poles of the 3-pole circuit breaker
Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
e31-5
Features
UL489 listed performance for branch circuit overcurrent protection and disconnecting means Patented contact conductor designs featuring high-speed blow-open action, providing superior performance when high level fault currents produce extra-ordinary electromechanical forces Advanced arc extinguishing technology Toggle handle provides three positions (on/off/tripped) along with visual indicators Manufactured in ISO 9000 certified facilities HACR (heating, air conditioning and refrigeration) rated G-Frame and F-Frame breakers are suitable for reverse feed K-Frame and L-Frame breakers include 3-pole adjustable magnetic trip.
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders
Listings
UL 489 MCCB, File: E7819 Field-installed accessories: UL file E64983 CSA 22.2 No.5, File: 43556 IEC 157-1 NEMA Standards Pub. No. AB1-1993
Note: These parts available for sale to North American locations only.
Molded Case Circuit Breakers Technical Specifications UL 489 Interrupting Ratings Volts Type Federal (rms Symmetrical Amperes) (kA) No. of Specification Volts AC (50/60 Hz) Volts DC Poles AC DC Trip* W-C-375b
240
65 65 65 65
Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power
480
22 35 35 35
600
18 25 25
250**
10 10 10 22
3 3 3 3
*Note: N.I.T.U denotes non-interchangeable trip unit. I.T.U denotes interchangeable trip unit. **Note: Two poles of 3-pole circuit breaker
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
e31-31