Users Manual PS4840 Power Supply System and Components

Components Part Rectifier Modules HD4810-5 and HD4810-51

Chapter 1 Rectifier Modules HD4810-5 and HD4810-51


1.1 Outlines of HD4810-5 and HD4810-51
Outline of HD4810-5 rectifier module is illustrated in Figure H-1. Outline of HD4810-51 rectifier module is illustrated in Figure H-2. As illustrated in the figures, HD4810-5 is vertical frame and HD4810-51 is horizontal frame.

Figure H-1

Outline of HD4810-5 rectifier module

Figure H-2

Outline of HD4810-51 rectifier module

Users Manual PS4840 Power Supply System and Components

Components Part Rectifier Modules HD4810-5 and HD4810-51

1.2

Technical Performance of HD4810-5 and HD4810-51


HD4810-5 and HD4810-51 are rectifier modules developed by Huawei Technologies Co., Ltd., with the rated output of 48V/10A. They are different in structure: HD4810-5 is vertical while HD4810-51 is horizontal. They feature same basic operating theories and specifications. The commonness of HD4810-5 and HD4810-51, represented by HD4810-5 (51) are described in the following.

1.2.1

Basic Operating Theory


Basic operating theory of HD4810-5 (51) is illustrated in Figure H-3:
Output rectifying/ Filtering circuit DC output

AC input EMI

Full bridge rectification

DC/DC Converter

PWM Control circuit

Figure H-3

Basic operating theory of HD4810-5 (51) rectifier module

The single-phase AC power is first input through EMI filtering circuit, which enables two functions: 1) To prevent the line peak voltage caused by other related equipment (such as thysristor) or due to the lightning strike from damaging the rectifier module. 2) To prevent the rectifier module from feeding high-frequency disturbance caused in switching modulation to the power network. In addition, a surge current suppressing circuit is provided in the AC input circuit to reduce the surge from the power supply to the power network and to protect against lightning strike, thus the reliability of power supply is greatly improved. 1. DC-DC Circuit DC-DC main circuit adopts the topology of single-end flyback structure. The control circuit adopts pulse width modulation (PWM) control mode, in which the pulse width of power transistor is automatically regulated according to the load, high-voltage DC current is inverted to the pulse voltage whose width is regulated. After the pulse is rectified and filtered, stable DC voltage is output. The circuit

Users Manual PS4840 Power Supply System and Components

Components Part Rectifier Modules HD4810-5 and HD4810-51

adopts advanced switching technologies such as lossless ZVS and ZCS, thus the switching loss is greatly lowered and the efficiency reaches up to 87%. 2. Load-sharing technology HD4810-5 (51) module adopts advanced low-difference active load sharing technology. When multiple HD4810 rectifier modules are operating in parallel, they enable a good load sharing performance. The operating theory is illustrated in Figure H-4. Each module load-sharing unit samples its own output current via a uniform amplying factor in order to form a sampling voltage. After comparing all sampling voltage, the highest one is selected as the reference voltage VBUS on the current sharing bus. The module corresponding to the reference voltage is called master module, and it has the highest output current. Other modules are called slave modules. The reference voltage passes into respective current sharing unit of each module via current sharing bus, and controls the switch pulse width of DC/DC converter of the module after the difference comparison and amplification with its sampling voltage, then enables the output currents tending to be uniform by regulating the output voltage of all the modules. When EC is balanced, the output current of the slave modules is very close to that of the master module and current difference is tending to zero. Advantages of this current sharing method are in two aspects: 1) Load is well shared with imbalance less than 3%, which is better than ministry standard 5%. 2) The master rectifier module is arbitrarily generated through comparison. When the master module stops working for some reason, the system will compare automatically to generate another module with the largest output current as the master module and re-adjust the output current to reach new balance. Thus, the system breakdown caused by module failure can be avoided.

Users Manual PS4840 Power Supply System and Components

Components Part Rectifier Modules HD4810-5 and HD4810-51

V11

V12

V13

HD4810
load sharing adjust

HD4810
load sharing adjust

HD4810
load sharing adjust

Vbus

Figure H-4

Current Sharing Principle of HD4810-5 (51) Rectifier Modules in Parallel

3. Monitor processing interface The rectifier module has interfaces for monitor signal and sends the signal to monitor module through motherboard. The PSM-8 monitor module is provided for HD4810-5 rectifier module, and the PSM-81 monitor module is provided for HD4810-51 rectifier module to form a complete set. The output status information of rectifier module is: Mains input, AC input over/under-voltage and module failure signal. The input control signals of the rectifier module are: switching signal of Equalized/Floating charge, current-limiting control signal and On/Off signal. Above signals are all the digital value.

1.2.2

Specifications
1. AC input AC input rated voltage: 220V, 50Hz Voltage fluctuation range: 150V 300V

Line frequency range: 50Hz 10% 2. Rated values of DC Output Equalized charge voltage: 56.5V(can be regulated internally) Floating charge voltage: 53.5V (can be regulated internally)

Users Manual PS4840 Power Supply System and Components

Components Part Rectifier Modules HD4810-5 and HD4810-51

Voltage regulation range: 40V

60V 176V, the

Rated output current: 10A (When the input voltage is between 150V output current should be higher than 7A.) 3. Alarm and safety protection 1) Input over-voltage protection

The module alarms and shuts down to protect itself when the AC input over-voltage reaches 305 3VAC, and automatically restores to normal operation when the voltage drops to 295 3VAC. 2) Input under-voltage protection The module alarms and shuts down to protect itself when the AC input under-voltage drops to 145 3VAC, and automatically restores to normal 3VAC.

operation when the voltage rises up to 160 3) Output over-voltage protection

The modules will give alarm and will be turned off and locked for protection when the DC output over-voltage reaches 59.5 0.5V, and after troubleshooting, the rectifier module will be restarted. 4) Current-limiting protection The module has two-level current-limiting protection; the current-limiting protection values of the first level and the second level are 10.5 11.0A and 6.5 7.0A respectively.

5) Short-circuit protection The rectifier module has current limiting retraction and short-circuit protection. When short-circuit occurs at the output terminals of the rectifier module, the retraction current eliminated. 4.0A, and the rectifier can restore to work after the fault is

Users Manual PS4840 Power Supply System and Components

Components Part Rectifier Modules HD4810-5 and HD4810-51

6) Overheating protection Detecting the temperature of the heatsink, when the temperature is higher than 90 65 , the module will alarm and protect. When the temperature drops to below , operation can be automatically resumed.

4. Intelligent information processing HD4810-5 (51) rectifier module provides remote control terminal and remote communication terminal, where: Remote control functions include: Power on/off, equalized/floating charge switching, and current-limiting control. Remote communication signals include: AC Mains available/unavailable, AC over/under-voltage, and module failure. 5. Mechanical features HD4810-5 rectifier module: Dimensions (Length Width Weight: 2.3kg HD4810-51 rectifier module: Dimensions (Length Width Weight: 2.3kg 6. Efficiency Overall efficiency is higher than 87%. Height): 318.5mm 144mm 70mm Height): 318.5mm 60mm 167mm

1.3
1.3.1

Applications of HD4810-5 and HD4810-51


Operating Environment Requirements
Operating temperature: -5 Storage temperature: -40 Relative humidity: Air pressure: 70 90% 106kPa 40 70

Users Manual PS4840 Power Supply System and Components

Components Part AC&DC Power Distribution Unite PDU4840CF

Chapter 3 AC&DC Power Distribution Unit PDU4840CF


3.1 Outline of PDU4840CF
Outline of PDU4840CF is illustrated in Figure PU-1.

Figure PU-1

Outline of PDU4840CF AC&DC power distribution unit

3.2

Technical Performance of PDU4840CF


PDU4840CF has one branch circuit of AC mains input, and its AC&DC power distribution unit enables AC input overload and short circuit protection functions. The AC&DC power distribution unit provides DC branch circuits needed by users, each branch circuit enables overload and short circuit protection function. PDU4840CF can be connected to two groups of batteries. It also enables battery over-discharge protection, battery loop connection/disconnection detection and LLVD (load low voltage disconnection) functions.

25

Users Manual PS4840 Power Supply System and Components

Components Part AC&DC Power Distribution Unite PDU4840CF

3.2.1

Operating Theory
Operating theory of PDU4840CF AC&DC power distribution unit is illustrated in Figure PU-2.

Figure PU-2

Operating theory of PDU4840CF

In AC&DC power distribution unit, AC power input is introduced into the AC over/under voltage protection board via circuit breaker QF1, then to the backboard, and finally supplies power to the rectifier module via the connectors on the backboard. DC output is connected to two groups of batteries and three branch circuits of loads via the backboard. Shunts R1, R2, R3, and R4 respective detect the current of two groups of batteries and three branch circuits of loads. Contactors KM1 and KM2 are controlled by the monitor module to enable automatically load connection function. Connection/disconnection signals of QF2, QF3, QF4, QF5 and QF6 and current signals of R1, R2, R3 and R4 are sent to the monitor module via the backboard.

3.2.2

Performance Description
1. Secondary LVD functions When the AC power failure occurs and the battery voltage lower than the secondary LVD voltage, DC output of QF4 and QF5 will be automatically disconnected.

26

Users Manual PS4840 Power Supply System and Components

Components Part AC&DC Power Distribution Unite PDU4840CF

2. Battery over-discharge protection When the AC power failure occurs, the battery connected to the AC&DC power distribution unit will supply power to the system. When the battery voltage is lower than the battery over-discharge protection voltage, the battery and all DC loads will be automatically disconnected to avoid over discharge of the battery.

3.2.3

Specifications
1. AC input Input voltage: 150VAC 300VAC

Input current: the highest current is 20A Frequency: 45Hz 65Hz

2. Battery branch circuit Two branches, 50A for each 3. DC load branch circuit -48V/32A, three circuits, and the total operating current is not higher than 40 A. 4. Secondary LVD voltage -44.0 0.2V

When the battery voltage is lower than -44.0 0.2V, DC output of QF4 and QF5 will be automatically disconnected to enable secondary LVD protection. 5. Battery over-discharge protection voltage -41.0 0.2V 0.2V, all

When the battery over-discharge voltage is lower than -41.0

connection between the battery and loads will be automatically disconnected to enable automatically battery over-discharge protection.

27

Users Manual PS4840 Power Supply System and Components

Components Part Monitoring Modules PSM-8 and PSM-81

Chapter 4 Monitor Modules PSM-8 and PSM-81


4.1 Outlines Of PSM-8 and PSM-81
Dimension of PSM-8 is shown in Figure PM-1: 1. Dimension: 318.5mm 2. Weight: 1.3 Kg 60mm 167mm

Figure PM-1 Outline of PSM-8 monitor module

Dimension of PSM-81 is shown in Figure PM-2: 1. Dimension: 330mm 2. Weight: 1.45 Kg 144mm 55mm(the height of the panel is 70mm)

Figure PM-2 Outline of PSM-82 monitor module

31

Users Manual PS4840 Power Supply System and Components

Components Part Monitoring Modules PSM-8 and PSM-81

4.2

Technical Performance Of PSM - 8 and PSM - 81


Difference between PSM-8 and PSM-81: Monitor module PSM-81 is designed on the basis of monitor module PSM-8. Their performances (including the interfaces) excluding their dimensions are fully same. With good detecting and control functions, Monitor module PSM-82 can detect the operating states of power supply system in real-time and control the rectifier module with the detecting parameters, which satisfy the maintenance requirements of battery group and make sure the safety and reliable work of the PS4840-2B/10 power supply system. Visual/audible alarm can be sent out when rectifier module is abnormal or other faults occur. The monitor module PSM-82 also has communication and report functions. It can communicate with background host and accept the inquiry, setup and control and report the detected signal to background host to realize centralized management through RS232 or RS422 port according to PSM 82 Monitor Module and Its

Communication Protocol with Host.

4.2.1

Design Of Monitor Modules


The monitoring scheme of PSM-8 of PS4840/10 power supply system is illustrated in Figure PM-3.

Figure PM-3

The monitoring scheme of PSM-8 of PS4840/10 power supply system


2: Water-immersing sensor 5: Gate magnetic 8: User's module 3: Temperature sensor 6: Battery group 1 9: Transmission module

1: smoke sensor 4: Humidity sensor 7: Battery group 2

32

Users Manual PS4840 Power Supply System and Components

Components Part Monitoring Modules PSM-8 and PSM-81

4.2.2

Functions of Monitor Modules


1. Communication Between Monitor Module And Background Host One of important features of PSM-82 is to communicate with host. PSM-82 provides a RS232 and a RS422 port to host and communicate with the host according to PSM 82 Monitor Module and Its Communication Protocol with Host. The main functions: (1) Sending real time analog data from the monitoring unit to the host. (2) Sending real time digital data from the monitoring unit to the host. (3) Send the current state and alarm of the power supply system to the host. (4) Accept the system parameters configuration instructions. (5) Accept the instructions sent by the host, such as equalized/floating charge switch and smoke sensor reset instructions. Since the relationship between the host and the monitor module is that of master and slave, besides the alarm information is reported actively by the monitor module, the other processes such as reading, setting and controlling are start by the host, and the monitor module is always in the slave state. The monitor module won't report other data to the host without the instructions of the host. The analog values acquired by the host from the monitor module: busbar voltage, ambient temperature, ambient humidity, one branch circuit of reserved analog values, current of battery group 1, current of battery group 2, current of user module and current of transfer module. The digital values acquired by the host from the monitor module: two reserved high-level alarm states, AC mains supply over/under voltage, AC mains supply available/unavailable, fault of 4 rectifiers, alarm of water logging sensor, a reserved input low-level alarm state, infrared /magnetic door alarm, smog and fog alarm, transfer module power off, user module power off, fuse state of battery group 2, fuse state of battery group1, DC under voltage, equalize/float discharge state of battery, current-limiting state of 28A, On/Off state of transfer module, On/Off state of user module, and On/Off states of four rectifier modules. The alarm state acquired by the host from the monitor module: A reserved input digital value state, AC mains supply over/under voltage, AC mains supply available/unavailable, fault signals of four rectifier modules, water logging alarm, infrared/magnetic door alarm, transfer module power off, user module power off, fuse state of battery group 2, fuse state of battery group 1, DC under voltage,

33

Users Manual PS4840 Power Supply System and Components

Components Part Monitoring Modules PSM-8 and PSM-81

reserved values, overlimit of ambient temperature, and overlimit of ambient humidity. The setup parameters sent by the host to the monitor module are: voltage for disconnection of transfer module, voltage for disconnection of user module, current-limiting state of 28A, temperature alarm upper limit, temperature alarm lower limit, temperature sensor measurement lower limit, temperature sensor measurement upper limit, humidity alarm upper limit, humidity alarm lower limit, humidity sensor measurement lower limit, humidity sensor measurement upper limit, reserved capacity alarm upper limit, reserved capacity alarm lower limit, reserved values measurement lower limit, and reserved values measurement upper limit. The control commands sent by the host to the monitor module:

disconnection/connection of master load, disconnection/connection of slave load, disconnection/connection of rectifier module 4, disconnection/connection of rectifier module 3, disconnection/connection of rectifier module 2,

disconnection/connection of rectifier module 1, and current-limiting control. 2. Control Functions PSM-8 can send control signal according to detected values or the control commands sent by the host. (1) The host sends On/Off command of the rectifier module to the monitor module according to the rectifier module alarm signal sent by the monitor module and users requirements. Upon receiving the On/Off command, the monitor module enables On/Off of the corresponding rectifier module. (2) The host sends 28A current-limiting signal. The monitor module controls the state of current-limiting of 28A via the instructions. (3) The host sends user module power on/off and transfer module on/off commands to the monitor module according to users requirements. The monitor module sends corresponding control signals to control the power on/off of the user module and of the transfer module. When all rectifier modules are not powered, the monitor module disconnects the user module and transfer module at differently time according to the voltage of the busbar. When the voltage of the busbar is lower than the power off voltage of the user module, the user module will be disconnected.; when it is lower than the power off voltage of the transfer

34

Users Manual PS4840 Power Supply System and Components

Components Part Monitoring Modules PSM-8 and PSM-81

module, the transfer module will be disconnected. When the rectifier module is powered, the transfer module and user module will be connected. (4) Conduct equalized charge once if the two groups of batteries have operated for 60 days in mode of continuous floating charge, and conduct equalized charging if the charging power recovers after the power have been off for longer than15 minutes. 3. Detecting Functions PSM-8 monitor module can detect AC power distribution cabinet, modules, and DC power distribution cabinet and environment values. (1) AC power distribution cabinet PSM-8 can monitor AC mains available/unavailable state, AC mains over/under-voltage state. (2) Rectifier module Detect the fault state and on/off states of 4 rectifier modules. (3) DC power distribution--Bus-bar voltage, current of user load, current of transfer load, fuse state of user load, fuse state of transfer load, current of battery group 1, current of battery group 2, fuse state of battery group 1 and fuse state of battery group 2. (4) Environment values-- Environment temperature and humidity, smoke and fog alarm, infrared/magnetic door alarm and water-immersing sensor alarm according to the installation of sensors. Of the above detected values, bus-bar voltage, ambient temperature, humidity, current of modules, battery current, current of user load, current of transferring load are all analog values, others are digital values. 4. Power Failure Protection Functions When the power failure occurs in the monitor module, the configuration parameters and control state that have already been set remain unchanged. If the user wants to use the default parameters, he can short circuit the No.1 and 2 pins of J4 on the M1441U1 printed board of the monitoring module and the default configured values can recover after the system is powered on again.

35

User's Manual PS4840-2B/10 Power Supply System and Components

System Part PS4840/10 Power Supply System

Chapter 1 PS4840/10 Power Supply System


1.1
1.1.1

PS4840/10 System Configuration


Standard Full Configuration
1. Four HD4810-5 rectifier modules, one PSM-8 monitor module (communication protocol or software is needed if it needs to communicate with the host). 2. One AC&DC power distribution cabinet PD220/60AD or one single-phase power supply lightning protection box. 3. Optional environmental sensors: (1) Temperature sensor: HMW40Y (2) Smoking sensor: JTY-LZ901 (3) Infrared detector: XP-3 (4) Magnetic-door switch: PS1531 (5) Water-immersing sensor: LL131Z

1.1.2

Common Configuration
Rectifier module, environment values and AC power distribution of PS4840/10 power supply system can be configured as following: 1. Using 2, 3 or 4 rectifier modules can form 20A, 30A or 40A power supply system can be formed. 2. Environment values: temperature, humidity, smoke sensor, water-immersing, infrared and magnetic door. 3. PD220/60A power distribution cabinet enables good AC input protection function and lightning protection function, so it should be preferred in the configuration of the system. But HD4810-5 has AC input alarm function, so PD220/60AD power distribution cabinet may not be provided in the system. In addition, one single-phase lightning protection box SPD23SZ can be selected to satisfy the requirements for lightning protection.

41

User's Manual PS4840-2B/10 Power Supply System and Components

System Part PS4840/10 Power Supply System

1.2

Technical Performance of PS4840/10


PS4840/10 power supply system is used for small program controlled exchange, access network, transmission equipment, mobile communication, terrestrial stations of satellite communication and microwave communication equipment as well as other communication equipment.

1.2.1

Basic Operating Theory (PD220/60AD is configured)


As shown in Figure P1-1, Operating with one AC mains input, the AC&DC Power Distribution Cabinet feeds AC power to rectifier module. The DC output power of rectifier module is converged to the bus-bar through DC backboard. The DC output provides two DC output branch circuit and two branch circuits of battery for user. Under normal condition, operating according to preset parameters or customer instructions and monitoring each kind of state and data, the rectifier module, battery circuit and the load are all controlled by monitor module. If AC mains 1 failure occurs, the system changes to AC mains 2 to supply power automatically. If two branches AC mains fails at the same time, the battery connected with the system powers the load with a premise that the battery must be connected before power failure occurs. Under the conditions that the AC mains fail and the battery begins to discharge, the monitor unit reports the signal of AC mains unavailable. With the discharge of battery, battery terminal voltage begins to drop and when it drops below 46V, (2V higher than the voltage for secondary LVD), the monitor module will report DC under-voltage alarm signal. When the battery voltage reaches 44V due to discharging, battery protection circuit loop acts for the first time (secondary LVD) and disconnects the user load; When the battery discharges to the end of discharge voltage 41V, battery protection circuit loop acts for the second time (battery protection) disconnects the battery and the transfer load, and enables automatic battery protection (The LVD order of the above loads is the default value for monitoring. The user can allocate high priority load and low priority load according to the above order to connect the low priority load to the user load interface and the high priority load to the transfer load interface in order to ensure that the low priority load will be disconnected and then the high priority load be disconnected in case of LVD). When the AC mains supply recovers, the system restores to normal work.

42

User's Manual PS4840-2B/10 Power Supply System and Components

System Part PS4840/10 Power Supply System

Each

environment

value

including

smoking,

infrared/magnetic

door,

water-immersing, temperature and humidity can be acquired and reported by the system through monitor module.
AC Input
AC mains I AC mains II

AC Distribution output output

power module

power module

power module

power module

DC backboard

Sensor Smoking Temperature Humidity Water infrared/ gate-magnetic Battery group 1 Battery group 2 User 1 User 2 Monitoring module

Host computer

Figure P1-1

Operating theory of PS4840/10 power supply system

43

User's Manual PS4840-2B/10 Power Supply System and Components

System Part PS4840/10 Power Supply System

1.2.2

Specifications
1. AC Input (PD220/60AD is configured) Two branch circuits of single-phase AC mains input (one for master input, the other for reserved input) Rated input voltage: 220VAC Maximum input current: 63A Frequency: 50Hz 10% 2. Battery Input Working in equalized or floating charge mode, the positive and negative poles of two groups of batteries are connected in parallel with the DC output of the rectifier module. Rated input voltage of each group of battery is 48V and the rated capacity is 100Ah or more. 3. AC Power Distribution output Three circuits of output, 220VAC and 20A for each. 4. DC Output Standard voltage: -48VDC Voltage regulation range: -43V ~ -58V (adjustable inside the rectifier module ) Total DC output current: 40A DC power distribution branch-circuit: Users load 1 Users load 2 Battery 1 Battery 2 5. DC Output Noise Psophometrically weighted noise: Broad band noise voltage: 2mV 150KHz) 30A 30A 45A 45A

50mV (3.4KHz

20mV (150KHz 30MHz) Peak-peak noise voltage: 400mV(within 20MHz)

44

User's Manual PS4840-2B/10 Power Supply System and Components

System Part PS4840/10 Power Supply System

6. Voltage Regulation Precision Load regulation: Line regulation: 0.5% 0.1%

7. Operating Efficiency 87% 8. Dynamic Load Response When the load is changed from 20% to 80% rated load, recovery time is shorter than or equal to 200mS and the over-shoot is lower than or equal to 0.5%. 9. Anti-lightning Strike Index Maximum operating line-to-neutral voltage: 385V, 50Hz Maximum discharge: The maximum through capacity is 40kA, once, 8/20 surge current Rated through capacity: 20kA, 20 times, 8/20 Maximum response time: 25ns 10. Insulation Resistance The insulation resistance between DC part, AC part and cases should be higher than 2M (experimental voltage is 500VDC). s surge current s

11. Insulation Strength Apply 50Hz, 3000V AC power between AC input and DC output for 1 minute, there should be no breakdown nor arc; Apply 50Hz, 1500V AC power between AC mains and case for 1min, there should be no breakdown nor arc; Apply 50Hz, 500V AC power between cases and DC output for 1min, there should be no breakdown nor arc. 12. Mechanical Features Cooling method: Air cooling Dimension: 177mm 483mm 386.2mm (Height Width Depth)

Weight (rectifier module excluded): 3.18 Kg

45

User's Manual PS4840-2B/10 Power Supply System and Components

System Part PS4840/10 Power Supply System

1.3

Installation of PS4840/10
Upon the transportation of PS4840/10, monitor module and all rectifier modules have already been installed in the main case of the system, as shown in Figure P1-2. (System capacity is 30A, combined by three HD4810-5 rectifier modules and one monitor module). Popular 19-inch/4U structure is adopted in main case of PS4840/10 power supply system, with system backboard installed in the rea part used for electrical connection with external devices.

PSM8
OFF VocEN

HD48105
ON OFF

HD48105
ON OFF

HD48105
ON OFF

ON RESET

VocDIS VinON VinALM FAIL RECHARG TXD Vin ALM RUN Vin ALM RUN Vin ALM RUN

RUN

RXD

Figure P1-2 Main case of PS4840-2B/10 power supply system


1. Holes for fixing screws 3. Monitor module PSM-8 5. Rectifier module 7. Rectifier module 2. False ESC panel 4. False panel of rectifier module 6. Rectifier module

The parts need to be installed at the site of users of PS4840/10 include AC power distribution cabinet PD220/60AD, main case of the system, lightning protection box and sensors. Please refer to the Section 2.3 Installation of PD220/60AD in Chapter two of Part One System (page 12) and Installation of Sensors of PS4840/10 and PS4840-2/10 Power Supply Systems in Chapter Six of Part Two System for installation of AC power distribution cabinet PD220/60AD and sensors. The lightning protection box has its own users manual. The installation of the main case of the system is mainly described in the following. When connecting the main case with external equipment, users only need to finish the electrical connection between the main case and external equipment.

46