TRANSFORMER OIL QUALITY AND DISSOLVED GAS ANALYSIS

COTABATO LIGHT POWER CO.


COTABATO CITY

MAY 26, 2011

A subsidiary of

1150 Pres. Quirino Avenue Extension, Paco, Manila 1007, Philippines Tel Nos.: (02) 563-8338 to 42 Fax Nos.: (02) 561-9490 / 563-2529 / 562-8862 Website: http://www.asiaphil.com * http://www.giniphil.com

Service Report
Project Name : TRANSFORMER OIL QUALITY AND DISSOLVE GAS ANALYSIS Customer : COTABATO LIGHTS AND POWER CO. Location : COTABATO CITY Date : MAY 26, 2011

Oil Quality and Dissolve Gas Analysis


Recommendation/Analysis: See all the test results. It will serve as our reference data for future maintenance to be conducted.

Oil Quality and Dissolve Gas Analysis


Equipment : POWER TRANSFORMER Capacity : 10/12.5MVA Serial Number: T990151 Brand : SHIHLIN EQUIPMENT TEST SAMPLE SAMPLE NUMBER

OIL QUALITY

DISSOLVE GAS

REMARKS

CLPC Power Transformer

12188

Data are within standard limits.

Data are within standard limits.

Fit for operation.

Prepared by:

Field A subsidiary of

Marloo ray N. Belviz, REE Service/ Testing Engineer


1150 Pres. Quirino Avenue Extension, Paco, Manila 1007, Philippines Tel Nos.: (02) 563-8338 to 42 Fax Nos.: (02) 561-9490 / 563-2529 / 562-8862 Website: http://www.asiaphil.com * http://www.giniphil.com

Dissolved Gas Analysis and Oil Quality Results

A subsidiary of

1150 Pres. Quirino Avenue Extension, Paco, Manila 1007, Philippines Tel Nos.: (02) 563-8338 to 42 Fax Nos.: (02) 561-9490 / 563-2529 / 562-8862 Website: http://www.asiaphil.com * http://www.giniphil.com

LABORATORY RESULTS NAME PLATE DATA


Location Company Code Serial Number Make/Brand Year Manufactured MVA Oil Temperature Notes : CLPC SS : Power Transformer : T990151 : Shihlin : : 10/12.5 MVA : : :

CUSTOMER DATA
Customer Address Sample ID Analysis Date Container Oil Type : Cotabato Light Power Co : Cotabato City : 12188 : 05/26/11 : Plastic Bottle : Mineral

All detection limits are less than 1 ppm.

Note: Interpretations and diagnostics developed using mineral oil.

DISSOLVED GAS RESULTS ASTM 3612


* Hydrogen * Methane * Ethane * Ethylene * Acetylene * Carbon Monoxide Carbon Dioxide Nitrogen Oxygen Total Diss. Comb. Gas Total Gas Content H2 CH4 C2H6 C2H4 C2H2 CO CO2 N2 O2 TDCG 2 ppm 1 ppm 0 ppm 0 ppm 0 ppm 5 ppm 113 ppm 17432 ppm 6150 ppm 8 ppm 23704 ppm

* Combustible gasses.

Est. TCG (%)

0.04

Estimated Total Combustible gas (TCG) if transformer has a Gas space over the oil. The value is calculated from the Solubility factors of the gasses involved.

INTERPRETIVE or KEY GAS METHOD (present sample only) INDICATES:


Hydrogen within normal limits (< 1500ppm). Methane within normal limits (< 80ppm). Ethane within normal limits (< 35ppm). Ethylene within normal limits (< 150ppm). Acetylene within normal limits (< 7ppm). Carbon Monoxide within normal limits (< 1000ppm). Carbon Dioxide within normal limits (< 10000ppm).

ROGERS RATIOS (present sample only) INDICATES:


CH4/H2 = C2H6/CH4 = C2H4/C2H6 = C2H2/C2H4 = CO/CO2 = 0.40 0.17 2.79 0.00 0.04 Code = 0 Code = 0 Code = 1 Code = 0 Since total TDCG < 500ppm, the Rogers Ratio indicated below is considered less significant.

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) Suggest:
TDCG Level: 8 ppm A subsidiary Sampling Interval: ----of Rate: ----- ppm/day
1150 Pres. Quirino Avenue Extension, Paco, Manila 1007, Philippines Tel Nos.: (02) 563-8338 to 42 Fax Nos.: (02) 561-9490 / 563-2529 / 562-8862 Website: http://www.asiaphil.com * http://www.giniphil.com

Operating Interval: ----No prior sample found for this sample. Therefore cannot perform guideline.

TRANSFORMER OIL TESTING LABORATORY OIL QUALITY TEST REPORT Customer Cotabato Light Power Co. Address Cotabato City Fax No. Contact --Sample No. Sample Type Container Date Sampled Date Tested Capacity Rated Voltage Oil Volume Mass Oil Type Units NTU dynes/cm mg KOH/g kV ppm % T-m pS/m % Abs. nm cSt cSt mg KOH/g % C 12188 Mineral Oil 1 Litter Bottle -05/26/11 10000/12500Kva ---Mineral oil ASTM Method D1500 D1524 D6081 D971 D974 D877 D1533B D924 D924 D1169 Calculated D924 D2668 D6802 D1298 D445 D445 D2440 D1275B D92

SITE & NAMEPLATE DATA Location CLPC SS Serial No. T990151 Brand Shihlin Year Built -%Z -Test Description 1) Color 2) Visual Examination 3) Turbidity 4) Interfacial Tension 5) Neutralization Number 6) Dielectric Strength, 2.5mm gap 7) Water Content 8) Oil Power Factor @ 60Hz, 25 C 9) Dielectric Constant () 10) Resistivity () 11) Conductivity 12) Oil Power Factor @ 60Hz, 100 C 13) Oxidation Inhibitor Content 14) Dissolved Decay Products 15) Specific Gravity 16) Viscosity, 40 C 17) Viscosity, 100 C 18) Oxidation Stability, 72 hours Total Acid Number Sludge Content, by Mass 19) Corrosive Sulfur A subsidiary Flash Point 20)
of

Result L 0.5 Clear & Bright 43.4 0.00122 44.49 4.2 0.023 2.166 5.03 0.20

1150 Pres. Quirino Avenue Extension, Paco, Manila 1007, Philippines Tel Nos.: (02) 563-8338 to 42 Fax Nos.: (02) 561-9490 / 563-2529 / 562-8862 Website: http://www.asiaphil.com * http://www.giniphil.com

21) Fire Point 22) 2-Furfuraldehyde in Oil

C g/L

D92 D5837

IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment. IEEE C57.106-2006 Suggested Limits for Continued Use of Service-Aged Insulating Oil (69kv) Test Description Units IEEE LIMIT ASTM Method VALUES 1) Color L2.5(max) D1500 2) Visual Inspection Clear D1524 3) Interfacial Tension dynes/cm 25(min) D971 4) Neutralization Number mg 0.20(max) D974 KOH/g 5) Dielectric Strength, disk electrode kV Unspecified D877 6) Water content ppm 35(max) D1533B 7) Oil power factor@60 Hz, 25C % 0.50(max) D924 8) Dielectric constant D924

IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers. IEEE Std C57.104-2008
Table 6- Rogers ratios for key gases Case 0 1 2 3 4 5 R2 C2H2/C2H4 <0.1 <0.1 0.1 to 3.0 <0.1 <0.1 <0.1 R1 CH4/H2 >0.1 to <1.0 <0.1 0.1 to 1.0 >0.1 to <1.0 >1.0 >1.0 R5 C2H4/C2H6 <0.1 <0.1 >3.0 1.0 to 3.0 1.0 to 3.0 >3.0 Suggested fault diagnosis Unit normal Low-energy density arcing -PDa Arcing-High energy discharge Low Temperature thermal Thermal <700C Thermal >700C

There will be a tendency for the ratios R2 and R5 to increase to a ratio above 3 as the discharge develops in intensity.