SPECIFICATION DATA
LQR1
FEATURES
Sensor for measuring and controlling the air quality in air-conditioned rooms. Heated metal oxide semiconductor gas sensor which changes its electrical conductivity in the presence of / upon an increase in the concentration of air pollutants. Own power supply unit 24 Vac. Current consumption 200 mA Output a) sliding signal for minimum limitation of the CR controller b) 0...10 V Plastic housing for wall mounting
transmits a 0...10-volt signal. This signal is applied to one (or more) CRE 1s, so that (given an adjustable signal current of y) the CRE 1(s) switch(es) and (in conjunction with a two-point switch) can e.g. turn on a fan or activate an flap. Because the CRE 1 is connected to 24 AC current, no CR power supply unit is necessary. If time lags are necessary for stepped switches, the CRW 3 (three times two-point) output modules should be employed. In this case, a CRN 1 power supply unit is needed, or the CRW 3 must be supplied with electricity via a CR controller already in place. Maximum limitation of the output signal (y and/or y) As a rule, because of the air heater's design, given very low outdoor temperatures, the external air flap cannot open to the maximum extent insofar as the necessary temperature of the incoming air would then no longer be guaranteed. In order to guarantee the necessary temperature of the incoming air, the maximum permissible extent of opening of the external air flap can be adjusted using the P4 potentiometer. This maximum limitation will be in effect only if terminals 5 and 6 of the LQR 1 are connected with each other. This makes it possible to operate in the "normal" operational mode without maximum limitation and to shift to maximum limitation only when a certain limit value is attained (via an external switching signal e.g. from an outdoor thermostat).
b) c)
EN0B0289 GE51R1000
LQR1
ELECTRICAL CONNECTION
There is a three-prong connection in the controller.
ASSEMBLY
After unscrewing both screws "C1" and "C2", the upper portion "A" of the device can be removed from the base "B". The base "B" is then fastened to the wall with two screws ("D1" and "D2"). Complete the electrical connection. Insert the device onto the base "B". Select a suitable measuring site in the inside of the room. Do not install the device directly next to doors or windows and air vents or near radiators / heat sources. Height: approx. 1.50 to 2.00 meters.
C1
1
D1
2 3 4 5 6
Terminals 1 - 2: 24 Vac, with terminal 2 acting as the system mass. Terminal 3: Terminal 4: Output 0...10 V (necessary only for applications "b" or "c") Output Ymin (necessary in conjunction with CR controllers, see application "a"). Terminal 4 of the LQR 1 is to be connected with: terminal 14 in the case of the CRR 1 or CRX 1 terminal 2 in the case of the CRF 5 terminal 7 in the case of the CRR 2 the blue wire of the BVK 3 in the case of the CRS 3 Terminals 5 - 6: Necessary only if maximum limitation is to be used. When connecting 5 6 via an external switch (e.g. an outdoor thermostat), the maximum limitation comes into effect.
C2
D2
CENTRATHERM
EN0B0289 GE51R1000
LQR1
The potentiometer S can also be thought of as shifting the control range. Vary the basic setting (S = 2) only in small steps (one graduation at a time). When S has a small value, the influence on the proportion of outdoor air is low. When S has a high value, the same change in the concentration of pollutants has a stronger influence on the proportion of outdoor air.
Potentiometer P4 Maximum Limitation of the Output Signal y (or y, as the case may be)
Using the potentiometer P4, the desired permissible maximum proportion of outdoor air can be adjusted. This is necessary only in certain cases (see also above). When set at 100%, the external air flap can be opened to the maximum possible extent, if necessary.
Potentiometer S Steepness
The higher the value set using the potentiometer S, the faster y (or y, as the case may be) rises and the more the proportion of outdoor is elevated as the concentration of pollutants increases.
EN0B0289 GE51R1000
LQR1