Sei sulla pagina 1di 64

SION Vacuum Circuit-Breakers

R-HG11-172.tif

2 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Contents

Contents Page

SION Vacuum Description 5


Circuit-Breakers General
Construction and mode of operation, standards
6
7
1
Ambient conditions,
current carrying capacity and dielectric strength 10
Medium-Voltage Equipment Product range overview and basic equipment 11

Catalog HG 11.02 · 2006

Equipment Selection 13
Ordering data and configuration example
Selection of basic types, standard circuit-breakers 15
14
2
Secondary equipment for standard circuit-breakers 23
Selection of basic types, slide-in modules 28
Secondary equipment for slide-in modules 32
Accessories and spare parts 37

Technical Data 41
Electrical data, dimensions and weights:
Voltage levels 7.2 kV, 12 kV, 17.5 kV 42
3
Voltage level 24 kV 56
Operating times, short-circuit protection
of motors, consumption data of releases 59
Circuit diagrams 60

Annex 61
Inquiry form
Configuration instructions
62
63 4
Configuration aid Foldout page

© Siemens AG 2006

Siemens HG 11.02 · 2006 3


SION Vacuum Circuit-Breakers

R-HG11-173.tif

4 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Description
Contents

Contents Page

Description 5
General 6 1
Construction and mode of operation:
Switching medium 7
Pole assemblies 7
Operating mechanism 7
Trip-free mechanism 7
Releases 8
Closing / Circuit-breaker tripping signal 8
Interlocking 8
Low-voltage interface 8
Slide-in module 9
R-HG11-174.tif

Standards 9
Ambient conditions 10
Industrial application: Refinery
Current carrying capacity 10
Dielectric strength 10
Product range overview and basic equipment 11

Siemens HG 11.02 · 2006 5


Description SION Vacuum Circuit-Breakers
General

SION vacuum circuit-breaker from 7.2 to 24 kV – The Innovative

SION vacuum circuit-breakers control all switching capacitors, generators, filter circuits, motors and
duties in medium-voltage distribution systems and are reactors. The comprehensive installation accessories

1 suitable for installation in all customary air-insulated


medium-voltage switchgear types. They are applicable
for operation of e.g. overhead lines, cables, transformers,
enable easy integration in the panel and form –
maximally equipped as a slide-in module – almost the
complete circuit-breaker compartment.

SION standard circuit-breaker – the variable R-HG11-167.eps


SION slide-in module – the complete

R-HG11-168.eps

Our comprehensive range of standard circuit-breakers offers The slide-in module contains all components required for
a wide selection for pole-center distances and widths across the circuit-breaker compartment of a panel. It consists of the
flats as well as various built-in accessories packages for circuit-breaker on a drawout element with contact arms,
voltage levels from 7.2 to 24 kV. The drawout element, fitted in a cartridge with side and rear walls. The module is
contact arms, contact systems and bushings enable easy equipped with bushings, fixed contacts, shutters and the
integration in all customary medium-voltage switchgear shutter mechanism. The surfaces of the side and rear walls
types. Identical dimensions and connection dimensions form the tested connection compartment.
across several voltage levels reduce planning costs and the
diversity of panel versions. High reliability and availability
are just as much a matter of course as 10,000 maintenance-
free operating cycles.

6 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Description
Construction and mode of operation

Switching medium
The vacuum switching technology of the vacuum interrup-
ters, which has been proven for 30 years, serves as arc-
quenching principle.

Pole assemblies
The pole assemblies consist of the vacuum interrupters and
1
the pole shells. The vacuum interrupters are air-insulated

R-HG11-170.eps
and freely accessible. The pole assemblies are fixed on the
mounting plate of the operating mechanism and supported
by means of the pole shell. The vacuum interrupter (3) is Vacuum circuit-breaker
3AE12
mounted rigidly to the upper interrupter support. The lower 17.5 kV / 25 kA /
part of the interrupter is guided in the lower interrupter 1250 A

support, allowing axial movement. The pole shell (4) absorbs


the external forces resulting from switching operations and
the contact pressure. HG11-2500 eps 1

2
Operating mechanism 1 Separating shell
3 to the operating
The whole operating mechanism is mounted on its mount-
mechanism
ing plate, including the motor, releases, indicators and 4 2 Upper connection
actuating devices. 3 Interrupter
Stored-energy operating mechanism 5 4 Pole shell
5 Lower connection
The operating mechanism is a stored-energy spring mechan- 6 6 Bell-type insulator
ism. The force is transmitted from the operating mechan-
ism to the pole assemblies via operating levers. The closing Pole structure
spring can be charged either electrically or manually and
latches automatically in when charging is complete. The
closing spring acts as the stored-energy mechanism.
To close the breaker, the closing spring can be unlatched
either mechanically by means of the local “ON” pushbutton
or electrically by remote control. The closing spring charges 1
the contact-pressure / opening springs as the breaker closes. 1 Cover of low-voltage
interface
The now discharged closing spring will be charged again 2 Central control board
automatically by the mechanism motor. 2
HG11-2501 eps

The breaker is now capable of performing the OPEN – CLOSE


– OPEN operating sequence that is required for an unsuc-
cessful auto-reclosing operation. All stored-energy mecha- Front view
nisms perform the switching duties of synchronizing and
rapid load transfer as well as auto-reclosing.

Trip-free mechanism
In the event of an opening command being given after a 3 1 Auxiliary switch
2 1st release
closing operation has been initiated, the moving contacts 1 4
3 Terminal strip
return to the open position and remain there even if the
5 4 Motor
closing command is sustained. This means that the contacts
2 5 Closing solenoid
of the vacuum circuit-breakers are momentarily in the closed 6
6 Closing spring
position. 7 7 Gear
HG11-2502 eps

The motors for charging the closing spring operate in


short-time duty. Therefore the voltage and power con-
Operating mechanism
sumption might differ from the data of the rating plate. without cover

Siemens HG 11.02 · 2006 7


Description SION Vacuum Circuit-Breakers
Construction and mode of operation

Releases The NO contact S6 makes brief contact while the circuit-


A release is a device which transfers commands from an breaker is opening, and this is often used to operate a
external source, such as a control room, to the latching hazard-warning system which, however, is only allowed to
mechanism of the circuit-breaker so that it can be opened or respond to automatic tripping of the circuit-breaker. There-
closed. The releases are designed for short-time duty up to fore, the signal from the NO contact must be interrupted

1 1 minute and are reset internally. The various types of


releases available are described in detail below:
when the circuit-breaker is being opened intentionally. This
is accomplished under local control with the cut-out switch
S7 that is connected in series with the NO contact.
• The closing solenoid unlatches the charged closing spring
of the vacuum circuit-breaker, closing it by electrical means. For the corresponding circuit diagrams, refer to page 60.

• Shunt releases are used for automatic tripping of vacuum


circuit-breakers by suitable protection relays and for delib- Interlocking
erate tripping by electrical means. They are intended for Mechanical interlocking
connection to an external power supply (DC or AC voltage) At the interface of the mechanical interlocking of the
but, in special cases, may also be connected to a voltage vacuum circuit-breaker, sensors on the switchgear side can
transformer for manual operation. check the switch position and prevent the associated dis-
• Current-transformer operated releases comprise a connector from being closed while the vacuum circuit-
stored-energy mechanism, an unlatching mechanism, and breaker is closed. The system also prevents the vacuum
an electromagnetic system. They are used when there is no circuit-breaker from being closed while the associated
external source of auxiliary power (e.g. a battery). Tripping disconnector is in a faulty position.
is effected by means of a protection relay (e.g. overcurrent- Vacuum circuit-breakers mounted on drawout elements are
time protection) acting on the current-transformer operated mechanically interlocked, with the result that the handle for
release. racking the drawout element can only be inserted in the
• Undervoltage releases comprise a stored-energy mecha- “OPEN” position. The lock of the drawout element can only
nism, an unlatching mechanism and an electromagnetic be released in the disconnected position by operating the
system which is permanently connected to the secondary or pushing handles.
auxiliary voltage while the vacuum circuit-breaker is closed. If the vacuum circuit-breaker on the drawout element is in
If the voltage falls below a predetermined value, unlatching an intermediate position (neither in the service nor in the
of the release is enabled and the circuit-breaker is opened disconnected position), operation is not possible due to the
via the stored-energy mechanism. mechanical interlocking.
The maximum equipment are 2 freely selected releases. For Electrical interlocking
release combinations, refer to page 23 or page 32. For con-
The auxiliary and signaling contacts which show the switch
sumption data, refer to page 59.
position of the vacuum circuit-breaker or the position of the
drawout element can be integrated in the switchgear inter-
Closing / Circuit-breaker tripping signal locking concept in order to exclude impermissible switching
In the standard version, the vacuum circuit-breakers can be sequences.
remote-closed electrically. In addition, they can be mechani-
cally closed locally by direct unlatching of the closing spring. Low-voltage interface
If constant CLOSE and OPEN commands are present at the The separate cover enables easy access to the low-voltage
vacuum circuit-breaker at the same time, the vacuum circuit- interface. All possible customer-side control and signaling
breaker will return to the open position after closing. It re- connections are concentrated here.
mains in this position until a new CLOSE command is given.
In this manner, continual closing and opening (= “pumping”)
is prevented.
The charging status of the closing spring in the vacuum
circuit-breaker can be interrogated electrically by means of
the position switch.

8 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Description
Construction and mode of operation

Slide-in module
Besides the circuit-breaker installation equipment available for
standard circuit-breakers by means of the packages for the
drawout element, contact arms, fixed contacts and bushings,
it is also possible to supply a complete slide-in module.
The slide-in module contains all necessary components for
the circuit-breaker compartment of a panel. It consists of the
circuit-breaker on a drawout element with contact arms,
1
mounted in a cartridge with side and rear walls, equipped
with bushings, fixed contacts, shutters and shutter mecha-
nism. The surfaces of the side and rear walls form the tested

R-HG11-171.eps
connection compartment.
The vacuum circuit-breaker on the drawout element is
racked into the cartridge with the associated handle by the
rotary movement of the spindle. The shutter mechanism
is controlled by lateral gates, and the shutters are opened Slide-in module
for contacting. Signals for the service and disconnected 1 Contact system
positions are transmitted to the module connector at the 2 Fixed contact 6 Contact arm
3 Shutter 7 Low-voltage interface
low-voltage interface of the vacuum circuit-breaker via the
4 Bushing 8 Vacuum circuit-breaker
position switches of the drawout element.
5 Cartridge 9 Drawout element

Standards
The vacuum circuit-breakers conform to the following
standards:
• IEC 60 694
• IEC 62 271-100
All SION vacuum circuit-breakers fulfil the endurance
classes E2, M2 and C2 according to IEC 62 271-100.
The slide-in modules have been tested according to
• IEC 62 271-200 regarding
– Dielectric strength
– Temperature rise
– Switching capacity.

Siemens HG 11.02 · 2006 9


Description SION Vacuum Circuit-Breakers
Ambient conditions, current carrying capacity and dielectric strength

Ambient conditions
Condensation can occasionally occur under the ambient
conditions shown opposite.
SION vacuum circuit-breakers are suitable for use in the
following climatic classes according to IEC 60 721, Part 3-3:

1 40°C
Climatic ambient conditions:
Biological ambient conditions:
Class 3K41)
Class 3B1

max. 95% per day Mechanical ambient conditions: Class 3M2


max. 90% per month Chemically-active substances: Class 3C22)
-5°C
Mechanically-active substances: Class 3C23)

1) Low temperature limit: - 5 °C


HG11-2515_en eps

2) Without icing and wind-driven precipitation


3) Restriction: Clean insulation parts

Current carrying capacity


The rated normal currents specified in the diagram have
been defined according to IEC 62 271-100 for an ambient
3400
HG11-2516a_en eps

temperature of + 40 °C and apply to open switchgear.


A
3000 For enclosed switchgear the data of the switchgear
Rated normal current

5
manufacturer applies.
2600
At ambient temperatures below + 40 °C, higher normal
4
2200 currents can be carried (see diagram):
3 Characteristics curve 1 = Rated normal current 800 A
1800
Characteristics curve 2 = Rated normal current 1250 A
1400 Characteristics curve 3 = Rated normal current 2000 A
2 Characteristics curve 4 = Rated normal current 2500 A
1000 Characteristics curve 5 = Rated normal current 3150 A
1
600
10 20 30 40 50 60 °C 70
Ambient temperature Dielectric strength
The dielectric strength of air insulation decreases with
increasing altitude due to low air density. According to
IEC 60 694, the rated lightning impulse withstand voltage
values specified in the chapter “Technical Data” apply to a
1.50
HG11-2517c_en eps

site altitude of 1000 m above sea level. For an altitude


above 1000 m, the insulation level must be corrected
Altitude correction factor

1.40 according to the opposite diagram.


The characteristic shown applies to the rated short-duration
1.30 power-frequency withstand voltage and the rated lightning
impulse withstand voltage.
1.20 To select the devices, the following applies:
U W U 0 x Ka
1.10 U Rated withstand voltage under standard reference atmosphere
U0 Rated withstand voltage requested for the place of installation
Ka Altitude correction factor according to the opposite diagram
1.00
1000 1500 2000 2500 3000 3500 m 4000 Example
Site altitude
For a requested rated lightning impulse withstand voltage
of 75 kV at an altitude of 2500 m, an insulation level of
90 kV under standard reference atmosphere is required as
a minimum:
90 kV W 75 kV x 1.2

10 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Description
Product range overview and basic equipment

Product range overview


circuit breaking
Pole center distance (in mm)

normal current
Rated short-

150 160 210 275


voltage

current
Rated

Rated Width across flats (in mm)

Type
3AE10
kV
7.2
kA
16
A
800/1250
205
n
275
no
310
no
205
n
275
n
310
n
205
n
275
no
310
no
310
1
20 800/1250 n no no n n n n no no
25 800/1250 n no no n n n n no no
25 2000 no
31.5 800/1250 n no no n n n n no no
31.5 2000/2500 no
40 1250/2000 no
40 2500/3150 no
3AE11 12 16 800/1250 n no no n n n n no no
20 800/1250 n no no n n n n no no
25 800/1250 n no no n n n n no no
25 2000/2500 no
31.5 800/1250 n no no n n n n no no
31.5 2000/2500 no
40 1250/2000 no
40 2500/3150 no
3AE12 17.5 12.5 800/1250 n no no n n n n no no
16 800/1250 n no no n n n n no no
25 800/1250 n no no n n n n no no
25 2000/2500 no
31.5 800/1250 n no no n n n n no no
31.5 2000/2500 no
40 1250/2000 no
40 2500/3150 no
3AE13 24 12.5 800/1250 no
16 800/1250/2000 no no
20 800/1250 no no
20 2000/2500 no no
25 800/1250 no no
25 2000/2500 no no
n Standard circuit-breaker (fixed-mounted/drawout version with installation accessories) o Slide-in module
Basic equipment

Features Standard Alternative Remarks

Operating mechanism Electrical operating mechanism – Also for manual operation


Closing Closing solenoid and – –
electrical manual closing
1st release Shunt release Undervoltage release, –
c.t.-operated release
2nd release Without Shunt release, –
undervoltage release,
c.t.-operated release
Varistor circuit For W 60 V DC – For limiting switching
overvoltages
Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC –
Plug connection 27-pole terminal strip 24-pole plug, 12 NO + 12 NC not available
64-pole plug with 24-pole plug
Anti-pumping Available – –
Circuit-breaker tripping Without Possible –
signal
Operating cycle counter Available – –
Position switches 2 – –
Mechanical interlocking Available for slide-in module Mechanical interlocking for circuit-breaker Required for slide-in module
Installation accessories Fixed-mounted With drawout element, contact arms, contact –
system, with fixed contacts and bushings,
complete slide-in module

Siemens HG 11.02 · 2006 11


SION Vacuum Circuit-Breakers

R-HG11-175.tif

12 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Contents

Contents Page

Equipment Selection 13
Ordering data and configuration example 14
Selection of basic types, standard circuit-breakers:
Voltage level 7.2 kV 15
Voltage level 12 kV 17
Voltage level 17.5 kV 20
Voltage level 24 kV 22

Secondary equipment for standard circuit-breakers 23


Additional equipment for standard circuit-breakers

Selection of basic types, slide-in modules:


27
2
Voltage level 7.2 kV 28
Voltage level 12 kV 29
R-HG11-176.eps

Voltage level 17.5 kV 30


Voltage level 24 kV 31
Standard circuit-breaker

Secondary equipment for slide-in modules 32


Additional equipment for slide-in modules 36
Accessories and spare parts 37
R-HG11-168.eps

Slide-in module

Siemens HG 11.02 · 2006 13


Equipment Selection SION Vacuum Circuit-Breakers
Ordering data and configuration example

Order number structure Special versions ( ) «


The vacuum circuit-breakers consist of a primary and a In case of special versions, “-Z” is added to the order num-
secondary part. The relevant data make up the 16-digit ber and a descriptive order code follows. If several special
order number. The primary part covers the main electrical versions are required, the suffix “-Z” is listed only once.
data of the circuit-breaker poles. The secondary part covers If a requested special version is not in the catalog and can
the auxiliary devices which are necessary for operating and therefore not be ordered via order code, it has to be identi-
controlling the vacuum circuit-breaker. fied with Y 9 9 after consultation. The agreement hereto
Order codes is made between your responsible sales partner and the
order processing department (PTD M C S) in our Switchgear
Individual equipment versions, identified with 9 or Z in the
Factory in Berlin.
9th or 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.

2 Position:
a: alphabetical
1
3 A
2 3
E
4
n
5
n
n: numerical
6
n
7
n


8
n
9
a
10 11 12 –
a n n –
13 14 15 16
n a a n –
Order codes
« n n n
Order No.:
Primary part
1st position Superior group
Switching devices

2nd position Main group


Circuit-breaker

3rd position Subgroup


Circuit-breaker type series

4th to 8th position Basic equipment


Design and ratings
primary part

Secondary part
9th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment

Order codes
Group of 3 after the Order No.
Format: a n a

Special versions ( )«
Initiated with “-Z”
Group of 3 after the Order No.
Format: a n n

Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a con-
figuration example on each side of the chapter “Equipment
Selection”. For the selection of the secondary part, always
the last example of the primary part was taken over and
continued, so that at the end of the equipment selection On the foldout page we offer a configuring aid.
(pages 27 and 36) a completely configured circuit-breaker Here you can fill in the order number you have deter-
results as an example. mined for your circuit-breaker.

Example for Order No.: 3 A E 1 0 8 3 – 2 n n n n – n n n n


Order codes:

14 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, standard circuit-breakers

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 – 1
310 1250 3 A E 1 0 8 2 – 2
275 800 3 A E 1 0 7 2 – 1
275 1250 3 A E 1 0 7 2 – 2
205 800 3 A E 1 0 6 2 – 1

2
205 1250 3 A E 1 0 6 2 – 2
160 310 800 3 A E 1 0 5 2 – 1
310 1250 3 A E 1 0 5 2 – 2
275 800 3 A E 1 0 4 2 – 1
275 1250 3 A E 1 0 4 2 – 2
205 800 3 A E 1 0 3 2 – 1
205 1250 3 A E 1 0 3 2 – 2
150 310 800 3 A E 1 0 2 2 – 1
310 1250 3 A E 1 0 2 2 – 2
275 800 3 A E 1 0 1 2 – 1
275 1250 3 A E 1 0 1 2 – 2
205 800 3 A E 1 0 0 2 – 1
205 1250 3 A E 1 0 0 2 – 2
7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 – 1
310 1250 3 A E 1 0 8 3 – 2
275 800 3 A E 1 0 7 3 – 1
275 1250 3 A E 1 0 7 3 – 2
205 800 3 A E 1 0 6 3 – 1
205 1250 3 A E 1 0 6 3 – 2
160 310 800 3 A E 1 0 5 3 – 1
310 1250 3 A E 1 0 5 3 – 2
275 800 3 A E 1 0 4 3 – 1
275 1250 3 A E 1 0 4 3 – 2
205 800 3 A E 1 0 3 3 – 1
205 1250 3 A E 1 0 3 3 – 2
150 310 800 3 A E 1 0 2 3 – 1
310 1250 3 A E 1 0 2 3 – 2
275 800 3 A E 1 0 1 3 – 1
275 1250 3 A E 1 0 1 3 – 2
205 800 3 A E 1 0 0 3 – 1
205 1250 3 A E 1 0 0 3 – 2

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 20 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 310 mm 0 8 3 – 2

Example for Order No.: 3 A E 1 0 8 3 – 2 n n n n – n n n n


Order codes:

Siemens HG 11.02 · 2006 15


Equipment Selection SION Vacuum Circuit-Breakers
Selection of basic types, standard circuit-breakers

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 – 1
310 1250 3 A E 1 0 8 4 – 2
310 2000 3 A E 1 0 8 4 – 4
275 800 3 A E 1 0 7 4 – 1
275 1250 3 A E 1 0 7 4 – 2

2
205 800 3 A E 1 0 6 4 – 1
205 1250 3 A E 1 0 6 4 – 2
160 310 800 3 A E 1 0 5 4 – 1
310 1250 3 A E 1 0 5 4 – 2
275 800 3 A E 1 0 4 4 – 1
275 1250 3 A E 1 0 4 4 – 2
205 800 3 A E 1 0 3 4 – 1
205 1250 3 A E 1 0 3 4 – 2
150 310 800 3 A E 1 0 2 4 – 1
310 1250 3 A E 1 0 2 4 – 2
275 800 3 A E 1 0 1 4 – 1
275 1250 3 A E 1 0 1 4 – 2
205 800 3 A E 1 0 0 4 – 1
205 1250 3 A E 1 0 0 4 – 2
7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 – 1
310 1250 3 A E 1 0 8 5 – 2
310 2000 3 A E 1 0 8 5 – 4
310 2500 3 A E 1 0 8 5 – 6
275 800 3 A E 1 0 7 5 – 1
275 1250 3 A E 1 0 7 5 – 2
205 800 3 A E 1 0 6 5 – 1
205 1250 3 A E 1 0 6 5 – 2
160 310 800 3 A E 1 0 5 5 – 1
310 1250 3 A E 1 0 5 5 – 2
275 800 3 A E 1 0 4 5 – 1
275 1250 3 A E 1 0 4 5 – 2
205 800 3 A E 1 0 3 5 – 1
205 1250 3 A E 1 0 3 5 – 2
150 310 800 3 A E 1 0 2 5 – 1
310 1250 3 A E 1 0 2 5 – 2
275 800 3 A E 1 0 1 5 – 1
275 1250 3 A E 1 0 1 5 – 2
205 800 3 A E 1 0 0 5 – 1
205 1250 3 A E 1 0 0 5 – 2
7.2 60 20 40 100/104 210 310 1250 3 A E 1 0 8 6 – 2
310 2000 3 A E 1 0 8 6 – 4
310 2500 3 A E 1 0 8 6 – 6
310 3150 3 A E 1 0 8 6 – 7
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 40 kA
Rated normal current Ir = 2000 A
Pole-center distance = 210 mm, width across flats = 310 mm 0 8 6 – 4

Example for Order No.: 3 A E 1 0 8 6 – 4 n n n n – n n n n


Order codes:

16 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, standard circuit-breakers

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
12 75 28 310 16 40/42 210 800 3 A E 1 1 8 2 – 1
310 1250 3 A E 1 1 8 2 – 2
275 800 3 A E 1 1 7 2 – 1
275 1250 3 A E 1 1 7 2 – 2
205 800 3 A E 1 1 6 2 – 1

2
205 1250 3 A E 1 1 6 2 – 2
160 310 800 3 A E 1 1 5 2 – 1
310 1250 3 A E 1 1 5 2 – 2
275 800 3 A E 1 1 4 2 – 1
275 1250 3 A E 1 1 4 2 – 2
205 800 3 A E 1 1 3 2 – 1
205 1250 3 A E 1 1 3 2 – 2
150 310 800 3 A E 1 1 2 2 – 1
310 1250 3 A E 1 1 2 2 – 2
275 800 3 A E 1 1 1 2 – 1
275 1250 3 A E 1 1 1 2 – 2
205 800 3 A E 1 1 0 2 – 1
205 1250 3 A E 1 1 0 2 – 2
12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 – 1
310 1250 3 A E 1 1 8 3 – 2
275 800 3 A E 1 1 7 3 – 1
275 1250 3 A E 1 1 7 3 – 2
205 800 3 A E 1 1 6 3 – 1
205 1250 3 A E 1 1 6 3 – 2
160 310 800 3 A E 1 1 5 3 – 1
310 1250 3 A E 1 1 5 3 – 2
275 800 3 A E 1 1 4 3 – 1
275 1250 3 A E 1 1 4 3 – 2
205 800 3 A E 1 1 3 3 – 1
205 1250 3 A E 1 1 3 3 – 2
150 310 800 3 A E 1 1 2 3 – 1
310 1250 3 A E 1 1 2 3 – 2
275 800 3 A E 1 1 1 3 – 1
275 1250 3 A E 1 1 1 3 – 2
205 800 3 A E 1 1 0 3 – 1
205 1250 3 A E 1 1 0 3 – 2
Special version (available for all 12 kV standard circuit-breakers)
Ud = 42 kV – Z E 1 3

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 800 A
Pole-center distance = 160 mm, width across flats = 275 mm 1 4 2 – 1
Rated short-duration power-frequency withstand voltage Ud = 42 kV – Z E 1 3

Example for Order No.: 3 A E 1 1 4 2 – 1 n n n n – n n n n – Z


Order codes: E 1 3

Siemens HG 11.02 · 2006 17


Equipment Selection SION Vacuum Circuit-Breakers
Selection of basic types, standard circuit-breakers

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
12 75 28 310 25 63/65 210 800 3 A E 1 1 8 4 – 1
310 1250 3 A E 1 1 8 4 – 2
310 2000 3 A E 1 1 8 4 – 4
310 2500 3 A E 1 1 8 4 – 6
275 800 3 A E 1 1 7 4 – 1

2
275 1250 3 A E 1 1 7 4 – 2
205 800 3 A E 1 1 6 4 – 1
205 1250 3 A E 1 1 6 4 – 2
160 310 800 3 A E 1 1 5 4 – 1
310 1250 3 A E 1 1 5 4 – 2
275 800 3 A E 1 1 4 4 – 1
275 1250 3 A E 1 1 4 4 – 2
205 800 3 A E 1 1 3 4 – 1
205 1250 3 A E 1 1 3 4 – 2
150 310 800 3 A E 1 1 2 4 – 1
310 1250 3 A E 1 1 2 4 – 2
275 800 3 A E 1 1 1 4 – 1
275 1250 3 A E 1 1 1 4 – 2
205 800 3 A E 1 1 0 4 – 1
205 1250 3 A E 1 1 0 4 – 2
12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 – 1
310 1250 3 A E 1 1 8 5 – 2
310 2000 3 A E 1 1 8 5 – 4
310 2500 3 A E 1 1 8 5 – 6
275 800 3 A E 1 1 7 5 – 1
275 1250 3 A E 1 1 7 5 – 2
205 800 3 A E 1 1 6 5 – 1
205 1250 3 A E 1 1 6 5 – 2
160 310 800 3 A E 1 1 5 5 – 1
310 1250 3 A E 1 1 5 5 – 2
275 800 3 A E 1 1 4 5 – 1
275 1250 3 A E 1 1 4 5 – 2
205 800 3 A E 1 1 3 5 – 1
205 1250 3 A E 1 1 3 5 – 2
150 310 800 3 A E 1 1 2 5 – 1
310 1250 3 A E 1 1 2 5 – 2
275 800 3 A E 1 1 1 5 – 1
275 1250 3 A E 1 1 1 5 – 2
205 800 3 A E 1 1 0 5 – 1
205 1250 3 A E 1 1 0 5 – 2
Special version (available for all 12 kV standard circuit-breakers)
Ud = 42 kV – Z E 1 3

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 31.5 kA
Rated normal current Ir = 1250 A
Pole-center distance = 150 mm, width across flats = 205 mm 1 0 5 – 2

Example for Order No.: 3 A E 1 1 0 5 – 2 n n n n – n n n n


Order codes:

18 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, standard circuit-breakers

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
12 75 28 310 40 100/104 210 1250 3 A E 1 1 8 6 – 2
310 2000 3 A E 1 1 8 6 – 4
310 2500 3 A E 1 1 8 6 – 6
310 3150 3 A E 1 1 8 6 – 7
Special version (available for all 12 kV standard circuit-breakers)

2
Ud = 42 kV – Z E 1 3

Circuit-breaker for installation in NXAIR


12 75 28 31.5 80/82 210 275 1250 3 A E 1 5 7 5 – 2
275 2500 3 A E 1 5 7 5 – 6
160 275 1250 3 A E 1 5 4 5 – 2
12 75 28 40 100/104 210 275 1250 3 A E 1 5 7 6 – 2
275 2000 3 A E 1 5 7 6 – 4
275 2500 3 A E 1 5 7 6 – 6
275 3150 3 A E 1 5 7 6 – 7

Special version (available for all 12 kV standard circuit-breakers)


Ud = 42 kV – Z E 1 3

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 40 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 310 mm 1 8 6 – 2

Example for Order No.: 3 A E 1 1 8 6 – 2 n n n n – n n n n


Order codes:

Siemens HG 11.02 · 2006 19


Equipment Selection SION Vacuum Circuit-Breakers
Selection of basic types, standard circuit-breakers

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 – 1
310 1250 3 A E 1 2 8 1 – 2
275 800 3 A E 1 2 7 1 – 1
275 1250 3 A E 1 2 7 1 – 2
205 800 3 A E 1 2 6 1 – 1

2
205 1250 3 A E 1 2 6 1 – 2
160 310 800 3 A E 1 2 5 1 – 1
310 1250 3 A E 1 2 5 1 – 2
275 800 3 A E 1 2 4 1 – 1
275 1250 3 A E 1 2 4 1 – 2
205 800 3 A E 1 2 3 1 – 1
205 1250 3 A E 1 2 3 1 – 2
150 310 800 3 A E 1 2 2 1 – 1
310 1250 3 A E 1 2 2 1 – 2
275 800 3 A E 1 2 1 1 – 1
275 1250 3 A E 1 2 1 1 – 2
205 800 3 A E 1 2 0 1 – 1
205 1250 3 A E 1 2 0 1 – 2
17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 – 1
310 1250 3 A E 1 2 8 2 – 2
275 800 3 A E 1 2 7 2 – 1
275 1250 3 A E 1 2 7 2 – 2
205 800 3 A E 1 2 6 2 – 1
205 1250 3 A E 1 2 6 2 – 2
160 310 800 3 A E 1 2 5 2 – 1
310 1250 3 A E 1 2 5 2 – 2
275 800 3 A E 1 2 4 2 – 1
275 1250 3 A E 1 2 4 2 – 2
205 800 3 A E 1 2 3 2 – 1
205 1250 3 A E 1 2 3 2 – 2
150 310 800 3 A E 1 2 2 2 – 1
310 1250 3 A E 1 2 2 2 – 2
275 800 3 A E 1 2 1 2 – 1
275 1250 3 A E 1 2 1 2 – 2
205 800 3 A E 1 2 0 2 – 1
205 1250 3 A E 1 2 0 2 – 2
17.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 – 1
310 1250 3 A E 1 2 8 4 – 2
310 2000 3 A E 1 2 8 4 – 4
310 2500 3 A E 1 2 8 4 – 6

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 275 mm 2 7 2 – 2

Example for Order No.: 3 A E 1 2 7 2 – 2 n n n n – n n n n


Order codes:

20 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, standard circuit-breakers

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
17.5 95 38 25 63/65 210 275 800 3 A E 1 2 7 4 – 1
275 1250 3 A E 1 2 7 4 – 2
205 800 3 A E 1 2 6 4 – 1
205 1250 3 A E 1 2 6 4 – 2
160 310 800 3 A E 1 2 5 4 – 1

2
310 1250 3 A E 1 2 5 4 – 2
275 800 3 A E 1 2 4 4 – 1
275 1250 3 A E 1 2 4 4 – 2
205 800 3 A E 1 2 3 4 – 1
205 1250 3 A E 1 2 3 4 – 2
150 310 800 3 A E 1 2 2 4 – 1
310 1250 3 A E 1 2 2 4 – 2
275 800 3 A E 1 2 1 4 – 1
275 1250 3 A E 1 2 1 4 – 2
205 800 3 A E 1 2 0 4 – 1
205 1250 3 A E 1 2 0 4 – 2
17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 – 1
310 1250 3 A E 1 2 8 5 – 2
310 2000 3 A E 1 2 8 5 – 4
310 2500 3 A E 1 2 8 5 – 6
275 800 3 A E 1 2 7 5 – 1
275 1250 3 A E 1 2 7 5 – 2
205 800 3 A E 1 2 6 5 – 1
205 1250 3 A E 1 2 6 5 – 2
160 310 800 3 A E 1 2 5 5 – 1
310 1250 3 A E 1 2 5 5 – 2
275 800 3 A E 1 2 4 5 – 1
275 1250 3 A E 1 2 4 5 – 2
205 800 3 A E 1 2 3 5 – 1
205 1250 3 A E 1 2 3 5 – 2
150 310 800 3 A E 1 2 2 5 – 1
310 1250 3 A E 1 2 2 5 – 2
275 800 3 A E 1 2 1 5 – 1
275 1250 3 A E 1 2 1 5 – 2
205 800 3 A E 1 2 0 5 – 1
205 1250 3 A E 1 2 0 5 – 2
17.5 95 38 40 100/104 210 310 1250 3 A E 1 2 8 6 – 2
310 2000 3 A E 1 2 8 6 – 4
310 2500 3 A E 1 2 8 6 – 6
310 3150 3 A E 1 2 8 6 – 7

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 31.5 kA
Rated normal current Ir = 2500 A
Pole-center distance = 210 mm, width across flats = 310 mm 2 8 5 – 6

Example for Order No.: 3 A E 1 2 8 5 – 6 n n n n – n n n n


Order codes:

Siemens HG 11.02 · 2006 21


Equipment Selection SION Vacuum Circuit-Breakers
Selection of basic types, standard circuit-breakers

24 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 23
See page 23
See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
24 125 50 310 12.5 31/33 210 800 3 A E 1 3 2 1 – 1
310 1250 3 A E 1 3 2 1 – 2
24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 – 1
310 1250 3 A E 1 3 2 2 – 2
310 2000 3 A E 1 3 2 2 – 4

2
275 310 800 3 A E 1 3 5 2 – 1
310 1250 3 A E 1 3 5 2 – 2
310 2000 3 A E 1 3 5 2 – 4
24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 – 1
310 1250 3 A E 1 3 2 3 – 2
310 2000 3 A E 1 3 2 3 – 4
310 2500 3 A E 1 3 2 3 – 6
275 310 800 3 A E 1 3 5 3 – 1
310 1250 3 A E 1 3 5 3 – 2
310 2000 3 A E 1 3 5 3 – 4
310 2500 3 A E 1 3 5 3 – 6
24 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 – 1
310 1250 3 A E 1 3 2 4 – 2
310 2000 3 A E 1 3 2 4 – 4
310 2500 3 A E 1 3 2 4 – 6
275 310 800 3 A E 1 3 5 4 – 1
310 1250 3 A E 1 3 5 4 – 2
310 2000 3 A E 1 3 5 4 – 4
310 2500 3 A E 1 3 5 4 – 6
Special version (available for all 24 kV standard circuit-breakers)
Ud = 55 kV – Z E 5 5

Circuit-breaker for installation in NXAIR


24 125 50 25 63/65 210 320 1250 3 A E 1 7 2 4 – 2
275 320 2500 3 A E 1 7 5 4 – 6
Special version (available for all 24 kV standard circuit-breakers)
Ud = 55 kV – Z E 5 5

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 24 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-center distance = 275 mm, width across flats = 310 mm 3 5 4 – 4

Example for Order No.: 3 A E 1 3 5 4 – 4 n n n n – n n n n


Order codes:

22 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Secondary equipment for standard circuit-breakers

9th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Release combination Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

C.t.-operated release
with tripping pulse
2nd shunt release
1st shunt release

W 0.1 Ws (20 O)
Undervoltage

C.t.-operated

C.t.-operated

See page 24
See page 24

See page 25
See page 25
See page 26
See page 26

See page 27
release 0.5 A

release 1.0 A
release

n A
n n B
n n C
n n G
n n H
n n F
n E
n n N
n n
n
n
n
n
P
Q
J
L
2
n M

10th position
Operating voltage of the closing solenoid

Standard voltages Special voltages

24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 26)

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C

Example for Order No.: 3 A E 1 3 5 4 – 4 A C n n – n n n n


Order codes:

Siemens HG 11.02 · 2006 23


Equipment Selection SION Vacuum Circuit-Breakers
Secondary equipment for standard circuit-breakers

11th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the 1st release Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

See page 25
See page 25
See page 26
See page 26

See page 27
Standard voltages Special voltages

C.t.-operated release 0
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C

2 125 V DC
127 V DC
240 V DC
9
9
9
With order code
With order code
With order code
L
L
L
1 D
1 E
1 F
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M

12th position
Operating voltage of the 2nd release

Standard voltages Special voltages

Without, or c.t.-operated release 0


24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code M 1 A
32 V DC 9 With order code M 1 B
120 V DC 9 With order code M 1 C
125 V DC 9 With order code M 1 D
127 V DC 9 With order code M 1 E
240 V DC 9 With order code M 1 F
120 V AC 50/60 Hz 1) 9 With order code M 1 K
125 V AC 50/60 Hz 1) 9 With order code M 1 L
240 V AC 50/60 Hz 1) 9 With order code M 1 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 26)

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C
Operating voltage of the 1st release 32 V DC 9 L 1 B
Without 2nd release 0

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – n n n n


Order codes: L 1 B

24 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Secondary equipment for standard circuit-breakers

13th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Circuit-breaker installation accessories Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

See page 26
See page 26

See page 27
Options

Without circuit-breaker installation accessories,


fixed-mounted circuit-breaker 0
With drawout element 1
With drawout element, contact arms and contact system 2
With drawout element, contact arms and contact system,
fixed contacts and bushings 3

14th position
Operating voltage of the motor operating mechanism

Standard voltages Special voltages

24 V DC B
2
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 26)

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 –
Fixed-mounted circuit-breaker 0
Operating voltage of the motor operating mechanism 230 V AC K

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K n n


Order codes: L 1 B

Siemens HG 11.02 · 2006 25


Equipment Selection SION Vacuum Circuit-Breakers
Secondary equipment for standard circuit-breakers

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Interlocking, auxiliary switch, circuit-breaker Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n
tripping signal and control cable connection
Auxiliary switch Control cable connection

See page 27
12 NO + 12 NC

Circuit-breaker
tripping signal

terminal strip

24-pole plug

64-pole plug
6 NO + 6 NC
interlocking
Mechanical

27-pole

n n n B
n n D
n n n F
n n H
n n n K
n n M
n n n R
n n
2 n
n
n
n
n n
n
Q
A
C
n n n n E
n n n G
n n n n J
n n n L
n n n n N
n n n P
Special versions
Auxiliary switch contacts 12 NO + 12 NC and pins
of the 64-pole plug connector gold-plated – Z A 2 1
Key-interlocking (RONIS-lock at the vacuum circuit-breaker)
Only for circuit-breakers without mechanical interlocking – Z J 6 0

16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate

Language Frequency

German 50 Hz or DC 0
60 Hz 1
English 50 Hz or DC 2
60 Hz 3
French 50 Hz or DC 4
60 Hz 5
Spanish 50 Hz or DC 6
60 Hz 7
Other languages on request

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 – 0 K
With mechanical interlocking, circuit-breaker tripping signal,
auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in German 0

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K N 0


Order codes: L 1 B

26 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Additional equipment for standard circuit-breakers

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

Options

Wiring cables, halogen-free and flame-retardant – Z A 1 0


Condensation protection, heating for 230 V AC, 50 W – Z A 3 0
Silicone-free design – Z A 3 1
For circuit-breaker operation at ambient air temperatures down to -25° C – Z A 4 0
Electrical closing lock-out – Z A 4 7
Additional rating plate, loose delivery – Z B 0 0
Separating shell towards contact arm side (standard version) – Z D 9 0
Separating shell towards contact arm side (short version) – Z D 9 1
Routine test certificate (enclosed with delivery) – Z F 2 0
Routine test certificate (with stamp and signature) – Z F 2 1
Routine test certificate (to orderer) – Z F 2 3
Hand crank (for manual charging of the closing spring) – Z F 3 0
Handle for drawout element (for racking the circuit-breaker on the
drawout element)
Indication of disconnected position of the circuit-breaker
(circuit-breaker with drawout element)


Z

Z
F

J
3

6
2

1
2

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C
Operating voltage of the 1st release 32 V DC 9 With order code L 1 B
Without 2nd release 0 –
Fixed-mounted circuit-breaker 0
Operating voltage of the motor operating mechanism 230 V AC K
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in German 0
Hand crank – Z F 3 0

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K N 0 – Z


Order codes: L 1 B + F 3 0

Siemens HG 11.02 · 2006 27


Equipment Selection SION Vacuum Circuit-Breakers
Selection of basic types, slide-in modules

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 32
See page 32
See page 33
See page 33

See page 34
See page 34
See page 35
See page 35

See page 36
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 – 1
310 1250 3 A E 1 0 8 2 – 2
275 800 3 A E 1 0 7 2 – 1
275 1250 3 A E 1 0 7 2 – 2
150 310 800 3 A E 1 0 2 2 – 1

2
310 1250 3 A E 1 0 2 2 – 2
275 800 3 A E 1 0 1 2 – 1
275 1250 3 A E 1 0 1 2 – 2
7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 – 1
310 1250 3 A E 1 0 8 3 – 2
275 800 3 A E 1 0 7 3 – 1
275 1250 3 A E 1 0 7 3 – 2
150 310 800 3 A E 1 0 2 3 – 1
310 1250 3 A E 1 0 2 3 – 2
275 800 3 A E 1 0 1 3 – 1
275 1250 3 A E 1 0 1 3 – 2
7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 – 1
310 1250 3 A E 1 0 8 4 – 2
310 2000 3 A E 1 0 8 4 – 4
275 800 3 A E 1 0 7 4 – 1
275 1250 3 A E 1 0 7 4 – 2
150 310 800 3 A E 1 0 2 4 – 1
310 1250 3 A E 1 0 2 4 – 2
275 800 3 A E 1 0 1 4 – 1
275 1250 3 A E 1 0 1 4 – 2
7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 – 1
310 1250 3 A E 1 0 8 5 – 2
310 2000 3 A E 1 0 8 5 – 4
310 2500 3 A E 1 0 8 5 – 6
275 800 3 A E 1 0 7 5 – 1
275 1250 3 A E 1 0 7 5 – 2
150 310 800 3 A E 1 0 2 5 – 1
310 1250 3 A E 1 0 2 5 – 2
275 800 3 A E 1 0 1 5 – 1
275 1250 3 A E 1 0 1 5 – 2
7.2 60 20 40 100/104 210 310 1250 3 A E 1 0 8 6 – 2
310 2000 3 A E 1 0 8 6 – 4
310 2500 3 A E 1 0 8 6 – 6
310 3150 3 A E 1 0 8 6 – 7

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 20 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 310 mm 0 8 3 – 2

Example for Order No.: 3 A E 1 0 8 3 – 2 n n n n – n n n n


Order codes:

28 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, slide-in modules

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 32
See page 32
See page 33
See page 33

See page 34
See page 34
See page 35
See page 35

See page 36
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
12 75 28 16 40/42 210 310 800 3 A E 1 1 8 2 – 1
310 1250 3 A E 1 1 8 2 – 2
275 800 3 A E 1 1 7 2 – 1
275 1250 3 A E 1 1 7 2 – 2
150 310 800 3 A E 1 1 2 2 – 1

2
310 1250 3 A E 1 1 2 2 – 2
275 800 3 A E 1 1 1 2 – 1
275 1250 3 A E 1 1 1 2 – 2
12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 – 1
310 1250 3 A E 1 1 8 3 – 2
275 800 3 A E 1 1 7 3 – 1
275 1250 3 A E 1 1 7 3 – 2
150 310 800 3 A E 1 1 2 3 – 1
310 1250 3 A E 1 1 2 3 – 2
275 800 3 A E 1 1 1 3 – 1
275 1250 3 A E 1 1 1 3 – 2
12 75 28 25 63/65 210 310 800 3 A E 1 1 8 4 – 1
310 1250 3 A E 1 1 8 4 – 2
310 2000 3 A E 1 1 8 4 – 4
310 2500 3 A E 1 1 8 4 – 6
275 800 3 A E 1 1 7 4 – 1
275 1250 3 A E 1 1 7 4 – 2
150 310 800 3 A E 1 1 2 4 – 1
310 1250 3 A E 1 1 2 4 – 2
275 800 3 A E 1 1 1 4 – 1
275 1250 3 A E 1 1 1 4 – 2
12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 – 1
310 1250 3 A E 1 1 8 5 – 2
310 2000 3 A E 1 1 8 5 – 4
310 2500 3 A E 1 1 8 5 – 6
275 800 3 A E 1 1 7 5 – 1
275 1250 3 A E 1 1 7 5 – 2
150 310 800 3 A E 1 1 2 5 – 1
310 1250 3 A E 1 1 2 5 – 2
275 800 3 A E 1 1 1 5 – 1
275 1250 3 A E 1 1 1 5 – 2
12 75 28 40 100/104 210 310 1250 3 A E 1 1 8 6 – 2
310 2000 3 A E 1 1 8 6 – 4
310 2500 3 A E 1 1 8 6 – 6
310 3150 3 A E 1 1 8 6 – 7
Special version (available for all 12 kV slide-in modules)
Ud = 42 kV – Z E 1 3
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 800 A
Pole-center distance = 150 mm, width across flats = 275 mm 1 1 4 – 1
Rated short-duration power-frequency withstand voltage Ud = 42 kV – Z E 1 3

Example for Order No.: 3 A E 1 1 1 4 – 1 n n n n – n n n n – Z


Order codes: E 1 3

Siemens HG 11.02 · 2006 29


Equipment Selection SION Vacuum Circuit-Breakers
Selection of basic types, slide-in modules

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 32
See page 32
See page 33
See page 33

See page 34
See page 34
See page 35
See page 35

See page 36
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 – 1
310 1250 3 A E 1 2 8 1 – 2
275 800 3 A E 1 2 7 1 – 1
275 1250 3 A E 1 2 7 1 – 2
150 310 800 3 A E 1 2 2 1 – 1

2
310 1250 3 A E 1 2 2 1 – 2
275 800 3 A E 1 2 1 1 – 1
275 1250 3 A E 1 2 1 1 – 2
17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 – 1
310 1250 3 A E 1 2 8 2 – 2
275 800 3 A E 1 2 7 2 – 1
275 1250 3 A E 1 2 7 2 – 2
150 310 800 3 A E 1 2 2 2 – 1
310 1250 3 A E 1 2 2 2 – 2
275 800 3 A E 1 2 1 2 – 1
275 1250 3 A E 1 2 1 2 – 2
17.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 – 1
310 1250 3 A E 1 2 8 4 – 2
310 2000 3 A E 1 2 8 4 – 4
310 2500 3 A E 1 2 8 4 – 6
275 800 3 A E 1 2 7 4 – 1
275 1250 3 A E 1 2 7 4 – 2
150 310 800 3 A E 1 2 2 4 – 1
310 1250 3 A E 1 2 2 4 – 2
275 800 3 A E 1 2 1 4 – 1
275 1250 3 A E 1 2 1 4 – 2
17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 – 1
310 1250 3 A E 1 2 8 5 – 2
310 2000 3 A E 1 2 8 5 – 4
310 2500 3 A E 1 2 8 5 – 6
275 800 3 A E 1 2 7 5 – 1
275 1250 3 A E 1 2 7 5 – 2
150 310 800 3 A E 1 2 2 5 – 1
310 1250 3 A E 1 2 2 5 – 2
275 800 3 A E 1 2 1 5 – 1
275 1250 3 A E 1 2 1 5 – 2
17.5 95 38 40 100/104 210 310 1250 3 A E 1 2 8 6 – 2
310 2000 3 A E 1 2 8 6 – 4
310 2500 3 A E 1 2 8 6 – 6
310 3150 3 A E 1 2 8 6 – 7

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 275 mm 2 7 2 – 2

Example for Order No.: 3 A E 1 2 7 2 – 2 n n n n – n n n n


Order codes:

30 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, slide-in modules

24 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % AC component
Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

Width across flats


power-frequency

breaking current

making current

Rated normal
(at 50/60 Hz)

See page 32
See page 32
See page 33
See page 33

See page 34
See page 34
See page 35
See page 35

See page 36
voltage

current
Rated

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A
24 125 50 12.5 31/33 210 310 800 3 A E 1 3 2 1 – 1
310 1250 3 A E 1 3 2 1 – 2
24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 – 1
310 1250 3 A E 1 3 2 2 – 2
310 2000 3 A E 1 3 2 2 – 4

2
275 310 800 3 A E 1 3 5 2 – 1
310 1250 3 A E 1 3 5 2 – 2
310 2000 3 A E 1 3 5 2 – 4
24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 – 1
310 1250 3 A E 1 3 2 3 – 2
310 2000 3 A E 1 3 2 3 – 4
310 2500 3 A E 1 3 2 3 – 6
275 310 800 3 A E 1 3 5 3 – 1
310 1250 3 A E 1 3 5 3 – 2
310 2000 3 A E 1 3 5 3 – 4
310 2500 3 A E 1 3 5 3 – 6
24 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 – 1
310 1250 3 A E 1 3 2 4 – 2
310 2000 3 A E 1 3 2 4 – 4
310 2500 3 A E 1 3 2 4 – 6
275 310 800 3 A E 1 3 5 4 – 1
310 1250 3 A E 1 3 5 4 – 2
310 2000 3 A E 1 3 5 4 – 4
310 2500 3 A E 1 3 5 4 – 6

Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 24 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-center distance = 275 mm, width across flats = 310 mm 3 5 4 – 4

Example for Order No.: 3 A E 1 3 5 4 – 4 n n n n – n n n n


Order codes:

Siemens HG 11.02 · 2006 31


Equipment Selection SION Vacuum Circuit-Breakers
Secondary equipment for slide-in modules

9th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Release combination Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

C.t.-operated release
with tripping pulse
2nd shunt release
1st shunt release

W 0.1 Ws (20 O)
Undervoltage

C.t.-operated

C.t.-operated

See page 33
See page 33

See page 34
See page 34
See page 35
See page 35

See page 36
release 0.5 A

release 1.0 A
release

n A
n n B
n n C
n n G
n n H
n n F
n E
n n N
n n
2 n
n
n
n
P
Q
J
L
n M

10th position
Operating voltage of the closing solenoid

Standard voltages Special voltages

24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 35)

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C

Example for Order No.: 3 A E 1 3 5 4 – 4 A C n n – n n n n


Order codes:

32 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Secondary equipment for slide-in modules

11th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the 1st release Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

See page 34
See page 34
See page 35
See page 35

See page 36
Standard voltages Special voltages

C.t.-operated release 0
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
125 V DC
127 V DC
240 V DC
9
9
9
With order code
With order code
With order code
L
L
L
1 D
1 E
1 F
2
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M

12th position
Operating voltage of the 2nd release

Standard voltages Special voltages

Without, or c.t.-operated release 0


24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code M 1 A
32 V DC 9 With order code M 1 B
120 V DC 9 With order code M 1 C
125 V DC 9 With order code M 1 D
127 V DC 9 With order code M 1 E
240 V DC 9 With order code M 1 F
120 V AC 50/60 Hz 1) 9 With order code M 1 K
125 V AC 50/60 Hz 1) 9 With order code M 1 L
240 V AC 50/60 Hz 1) 9 With order code M 1 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 35)

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C
Operating voltage of the 1st release 32 V DC 9 L 1 B
Without 2nd release 0

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – n n n n


Order codes: L 1 B

Siemens HG 11.02 · 2006 33


Equipment Selection SION Vacuum Circuit-Breakers
Secondary equipment for slide-in modules

13th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Circuit-breaker installation accessories Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

See page 35
See page 35

See page 36
Options

On cartridge, with drawout element, contact arms, contact system,


fixed contacts, bushings and shutters 5
On cartridge, with drawout element, contact arms, contact system,
fixed contacts, bushings, shutters and earthing switch
with short-circuit making capacity 6
Drawings of the fully equipped slide-in-module.
Scope of supply includes fixed-mounted circuit-breaker 8

14th position
Operating voltage of the motor operating mechanism

2 Standard voltages Special voltages

24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 35)

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 –
Circuit-breaker on cartridge, with drawout element, contact arms,
contact system, fixed contacts, bushings and shutters 5
Operating voltage of the motor operating mechanism 240 V DC S

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S n n


Order codes: L 1 B

34 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Secondary equipment for slide-in modules

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Interlocking, auxiliary switch, circuit-breaker Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n
tripping signal and control cable connection
Auxiliary switch Control cable connection
12 NO + 12 NC

Circuit-breaker
tripping signal

terminal strip

64-pole plug

See page 36
6 NO + 6 NC
interlocking
Mechanical

27-pole

n n n n A
n n n C
n n n n J
n n n L
n n n n N
n n n P
Special versions
Auxiliary switch contacts 12 NO + 12 NC and pins
of the 64-pole plug connector gold-plated – Z A 2 1
2
16th position
AC frequency of operating voltages
Languages of operating instructions
and rating plate

Language Frequency

German 50 Hz or DC 0
60 Hz 1
English 50 Hz or DC 2
60 Hz 3
French 50 Hz or DC 4
60 Hz 5
Spanish 50 Hz or DC 6
60 Hz 7
Other languages on request

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 – 5 S
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instruction and rating plate in Spanish 6
Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated – Z A 2 1

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S N 6 – Z


Order codes: L 1 B + A 2 1

Siemens HG 11.02 · 2006 35


Equipment Selection SION Vacuum Circuit-Breakers
Additional equipment for slide-in modules

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n

Options

Wiring cables, halogen-free and flame-retardant – Z A 1 0


Condensation protection, heating for 230 V AC, 50 W – Z A 3 0
Silicone-free design – Z A 3 1
For circuit-breaker operation at ambient air temperatures down to -25° C – Z A 4 0
Electrical closing lock-out – Z A 4 7
Additional rating plate, loose delivery – Z B 0 0
Routine test certificate (enclosed with delivery) – Z F 2 0
Routine test certificate (with stamp and signature) – Z F 2 1
Routine test certificate (to orderer) – Z F 2 3
Hand crank (for manual charging of the closing spring) – Z F 3 0
Handle for drawout element (for racking the circuit-breaker on the – Z F 3 2
drawout element)
Handle for earthing switch (for operating the switch at the module) – Z F 3 4

Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C
Operating voltage of the 1st release 32 V DC 9 With order code L 1 B
Without 2nd release 0 –
Circuit-breaker on cartridge, with drawout element, contact arms,
contact system, fixed contacts, bushings and shutters 5
Operating voltage of the motor operating mechanism 240 V DC S
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in Spanish 6
Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated – Z A 2 1
Wiring cables halogen-free and flame-retardant – Z A 1 0
Silicone-free design – Z A 3 1
Electrical closing lock-out – Z A 4 7

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S N 6 – Z


Order codes: L 1 B + A 2 1 + A 1 0 + A 3 1 + A 4 7

36 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Accessories and spare parts

Retrofitting Accessories for the plug connector


When releases / solenoids are retrofitted, the order num- Included in the scope of supply of the basic equipment for
bers of the built-on parts must also be specified. For other standard circuit-breakers:
additional equipment, the required mounting parts are For 24-pole plug connector
included in the delivery.
– Lower part of plug
– Crimp sockets acc. to number of contacts
Spare parts – Upper part of plug with screwed contacts
When releases / solenoids are required as spare parts, the (no crimp sockets required)
order number and the type of construction of the asso- For 64-pole plug connector
ciated standard circuit-breaker must also be specified. – Lower part of plug
– Upper part of plug
Remark for orders – Crimp sockets according to number of contacts
The order numbers are applicable to standard circuit- Vacuum interrupters and other spare parts must only be
breakers of current manufacture. When mounting parts replaced by instructed personnel.
or spare parts are being ordered for an existing standard
circuit-breaker, always quote the type designation, serial No.,
design code and the year of manufacture of the circuit-
2
breaker to be sure to get the correct delivery.

Designation Remarks Operating voltage Order No.

Handles Hand crank for circuit-breaker 3AX15 30-2B


Long hand crank for circuit-breaker 3AX14 30-2B
Handle for drawout element 3AX14 30-2C
Handle for earthing switch (for slide-in module) 3AX14 30-2D
Lubricant 180 g of Klüber-Isoflex Topas L32 3AX11 33-3H
1 kg of Klüber-Isoflex Topas L32 3AX11 33-3E
1 kg of Molykote grease 3AX11 33-2L
Operating solenoid Used as closing solenoid or 24 V DC 3AY15 10-5B
1st shunt release 30/32 V DC 3AY15 10-5M
48 V DC 3AY15 10-5C
60 V DC 3AY15 10-5D
100/124 V DC 3AY15 10-5E
125/144 V DC 3AY15 10-5N
220/250 V DC 3AY15 10-5F
100/125 V AC, 50/60 Hz 3AY15 10-5E
230/240 V AC, 50/60 Hz 3AY15 10-5F
2nd shunt release 24/32 V DC 3AX11 01-2B
48/60 V DC 3AX11 01-2C
110/127 V DC 3AX11 01-2E
220/240 V DC 3AX11 01-2F
100/125 V AC, 50 Hz 3AX11 01-2G
230/240 V AC, 50 Hz 3AX11 01-2J
100/125 V AC, 60 Hz 3AX11 01-3G
230/240 V AC, 60 Hz 3AX11 01-3J
Mounting parts For 2nd shunt release 3AX14 11-2A
Current-transformer For rated normal current 0.5 A 3AX11 02-2A
operated release
For rated normal current 1 A 3AX11 02-2B
For tripping pulse W 0.1 Ws, 20 O for protection relay 7SJ45 3AX11 04-2B
Mounting parts For current-transformer operated release 3AX14 11-2A

Siemens HG 11.02 · 2006 37


Equipment Selection SION Vacuum Circuit-Breakers
Accessories and spare parts

Designation Remarks Operating voltage Order No.

Undervoltage release 24 V DC 3AX11 03-2B


30/32 V DC 3AX11 03-2L
48 V DC 3AX11 03-2C
60 V DC 3AX11 03-2D
110 V DC 3AX11 03-2E
120/127 V DC 3AX11 03-2N
220 V DC 3AX11 03-2F
240 V DC 3AX11 03-2P
100 V AC, 50 Hz 3AX11 03-2G
110/125 V AC, 50 Hz 3AX11 03-2H
230 V AC, 50 Hz 3AX11 03-2J
240 V AC, 50 Hz 3AX11 03-2M
100 V AC, 60 Hz 3AX11 03-3G
110/125 V AC, 60 Hz 3AX11 03-3H
230 V AC, 60 Hz 3AX11 03-3J

2 Mounting parts
Drive motor
For undervoltage release
240 V AC, 60 Hz

24/30/32 V DC
3AX11 03-3M
3AX14 11-2A
3AY17 11-2B
48 V DC 3AY17 11-2C
60 V DC 3AY17 11-2D
100/110/125 V DC/AC 3AY17 11-2E
220 V DC/230 V AC 3AY17 11-2F
Auxiliary contactor 24 V DC SWB: 55656
type 3RH11 22 for anti-pumping 30/32 V DC SWB: 55658
48 V DC SWB: 55659
60 V DC SWB: 55660
110 V DC SWB: 55661
120/127 V DC SWB: 55662
220 V DC SWB: 55663
240/250 V AC SWB: 55665
110 V AC, 50/60 Hz SWB: 55666
120 V AC, 50/60 Hz SWB: 55667
125 V AC, 50/60 Hz SWB: 55668
230 V AC, 50/60 Hz SWB: 55669
240 V AC, 50/60 Hz SWB: 55670
Position switch Type SE4 without installation accessories SWB: 46677
Used for: Nos.
– Electrical anti-pumping (-S3) 1
– Electrical interlocking (-S12) 1
– Motor control (-S21, -S22) 2
– Closing spring charged (-S4) 1
– Circuit-breaker tripping signal (-S6, -S7) 2
– Electrical closing lock-out (-S5) 1
– Drawout element (-S1.0 to – S1.9) 10
Auxiliary switch (-S1) 6 NO + 6 NC 3SV92 73-2AA0
12 NO + 12 NC 3SV92 74-2AA0
Mechanical interlocking 3AX14 20-2A
Key-operated interlocking 3AX14 37-2A
Module connector State position indicator of drawout element 3AX14 60-2A
Accessories for plug connector (for conductor cross-section 1.5 mm)
Crimp pins (for lower part of plug) 24-pole 3AX11 34-3A
64-pole 3AX11 34-4B
Crimp sockets (for upper part of plug) 64-pole 3AX11 34-4C

Crimping pliers For notching the crimp pins and crimp sockets 3AX11 34-4D
Disassembly tool 3AX11 34-4G
Plug connector complete 24-pole 3AX11 34-7A
64-pole 3AX11 34-6A

38 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Equipment Selection
Accessories and spare parts

Designation Remarks Operating voltage Order No.

Electrical closing lock-out 24 V DC 3AX14 05-2B


30/32 V DC 3AX14 05-2K
48 V DC 3AX14 05-2C
60 V DC 3AX14 05-2D
110/127 V DC 3AX14 05-2E
220/240 V DC 3AX14 05-2F
100 V AC, 50/60 Hz 3AX14 05-2G
110/125 V AC, 50/60 Hz 3AX14 05-2H
220/240 V AC, 50/60 Hz 3AX14 05-2J
Mounting parts For electrical closing lock-out 3AX14 15-2A
Bushing 7.2 to 17.5 kV to 1250 A 3AX14 51-2A
7.2 to 17.5 kV to 3150 A 3AX14 51-2B
24 kV to 2500 A 3AX14 51-2B
Separating shell towards Additional shielding for narrow mounting conditions
contact arm side, for standard Standard version, width across flats 310 mm 7.2 to 17.5 kV 3AX14 38-2A
circuit-breakers only Standard version, width across flats 275 mm
Standard version, width across flats 205 mm
Standard version, width across flats 310 mm
7.2 to 17.5 kV
7.2 to 17.5 kV
24 kV
3AX14 38-2C
3AX14 38-2D
3AX14 38-2B
2
Short version, width across flats 310 mm 24 kV 3AX14 38-3B
Gate for cartridge Short version 3AX14 52-2B
Contact system 7.2/12/24 kV, 800 to 1250 A 3AX14 42-2A
17.5 kV, 800 to 1250 A 3AX14 42-2B
7.2/12/24 kV, to 3150 A 3AX14 42-2C
17.5 kV, to 3150 A 3AX14 42-2D

Note:
HG11-2518_en eps

For any query regarding spare parts,


subsequent deliveries, etc., the following
four details are necessary:
– Type designation
– Serial No.
– Design code
– Year of manufacture

Siemens HG 11.02 · 2006 39


SION Vacuum Circuit-Breakers

R-HG11-177.tif

40 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Contents

Contents Page

Technical Data 41
Electrical data, dimensions and weights:
Voltage level 7.2 kV 42
Voltage level 12 kV 46
Voltage level 17.5 kV 50
Voltage level 24 kV 56

Dimension drawings:
Voltage levels 7.2 to 17.5 kV 54
Voltage level 24 kV 58

Operating times, short-circuit protection


of motors, consumption data of releases 59
Circuit diagrams 60
R-HG11-178.eps

SION vacuum circuit-breaker with drawout element,


contact arms and contact system

3
R-HG11-179.eps

SION vacuum circuit-breaker with drawout element,


contact arms and contact system

Siemens HG 11.02 · 2006 41


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 45)
Rated lightning impulse withstand voltage
7.2 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 002-1 ... 800 205 150 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
1 K/–

3AE1 002-2 ... 1250 205 150 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
1 K/–

3AE1 003-1 ... 800 205 150 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
2 K/–

3AE1 003-2 ... 1250 205 150 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
2 K/–

3AE1 004-1 ... 800 205 150 n 3 25 36 28 63/


65
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
3 K/–

3AE1 004-2 ... 1250 205 150 n 3 25 36 28 63/


65
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
3 K/–

3AE1 005-1 ... 800 205 150 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
4 K/–

3AE1 005-2 ... 1250 205 150 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 105 75 80/ – 3M 442
02010 001
4 K/–

3 3AE1 012-1 ...

3AE1 012-2 ...


800 275 150

1250 275 150


n
n
3

3
16

16
36

36
17.9

17.9
40/
42
40/
42
60

60
20

20
2.1

2.1
129 140 105

129 140 105


75

75
80/
120
80/
120
3M 442
02011 001
3M 442
02011 001
1

1
I/J

I/J

3AE1 013-1 ... 800 275 150 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 105 75 80/
120
3M 442
02011 001
2 I/J

3AE1 013-2 ... 1250 275 150 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 105 75 80/
120
3M 442
02011 001
2 I/J

3AE1 014-1 ... 800 275 150 n 3 25 36 28 63/


65
60 20 2.1 129 140 105 75 80/
120
3M 442
02011 001
3 I/J

3AE1 014-2 ... 1250 275 150 n 3 25 36 28 63/


65
60 20 2.1 129 140 105 75 80/
120
3M 442
02011 001
3 I/J

3AE1 015-1 ... 800 275 150 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 105 75 80/
120
3M 442
02011 001
4 I/J

3AE1 015-2 ... 1250 275 150 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 105 75 80/
120
3M 442
02011 001
4 I/J

3AE1 022-1 ... 800 310 150 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
1 H/J

3AE1 022-2 ... 1250 310 150 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
1 H/J

3AE1 023-1 ... 800 310 150 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
2 H/J

3AE1 023-2 ... 1250 310 150 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
2 H/J

3AE1 024-1 ... 800 310 150 n 3 25 36 28 63/


65
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
3 H/J

3AE1 024-2 ... 1250 310 150 n 3 25 36 28 63/


65
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
3 H/J

3AE1 025-1 ... 800 310 150 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
4 H/J

3AE1 025-2 ... 1250 310 150 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 100 75 80/
120
3M 442
02012 001
4 H/J

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

42 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 45)
Rated lightning impulse withstand voltage
7.2 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 032-1 ... 800 205 160 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
1 G/–

3AE1 032-2 ... 1250 205 160 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
1 G/–

3AE1 033-1 ... 800 205 160 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
2 G/–

3AE1 033-2 ... 1250 205 160 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
2 G/–

3AE1 034-1 ... 800 205 160 n 3 25 36 28 63/


65
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
3 G/–

3AE1 034-2 ... 1250 205 160 n 3 25 36 28 63/


65
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
3 G/–

3AE1 035-1 ... 800 205 160 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
4 G/–

3AE1 035-2 ... 1250 205 160 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 115 75 80/ – 3M 442
02016 001
4 G/–

3AE1 042-1 ...

3AE1 042-2 ...


800 275 160

1250 275 160


n
n
3

3
16

16
36

36
17.9

17.9
40/
42
40/
42
60

60
20

20
2.1

2.1
129 140 115

129 140 115


75

75
80/ –

80/ –
3M 442
02017 001
3M 442
02017 001
1

1
F/–

F/–
3
3AE1 043-1 ... 800 275 160 n 3 20 36 22.4 50/
52
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
2 F/–

3AE1 043-2 ... 1250 275 160 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
2 F/–

3AE1 044-1 ... 800 275 160 n 3 25 36 28 63/


65
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
3 F/–

3AE1 044-2 ... 1250 275 160 n 3 25 36 28 63/


65
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
3 F/–

3AE1 045-1 ... 800 275 160 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
4 F/–

3AE1 045-2 ... 1250 275 160 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
4 F/–

3AE1 052-1 ... 800 310 160 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
1 E/–

3AE1 052-2 ... 1250 310 160 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
1 E/–

3AE1 053-1 ... 800 310 160 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
2 E/–

3AE1 053-2 ... 1250 310 160 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
2 E/–

3AE1 054-1 ... 800 310 160 n 3 25 36 28 63/


65
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
3 E/–

3AE1 054-2 ... 1250 310 160 n 3 25 36 28 63/


65
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
3 E/–

3AE1 055-1 ... 800 310 160 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
4 E/–

3AE1 055-2 ... 1250 310 160 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 110 75 80/ – 3M 442
02018 001
4 E/–

3AE1 062-1 ... 800 205 210 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
1 D/–

3AE1 062-2 ... 1250 205 210 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
1 D/–

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

Siemens HG 11.02 · 2006 43


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 45)
Rated lightning impulse withstand voltage
7.2 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 063-1 ... 800 205 210 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
2 D/–

3AE1 063-2 ... 1250 205 210 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
2 D/–

3AE1 064-1 ... 800 205 210 n 3 25 36 28 63/


65
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
3 D/–

3AE1 064-2 ... 1250 205 210 n 3 25 36 28 63/


65
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
3 D/–

3AE1 065-1 ... 800 205 210 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
4 D/–

3AE1 065-2 ... 1250 205 210 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 165 75 90/ – 3M 442
02022 001
4 D/–

3AE1 072-1 ... 800 275 210 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
1 B/C

3AE1 072-2 ... 1250 275 210 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
1 B/C

3 3AE1 073-1 ...

3AE1 073-2 ...


800 275 210

1250 275 210


n
n
3

3
20

20
36

36
22.4

22.4
50/
52
50/
52
60

60
20

20
2.1

2.1
129 140 165

129 140 165


75

75
90/
130
90/
130
3M 442
02023 001
3M 442
02023 001
2

2
B/C

B/C

3AE1 074-1 ... 800 275 210 n 3 25 36 28 63/


65
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
3 B/C

3AE1 074-2 ... 1250 275 210 n 3 25 36 28 63/


65
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
3 B/C

3AE1 075-1 ... 800 275 210 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
4 B/C

3AE1 075-2 ... 1250 275 210 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
4 B/C

3AE1 082-1 ... 800 310 210 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
1 A/C

3AE1 082-2 ... 1250 310 210 n 3 16 36 17.9 40/


42
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
1 A/C

3AE1 083-1 ... 800 310 210 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
2 A/C

3AE1 083-2 ... 1250 310 210 n 3 20 36 22.4 50/


52
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
2 A/C

3AE1 084-1 ... 800 310 210 n 3 25 36 28 63/


65
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
3 A/C

3AE1 084-2 ... 1250 310 210 n 3 25 36 28 63/


65
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
3 A/C

3AE1 084-4 ... 2000 310 210 n 3 25 36 28 63/


65
60 20 1.5 129 265 130 130 110/
150
3M 442
02028 001
3 L/C

3AE1 085-1 ... 800 310 210 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
4 A/C

3AE1 085-2 ... 1250 310 210 n 3 31.5 36 35.4 80/


82
60 20 2.1 129 140 160 75 90/
130
3M 442
02024 001
4 A/C

3AE1 085-4 ... 2000 310 210 n 3 31.5 36 35.4 80/


82
60 20 1.5 129 265 130 130 110/
150
3M 442
02028 001
4 L/C

3AE1 085-6 ... 2500 310 210 n 3 31.5 36 35.4 80/


82
60 20 1.5 129 265 130 130 110/
150
3M 442
02028 001
4 L/C

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

44 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Rated lightning impulse withstand voltage

Operating cycle diagram No. (see below)


7.2 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 086-2 ... 1250 310 210 n 3 40 36 44.9 100/


104
60 20 1.7 145 155 169 140 120/
160
3M 442
02070 001
5 M/C

3AE1 086-4 ... 2000 310 210 n 3 40 36 44.9 100/


104
60 20 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 086-6 ... 2500 310 210 n 3 40 36 44.9 100/


104
60 20 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 086-7 ... 3150 310 210 n 3 40 36 44.9 100/


104
60 20 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

3
Operating cycle diagram Operating cycle diagram
The permissible number of
Operating cycle No. n Operating cycle No. n
20 000 electrical operating cycles 20 000
HG11-2540_en eps
HG11-2539a_en eps

is shown as a function of
10 000 10 000
the breaking current
5 000 5 000
(r.m.s. value). All SION
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
curve shape beyond the
200 200
180 parameters defined in
130
100 IEC 62 271-100 is based on 100
80
50 average experience data. 50
The number of operating
20 cycles that can actually be 20
1 3 5 2 4
10 reached can be different 10
0.5 1 2 5 kA 10 16 20 25 40 50 0.5 1 2 5 kA 10 20 31.5 50
depending on the respec-
tive application.

Siemens HG 11.02 · 2006 45


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 49)
Rated lightning impulse withstand voltage
12 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 102-1 ... 800 205 150 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
1 K/–

3AE1 102-2 ... 1250 205 150 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
1 K/–

3AE1 103-1 ... 800 205 150 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
2 K/–

3AE1 103-2 ... 1250 205 150 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
2 K/–

3AE1 104-1 ... 800 205 150 n 3 25 36 28 63/


65
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
3 K/–

3AE1 104-2 ... 1250 205 150 n 3 25 36 28 63/


65
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
3 K/–

3AE1 105-1 ... 800 205 150 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
4 K/–

3AE1 105-2 ... 1250 205 150 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 105 75 80/ – 3M 442
02010 001
4 K/–

3 3AE1 112-1 ...

3AE1 112-2 ...


800 275 150

1250 275 150


n
n
3

3
16

16
36

36
17.9

17.9
40/
42
40/
42
75

75
28

28
2.1

2.1
129 140 105

129 140 105


75

75
80/
120
80/
120
3M 442
02011 001
3M 442
02011 001
1

1
I/J

I/J

3AE1 113-1 ... 800 275 150 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 105 75 80/
120
3M 442
02011 001
2 I/J

3AE1 113-2 ... 1250 275 150 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 105 75 80/
120
3M 442
02011 001
2 I/J

3AE1 114-1 ... 800 275 150 n 3 25 36 28 63/


65
75 28 2.1 129 140 105 75 80/
120
3M 442
02011 001
3 I/J

3AE1 114-2 ... 1250 275 150 n 3 25 36 28 63/


65
75 28 2.1 129 140 105 75 80/
120
3M 442
02011 001
3 I/J

3AE1 115-1 ... 800 275 150 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 105 75 80/
120
3M 442
02011 001
4 I/J

3AE1 115-2 ... 1250 275 150 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 105 75 80/
120
3M 442
02011 001
4 I/J

3AE1 122-1 ... 800 310 150 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
1 H/J

3AE1 122-2 ... 1250 310 150 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
1 H/J

3AE1 123-1 ... 800 310 150 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
2 H/J

3AE1 123-2 ... 1250 310 150 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
2 H/J

3AE1 124-1 ... 800 310 150 n 3 25 36 28 63/


65
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
3 H/J

3AE1 124-2 ... 1250 310 150 n 3 25 36 28 63/


65
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
3 H/J

3AE1 125-1 ... 800 310 150 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
4 H/J

3AE1 125-2 ... 1250 310 150 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 100 75 80/
120
3M 442
02012 001
4 H/J

3AE1 132-1 ... 800 205 160 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
1 G/–

3AE1 132-2 ... 1250 205 160 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
1 G/–

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

46 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 49)
Rated lightning impulse withstand voltage
12 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 133-1 ... 800 205 160 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
2 G/–

3AE1 133-2 ... 1250 205 160 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
2 G/–

3AE1 134-1 ... 800 205 160 n 3 25 36 28 63/


65
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
3 G/–

3AE1 134-2 ... 1250 205 160 n 3 25 36 28 63/


65
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
3 G/–

3AE1 135-1 ... 800 205 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
4 G/–

3AE1 135-2 ... 1250 205 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 115 75 80/ – 3M 442
02016 001
4 G/–

3AE1 142-1 ... 800 275 160 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
1 F/–

3AE1 142-2 ... 1250 275 160 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
1 F/–

3AE1 143-1 ...

3AE1 143-2 ...


800 275 160

1250 275 160


n
n
3

3
20

20
36

36
22.4

22.4
50/
52
50/
52
75

75
28

28
2.1

2.1
129 140 115

129 140 115


75

75
80/ –

80/ –
3M 442
02017 001
3M 442
02017 001
2

2
F/–

F/–
3
3AE1 144-1 ... 800 275 160 n 3 25 36 28 63/
65
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
3 F/–

3AE1 144-2 ... 1250 275 160 n 3 25 36 28 63/


65
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
3 F/–

3AE1 145-1 ... 800 275 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
4 F/–

3AE1 145-2 ... 1250 275 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
4 F/–

3AE1 152-1 ... 800 310 160 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
1 E/–

3AE1 152-2 ... 1250 310 160 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
1 E/–

3AE1 153-1 ... 800 310 160 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
2 E/–

3AE1 153-2 ... 1250 310 160 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
2 E/–

3AE1 154-1 ... 800 310 160 n 3 25 36 28 63/


65
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
3 E/–

3AE1 154-2 ... 1250 310 160 n 3 25 36 28 63/


65
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
3 E/–

3AE1 155-1 ... 800 310 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
4 E/–

3AE1 155-2 ... 1250 310 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 110 75 80/ – 3M 442
02018 001
4 E/–

3AE1 162-1 ... 800 205 210 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
1 D/–

3AE1 162-2 ... 1250 205 210 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
1 D/–

3AE1 163-1 ... 800 205 210 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
2 D/–

3AE1 163-2 ... 1250 205 210 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
2 D/–

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

Siemens HG 11.02 · 2006 47


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 49)
Rated lightning impulse withstand voltage
12 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 164-1 ... 800 205 210 n 3 25 36 28 63/


65
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
3 D/–

3AE1 164-2 ... 1250 205 210 n 3 25 36 28 63/


65
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
3 D/–

3AE1 165-1 ... 800 205 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
4 D/–

3AE1 165-2 ... 1250 205 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 165 75 90/ – 3M 442
02022 001
4 D/–

3AE1 172-1 ... 800 275 210 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 165 75 90/
130
3M 442
02023 001
1 B/C

3AE1 172-2 ... 1250 275 210 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 165 75 90/
130
3M 442
02023 001
1 B/C

3AE1 173-1 ... 800 275 210 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 165 75 90/
130
3M 442
02023 001
2 B/C

3AE1 173-2 ... 1250 275 210 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 165 75 90/
130
3M 442
02023 001
2 B/C

3 3AE1 174-1 ...

3AE1 174-2 ...


800 275 210

1250 275 210


n
n
3

3
25

25
36

36
28

28
63/
65
63/
65
75

75
28

28
2.1

2.1
129 140 165

129 140 165


75

75
90/
130
90/
130
3M 442
02023 001
3M 442
02023 001
3

3
B/C

B/C

3AE1 175-1 ... 800 275 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 165 75 90/
130
3M 442
02023 001
4 B/C

3AE1 175-2 ... 1250 275 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 165 75 90/
130
3M 442
02023 001
4 B/C

3AE1 182-1 ... 800 310 210 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
1 A/C

3AE1 182-2 ... 1250 310 210 n 3 16 36 17.9 40/


42
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
1 A/C

3AE1 183-1 ... 800 310 210 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
2 A/C

3AE1 183-2 ... 1250 310 210 n 3 20 36 22.4 50/


52
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
2 A/C

3AE1 184-1 ... 800 310 210 n 3 25 36 28 63/


65
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
3 A/C

3AE1 184-2 ... 1250 310 210 n 3 25 36 28 63/


65
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
3 A/C

3AE1 184-4 ... 2000 310 210 n 3 25 36 28 63/


65
75 28 1.5 129 265 130 130 110/
150
3M 442
02028 001
3 L/C

3AE1 184-6 ... 2500 310 210 n 3 25 36 28 63/


65
75 28 1.5 129 265 130 130 110/
150
3M 442
02028 001
3 L/C

3AE1 185-1 ... 800 310 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
4 A/C

3AE1 185-2 ... 1250 310 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 160 75 90/
130
3M 442
02024 001
4 A/C

3AE1 185-4 ... 2000 310 210 n 3 31.5 36 35.4 80/


82
75 28 1.5 129 265 130 130 110/
150
3M 442
02028 001
4 L/C

3AE1 185-6 ... 2500 310 210 n 3 31.5 36 35.4 80/


82
75 28 1.5 129 265 130 130 110/
150
3M 442
02028 001
4 L/C

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

48 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Rated lightning impulse withstand voltage

Catalog dimension drawings (see pages 54)


Operating cycle diagram No. (see below)
12 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 186-2 ... 1250 310 210 n 3 40 36 44.9 100/


104
75 28 1.7 145 155 169 140 120/
160
3M 442
02070 001
5 M/C

3AE1 186-4 ... 2000 310 210 n 3 40 36 44.9 100/


104
75 28 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 186-6 ... 2500 310 210 n 3 40 36 44.9 100/


104
75 28 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 186-7 ... 3150 310 210 n 3 40 36 44.9 100/


104
75 28 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 545-2 ... 1250 275 160 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 115 75 80/ – – 4 –/–

3AE1 575-2 ... 1250 275 210 n 3 31.5 36 35.4 80/


82
75 28 2.1 129 140 160 75 90/ – – 4 –/–

3AE1 575-6 ... 2500 275 210 n 3 31.5 36 35.4 80/


82
75 28 1.5 129 265 130 130 110/ – – 4 –/–

3AE1 576-2 ... 1250 275 210 n 3 40 36 44.9 100/


104
75 28 1.7 145 155 169 140 120/ – – 5 –/–

3AE1 576-4 ...

3AE1 576-6 ...


2000 275 210

2500 310 210


n
n
3

3
40

40
36

36
44.9

44.9
100/
104
100/
104
75

75
28

28
1.0

1.0
145 249 149 140 160/ –

145 249 149 140 160/ –



5

5
–/–

–/–
3
3AE1 576-7 ... 3150 310 210 n 3 40 36 44.9 100/
104
75 28 1.0 145 249 149 140 160/ – – 5 –/–

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

Operating cycle diagram Operating cycle diagram


The permissible number of
Operating cycle No. n Operating cycle No. n
20 000 electrical operating cycles 20 000
HG11-2540_en eps
HG11-2539a_en eps

is shown as a function of
10 000 10 000
the breaking current
5 000 (r.m.s. value). All SION 5 000

vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
curve shape beyond the
200 200
180 parameters defined in
130
100 IEC 62 271-100 is based on 100
80
50 average experience data. 50
The number of operating
20 cycles that can actually be 20
1 3 5 2 4
10 reached can be different 10
0.5 1 2 5 kA 10 16 20 25 40 50 0.5 1 2 5 kA 10 20 31.5 50
depending on the respec-
tive application.

Siemens HG 11.02 · 2006 49


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 53)
Rated lightning impulse withstand voltage
17.5 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 201-1 ... 800 205 150 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
1 K/–

3AE1 201-2 ... 1250 205 150 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
1 K/–

3AE1 202-1 ... 800 205 150 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
2 K/–

3AE1 202-2 ... 1250 205 150 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
2 K/–

3AE1 204-1 ... 800 205 150 n 3 25 36 28 63/


65
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
3 K/–

3AE1 204-2 ... 1250 205 150 n 3 25 36 28 63/


65
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
3 K/–

3AE1 205-1 ... 800 205 150 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
4 K/–

3AE1 205-2 ... 1250 205 150 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 237 150 80/ – 3M 442
02013 001
4 K/–

3 3AE1 211-1 ...

3AE1 211-2 ...


800 275 150

1250 275 150


n
n
3

3
12.5

12.5
36

36
14.9

14.9
31/
33
31/
33
95

95
38

38
2.1

2.1
129 275 214 150

129 275 214 150


80/
120
80/
120
3M 442
02014 001
3M 442
02014 001
1

1
I/J

I/J

3AE1 212-1 ... 800 275 150 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 214 150 80/
120
3M 442
02014 001
2 I/J

3AE1 212-2 ... 1250 275 150 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 214 150 80/
120
3M 442
02014 001
2 I/J

3AE1 214-1 ... 800 275 150 n 3 25 36 28 63/


65
95 38 2.1 129 275 214 150 80/
120
3M 442
02014 001
3 I/J

3AE1 214-2 ... 1250 275 150 n 3 25 36 28 63/


65
95 38 2.1 129 275 214 150 80/
120
3M 442
02014 001
3 I/J

3AE1 215-1 ... 800 275 150 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 214 150 80/
120
3M 442
02014 001
4 I/J

3AE1 215-2 ... 1250 275 150 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 214 150 80/
120
3M 442
02014 001
4 I/J

3AE1 221-1 ... 800 310 150 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
1 H/J

3AE1 221-2 ... 1250 310 150 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
1 H/J

3AE1 222-1 ... 800 310 150 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
2 H/J

3AE1 222-2 ... 1250 310 150 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
2 H/J

3AE1 224-1 ... 800 310 150 n 3 25 36 28 63/


65
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
3 H/J

3AE1 224-2 ... 1250 310 150 n 3 25 36 28 63/


65
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
3 H/J

3AE1 225-1 ... 800 310 150 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
4 H/J

3AE1 225-2 ... 1250 310 150 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 190 150 80/
120
3M 442
02015 001
4 H/J

3AE1 231-1 ... 800 205 160 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
1 G/–

3AE1 231-2 ... 1250 205 160 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
1 G/–

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

50 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 53)
Rated lightning impulse withstand voltage
17.5 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 232-1 ... 800 205 160 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
2 G/–

3AE1 232-2 ... 1250 205 160 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
2 G/–

3AE1 234-1 ... 800 205 160 n 3 25 36 28 63/


65
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
3 G/–

3AE1 234-2 ... 1250 205 160 n 3 25 36 28 63/


65
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
3 G/–

3AE1 235-1 ... 800 205 160 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
4 G/–

3AE1 235-2 ... 1250 205 160 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 247 150 80/ – 3M 442
02019 001
4 G/–

3AE1 241-1 ... 800 275 160 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
1 F/–

3AE1 241-2 ... 1250 275 160 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
1 F/–

3AE1 242-1 ...

3AE1 242-2 ...


800 275 160

1250 275 160


n
n
3

3
16

16
36

36
17.9

17.9
40/
42
40/
42
95

95
38

38
2.1

2.1
129 275 224 150

129 275 224 150


80/ –

80/ –
3M 442
02020 001
3M 442
02020 001
2

2
F/–

F/–
3
3AE1 244-1 ... 800 275 160 n 3 25 36 28 63/
65
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
3 F/–

3AE1 244-2 ... 1250 275 160 n 3 25 36 28 63/


65
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
3 F/–

3AE1 245-1 ... 800 275 160 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
4 F/–

3AE1 245-2 ... 1250 275 160 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
4 F/–

3AE1 251-1 ... 800 310 160 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
1 E/–

3AE1 251-2 ... 1250 310 160 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
1 E/–

3AE1 252-1 ... 800 310 160 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
2 E/–

3AE1 252-2 ... 1250 310 160 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
2 E/–

3AE1 254-1 ... 800 310 160 n 3 25 36 28 63/


65
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
3 E/–

3AE1 254-2 ... 1250 310 160 n 3 25 36 28 63/


65
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
3 E/–

3AE1 255-1 ... 800 310 160 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
4 E/–

3AE1 255-2 ... 1250 310 160 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 200 150 80/ – 3M 442
02021 001
4 E/–

3AE1 261-1 ... 800 205 210 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
1 D/–

3AE1 261-2 ... 1250 205 210 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
1 D/–

3AE1 262-1 ... 800 205 210 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
2 D/–

3AE1 262-2 ... 1250 205 210 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
2 D/–

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

Siemens HG 11.02 · 2006 51


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Operating cycle diagram No. (see page 53)
Rated lightning impulse withstand voltage
17.5 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 264-1 ... 800 205 210 n 3 25 36 28 63/


65
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
3 D/–

3AE1 264-2 ... 1250 205 210 n 3 25 36 28 63/


65
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
3 D/–

3AE1 265-1 ... 800 205 210 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
4 D/–

3AE1 265-2 ... 1250 205 210 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 165 150 90/ – 3M 442
02025 001
4 D/–

3AE1 271-1 ... 800 275 210 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 165 150 90/
130
3M 442
02026 001
1 B/C

3AE1 271-2 ... 1250 275 210 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 165 150 90/
130
3M 442
02026 001
1 B/C

3AE1 272-1 ... 800 275 210 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 165 150 90/
130
3M 442
02026 001
2 B/C

3AE1 272-2 ... 1250 275 210 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 165 150 90/
130
3M 442
02026 001
2 B/C

3 3AE1 274-1 ...

3AE1 274-2 ...


800 275 210

1250 275 210


n
n
3

3
25

25
36

36
28

28
63/
65
63/
65
95

95
38

38
2.1

2.1
129 275 165 150

129 275 165 150


90/
130
90/
130
3M 442
02026 001
3M 442
02026 001
3

3
B/C

B/C

3AE1 275-1 ... 800 275 210 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 165 150 90/
130
3M 442
02026 001
4 B/C

3AE1 275-2 ... 1250 275 210 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 165 150 90/
130
3M 442
02026 001
4 B/C

3AE1 281-1 ... 800 310 210 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
1 A/C

3AE1 281-2 ... 1250 310 210 n 3 12.5 36 14.9 31/


33
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
1 A/C

3AE1 282-1 ... 800 310 210 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
2 A/C

3AE1 282-2 ... 1250 310 210 n 3 16 36 17.9 40/


42
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
2 A/C

3AE1 284-1 ... 800 310 210 n 3 25 36 28 63/


65
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
3 A/C

3AE1 284-2 ... 1250 310 210 n 3 25 36 28 63/


65
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
3 A/C

3AE1 284-4 ... 2000 310 210 n 3 25 36 28 63/


65
95 38 1.5 129 265 130 130 110/
150
3M 442
02029 001
3 L/C

3AE1 284-6 ... 2500 310 210 n 3 25 36 28 63/


65
95 38 1.5 129 265 130 130 110/
150
3M 442
02029 001
3 L/C

3AE1 285-1 ... 800 310 210 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
4 A/C

3AE1 285-2 ... 1250 310 210 n 3 31.5 36 35.4 80/


82
95 38 2.1 129 275 160 150 90/
130
3M 442
02027 001
4 A/C

3AE1 285-4 ... 2000 310 210 n 3 31.5 36 35.4 80/


82
95 38 1.5 129 265 130 130 110/
150
3M 442
02029 001
4 L/C

3AE1 285-6 ... 2500 310 210 n 3 31.5 36 35.4 80/


82
95 38 1.5 129 265 130 130 110/
150
3M 442
02029 001
4 L/C

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

52 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Catalog dimension drawings (see pages 54/55)
Rated lightning impulse withstand voltage

Operating cycle diagram No. (see below)


17.5 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 286-2 ... 1250 310 210 n 3 40 36 44.9 100/


104
95 38 1.7 145 249 169 140 120/
160
3M 442
02070 001
5 M/C

3AE1 286-4 ... 2000 310 210 n 3 40 36 44.9 100/


104
95 38 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 286-6 ... 2500 310 210 n 3 40 36 44.9 100/


104
95 38 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

3AE1 286-7 ... 3150 310 210 n 3 40 36 44.9 100/


104
95 38 1.0 145 249 149 140 160/
210
3M 442
02071 001
5 M/C

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N

3
Operating cycle diagram Operating cycle diagram
The permissible number of
Operating cycle No. n Operating cycle No. n
20 000 electrical operating cycles 20 000 HG11-2541_en eps
HG11-2537a_en eps

is shown as a function of
10 000 10 000
the breaking current
5 000 5 000
(r.m.s. value). All SION
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
350
curve shape beyond the
200
180 200 parameters defined in
100 IEC 62 271-100 is based on 100
80
50 average experience data. 50
The number of operating
20 20
cycles that can actually be 1 4
2 3 5
10 reached can be different 10
0.5 1 2 5 kA 10 16 20 25 40 50 0.5 1 2 5 kA 10 12.5 20 31.5 50
depending on the respec-
tive application.

Siemens HG 11.02 · 2006 53


Technical Data SION Vacuum Circuit-Breakers
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV

Dimension drawing A Dimension drawing B


370 565 370 565

HG11-2520 eps
HG11-2519 eps
ca.93

ca.93
210 210 210 210

310

275
572,5

562,5
562,5
517,5

517,5
540

540
237,5

217,5
20 20
310 279 310 279
380 380

Dimension drawing C
472/5221) 794

HG11-2521a eps
102 210 210 187
100

30
Width across flats mm Height mm
a b
310 905
a
b

275 850
1) for 40 kA
345

286,5

43

3
27,5

27,5

688/7381)

Dimension drawing D Dimension drawing E


370 565 370 465
HG11-2522 eps

HG11-2523 eps
ca.93

ca.93

210 210 160 160


310
205

572,5
562,5

562,5
517,5

517,5
540

540

237,5
217,5

20 20
310 279 310 279
380 380

Dimension drawing F Dimension drawing G


370 465 370 465
HG11-2525 eps
HG11-2524 eps
ca.93

ca.93

160 160 160 160


275

205
562,5

562,5
517,5

517,5
540

540
217,5

217,5

20 20
310 279 310 279
380 380

54 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV

Dimension drawing H Dimension drawing I


370 445 370 445

HG11-2527 eps
HG11-2526 eps
ca.93

ca.93
150 150 150 150

310

275
572,5

562,5
562,5
517,5

517,5
540

540
237,5

217,5
20 20
310 279 310 279
380 380

Dimension drawing J
472 594

HG11-2528a eps
102 150 150 147
100

30
Width across flats mm Height mm
a b
310 905
a
b

275 850
341

266,5

43
27,5
27,5

688
710
3
Dimension drawing K Dimension drawing L
370 445 370 565
HG11-2529 eps

HG11-2530 eps
ca.93

ca.93

150 150 210 210


310
205
562,5

562,5
581
517,5

517,5
540

540

237,5
217,5

20 20
310 279 310 279
380 380

Dimension drawing M Dimension drawing N


420 210 210 a
PCD a c d Weight
HG11-2531 eps
ca.93

150 529 500 470 ca. 15 kg


160 529 500 470 ca. 15 kg
424

210 679 650 620 ca. 20 kg


310
600

Height of drawout element: 60


540

107

PCD Pole-center distance


237,5

a Width of drawout element


c
c Total width across wheels
50 d Distance between wheels
HG11-2589 eps

350 279
450
d

Siemens HG 11.02 · 2006 55


Technical Data SION Vacuum Circuit-Breakers
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Operating cycle diagram No. (see page 57)
Rated lightning impulse withstand voltage
24 kV

Catalog dimension drawings (see page 58)


Voltage drop ΔU between connections
Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


50/60 Hz

Rated short-circuit breaking current

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 321-1 ... 800 310 210 n 3 12.5 36 14.9 31/


33
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
1 A/B

3AE1 321-2 ... 1250 310 210 n 3 12.5 36 14.9 31/


33
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
1 A/B

3AE1 322-1 ... 800 310 210 n 3 16 36 17.9 40/


42
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
2 A/B

3AE1 322-2 ... 1250 310 210 n 3 16 36 17.9 40/


42
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
2 A/B

3AE1 322-4 ... 2000 310 210 n 3 16 36 17.9 40/


42
125 50 2.0 200 340 200 205 140/
180
3M 442
02051 001
2 A/B

3AE1 323-1 ... 800 310 210 n 3 20 36 22.4 50/


52
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
3 A/B

3AE1 323-2 ... 1250 310 210 n 3 20 36 22.4 50/


52
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
3 A/B

3AE1 323-4 ... 2000 310 210 n 3 20 36 22.4 50/


52
125 50 2.0 200 340 200 205 140/
180
3M 442
02051 001
3 A/B

3 3AE1 323-6 ...

3AE1 324-1 ...


2500 310 210

800 310 210


n
n
3

3
20

25
36

36
22.4

28
50/
52
63/
65
125

125
50

50
2.0

2.6
200 340 200 205

200 350 200 210


140/
180
120/
160
3M 442
02051 001
3M 442
02050 001
3

4
A/B

A/B

3AE1 324-2 ... 1250 310 210 n 3 25 36 28 63/


65
125 50 2.6 200 350 200 210 120/
160
3M 442
02050 001
4 A/B

3AE1 324-4 ... 2000 310 210 n 3 25 36 28 63/


65
125 50 2.0 200 340 200 205 140/
180
3M 442
02051 001
4 A/B

3AE1 324-6 ... 2500 310 210 n 3 25 36 28 63/


65
125 50 2.0 200 340 200 205 140/
180
3M 442
02051 001
4 A/B

3AE1 352-1 ... 800 310 275 n 3 16 36 17.9 40/


42
125 50 2.6 200 350 265 210 130/
180
3M 442
02052 001
2 C/E

3AE1 352-2 ... 1250 310 275 n 3 16 36 17.9 40/


42
125 50 2.6 200 350 265 210 130/
180
3M 442
02052 001
2 C/E

3AE1 352-4 ... 2000 310 275 n 3 16 36 17.9 40/


42
125 50 2.0 200 340 265 205 150/
200
3M 442
02053 001
2 D/E

n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing F

56 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

(fixed-mounted circuit-breaker/slide-in module)

(fixed-mounted circuit-breaker/slide-in module)


Rated lightning impulse withstand voltage

Catalog dimension drawings (see page 58)


Operating cycle diagram No. (see below)
24 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60 694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

rated short-circuit breaking current

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO

DC component in % of the
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,

(has to be ordered)
Width across flats

withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weight 1)
Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 353-1 ... 800 310 275 n 3 20 36 22.4 50/


52
125 50 2.6 200 350 265 210 130/
180
3M 442
02052 001
3 C/E

3AE1 353-2 ... 1250 310 275 n 3 20 36 22.4 50/


52
125 50 2.6 200 350 265 210 130/
180
3M 442
02052 001
3 C/E

3AE1 353-4 ... 2000 310 275 n 3 20 36 22.4 50/


52
125 50 2.0 200 340 265 205 150/
200
3M 442
02053 001
3 D/E

3AE1 353-6 ... 2500 310 275 n 3 20 36 22.4 50/


52
125 50 2.0 200 340 265 205 150/
200
3M 442
02053 001
3 D/E

3AE1 354-1 ... 800 310 275 n 3 25 36 28 63/


65
125 50 2.6 200 350 265 210 130/
180
3M 442
02052 001
4 C/E

3AE1 354-2 ... 1250 310 275 n 3 25 36 28 63/


65
125 50 2.6 200 350 265 210 130/
180
3M 442
02052 001
4 C/E

3AE1 354-4 ... 2000 310 275 n 3 25 36 28 63/


65
125 50 2.0 200 340 265 205 150/
200
3M 442
02053 001
4 D/E

3AE1 354-6 ... 2500 310 275 n 3 25 36 28 63/


65
125 50 2.0 200 340 265 205 150/
200
3M 442
02053 001
4 D/E

3AE1 724-2 ...

3AE1 754-6 ...


1250 320 210

2500 320 275


n
n
3

3
25

25
36

36
28

28
63/
65
63/
65
125

125
50

50
2.6

2.0
200 350 200 210 120/ –

200 340 200 205 150/ –



4

4
–/–

–/–
3
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing F

Operating cycle diagram Operating cycle diagram


The permissible number of
Operating cycle No. n Operating cycle No. n
20 000 electrical operating cycles 20 000
HG11-2538a_en eps

HG11-2542_en eps

is shown as a function of
10 000 10 000
the breaking current
5 000 5 000
(r.m.s. value). All SION
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
curve shape beyond the
200 200
150 parameters defined in
100 100
IEC 62 271-100 is based on 90
50 average experience data. 50
The number of operating 30
20 cycles that can actually be 20
1 3 2 4
10 reached can be different 10
0.5 1 2 5 10 12.5 20 kA 50 0.5 1 2 5 10 16 25 kA 50
depending on the respec-
tive application.

Siemens HG 11.02 · 2006 57


Technical Data SION Vacuum Circuit-Breakers
Dimensions drawings for voltage level 24 kV

Dimension drawing A Dimension drawing F


420 570 a
PCD a c d Weight

HG11-2532 eps
210 210
210 679 650 620 ca. 20 kg
ca.93

275 879 850 820 ca. 25 kg

424
Height of drawout element: 60
310
739

739

PCD Pole-center distance

107
a Width of drawout element
540

c Total width across wheels


283

c d Distance between wheels

HG11-2590 eps
58 360 269
468
d
Dimension drawing B
532 794

HG11-2533a eps
112 210 210 187
100

30
1040,5
1013

310
485,5

346

332

41,5
27,5

27,5

788

3 Dimension drawing C
420
810

700
Dimension drawing D
420 700

HG11-2535 eps
HG11-2534 eps

275 275 275 275


ca.93
ca.93

310
310

739

739
739

739

540
540

283
283

58 360 269 58 360 269


468 468

Dimension drawing E
532 994
HG11-2536a eps

112 275 275 222


100

30
1040,5
1013

310
485,5

346

332

41,5
27,5

27,5

788
810

58 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Technical Data
Operating times, short-circuit protection of motors, consumption data of releases

Operating times at rated voltage of the secondary circuit

Vacuum circuit-breaker equipment Operating time

Closing time – < 75 ms


Opening time 1st shunt release < 65 ms
2nd release < 50 ms
Arcing time – < 15 ms
Opening time 1st shunt release < 80 ms
2nd release < 65 ms
Dead time – 300 ms
CLOSE/OPEN contact time 1st shunt release < 75 ms
2nd release < 60 ms
Minimum command duration Closing solenoid 45 ms
1st shunt release 40 ms
2nd release 20 ms
Pulse time for circuit-breaker tripping signal 1st shunt release > 15 ms
2nd release > 10 ms
Charging time for electrical operation < 10 s
Synchronism error between the poles 2 ms

Short-circuit protection of motors (fuse protection of drive motors)

Rated Operating voltage Power consumption Smallest possible rated


voltage of of the motor current1) of the m.c.b.
the motor (miniature circuit-breaker)
with C-characteristic

V
DC 24
DC 48
max. V
26
53
min. V
20
41
W (at DC)
350
350
VA (at AC)


A
8
6
3
DC 60 66 51 350 – 4
DC 110 121 93 350 – 2
DC 220 242 187 350 – 1.6
AC 110 121 93 – 400 2
AC 230 244 187 – 400 1.6

1) The current inrush in the drive motor can be neglected due to its very short presence

Consumption data of releases

Release Power consumption Tripping ranges

Operation at Tripping voltage Tripping voltage or


tripping current
DC AC 50/60 Hz at DC at AC 50/60 Hz
approx. W approx. VA
Closing solenoid 3AY15 10 140 140 85 to 110 % U 85 to 110 % U
1st shunt release 140 140 70 to 110 % U 85 to 110 % U
(without energy store) 3AY15 10
2nd shunt release 70 50 70 to 110 % U 85 to 110 % U
(with energy store) 3AY11 01
Undervoltage release 3AY11 03 20 20 35 to 0 % U 35 to 0 % U
Current-transformer operated release 3AX11 02 – 10 2) – 90 to 110 % Ia
(rated current 0.5 A or 1 A)
Current-transformer operated release 3AX11 04 – – – –
(tripping pulse W 0.1 Ws)

2) Consumption at pickup current (90 % of the rated current) and open armature

Siemens HG 11.02 · 2006 59


Technical Data SION Vacuum Circuit-Breakers
Circuit diagrams

Basic equipment
X1

21
-S3
21 13
21 22
-S21 -K1
22 14
22
31
A1 -K1 A1 11 13 21 23 31 33 41 43 51 53 61 63
32 -K1
M 11 23 -S1
-M1 A1 A2 12 14 22 24 32 34 42 44 52 54 62 64
1= -S1 -S4 13 21 -S1
-Y9 12 A1 24
D2 A2 14 22 -Y1
HG11-2506 eps
22
-S22
21 A2
HG11-2505 eps

X1

Motor Closing and anti- Signal 1st shunt Auxiliary switch 6 NO + 6 NC


operating pumping for motor “closing spring release
mecha- operating stored-energy charged“
nism mechanism

Additional equipment
X0 X0
X1 X1 -X0

21
-S3
21 13 22
-K1
22 14
13
31
-K1 -S6
A1 14
32 -K1 11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123
11
A1 A2 -S1
-S1 12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124
-Y9 12
A2 21
13 -S7
22
-S5
14
HG11-2508 eps
HG11-2507 eps

HG11-2509 eps
13
-S12

3 X1
X0
14

X1
X0
-X0

Closing and anti-pumping Circuit-breaker Auxiliary switch 12 NO + 12 NC


for motor operating tripping signal
stored-energy mechanism

Additional equipment: Releases (for possible combinations see chapter 2 under “Secondary equipment“)
X0 X0 X0 X0
X1 X1 X1 X1

D1
-Y7
33
-S1 D2
34 43
A1
-Y2 A1 A1 -S1
44
-Y4 -Y6
A2 A2
A2 -R1 1
HG11-2511 eps

HG11-2512 eps
HG11-2510 eps

HG11-2513 eps

X1 X1 X1 X1
X0 X0 X0 X0
2nd shunt Current-transformer Low-energy current- Undervoltage release
release operated release transformer operated
0.5 A or 1 A release 0.1 Ws

Legend
K1 Contactor (anti-pumping) S3 Position switch X0 Plug connector Y 6 Current-transformer operated
M1 Motor operating mechanism (anti-pumping) 24-pole or 64-pole release (tripping pulse W W 0.1 Ws)
R1 Resistance S4 Position switch X1 Terminal strip 25-pole Y7 Undervoltage release
S1 Auxiliary switch (for closing spring charged) Y1 1st shunt release Y9 Closing solenoid
S12 Mechanical interlocking S5 Electrical closing lock-out Y2 2nd shunt release
S21 Position switches S6 Circuit-breaker tripping signal Y4 Current-transformer Abbreviations:
S22 (to de-energize the motor oper- S7 Cutout switch for operated release NO Normally open
ating mechanism after charging) circuit-breaker tripping signal (rated current 0.5 A or 1 A) NC Normally closed

60 Siemens HG 11.02 · 2006


SION Vacuum Circuit-Breakers Annex
Contents

Contents Page

Annex 61

Inquiry form 62

Configuration instructions 63
Configuration aid Foldout page

R-HG11-181.tif

Brandenburger Tor, Berlin, Germany

4
R-HG11-180.eps

Switchgear Factory in Berlin, Germany

Siemens HG 11.02 · 2006 61


Annex SION Vacuum Circuit-Breakers
Inquiry form

Please copy and return to your Siemens partner


or you can use our prompted online configurator
under www.siemens.com/SION

Inquiry concerning
Technical data Other values

o SION standard Rated voltage o 7.2 kV


o 24 kV
o 12 kV o 17.5 kV
o _ _ _ kV
circuit-breaker
o SION slide-in module Rated lightning impulse
withstand voltage
o 60 kV
o 125 kV
o 75 kV o 95 kV
o _ _ _ kV
Rated short-duration o 20 kV o 28 kV o 38 kV
power-frequency withstand voltage o 42 kV o 50 kV o 55 kV o _ _ _ kV
Please
Rated short-circuit o 12.5 kA o 16 kA o 20 kA
o 25 kA o 31.5 kA o 40 kA o _ _ _ kA
o Submit an offer breaking current

o Call us Rated normal current o 800 A o 1250 A o 2000 A


o Visit us o 2500 A o 3150 A o _ _ _ kA
Pole-center distance o 150 mm o 160 mm o 210 mm o 275 mm
Width across flats o 205 mm o 275 mm o 310 mm
Your address
Secondary equipment
Company
For possible combinations see pages 23 to 26 or 32 to 35
Dept. Circuit-breaker equipment o Fixed mounting o With drawout element
(only for standard circuit-breaker) o Drawout element, contact arms
Name o Drawout element, contact arms, bushings
Motor operating mechanism o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz
Street
Closing solenoid o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz
Postal code/city 1st shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz
2nd shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz
Phone
Current-transformer operated release o
Fax Undervoltage release o _ _ _ V DC o AC _ _ _ V, _ _ _ Hz
Auxiliary switch o 6 NO + 6 NC o 12 NO + 12 NC
E-mail
Low-voltage connection o 27-pole o 24-pole o 64-pole
4 Siemens AG
o Mechanical interlocking
terminal strip plug plug

o Circuit-breaker tripping signal


Dept. o Electrical closing lock-out
o Operating instructions o English o German o French o Spanish
Name

Street
Application and other requirements
Postal code/city

Fax

o Please check off _ _ _ Please fill in

62 Siemens HG 11.02 · 2006


You prefer to configure your SION vacuum circuit-breaker on your own? For configuration of your
Please follow the steps for configuration and enter the order number in the configuration aid. SION vacuum circuit-breaker
Alternatively you can also use our prompted online configurator under www.siemens.com/SION.

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
3 A E 1 n n n – n n n n n – n n n n – Z
Instruction for configuration of the SION vacuum circuit-breaker

1st step: Definition of the primary part (see pages 15 to 22 and pages 28 to 31)

page 22 or 31
See page 15 or 28

See page 23 or 32
See page 23 or 32
See page 24 or 33
See page 24 or 33

See page 25 or 34
See page 25 or 34
See page 26 or 35
See page 26 or 35

See page 27 or 36
Please specify the following ratings: Possible options:

to
Rated voltage (Ur) Ur: 7.2 kV to 24 kV
Rated lightning impulse withstand voltage (Up) Up: 60 kV to 125 kV
Rated short-duration power-frequency withstand voltage (Ud) Ud: 20 kV to 55 kV
Rated short-circuit breaking current (Isc) Isc: 12.5 kA to 40 kA 3 A E 1 – –
Rated normal current (Ir) Ir: 800 A to 3150 A
Pole-centre distance 150 mm to 275 mm + + + +
Width across flats 205 mm to 310 mm
+ + + +
These ratings define the positions 5 to 8 of the order number
3 A E 1 – –

+ + + +
2nd step: Definition of the secondary equipment (see pages 23 to 26 and pages 32 to 35)
+ + + +

Please specify the following equipment features: Possible options: 3 A E 1 – –

+ + + +
Release combination Shunt release, current-transformer operated release
(position 9) and undervoltage release
Closing solenoid Operating voltages from 24 V DC to 240 V AC + + + +
(position 10)
Operating voltage of the releases Operating voltages from 24 V DC to 240 V AC 3 A E 1 – –
(positions 11 / 12)
Installation accessories Fixed mounting; with drawout element, contact + + + +
(position 13) arms, contact system; slide-in module
Motor operating mechanism Operating voltages from 24 V DC to 240 V AC
(position 14) + + + +
Number of auxiliary contacts 6 NO + 6 NC, 12 NO + 12 NC
(position 15) 3 A E 1 – –
Design of the control cable connection 27-pole terminal strip, 24-pole plug connector
(position 15) 64-pole plug connector
+ + + +
Mechanical interlocking, circuit-breaker tripping signal With or without
(position 15)
Language of the documentation English, German, French, Spanish + + + +
(position 16)
Frequency of the operating voltage of the 50 Hz/60 Hz 3 A E 1 – –
secondary equipment at AC (position 16)
+ + + +
These equipment features define the positions 9 to 16 of the order number
+ + + +
3rd step: Do you have any further requirements concerning the equipment? (Please refer to pages 27 and 36)
3 A E 1 – –
Should you still need more options than the possible special equipment like halogen-free and
flame-retardant or silicone-free version, condensate protection or an additional rating plate, etc., + + + +
please contact your responsible sales partner.
+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +
Siemens HG 11.02 · 2006 63
If not stated otherwise on the individual pages of this Siemens AG For questions concerning Subject to change without notice
Order No. E50001-K1511-A021-A1-7600
catalog, we reserve the right to include modifications, Power Transmission and Distribution Power Transmission and Distribution: Printed in Germany
especially regarding the stated values, dimensions and weights. Medium Voltage Division You can contact our Customer Support Dispo 31601
Drawings are not binding. All product designations used Nonnendammallee 104 Center 24 hours a day, 365 days a year. KG 12.06 7.0 60 En
are trademarks or product names of Siemens AG or other 13623 Berlin Tel.: +49 180/524 70 00 101983 6101/C6103
suppliers. If not stated otherwise, all dimensions in this Germany Fax: +49 180/524 24 71
catalog are given in mm. (Calls charged: e.g. 12 Ct/min)
www.siemens.com/SION E-mail: support.energy@siemens.com
www.siemens.com/energy-support
Responsible for
Technical contents: General editing:
Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC M The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
Berlin Erlangen The required features should therefore be specified in each individual case at the time of closing the contract.
R-HG11-182.tif