R-HG11-172.tif
Contents Page
Equipment Selection 13
Ordering data and configuration example
Selection of basic types, standard circuit-breakers 15
14
2
Secondary equipment for standard circuit-breakers 23
Selection of basic types, slide-in modules 28
Secondary equipment for slide-in modules 32
Accessories and spare parts 37
Technical Data 41
Electrical data, dimensions and weights:
Voltage levels 7.2 kV, 12 kV, 17.5 kV 42
3
Voltage level 24 kV 56
Operating times, short-circuit protection
of motors, consumption data of releases 59
Circuit diagrams 60
Annex 61
Inquiry form
Configuration instructions
62
63 4
Configuration aid Foldout page
© Siemens AG 2006
R-HG11-173.tif
Contents Page
Description 5
General 6 1
Construction and mode of operation:
Switching medium 7
Pole assemblies 7
Operating mechanism 7
Trip-free mechanism 7
Releases 8
Closing / Circuit-breaker tripping signal 8
Interlocking 8
Low-voltage interface 8
Slide-in module 9
R-HG11-174.tif
Standards 9
Ambient conditions 10
Industrial application: Refinery
Current carrying capacity 10
Dielectric strength 10
Product range overview and basic equipment 11
SION vacuum circuit-breakers control all switching capacitors, generators, filter circuits, motors and
duties in medium-voltage distribution systems and are reactors. The comprehensive installation accessories
R-HG11-168.eps
Our comprehensive range of standard circuit-breakers offers The slide-in module contains all components required for
a wide selection for pole-center distances and widths across the circuit-breaker compartment of a panel. It consists of the
flats as well as various built-in accessories packages for circuit-breaker on a drawout element with contact arms,
voltage levels from 7.2 to 24 kV. The drawout element, fitted in a cartridge with side and rear walls. The module is
contact arms, contact systems and bushings enable easy equipped with bushings, fixed contacts, shutters and the
integration in all customary medium-voltage switchgear shutter mechanism. The surfaces of the side and rear walls
types. Identical dimensions and connection dimensions form the tested connection compartment.
across several voltage levels reduce planning costs and the
diversity of panel versions. High reliability and availability
are just as much a matter of course as 10,000 maintenance-
free operating cycles.
Switching medium
The vacuum switching technology of the vacuum interrup-
ters, which has been proven for 30 years, serves as arc-
quenching principle.
Pole assemblies
The pole assemblies consist of the vacuum interrupters and
1
the pole shells. The vacuum interrupters are air-insulated
R-HG11-170.eps
and freely accessible. The pole assemblies are fixed on the
mounting plate of the operating mechanism and supported
by means of the pole shell. The vacuum interrupter (3) is Vacuum circuit-breaker
3AE12
mounted rigidly to the upper interrupter support. The lower 17.5 kV / 25 kA /
part of the interrupter is guided in the lower interrupter 1250 A
2
Operating mechanism 1 Separating shell
3 to the operating
The whole operating mechanism is mounted on its mount-
mechanism
ing plate, including the motor, releases, indicators and 4 2 Upper connection
actuating devices. 3 Interrupter
Stored-energy operating mechanism 5 4 Pole shell
5 Lower connection
The operating mechanism is a stored-energy spring mechan- 6 6 Bell-type insulator
ism. The force is transmitted from the operating mechan-
ism to the pole assemblies via operating levers. The closing Pole structure
spring can be charged either electrically or manually and
latches automatically in when charging is complete. The
closing spring acts as the stored-energy mechanism.
To close the breaker, the closing spring can be unlatched
either mechanically by means of the local “ON” pushbutton
or electrically by remote control. The closing spring charges 1
the contact-pressure / opening springs as the breaker closes. 1 Cover of low-voltage
interface
The now discharged closing spring will be charged again 2 Central control board
automatically by the mechanism motor. 2
HG11-2501 eps
Trip-free mechanism
In the event of an opening command being given after a 3 1 Auxiliary switch
2 1st release
closing operation has been initiated, the moving contacts 1 4
3 Terminal strip
return to the open position and remain there even if the
5 4 Motor
closing command is sustained. This means that the contacts
2 5 Closing solenoid
of the vacuum circuit-breakers are momentarily in the closed 6
6 Closing spring
position. 7 7 Gear
HG11-2502 eps
Slide-in module
Besides the circuit-breaker installation equipment available for
standard circuit-breakers by means of the packages for the
drawout element, contact arms, fixed contacts and bushings,
it is also possible to supply a complete slide-in module.
The slide-in module contains all necessary components for
the circuit-breaker compartment of a panel. It consists of the
circuit-breaker on a drawout element with contact arms,
1
mounted in a cartridge with side and rear walls, equipped
with bushings, fixed contacts, shutters and shutter mecha-
nism. The surfaces of the side and rear walls form the tested
R-HG11-171.eps
connection compartment.
The vacuum circuit-breaker on the drawout element is
racked into the cartridge with the associated handle by the
rotary movement of the spindle. The shutter mechanism
is controlled by lateral gates, and the shutters are opened Slide-in module
for contacting. Signals for the service and disconnected 1 Contact system
positions are transmitted to the module connector at the 2 Fixed contact 6 Contact arm
3 Shutter 7 Low-voltage interface
low-voltage interface of the vacuum circuit-breaker via the
4 Bushing 8 Vacuum circuit-breaker
position switches of the drawout element.
5 Cartridge 9 Drawout element
Standards
The vacuum circuit-breakers conform to the following
standards:
• IEC 60 694
• IEC 62 271-100
All SION vacuum circuit-breakers fulfil the endurance
classes E2, M2 and C2 according to IEC 62 271-100.
The slide-in modules have been tested according to
• IEC 62 271-200 regarding
– Dielectric strength
– Temperature rise
– Switching capacity.
Ambient conditions
Condensation can occasionally occur under the ambient
conditions shown opposite.
SION vacuum circuit-breakers are suitable for use in the
following climatic classes according to IEC 60 721, Part 3-3:
1 40°C
Climatic ambient conditions:
Biological ambient conditions:
Class 3K41)
Class 3B1
5
manufacturer applies.
2600
At ambient temperatures below + 40 °C, higher normal
4
2200 currents can be carried (see diagram):
3 Characteristics curve 1 = Rated normal current 800 A
1800
Characteristics curve 2 = Rated normal current 1250 A
1400 Characteristics curve 3 = Rated normal current 2000 A
2 Characteristics curve 4 = Rated normal current 2500 A
1000 Characteristics curve 5 = Rated normal current 3150 A
1
600
10 20 30 40 50 60 °C 70
Ambient temperature Dielectric strength
The dielectric strength of air insulation decreases with
increasing altitude due to low air density. According to
IEC 60 694, the rated lightning impulse withstand voltage
values specified in the chapter “Technical Data” apply to a
1.50
HG11-2517c_en eps
normal current
Rated short-
current
Rated
Type
3AE10
kV
7.2
kA
16
A
800/1250
205
n
275
no
310
no
205
n
275
n
310
n
205
n
275
no
310
no
310
1
20 800/1250 n no no n n n n no no
25 800/1250 n no no n n n n no no
25 2000 no
31.5 800/1250 n no no n n n n no no
31.5 2000/2500 no
40 1250/2000 no
40 2500/3150 no
3AE11 12 16 800/1250 n no no n n n n no no
20 800/1250 n no no n n n n no no
25 800/1250 n no no n n n n no no
25 2000/2500 no
31.5 800/1250 n no no n n n n no no
31.5 2000/2500 no
40 1250/2000 no
40 2500/3150 no
3AE12 17.5 12.5 800/1250 n no no n n n n no no
16 800/1250 n no no n n n n no no
25 800/1250 n no no n n n n no no
25 2000/2500 no
31.5 800/1250 n no no n n n n no no
31.5 2000/2500 no
40 1250/2000 no
40 2500/3150 no
3AE13 24 12.5 800/1250 no
16 800/1250/2000 no no
20 800/1250 no no
20 2000/2500 no no
25 800/1250 no no
25 2000/2500 no no
n Standard circuit-breaker (fixed-mounted/drawout version with installation accessories) o Slide-in module
Basic equipment
R-HG11-175.tif
Contents Page
Equipment Selection 13
Ordering data and configuration example 14
Selection of basic types, standard circuit-breakers:
Voltage level 7.2 kV 15
Voltage level 12 kV 17
Voltage level 17.5 kV 20
Voltage level 24 kV 22
Slide-in module
2 Position:
a: alphabetical
1
3 A
2 3
E
4
n
5
n
n: numerical
6
n
7
n
–
–
8
n
9
a
10 11 12 –
a n n –
13 14 15 16
n a a n –
Order codes
« n n n
Order No.:
Primary part
1st position Superior group
Switching devices
Secondary part
9th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment
Order codes
Group of 3 after the Order No.
Format: a n a
Special versions ( )«
Initiated with “-Z”
Group of 3 after the Order No.
Format: a n n
Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a con-
figuration example on each side of the chapter “Equipment
Selection”. For the selection of the secondary part, always
the last example of the primary part was taken over and
continued, so that at the end of the equipment selection On the foldout page we offer a configuring aid.
(pages 27 and 36) a completely configured circuit-breaker Here you can fill in the order number you have deter-
results as an example. mined for your circuit-breaker.
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 – 1
310 1250 3 A E 1 0 8 2 – 2
275 800 3 A E 1 0 7 2 – 1
275 1250 3 A E 1 0 7 2 – 2
205 800 3 A E 1 0 6 2 – 1
2
205 1250 3 A E 1 0 6 2 – 2
160 310 800 3 A E 1 0 5 2 – 1
310 1250 3 A E 1 0 5 2 – 2
275 800 3 A E 1 0 4 2 – 1
275 1250 3 A E 1 0 4 2 – 2
205 800 3 A E 1 0 3 2 – 1
205 1250 3 A E 1 0 3 2 – 2
150 310 800 3 A E 1 0 2 2 – 1
310 1250 3 A E 1 0 2 2 – 2
275 800 3 A E 1 0 1 2 – 1
275 1250 3 A E 1 0 1 2 – 2
205 800 3 A E 1 0 0 2 – 1
205 1250 3 A E 1 0 0 2 – 2
7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 – 1
310 1250 3 A E 1 0 8 3 – 2
275 800 3 A E 1 0 7 3 – 1
275 1250 3 A E 1 0 7 3 – 2
205 800 3 A E 1 0 6 3 – 1
205 1250 3 A E 1 0 6 3 – 2
160 310 800 3 A E 1 0 5 3 – 1
310 1250 3 A E 1 0 5 3 – 2
275 800 3 A E 1 0 4 3 – 1
275 1250 3 A E 1 0 4 3 – 2
205 800 3 A E 1 0 3 3 – 1
205 1250 3 A E 1 0 3 3 – 2
150 310 800 3 A E 1 0 2 3 – 1
310 1250 3 A E 1 0 2 3 – 2
275 800 3 A E 1 0 1 3 – 1
275 1250 3 A E 1 0 1 3 – 2
205 800 3 A E 1 0 0 3 – 1
205 1250 3 A E 1 0 0 3 – 2
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 20 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 310 mm 0 8 3 – 2
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 – 1
310 1250 3 A E 1 0 8 4 – 2
310 2000 3 A E 1 0 8 4 – 4
275 800 3 A E 1 0 7 4 – 1
275 1250 3 A E 1 0 7 4 – 2
2
205 800 3 A E 1 0 6 4 – 1
205 1250 3 A E 1 0 6 4 – 2
160 310 800 3 A E 1 0 5 4 – 1
310 1250 3 A E 1 0 5 4 – 2
275 800 3 A E 1 0 4 4 – 1
275 1250 3 A E 1 0 4 4 – 2
205 800 3 A E 1 0 3 4 – 1
205 1250 3 A E 1 0 3 4 – 2
150 310 800 3 A E 1 0 2 4 – 1
310 1250 3 A E 1 0 2 4 – 2
275 800 3 A E 1 0 1 4 – 1
275 1250 3 A E 1 0 1 4 – 2
205 800 3 A E 1 0 0 4 – 1
205 1250 3 A E 1 0 0 4 – 2
7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 – 1
310 1250 3 A E 1 0 8 5 – 2
310 2000 3 A E 1 0 8 5 – 4
310 2500 3 A E 1 0 8 5 – 6
275 800 3 A E 1 0 7 5 – 1
275 1250 3 A E 1 0 7 5 – 2
205 800 3 A E 1 0 6 5 – 1
205 1250 3 A E 1 0 6 5 – 2
160 310 800 3 A E 1 0 5 5 – 1
310 1250 3 A E 1 0 5 5 – 2
275 800 3 A E 1 0 4 5 – 1
275 1250 3 A E 1 0 4 5 – 2
205 800 3 A E 1 0 3 5 – 1
205 1250 3 A E 1 0 3 5 – 2
150 310 800 3 A E 1 0 2 5 – 1
310 1250 3 A E 1 0 2 5 – 2
275 800 3 A E 1 0 1 5 – 1
275 1250 3 A E 1 0 1 5 – 2
205 800 3 A E 1 0 0 5 – 1
205 1250 3 A E 1 0 0 5 – 2
7.2 60 20 40 100/104 210 310 1250 3 A E 1 0 8 6 – 2
310 2000 3 A E 1 0 8 6 – 4
310 2500 3 A E 1 0 8 6 – 6
310 3150 3 A E 1 0 8 6 – 7
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 40 kA
Rated normal current Ir = 2000 A
Pole-center distance = 210 mm, width across flats = 310 mm 0 8 6 – 4
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 310 16 40/42 210 800 3 A E 1 1 8 2 – 1
310 1250 3 A E 1 1 8 2 – 2
275 800 3 A E 1 1 7 2 – 1
275 1250 3 A E 1 1 7 2 – 2
205 800 3 A E 1 1 6 2 – 1
2
205 1250 3 A E 1 1 6 2 – 2
160 310 800 3 A E 1 1 5 2 – 1
310 1250 3 A E 1 1 5 2 – 2
275 800 3 A E 1 1 4 2 – 1
275 1250 3 A E 1 1 4 2 – 2
205 800 3 A E 1 1 3 2 – 1
205 1250 3 A E 1 1 3 2 – 2
150 310 800 3 A E 1 1 2 2 – 1
310 1250 3 A E 1 1 2 2 – 2
275 800 3 A E 1 1 1 2 – 1
275 1250 3 A E 1 1 1 2 – 2
205 800 3 A E 1 1 0 2 – 1
205 1250 3 A E 1 1 0 2 – 2
12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 – 1
310 1250 3 A E 1 1 8 3 – 2
275 800 3 A E 1 1 7 3 – 1
275 1250 3 A E 1 1 7 3 – 2
205 800 3 A E 1 1 6 3 – 1
205 1250 3 A E 1 1 6 3 – 2
160 310 800 3 A E 1 1 5 3 – 1
310 1250 3 A E 1 1 5 3 – 2
275 800 3 A E 1 1 4 3 – 1
275 1250 3 A E 1 1 4 3 – 2
205 800 3 A E 1 1 3 3 – 1
205 1250 3 A E 1 1 3 3 – 2
150 310 800 3 A E 1 1 2 3 – 1
310 1250 3 A E 1 1 2 3 – 2
275 800 3 A E 1 1 1 3 – 1
275 1250 3 A E 1 1 1 3 – 2
205 800 3 A E 1 1 0 3 – 1
205 1250 3 A E 1 1 0 3 – 2
Special version (available for all 12 kV standard circuit-breakers)
Ud = 42 kV – Z E 1 3
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 800 A
Pole-center distance = 160 mm, width across flats = 275 mm 1 4 2 – 1
Rated short-duration power-frequency withstand voltage Ud = 42 kV – Z E 1 3
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 310 25 63/65 210 800 3 A E 1 1 8 4 – 1
310 1250 3 A E 1 1 8 4 – 2
310 2000 3 A E 1 1 8 4 – 4
310 2500 3 A E 1 1 8 4 – 6
275 800 3 A E 1 1 7 4 – 1
2
275 1250 3 A E 1 1 7 4 – 2
205 800 3 A E 1 1 6 4 – 1
205 1250 3 A E 1 1 6 4 – 2
160 310 800 3 A E 1 1 5 4 – 1
310 1250 3 A E 1 1 5 4 – 2
275 800 3 A E 1 1 4 4 – 1
275 1250 3 A E 1 1 4 4 – 2
205 800 3 A E 1 1 3 4 – 1
205 1250 3 A E 1 1 3 4 – 2
150 310 800 3 A E 1 1 2 4 – 1
310 1250 3 A E 1 1 2 4 – 2
275 800 3 A E 1 1 1 4 – 1
275 1250 3 A E 1 1 1 4 – 2
205 800 3 A E 1 1 0 4 – 1
205 1250 3 A E 1 1 0 4 – 2
12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 – 1
310 1250 3 A E 1 1 8 5 – 2
310 2000 3 A E 1 1 8 5 – 4
310 2500 3 A E 1 1 8 5 – 6
275 800 3 A E 1 1 7 5 – 1
275 1250 3 A E 1 1 7 5 – 2
205 800 3 A E 1 1 6 5 – 1
205 1250 3 A E 1 1 6 5 – 2
160 310 800 3 A E 1 1 5 5 – 1
310 1250 3 A E 1 1 5 5 – 2
275 800 3 A E 1 1 4 5 – 1
275 1250 3 A E 1 1 4 5 – 2
205 800 3 A E 1 1 3 5 – 1
205 1250 3 A E 1 1 3 5 – 2
150 310 800 3 A E 1 1 2 5 – 1
310 1250 3 A E 1 1 2 5 – 2
275 800 3 A E 1 1 1 5 – 1
275 1250 3 A E 1 1 1 5 – 2
205 800 3 A E 1 1 0 5 – 1
205 1250 3 A E 1 1 0 5 – 2
Special version (available for all 12 kV standard circuit-breakers)
Ud = 42 kV – Z E 1 3
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 31.5 kA
Rated normal current Ir = 1250 A
Pole-center distance = 150 mm, width across flats = 205 mm 1 0 5 – 2
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 310 40 100/104 210 1250 3 A E 1 1 8 6 – 2
310 2000 3 A E 1 1 8 6 – 4
310 2500 3 A E 1 1 8 6 – 6
310 3150 3 A E 1 1 8 6 – 7
Special version (available for all 12 kV standard circuit-breakers)
2
Ud = 42 kV – Z E 1 3
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 40 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 310 mm 1 8 6 – 2
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 – 1
310 1250 3 A E 1 2 8 1 – 2
275 800 3 A E 1 2 7 1 – 1
275 1250 3 A E 1 2 7 1 – 2
205 800 3 A E 1 2 6 1 – 1
2
205 1250 3 A E 1 2 6 1 – 2
160 310 800 3 A E 1 2 5 1 – 1
310 1250 3 A E 1 2 5 1 – 2
275 800 3 A E 1 2 4 1 – 1
275 1250 3 A E 1 2 4 1 – 2
205 800 3 A E 1 2 3 1 – 1
205 1250 3 A E 1 2 3 1 – 2
150 310 800 3 A E 1 2 2 1 – 1
310 1250 3 A E 1 2 2 1 – 2
275 800 3 A E 1 2 1 1 – 1
275 1250 3 A E 1 2 1 1 – 2
205 800 3 A E 1 2 0 1 – 1
205 1250 3 A E 1 2 0 1 – 2
17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 – 1
310 1250 3 A E 1 2 8 2 – 2
275 800 3 A E 1 2 7 2 – 1
275 1250 3 A E 1 2 7 2 – 2
205 800 3 A E 1 2 6 2 – 1
205 1250 3 A E 1 2 6 2 – 2
160 310 800 3 A E 1 2 5 2 – 1
310 1250 3 A E 1 2 5 2 – 2
275 800 3 A E 1 2 4 2 – 1
275 1250 3 A E 1 2 4 2 – 2
205 800 3 A E 1 2 3 2 – 1
205 1250 3 A E 1 2 3 2 – 2
150 310 800 3 A E 1 2 2 2 – 1
310 1250 3 A E 1 2 2 2 – 2
275 800 3 A E 1 2 1 2 – 1
275 1250 3 A E 1 2 1 2 – 2
205 800 3 A E 1 2 0 2 – 1
205 1250 3 A E 1 2 0 2 – 2
17.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 – 1
310 1250 3 A E 1 2 8 4 – 2
310 2000 3 A E 1 2 8 4 – 4
310 2500 3 A E 1 2 8 4 – 6
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 275 mm 2 7 2 – 2
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
17.5 95 38 25 63/65 210 275 800 3 A E 1 2 7 4 – 1
275 1250 3 A E 1 2 7 4 – 2
205 800 3 A E 1 2 6 4 – 1
205 1250 3 A E 1 2 6 4 – 2
160 310 800 3 A E 1 2 5 4 – 1
2
310 1250 3 A E 1 2 5 4 – 2
275 800 3 A E 1 2 4 4 – 1
275 1250 3 A E 1 2 4 4 – 2
205 800 3 A E 1 2 3 4 – 1
205 1250 3 A E 1 2 3 4 – 2
150 310 800 3 A E 1 2 2 4 – 1
310 1250 3 A E 1 2 2 4 – 2
275 800 3 A E 1 2 1 4 – 1
275 1250 3 A E 1 2 1 4 – 2
205 800 3 A E 1 2 0 4 – 1
205 1250 3 A E 1 2 0 4 – 2
17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 – 1
310 1250 3 A E 1 2 8 5 – 2
310 2000 3 A E 1 2 8 5 – 4
310 2500 3 A E 1 2 8 5 – 6
275 800 3 A E 1 2 7 5 – 1
275 1250 3 A E 1 2 7 5 – 2
205 800 3 A E 1 2 6 5 – 1
205 1250 3 A E 1 2 6 5 – 2
160 310 800 3 A E 1 2 5 5 – 1
310 1250 3 A E 1 2 5 5 – 2
275 800 3 A E 1 2 4 5 – 1
275 1250 3 A E 1 2 4 5 – 2
205 800 3 A E 1 2 3 5 – 1
205 1250 3 A E 1 2 3 5 – 2
150 310 800 3 A E 1 2 2 5 – 1
310 1250 3 A E 1 2 2 5 – 2
275 800 3 A E 1 2 1 5 – 1
275 1250 3 A E 1 2 1 5 – 2
205 800 3 A E 1 2 0 5 – 1
205 1250 3 A E 1 2 0 5 – 2
17.5 95 38 40 100/104 210 310 1250 3 A E 1 2 8 6 – 2
310 2000 3 A E 1 2 8 6 – 4
310 2500 3 A E 1 2 8 6 – 6
310 3150 3 A E 1 2 8 6 – 7
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 31.5 kA
Rated normal current Ir = 2500 A
Pole-center distance = 210 mm, width across flats = 310 mm 2 8 5 – 6
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 23
See page 23
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
24 125 50 310 12.5 31/33 210 800 3 A E 1 3 2 1 – 1
310 1250 3 A E 1 3 2 1 – 2
24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 – 1
310 1250 3 A E 1 3 2 2 – 2
310 2000 3 A E 1 3 2 2 – 4
2
275 310 800 3 A E 1 3 5 2 – 1
310 1250 3 A E 1 3 5 2 – 2
310 2000 3 A E 1 3 5 2 – 4
24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 – 1
310 1250 3 A E 1 3 2 3 – 2
310 2000 3 A E 1 3 2 3 – 4
310 2500 3 A E 1 3 2 3 – 6
275 310 800 3 A E 1 3 5 3 – 1
310 1250 3 A E 1 3 5 3 – 2
310 2000 3 A E 1 3 5 3 – 4
310 2500 3 A E 1 3 5 3 – 6
24 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 – 1
310 1250 3 A E 1 3 2 4 – 2
310 2000 3 A E 1 3 2 4 – 4
310 2500 3 A E 1 3 2 4 – 6
275 310 800 3 A E 1 3 5 4 – 1
310 1250 3 A E 1 3 5 4 – 2
310 2000 3 A E 1 3 5 4 – 4
310 2500 3 A E 1 3 5 4 – 6
Special version (available for all 24 kV standard circuit-breakers)
Ud = 55 kV – Z E 5 5
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 24 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-center distance = 275 mm, width across flats = 310 mm 3 5 4 – 4
C.t.-operated release
with tripping pulse
2nd shunt release
1st shunt release
W 0.1 Ws (20 O)
Undervoltage
C.t.-operated
C.t.-operated
See page 24
See page 24
See page 25
See page 25
See page 26
See page 26
See page 27
release 0.5 A
release 1.0 A
release
n A
n n B
n n C
n n G
n n H
n n F
n E
n n N
n n
n
n
n
n
P
Q
J
L
2
n M
10th position
Operating voltage of the closing solenoid
24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C
See page 25
See page 25
See page 26
See page 26
See page 27
Standard voltages Special voltages
C.t.-operated release 0
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
2 125 V DC
127 V DC
240 V DC
9
9
9
With order code
With order code
With order code
L
L
L
1 D
1 E
1 F
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
12th position
Operating voltage of the 2nd release
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C
Operating voltage of the 1st release 32 V DC 9 L 1 B
Without 2nd release 0
See page 26
See page 26
See page 27
Options
14th position
Operating voltage of the motor operating mechanism
24 V DC B
2
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 –
Fixed-mounted circuit-breaker 0
Operating voltage of the motor operating mechanism 230 V AC K
See page 27
12 NO + 12 NC
Circuit-breaker
tripping signal
terminal strip
24-pole plug
64-pole plug
6 NO + 6 NC
interlocking
Mechanical
27-pole
n n n B
n n D
n n n F
n n H
n n n K
n n M
n n n R
n n
2 n
n
n
n
n n
n
Q
A
C
n n n n E
n n n G
n n n n J
n n n L
n n n n N
n n n P
Special versions
Auxiliary switch contacts 12 NO + 12 NC and pins
of the 64-pole plug connector gold-plated – Z A 2 1
Key-interlocking (RONIS-lock at the vacuum circuit-breaker)
Only for circuit-breakers without mechanical interlocking – Z J 6 0
16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate
Language Frequency
German 50 Hz or DC 0
60 Hz 1
English 50 Hz or DC 2
60 Hz 3
French 50 Hz or DC 4
60 Hz 5
Spanish 50 Hz or DC 6
60 Hz 7
Other languages on request
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 – 0 K
With mechanical interlocking, circuit-breaker tripping signal,
auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in German 0
Options
–
Z
Z
F
J
3
6
2
1
2
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C
Operating voltage of the 1st release 32 V DC 9 With order code L 1 B
Without 2nd release 0 –
Fixed-mounted circuit-breaker 0
Operating voltage of the motor operating mechanism 230 V AC K
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in German 0
Hand crank – Z F 3 0
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 32
See page 32
See page 33
See page 33
See page 34
See page 34
See page 35
See page 35
See page 36
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 – 1
310 1250 3 A E 1 0 8 2 – 2
275 800 3 A E 1 0 7 2 – 1
275 1250 3 A E 1 0 7 2 – 2
150 310 800 3 A E 1 0 2 2 – 1
2
310 1250 3 A E 1 0 2 2 – 2
275 800 3 A E 1 0 1 2 – 1
275 1250 3 A E 1 0 1 2 – 2
7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 – 1
310 1250 3 A E 1 0 8 3 – 2
275 800 3 A E 1 0 7 3 – 1
275 1250 3 A E 1 0 7 3 – 2
150 310 800 3 A E 1 0 2 3 – 1
310 1250 3 A E 1 0 2 3 – 2
275 800 3 A E 1 0 1 3 – 1
275 1250 3 A E 1 0 1 3 – 2
7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 – 1
310 1250 3 A E 1 0 8 4 – 2
310 2000 3 A E 1 0 8 4 – 4
275 800 3 A E 1 0 7 4 – 1
275 1250 3 A E 1 0 7 4 – 2
150 310 800 3 A E 1 0 2 4 – 1
310 1250 3 A E 1 0 2 4 – 2
275 800 3 A E 1 0 1 4 – 1
275 1250 3 A E 1 0 1 4 – 2
7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 – 1
310 1250 3 A E 1 0 8 5 – 2
310 2000 3 A E 1 0 8 5 – 4
310 2500 3 A E 1 0 8 5 – 6
275 800 3 A E 1 0 7 5 – 1
275 1250 3 A E 1 0 7 5 – 2
150 310 800 3 A E 1 0 2 5 – 1
310 1250 3 A E 1 0 2 5 – 2
275 800 3 A E 1 0 1 5 – 1
275 1250 3 A E 1 0 1 5 – 2
7.2 60 20 40 100/104 210 310 1250 3 A E 1 0 8 6 – 2
310 2000 3 A E 1 0 8 6 – 4
310 2500 3 A E 1 0 8 6 – 6
310 3150 3 A E 1 0 8 6 – 7
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 20 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 310 mm 0 8 3 – 2
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 32
See page 32
See page 33
See page 33
See page 34
See page 34
See page 35
See page 35
See page 36
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 16 40/42 210 310 800 3 A E 1 1 8 2 – 1
310 1250 3 A E 1 1 8 2 – 2
275 800 3 A E 1 1 7 2 – 1
275 1250 3 A E 1 1 7 2 – 2
150 310 800 3 A E 1 1 2 2 – 1
2
310 1250 3 A E 1 1 2 2 – 2
275 800 3 A E 1 1 1 2 – 1
275 1250 3 A E 1 1 1 2 – 2
12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 – 1
310 1250 3 A E 1 1 8 3 – 2
275 800 3 A E 1 1 7 3 – 1
275 1250 3 A E 1 1 7 3 – 2
150 310 800 3 A E 1 1 2 3 – 1
310 1250 3 A E 1 1 2 3 – 2
275 800 3 A E 1 1 1 3 – 1
275 1250 3 A E 1 1 1 3 – 2
12 75 28 25 63/65 210 310 800 3 A E 1 1 8 4 – 1
310 1250 3 A E 1 1 8 4 – 2
310 2000 3 A E 1 1 8 4 – 4
310 2500 3 A E 1 1 8 4 – 6
275 800 3 A E 1 1 7 4 – 1
275 1250 3 A E 1 1 7 4 – 2
150 310 800 3 A E 1 1 2 4 – 1
310 1250 3 A E 1 1 2 4 – 2
275 800 3 A E 1 1 1 4 – 1
275 1250 3 A E 1 1 1 4 – 2
12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 – 1
310 1250 3 A E 1 1 8 5 – 2
310 2000 3 A E 1 1 8 5 – 4
310 2500 3 A E 1 1 8 5 – 6
275 800 3 A E 1 1 7 5 – 1
275 1250 3 A E 1 1 7 5 – 2
150 310 800 3 A E 1 1 2 5 – 1
310 1250 3 A E 1 1 2 5 – 2
275 800 3 A E 1 1 1 5 – 1
275 1250 3 A E 1 1 1 5 – 2
12 75 28 40 100/104 210 310 1250 3 A E 1 1 8 6 – 2
310 2000 3 A E 1 1 8 6 – 4
310 2500 3 A E 1 1 8 6 – 6
310 3150 3 A E 1 1 8 6 – 7
Special version (available for all 12 kV slide-in modules)
Ud = 42 kV – Z E 1 3
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 800 A
Pole-center distance = 150 mm, width across flats = 275 mm 1 1 4 – 1
Rated short-duration power-frequency withstand voltage Ud = 42 kV – Z E 1 3
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 32
See page 32
See page 33
See page 33
See page 34
See page 34
See page 35
See page 35
See page 36
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 – 1
310 1250 3 A E 1 2 8 1 – 2
275 800 3 A E 1 2 7 1 – 1
275 1250 3 A E 1 2 7 1 – 2
150 310 800 3 A E 1 2 2 1 – 1
2
310 1250 3 A E 1 2 2 1 – 2
275 800 3 A E 1 2 1 1 – 1
275 1250 3 A E 1 2 1 1 – 2
17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 – 1
310 1250 3 A E 1 2 8 2 – 2
275 800 3 A E 1 2 7 2 – 1
275 1250 3 A E 1 2 7 2 – 2
150 310 800 3 A E 1 2 2 2 – 1
310 1250 3 A E 1 2 2 2 – 2
275 800 3 A E 1 2 1 2 – 1
275 1250 3 A E 1 2 1 2 – 2
17.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 – 1
310 1250 3 A E 1 2 8 4 – 2
310 2000 3 A E 1 2 8 4 – 4
310 2500 3 A E 1 2 8 4 – 6
275 800 3 A E 1 2 7 4 – 1
275 1250 3 A E 1 2 7 4 – 2
150 310 800 3 A E 1 2 2 4 – 1
310 1250 3 A E 1 2 2 4 – 2
275 800 3 A E 1 2 1 4 – 1
275 1250 3 A E 1 2 1 4 – 2
17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 – 1
310 1250 3 A E 1 2 8 5 – 2
310 2000 3 A E 1 2 8 5 – 4
310 2500 3 A E 1 2 8 5 – 6
275 800 3 A E 1 2 7 5 – 1
275 1250 3 A E 1 2 7 5 – 2
150 310 800 3 A E 1 2 2 5 – 1
310 1250 3 A E 1 2 2 5 – 2
275 800 3 A E 1 2 1 5 – 1
275 1250 3 A E 1 2 1 5 – 2
17.5 95 38 40 100/104 210 310 1250 3 A E 1 2 8 6 – 2
310 2000 3 A E 1 2 8 6 – 4
310 2500 3 A E 1 2 8 6 – 6
310 3150 3 A E 1 2 8 6 – 7
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm, width across flats = 275 mm 2 7 2 – 2
at 36 % AC component
Rated short-duration
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
breaking current
making current
Rated normal
(at 50/60 Hz)
See page 32
See page 32
See page 33
See page 33
See page 34
See page 34
See page 35
See page 35
See page 36
voltage
current
Rated
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
24 125 50 12.5 31/33 210 310 800 3 A E 1 3 2 1 – 1
310 1250 3 A E 1 3 2 1 – 2
24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 – 1
310 1250 3 A E 1 3 2 2 – 2
310 2000 3 A E 1 3 2 2 – 4
2
275 310 800 3 A E 1 3 5 2 – 1
310 1250 3 A E 1 3 5 2 – 2
310 2000 3 A E 1 3 5 2 – 4
24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 – 1
310 1250 3 A E 1 3 2 3 – 2
310 2000 3 A E 1 3 2 3 – 4
310 2500 3 A E 1 3 2 3 – 6
275 310 800 3 A E 1 3 5 3 – 1
310 1250 3 A E 1 3 5 3 – 2
310 2000 3 A E 1 3 5 3 – 4
310 2500 3 A E 1 3 5 3 – 6
24 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 – 1
310 1250 3 A E 1 3 2 4 – 2
310 2000 3 A E 1 3 2 4 – 4
310 2500 3 A E 1 3 2 4 – 6
275 310 800 3 A E 1 3 5 4 – 1
310 1250 3 A E 1 3 5 4 – 2
310 2000 3 A E 1 3 5 4 – 4
310 2500 3 A E 1 3 5 4 – 6
Configuration example
SION vacuum circuit-breaker 3 A E 1
Rated voltage Ur = 24 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-center distance = 275 mm, width across flats = 310 mm 3 5 4 – 4
C.t.-operated release
with tripping pulse
2nd shunt release
1st shunt release
W 0.1 Ws (20 O)
Undervoltage
C.t.-operated
C.t.-operated
See page 33
See page 33
See page 34
See page 34
See page 35
See page 35
See page 36
release 0.5 A
release 1.0 A
release
n A
n n B
n n C
n n G
n n H
n n F
n E
n n N
n n
2 n
n
n
n
P
Q
J
L
n M
10th position
Operating voltage of the closing solenoid
24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C
See page 34
See page 34
See page 35
See page 35
See page 36
Standard voltages Special voltages
C.t.-operated release 0
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
125 V DC
127 V DC
240 V DC
9
9
9
With order code
With order code
With order code
L
L
L
1 D
1 E
1 F
2
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
12th position
Operating voltage of the 2nd release
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C
Operating voltage of the 1st release 32 V DC 9 L 1 B
Without 2nd release 0
See page 35
See page 35
See page 36
Options
14th position
Operating voltage of the motor operating mechanism
24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC M
32 V DC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 –
Circuit-breaker on cartridge, with drawout element, contact arms,
contact system, fixed contacts, bushings and shutters 5
Operating voltage of the motor operating mechanism 240 V DC S
Circuit-breaker
tripping signal
terminal strip
64-pole plug
See page 36
6 NO + 6 NC
interlocking
Mechanical
27-pole
n n n n A
n n n C
n n n n J
n n n L
n n n n N
n n n P
Special versions
Auxiliary switch contacts 12 NO + 12 NC and pins
of the 64-pole plug connector gold-plated – Z A 2 1
2
16th position
AC frequency of operating voltages
Languages of operating instructions
and rating plate
Language Frequency
German 50 Hz or DC 0
60 Hz 1
English 50 Hz or DC 2
60 Hz 3
French 50 Hz or DC 4
60 Hz 5
Spanish 50 Hz or DC 6
60 Hz 7
Other languages on request
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 – 5 S
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instruction and rating plate in Spanish 6
Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated – Z A 2 1
Options
Configuration example
SION vacuum circuit-breaker 3 A E 1
(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,
Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4
1st shunt release A
Operating voltage of the closing solenoid 48 V DC C
Operating voltage of the 1st release 32 V DC 9 With order code L 1 B
Without 2nd release 0 –
Circuit-breaker on cartridge, with drawout element, contact arms,
contact system, fixed contacts, bushings and shutters 5
Operating voltage of the motor operating mechanism 240 V DC S
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N
Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in Spanish 6
Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated – Z A 2 1
Wiring cables halogen-free and flame-retardant – Z A 1 0
Silicone-free design – Z A 3 1
Electrical closing lock-out – Z A 4 7
2 Mounting parts
Drive motor
For undervoltage release
240 V AC, 60 Hz
24/30/32 V DC
3AX11 03-3M
3AX14 11-2A
3AY17 11-2B
48 V DC 3AY17 11-2C
60 V DC 3AY17 11-2D
100/110/125 V DC/AC 3AY17 11-2E
220 V DC/230 V AC 3AY17 11-2F
Auxiliary contactor 24 V DC SWB: 55656
type 3RH11 22 for anti-pumping 30/32 V DC SWB: 55658
48 V DC SWB: 55659
60 V DC SWB: 55660
110 V DC SWB: 55661
120/127 V DC SWB: 55662
220 V DC SWB: 55663
240/250 V AC SWB: 55665
110 V AC, 50/60 Hz SWB: 55666
120 V AC, 50/60 Hz SWB: 55667
125 V AC, 50/60 Hz SWB: 55668
230 V AC, 50/60 Hz SWB: 55669
240 V AC, 50/60 Hz SWB: 55670
Position switch Type SE4 without installation accessories SWB: 46677
Used for: Nos.
– Electrical anti-pumping (-S3) 1
– Electrical interlocking (-S12) 1
– Motor control (-S21, -S22) 2
– Closing spring charged (-S4) 1
– Circuit-breaker tripping signal (-S6, -S7) 2
– Electrical closing lock-out (-S5) 1
– Drawout element (-S1.0 to – S1.9) 10
Auxiliary switch (-S1) 6 NO + 6 NC 3SV92 73-2AA0
12 NO + 12 NC 3SV92 74-2AA0
Mechanical interlocking 3AX14 20-2A
Key-operated interlocking 3AX14 37-2A
Module connector State position indicator of drawout element 3AX14 60-2A
Accessories for plug connector (for conductor cross-section 1.5 mm)
Crimp pins (for lower part of plug) 24-pole 3AX11 34-3A
64-pole 3AX11 34-4B
Crimp sockets (for upper part of plug) 64-pole 3AX11 34-4C
Crimping pliers For notching the crimp pins and crimp sockets 3AX11 34-4D
Disassembly tool 3AX11 34-4G
Plug connector complete 24-pole 3AX11 34-7A
64-pole 3AX11 34-6A
Note:
HG11-2518_en eps
R-HG11-177.tif
Contents Page
Technical Data 41
Electrical data, dimensions and weights:
Voltage level 7.2 kV 42
Voltage level 12 kV 46
Voltage level 17.5 kV 50
Voltage level 24 kV 56
Dimension drawings:
Voltage levels 7.2 to 17.5 kV 54
Voltage level 24 kV 58
3
R-HG11-179.eps
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
16
16
36
36
17.9
17.9
40/
42
40/
42
60
60
20
20
2.1
2.1
129 140 105
75
80/
120
80/
120
3M 442
02011 001
3M 442
02011 001
1
1
I/J
I/J
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
16
16
36
36
17.9
17.9
40/
42
40/
42
60
60
20
20
2.1
2.1
129 140 115
75
80/ –
80/ –
3M 442
02017 001
3M 442
02017 001
1
1
F/–
F/–
3
3AE1 043-1 ... 800 275 160 n 3 20 36 22.4 50/
52
60 20 2.1 129 140 115 75 80/ – 3M 442
02017 001
2 F/–
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
20
20
36
36
22.4
22.4
50/
52
50/
52
60
60
20
20
2.1
2.1
129 140 165
75
90/
130
90/
130
3M 442
02023 001
3M 442
02023 001
2
2
B/C
B/C
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
3
Operating cycle diagram Operating cycle diagram
The permissible number of
Operating cycle No. n Operating cycle No. n
20 000 electrical operating cycles 20 000
HG11-2540_en eps
HG11-2539a_en eps
is shown as a function of
10 000 10 000
the breaking current
5 000 5 000
(r.m.s. value). All SION
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
curve shape beyond the
200 200
180 parameters defined in
130
100 IEC 62 271-100 is based on 100
80
50 average experience data. 50
The number of operating
20 cycles that can actually be 20
1 3 5 2 4
10 reached can be different 10
0.5 1 2 5 kA 10 16 20 25 40 50 0.5 1 2 5 kA 10 20 31.5 50
depending on the respec-
tive application.
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
16
16
36
36
17.9
17.9
40/
42
40/
42
75
75
28
28
2.1
2.1
129 140 105
75
80/
120
80/
120
3M 442
02011 001
3M 442
02011 001
1
1
I/J
I/J
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
20
20
36
36
22.4
22.4
50/
52
50/
52
75
75
28
28
2.1
2.1
129 140 115
75
80/ –
80/ –
3M 442
02017 001
3M 442
02017 001
2
2
F/–
F/–
3
3AE1 144-1 ... 800 275 160 n 3 25 36 28 63/
65
75 28 2.1 129 140 115 75 80/ – 3M 442
02017 001
3 F/–
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
25
25
36
36
28
28
63/
65
63/
65
75
75
28
28
2.1
2.1
129 140 165
75
90/
130
90/
130
3M 442
02023 001
3M 442
02023 001
3
3
B/C
B/C
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
40
40
36
36
44.9
44.9
100/
104
100/
104
75
75
28
28
1.0
1.0
145 249 149 140 160/ –
–
5
5
–/–
–/–
3
3AE1 576-7 ... 3150 310 210 n 3 40 36 44.9 100/
104
75 28 1.0 145 249 149 140 160/ – – 5 –/–
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
is shown as a function of
10 000 10 000
the breaking current
5 000 (r.m.s. value). All SION 5 000
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
curve shape beyond the
200 200
180 parameters defined in
130
100 IEC 62 271-100 is based on 100
80
50 average experience data. 50
The number of operating
20 cycles that can actually be 20
1 3 5 2 4
10 reached can be different 10
0.5 1 2 5 kA 10 16 20 25 40 50 0.5 1 2 5 kA 10 20 31.5 50
depending on the respec-
tive application.
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
12.5
12.5
36
36
14.9
14.9
31/
33
31/
33
95
95
38
38
2.1
2.1
129 275 214 150
1
I/J
I/J
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
16
16
36
36
17.9
17.9
40/
42
40/
42
95
95
38
38
2.1
2.1
129 275 224 150
80/ –
3M 442
02020 001
3M 442
02020 001
2
2
F/–
F/–
3
3AE1 244-1 ... 800 275 160 n 3 25 36 28 63/
65
95 38 2.1 129 275 224 150 80/ – 3M 442
02020 001
3 F/–
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
25
25
36
36
28
28
63/
65
63/
65
95
95
38
38
2.1
2.1
129 275 165 150
3
B/C
B/C
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing N
3
Operating cycle diagram Operating cycle diagram
The permissible number of
Operating cycle No. n Operating cycle No. n
20 000 electrical operating cycles 20 000 HG11-2541_en eps
HG11-2537a_en eps
is shown as a function of
10 000 10 000
the breaking current
5 000 5 000
(r.m.s. value). All SION
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
350
curve shape beyond the
200
180 200 parameters defined in
100 IEC 62 271-100 is based on 100
80
50 average experience data. 50
The number of operating
20 20
cycles that can actually be 1 4
2 3 5
10 reached can be different 10
0.5 1 2 5 kA 10 16 20 25 40 50 0.5 1 2 5 kA 10 12.5 20 31.5 50
depending on the respec-
tive application.
HG11-2520 eps
HG11-2519 eps
ca.93
ca.93
210 210 210 210
310
275
572,5
562,5
562,5
517,5
517,5
540
540
237,5
217,5
20 20
310 279 310 279
380 380
Dimension drawing C
472/5221) 794
HG11-2521a eps
102 210 210 187
100
30
Width across flats mm Height mm
a b
310 905
a
b
275 850
1) for 40 kA
345
286,5
43
3
27,5
27,5
688/7381)
HG11-2523 eps
ca.93
ca.93
572,5
562,5
562,5
517,5
517,5
540
540
237,5
217,5
20 20
310 279 310 279
380 380
ca.93
205
562,5
562,5
517,5
517,5
540
540
217,5
217,5
20 20
310 279 310 279
380 380
HG11-2527 eps
HG11-2526 eps
ca.93
ca.93
150 150 150 150
310
275
572,5
562,5
562,5
517,5
517,5
540
540
237,5
217,5
20 20
310 279 310 279
380 380
Dimension drawing J
472 594
HG11-2528a eps
102 150 150 147
100
30
Width across flats mm Height mm
a b
310 905
a
b
275 850
341
266,5
43
27,5
27,5
688
710
3
Dimension drawing K Dimension drawing L
370 445 370 565
HG11-2529 eps
HG11-2530 eps
ca.93
ca.93
562,5
581
517,5
517,5
540
540
237,5
217,5
20 20
310 279 310 279
380 380
107
350 279
450
d
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
20
25
36
36
22.4
28
50/
52
63/
65
125
125
50
50
2.0
2.6
200 340 200 205
4
A/B
A/B
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing F
DC component in % of the
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
(has to be ordered)
Width across flats
withstand voltage
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weight 1)
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3
25
25
36
36
28
28
63/
65
63/
65
125
125
50
50
2.6
2.0
200 350 200 210 120/ –
–
4
4
–/–
–/–
3
n Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-
out element increases by the values specified in dimension
drawing F
HG11-2542_en eps
is shown as a function of
10 000 10 000
the breaking current
5 000 5 000
(r.m.s. value). All SION
vacuum circuit-breakers
2 000 2 000
fulfil the endurance classes
1 000 1 000
E2, M2 and C2 according
500 to IEC 62 271-100. The 500
curve shape beyond the
200 200
150 parameters defined in
100 100
IEC 62 271-100 is based on 90
50 average experience data. 50
The number of operating 30
20 cycles that can actually be 20
1 3 2 4
10 reached can be different 10
0.5 1 2 5 10 12.5 20 kA 50 0.5 1 2 5 10 16 25 kA 50
depending on the respec-
tive application.
HG11-2532 eps
210 210
210 679 650 620 ca. 20 kg
ca.93
424
Height of drawout element: 60
310
739
739
107
a Width of drawout element
540
HG11-2590 eps
58 360 269
468
d
Dimension drawing B
532 794
HG11-2533a eps
112 210 210 187
100
30
1040,5
1013
310
485,5
346
332
41,5
27,5
27,5
788
3 Dimension drawing C
420
810
700
Dimension drawing D
420 700
HG11-2535 eps
HG11-2534 eps
310
310
739
739
739
739
540
540
283
283
Dimension drawing E
532 994
HG11-2536a eps
30
1040,5
1013
310
485,5
346
332
41,5
27,5
27,5
788
810
V
DC 24
DC 48
max. V
26
53
min. V
20
41
W (at DC)
350
350
VA (at AC)
–
–
A
8
6
3
DC 60 66 51 350 – 4
DC 110 121 93 350 – 2
DC 220 242 187 350 – 1.6
AC 110 121 93 – 400 2
AC 230 244 187 – 400 1.6
1) The current inrush in the drive motor can be neglected due to its very short presence
2) Consumption at pickup current (90 % of the rated current) and open armature
Basic equipment
X1
21
-S3
21 13
21 22
-S21 -K1
22 14
22
31
A1 -K1 A1 11 13 21 23 31 33 41 43 51 53 61 63
32 -K1
M 11 23 -S1
-M1 A1 A2 12 14 22 24 32 34 42 44 52 54 62 64
1= -S1 -S4 13 21 -S1
-Y9 12 A1 24
D2 A2 14 22 -Y1
HG11-2506 eps
22
-S22
21 A2
HG11-2505 eps
X1
Additional equipment
X0 X0
X1 X1 -X0
21
-S3
21 13 22
-K1
22 14
13
31
-K1 -S6
A1 14
32 -K1 11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123
11
A1 A2 -S1
-S1 12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124
-Y9 12
A2 21
13 -S7
22
-S5
14
HG11-2508 eps
HG11-2507 eps
HG11-2509 eps
13
-S12
3 X1
X0
14
X1
X0
-X0
Additional equipment: Releases (for possible combinations see chapter 2 under “Secondary equipment“)
X0 X0 X0 X0
X1 X1 X1 X1
D1
-Y7
33
-S1 D2
34 43
A1
-Y2 A1 A1 -S1
44
-Y4 -Y6
A2 A2
A2 -R1 1
HG11-2511 eps
HG11-2512 eps
HG11-2510 eps
HG11-2513 eps
X1 X1 X1 X1
X0 X0 X0 X0
2nd shunt Current-transformer Low-energy current- Undervoltage release
release operated release transformer operated
0.5 A or 1 A release 0.1 Ws
Legend
K1 Contactor (anti-pumping) S3 Position switch X0 Plug connector Y 6 Current-transformer operated
M1 Motor operating mechanism (anti-pumping) 24-pole or 64-pole release (tripping pulse W W 0.1 Ws)
R1 Resistance S4 Position switch X1 Terminal strip 25-pole Y7 Undervoltage release
S1 Auxiliary switch (for closing spring charged) Y1 1st shunt release Y9 Closing solenoid
S12 Mechanical interlocking S5 Electrical closing lock-out Y2 2nd shunt release
S21 Position switches S6 Circuit-breaker tripping signal Y4 Current-transformer Abbreviations:
S22 (to de-energize the motor oper- S7 Cutout switch for operated release NO Normally open
ating mechanism after charging) circuit-breaker tripping signal (rated current 0.5 A or 1 A) NC Normally closed
Contents Page
Annex 61
Inquiry form 62
Configuration instructions 63
Configuration aid Foldout page
R-HG11-181.tif
4
R-HG11-180.eps
Inquiry concerning
Technical data Other values
Street
Application and other requirements
Postal code/city
Fax
1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
3 A E 1 n n n – n n n n n – n n n n – Z
Instruction for configuration of the SION vacuum circuit-breaker
1st step: Definition of the primary part (see pages 15 to 22 and pages 28 to 31)
page 22 or 31
See page 15 or 28
See page 23 or 32
See page 23 or 32
See page 24 or 33
See page 24 or 33
See page 25 or 34
See page 25 or 34
See page 26 or 35
See page 26 or 35
See page 27 or 36
Please specify the following ratings: Possible options:
to
Rated voltage (Ur) Ur: 7.2 kV to 24 kV
Rated lightning impulse withstand voltage (Up) Up: 60 kV to 125 kV
Rated short-duration power-frequency withstand voltage (Ud) Ud: 20 kV to 55 kV
Rated short-circuit breaking current (Isc) Isc: 12.5 kA to 40 kA 3 A E 1 – –
Rated normal current (Ir) Ir: 800 A to 3150 A
Pole-centre distance 150 mm to 275 mm + + + +
Width across flats 205 mm to 310 mm
+ + + +
These ratings define the positions 5 to 8 of the order number
3 A E 1 – –
+ + + +
2nd step: Definition of the secondary equipment (see pages 23 to 26 and pages 32 to 35)
+ + + +
+ + + +
Release combination Shunt release, current-transformer operated release
(position 9) and undervoltage release
Closing solenoid Operating voltages from 24 V DC to 240 V AC + + + +
(position 10)
Operating voltage of the releases Operating voltages from 24 V DC to 240 V AC 3 A E 1 – –
(positions 11 / 12)
Installation accessories Fixed mounting; with drawout element, contact + + + +
(position 13) arms, contact system; slide-in module
Motor operating mechanism Operating voltages from 24 V DC to 240 V AC
(position 14) + + + +
Number of auxiliary contacts 6 NO + 6 NC, 12 NO + 12 NC
(position 15) 3 A E 1 – –
Design of the control cable connection 27-pole terminal strip, 24-pole plug connector
(position 15) 64-pole plug connector
+ + + +
Mechanical interlocking, circuit-breaker tripping signal With or without
(position 15)
Language of the documentation English, German, French, Spanish + + + +
(position 16)
Frequency of the operating voltage of the 50 Hz/60 Hz 3 A E 1 – –
secondary equipment at AC (position 16)
+ + + +
These equipment features define the positions 9 to 16 of the order number
+ + + +
3rd step: Do you have any further requirements concerning the equipment? (Please refer to pages 27 and 36)
3 A E 1 – –
Should you still need more options than the possible special equipment like halogen-free and
flame-retardant or silicone-free version, condensate protection or an additional rating plate, etc., + + + +
please contact your responsible sales partner.
+ + + +
3 A E 1 – –
+ + + +
+ + + +
3 A E 1 – –
+ + + +
+ + + +
Siemens HG 11.02 · 2006 63
If not stated otherwise on the individual pages of this Siemens AG For questions concerning Subject to change without notice
Order No. E50001-K1511-A021-A1-7600
catalog, we reserve the right to include modifications, Power Transmission and Distribution Power Transmission and Distribution: Printed in Germany
especially regarding the stated values, dimensions and weights. Medium Voltage Division You can contact our Customer Support Dispo 31601
Drawings are not binding. All product designations used Nonnendammallee 104 Center 24 hours a day, 365 days a year. KG 12.06 7.0 60 En
are trademarks or product names of Siemens AG or other 13623 Berlin Tel.: +49 180/524 70 00 101983 6101/C6103
suppliers. If not stated otherwise, all dimensions in this Germany Fax: +49 180/524 24 71
catalog are given in mm. (Calls charged: e.g. 12 Ct/min)
www.siemens.com/SION E-mail: support.energy@siemens.com
www.siemens.com/energy-support
Responsible for
Technical contents: General editing:
Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC M The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
Berlin Erlangen The required features should therefore be specified in each individual case at the time of closing the contract.
R-HG11-182.tif