Indian Standard
C DE OF PRACTICE FOR CONCR ETE
STRUCTURES FOR THE STORAGE
OF LIQUIDS
PART I GENERAL REQUIREMENTS
Cement and Concrete S~ectiona1 Committee, BDC 2
Chairman Representing
Sirax L’~. K. NAsiBIAR Tbe Concrete Association of India, Bombay
Members
SEas N. H. MOHILE (Alternate to
Shri K. K. Nambiar)
Ssrus K. F. ANTIA M. N. Dastur & Co (Pvt) Ltd, Calcutta
COL G. BENJAMIN Engineer-in-Chief’s Branch, Army Headquarters
SEas R. S. MErsANDssU (Alternate)
SERT P. S. BEATNAGAR Bhakra & Beas Designs Organization, New Delhi
DR I. C. Dos M. PAls CUDDoU Central Water & Power Comnsission (Ministry of
Irrigation & Powcr)
Smsi V. K. MUssTNY (Alternate
Sssai N. D. D~TARY In personal capacity ( Dutt Niwas, 27 Lahurnam
Road, Bombay-7)
Snax N. G. DEWAN Central Public Works Department, New Delhi
SUPEsuNTENDING ENGINEER,
2ND CIRcLE (Alternate)
Da R. R. HA~s,rsANoADI The Associated Cement Companies Ltd, Bombay
Snas V. N. PAl (Alternate)
SEar P. C. HAzssA Geological Survey of India, Calcutta
JOINT DzaEc~roR STANDARDS Research, Designs & Standards Organisation (Minis-
(B&S) try of Railways)
DRPxrrY DIRECTOR STANDARDS
(B&S) (Alternate)
SaRI S. B. JOSEX S. B. Joshi & Co Ltd, Bombay
SEEs M. M. LAL U. P. Government Cement Factory, Churk
PRoF S. R. MERRA Central Road Research Institute (CSIR), New
Delhi
DR R. K. GEosa (Alternate)
SaRI S. N. MuxaajI National Test House, Calcutta
SHE! N. C. SENGUPTA (Alternate)
Saxi ERAcss A. NADIEsHAR Institution of Engineers (India), Calcutta
Sam C. B. PATEL National Buildings Organization (Ministry of Works
& Housing)
Saas RABneDER SINost (Alternate)
PRoF G. S. RAaAswAaY Central Building Research Institute (CSIR),
Roorkee
SaRI M. C. TAMEANKAR (Alternate)
(Continued on page 2)
2
AMENDMENT NO. I COTOBER 198a
(DDC 2)
Indian Standard
CODE OF PRACTICE FOR CONCRETE
STRUCTURES FOR TFIE STORAGE
OF LIQUIDS
PART I GENERAL REQUIREMENTS
0. FOREWORD
0.1 This Indian Standard (Part I) was adopted by the Indian Standards
Institution on 19 November 1965, after the draft finalized by the
Cement and Concrete Sectional Committee had been approved by the
Civil Engineering Division Council.
0.2 The need for a code covering the design and construction of reinforced
concrete and prestressed concrete structures for the storage of liquids has
been long felt in this country. So far, such structures have been designed
to varying standards adapted from the recommendations of the Institution
of Civil Engineers and of the Portland Cement Association with the result
that the resultant structures cannot be guaranteed to possess a uniform
safety margin and dependability. Moreover, the design and construction
methods in reinforced concrete and prestressed concrete are influenced by
the prevailing construction practices, the physical properties of the
materials and the climatic conditions. The need was, therefore, felt to lay
down uniform requirements of structures for the storage of liquids giving
due consideration to these factors. In order to fulfil this need, formulation
of this Indian Standard code of practice for concrete structures for the
storage of liquids [IS:3370-1965] was undertaken. This part deals
with general requirements. Three other parts of the code are the
following:
Part II Reinforced concrete structures
Part III Prestressed concrete structures
Part IV Design tables
0.3 Although the provisions of this code cover mainly structures for the
storage of liquids the general provisions of this code may also be applied
with such modifications as foun~I necessary, to suit the special conditions in
the design of reinforced concrete and prestressed concrete structures for
the conveyance of liquids, such as aqueducts and superpassages.
0.4 While the common methods of design and construction have- been
covered in this code, design of structures of special forms or in unusual
circumstances should be left to the judgement of the engineer and in such
3
IS: 3370 (Part 1) 1965 -
1. SCOPE
1.1 This standard (Part I) lays down the general requirements for the
design and construction of concrete structures, plain, reinforced or pre~-
tressed concrete, intended for storage of liquids, mainly water.
The requirements applicable specifically to reinforced concrete liquid
retaining structures are covered in Part II.
*Code of practice for plain and reinforced concrete (second revision).
~Code of practice for prestressed concrete.
~Rules for rounding off numerical values (revised).
4
1ST 3370 (Part I)-1965
1.2 This code does not cover the requirements for reinforced and pies-
tressed concrete structures for storage of hot liquids and liquids of low
viscosity and high penetrating power like petrol, diesel oil etc. Special
problems of shrinkage arising in the storage of non-aqueous liquids and she
measures necessary where chemical attack is possible, are also not dealt
with. The recommendations, however, may generally be applicable to
the storage at normal temperatures of aqueous liquids and solutions which
have no deterimental action on concrete and steel or where sufficient
precautions are taken to ensure protection of concrete and steel from
damage due to action of such liquids as in the case of sewage.
2. MATERIALS
2.1 The requirements for materials shall be governed by 4 of
IS: 456~l964* and 4 of IS: 1343-1960t for reinforced concrete and pres-
tressed concrete members, respectively, with the following additional
requirements:
a) Porous aggregates — Under no circumstances shall the use of porous
aggregates, such as burnt clay and broken brick or tile, be
allowed for parts of structure either in contact with the liquids
on any face or enclosing the space above she liquid.
b) Prestressing steel — The prestressing steel for prestressed concrete
members of the structure shall comply with the requirements of
either IS: 1785-1964 or IS: 2090-1962§.
2.2 Jointing Materials —Joint, fillers, joint sealing compounds, water
bars and joint cover plates shall conform to the requirements of relevant
Indian Standards.
3. i~ONCRETE MIX
3.1 Provisions in 5 of IS : 456~l964* and 4.2.5 of IS: 1343-1960t shall
appiy for reinforced concrete and prestressed concrete members, respecti-
vely, subject to the following further requirements:
a) Except in case of thick sections as described in 7 and parts of
structure neither in contact with the liquid on any fice nor
enclosing the space above the liquid, concrete mix weaker than
M 200’ shall not be used.
4. SiTE CONDITIONS
~.1The following conditions of the site in relation to the functional and
structural requirements of the liquid retaining (storage) structure materi-
ally influence the methods of design and the cost of the structure:
a) Physical characteristics of soil in which the liquid retaining
structure may be partly or wholly enclosed and also the physical
and geological features of the supporting foundations,
b) Extent of water-logging at the site, and
c) Chemical properties of the soil and of the ground water.
4.2 In making the choice of the site and in the preparation of the design
the factors mentioned in 4.1 should be taken into account generally as
ndicated below:
a) External eaTtk pressure
— Relieffrom external earth pressures either
wholly or partially should not generally be relied upon, unless
the operation of such pressures throughout the service life of the
liquid retaining structure is ensured. On the other hand, walls of
the liquid retaining structure shall be checked for external
pressures under empty or partially-empty conditions.
b) Water-logged ground If in the sitting of a liquid retaining
—
8
IS: 3370 (Part I). 1965
causes of cracking in concrete and measures to be adopted for avoiding
them are given below.
6.1.1 Design of reinforced concrete members should be made in accor-
dance with the usual principle of ignoring the tensile resistance of concrete.
Additionally, it should also be ensured that the calculated tensile stress on
the liquid retaining face of the equivalent concrete section (after allowing
for the steel area in equivalent concrete units) does not exceed the limits
prescribed by this standard [see Table 1 of IS: 3370 (Part II) 1965*] -
assuming in the calculations that the entire section of the concrete (includ-
ing cover) participates in resisting the direct and flexural loads. The
permissible limits of tensile stress in the concrete fdr calculations relating to
resistance to cracking will naturally provide a much smaller margin of
safety against ultimate tensile strength of concrete because the consequences
of cracking are usually much less serious than those of structural failure.
In members less than 225 mm thick, the requirement of limiting the
tensile stress as given in 6.1.1 shall also be applied to the face remote from
the water retaining face.
6.1.2 Plain concrete liquid retaining structures or members may be
designed against structural failure by allowing tension in plain concrete as
per the permissible limits for tension in bending specified in IS : 456-19641.
This will automatically take care of failure due to cracking. However,
nominal reinforcement in accordance with the requirements of
IS: 456-19641 shall be provided for plain concrete structural members.
6.1.3 The design of prestressed concrete members is based upon ‘no
tension being developed in the concrete section under service conditions.
‘
9
IS: 3370 (Part I) - 1965
6.1.4.1 Correct placing of reinforcement, use of small sized bars and
use of deformed bars lead to a difused distribution of cracks.
6.1.4.2 The risk of cracking due to overall temperature and shrinkage
effects may be minimized by limiting the changes in moisture content and
temperature to which the structure as a whole is subjected. Underground
reservoirs can remain permanently wet. It will be advantageous if during
construction of such reservoirs thin sections below final water level could
be kept permanently damp. It will, however, be impracticable to main-
tain permanent wetness in elevated structures which unavoidably may be
left empty for a period.
6.1.4.3 Cracks can be prevented in thick walls (or even in thinner
sections) by avoiding the use of thick timber shuttering which prevent the
easy escape of the heat of hydration from the concrete mass. Due to such
heat of hydration, the concrete wall is raised to a relatively high tempera-
ture which will be retained during the period the concrete hardens. Or
removal of the form work, as the temperature of concrete falls to that of the
surrounding air, the concrete contracts. Such contraction will take place
without cracking if the free movement of the wall is unrestricted, but cracks
may subsequently develop where one or more of the edges are restrained.
6.1.4.4 The risk of cracking can also be minimized by reducing the
restraints on the free expansion or contraction of the structure. With long
walls or slab; founded at or below ground level, restraints can be
minimized by the provision of a sliding layer. This can be provid~8 hi’
founding the structure on a flat layer of concrete (see Note ) with inter-
position of some material to break the bond and facilitate movement.
However, the length of the wall that can be kept free of cracks by th~ use
of a sliding layer in its foundation is strictly limited and is related to the
tensile strength of the wall section. In approximate terms, the tensile
strength has to be sufficient to overcome the resistance to sliding of one
half of the length of the wall. Control of cracking thus requires sub-
division of the structure into suitable lengths separated by movement joints.
The maximum length desirable between joints will depend on the tensile
strength of tlse wall and may be increased by suitable reinforcement. The
effectiveness of movement joints in controlling cracking will depend not
only on their spacing but often on their precise location. This is a matter
of experience and may be characterized as the place where cracks would
otherwise develop, for example, at changes of section. The location of all
movement joints should be indicated on the drawings.
NOTE — In normal circumstances this flat layer of concrete may be weaker than that
used in other parts of the structure, but not weaker than M 100 specified in
IS 456.1964*. Where, however inlurious soils or agressive ground water are expected,
the concrete should not be weaker than M 150 specified in IS 456-1964, and if
necessary a sulphate resisting or other special cement should be used.
*Code of practice for plain aid reinforced concrete (second rerision ).
10
1St 3370 ( Part I) 1965
-
7. THICK SECTIONS
7.1 Thick sections shall be those parts of structure which have thickness
greater than 450 mm. There is a likelihood ofcracking in such sections as a
consequence of temperature rise during hydration of the cement and
subsequent cooling. Such cracking is not easy to control by reinforcement.
The following are some of the measures that may be adopted for reducing
the likelihood of cracking:
a) Magnitude of the temperature rise should be restricted by limiting
the cement content, or by using a type of cement with a low rate
of heat of evolution or adopting suitable construction methods~
Portland cements with lower rates or strength development
generally give lower rates of heat evolution. In such cases the
pennissible stresses shall conform to requirements of 3.3. Tem-
perature rise may also be restricted by casting the concrete in
II
IS: 3370 ( Part I) - 1965
12
IS a 3370 ( Part I) - 1965
DISCONTINUITY IN
CONCRETE BUT NO JOINT SEALING
INITIAL GAP WATER BAR COMPOIJND-\ STRIP PANIING
., V ~
~ S
.r.Y
V.. - .V . .
V .7 ~. .p. S S. .P~
DISCONTINUITY IN CONTINUITY OF
STEEL STEEL
DISCONTINUITY IN
CONCRETE BUT NO
lA INITIAL GAP
lB
IA Complete Contraction Joint lB Partial Contraction Joint
FTG. 1 TYsTOAL CoNTRAcTIoN JoiNTS
WATER
S .
JOINT FIL’~~
DISCONTINUITY IN BOTH
CONCRETE AND STEEL
Fzo. 2 A TYPiCAL ExPANsioN JoTNT
13
1St 3370 (Part 1) 1965
-
V
9
COMPOUND
V
V. . p.
:7
.
~
••V
‘V
F
1 ~
:.>.
,.— PREPARED
SURFACE
JOINT
pCONTINUITY OF
& I STEEL
.9. I
24.L L
Fro. 4 A Txpxo~ CoxsTaucTxoT JoINT
tVI~I.J.
b~~V
V. JOINT SEALING
COMPOUND
SURFACES
5A 5B
MORTAR FILLING
5C
Fin. 5 TYPIcAL TEMPORARY OPEN JOINTS
b) The design should provide for exclusion of grit and debris which
would prevent the closing of the joint.
c) The material used in the construction of movement joints should
have the following properties:
1) it should not suffer permanent dsstortion or extrusion and
should not be displaced by fluid pressurc
2) it should not slump unduly in hot weather or become brittle
in cold weather.
3) it should be insoluble and dusable and should not be affected
by exposure to light or by evaporation of solvent or
plasticisers.
4) in special cases, the materials should he non-toxic, taintless or
resistant to chemical and biological action as may be specified.
8.3 Spacing of Joints — Unless alternative effective means are taken to
avoid cracks by allowing for the additional stresses that may be induced by
temperature or shrinkage changes or by unequal settlement, movement
joints should be provided at the following spacings:
a) In reinforcement concrete floors, movement joints should be
spaced at not more than 7’S m apart in two directions at right
15
15i3370(Part I)-1965
angles. The wall and floor joints should be in line except where
sliding joints occur at the base of the wall in which case corres-
pondence is not so important.
b) For floors with only nominal percentage of reinforcement (smaller
than the minimum specified), the concrete floor should be cast in
panels with sides not more than 4’S m.
c) In concrete walls, the vertical movement joints should normally
be placed at a maximum spacing of 7.5 m in reinforced walls and
6 m in unreinforced walls. The maximum length desirable
between vertical movement joints will depend upon the tensile
strength of the walls, and may be increased by suitable reinforce-
ment. Thus when a sliding layer is placed at the foundation ofa
wall, the length of wall that can be kept free of cracks depends
upon the capacity of wall section to resist the friction induced at
the plane of sliding. Approximately the wall has to stand the
effect of a force at the plane of sliding equal to weight of half the
length of wall multiplied by the coefficient of friction.
d) Amongst the movement joints in floors and walls as mentioned
above, expansion joints should normally be provided at a spacing
of not more than 30 m between successive expansion joints or
between the end of the structure and the next expansion joint, all
other joints being of the contraction type.
e) When, however, the temperature changes to be accommodated
are abnormal or occur more frequently than usual as in the case
of storage of warm liquids or in unin~ulated roof slabs, a smaller
spacing than 30 m should be adopted, (that is a greater propor-
tion of the movement joints should be of the expansion type)
When the range of temperature is small, for example, in certain
covered structures, or where restraint is small, for example, in
certain elevated structures none of the movement joints provided
in small structures upto 45 m length need be of the expansion
type Where sliding joints are provided between the walls and
either the floor or roof, the provision of movement joints in each
element can be considered independently.
8.4 Making of Joints —Joints shall gc±ierallybe made according to the
broad principles discussed in 8.4.1 to 8.4.3.
8.4.1 Construction Joints— These should be set at right angles to the
general direction of the member (see Fig. 4). The position and arrange-
ment of construction joints should be determined by the engineer at the
design stage and indicated on the drawings.
The surface film of the first-placed concrete should preferably be
removed whilst the concrete is still green to expose the aggregate and leave
a sound irregular surface. This may be effected by spraying with water
16
IS~ 3370 (Part I)- 1965
or air and water, assisted by light brushing, where necessary. If the con-
crete has been allowed to harden, it will be necessary to achieve the desired
surface by hacking the whole of the surface, care being taken to avoid
damaging the aggregate.
V
• V.
U
II.- KLLLj~’~
V
1’
II
I
V.
A
V I
1POLY VINYL CHLORIDE
ZJoINT SEALING COMPOUND WATER BAR
6A
TWO COAT STRIP
PAINTING MOULDED WATER BAR
S. .vx1sJ
V.
..Zq w - --v• .I~v.
• .u~I
ZJOINT SEALING COMPOUND ‘‘‘.1
6C 6D
Fza. 6 TYPICAL DETAma SHowING Usx Os JOINTING MATERIAlS IN
MovEMENT JoINTS (CoNmAc1~IoN Tysx)
structure. The joint should be suitably treated so as to maintain water-
tightness during movemqnt of the joint (see 8.5 and Fig. 7).
8.4.2.3 Sliding joints — The two concrete faces of a sliding joint should
be plane and smooth.
Care should be taken by the use of a rigid screeding board or other
suitable means to make the top of the lower concrete as flat as possible.
This surface can usefully be improved by finishing with a steel float and
rubbing down with carborundum.
Bond between the concrete of the two components should be preven-
ted by painting or by inserting building paper or other suitable material.
The joint should be suitably treated so as to maintain watertightness
during movement of the joint.
8.4.3 Temporary Open Joints The concrete on both sides of the joints
—
18
IS: 3370 (Part I ) - 1965
l~.W4. p.
.1 W
7A 7B
COPPER JOINT CodER PLATE
CI CLAMPING
PLATE GASKET
JOINT FILLER PLASTIC POINTING
L±J
V ~ ~ p
V V V ,— RUSTLESS
BOLT
jV’ V V
WATER BAR
p V
L.
INTO CONCRETE
7C 70
LEAD CAULKING
SHEET LEAD JOINT
COVER PLATE
JOINT SEALING
COMPOUND- f TWO COAT STRIP
PAINTING
•~•
V
V •. - . -
9’
V V V
5
7
7
V...
• . . V.
9.9
.9’. • . 9/~•
qV
~TOINT FILLER
PAINT JOINT FILLER
7F
7E TWO COAT STRIP PAINTING
PRECAST COVER
.9’ P
1. 9
JOINT £EALING . V ., .
COMPOUND ~•. ‘-.
~~6~X~X\ JOINT FIL~LER
7G
FIG. 7 TY?ICAL DZT.&ua SHOWING Usx Os JoINTING MA~rxxsAlS IN MovzMaw~
JOINTS (BxPANsIoN Tyru)
19
IS:3370(Part Il- 1965
In order to minimize the extent of subsequent movements due to
shrinkage the joint should be left open until shortly before the reservoir is
put into service and then filled in with mortar or concrete of specified
proportions. Where possible, the joint should be filled when the tempera-
ture is low.
Immediatly before filling the gap, the joint faces should, if possible,
be thoroughly cleaned and prepared in the same way as for construction
joints (see 8.4.1).
20
IS: 3370 (Part I ) - 1965
9. CONSTRUCTION
9.0 Unless otherwise specilied in this code, and subject to the following
additional recommendations, the provisions of IS : 456.1964* and
IS: 1343-1960t shall apply to the construction of reinforced concrete and
prestressed concrete liquid retaining structures, respectively.
9.1 Thick Sections The precautions necessary in the construction of
—
22
IS: 3370 (Part I) - 1965
digester. The minimum amount of water should be injected into the
mixture as this will ensure maximum density of the mortar.
9.3.2 Placing — The pneumatic mortar should be applied with an
approved nozzle by a skilled operator. The velocity of the material leav-
ing the nozzle should be maintained uniform and should be such as to
produce minimum rebound of sand.
9.3.3 Curing— Immediately after pneumatic mortar has been placed it
should be protected against premature drying by shading from strong
sunshine and shielding from the wind. As soon as it has hardened just
sufficiently to avoid damage it should be thoroughly wetted and thereafter
kept wet continuously for at least seven days. Adequate protection
against fluctuations in temperature by shading and shielding, shall also
be given.
IS 456~l964*.
9.7.2 Bolts passing completely through liquid-retaining slabs for the
purpose of securing and aligning the form-work should not be used unles~
effective precautions are taken to ensure water-tightness after removal.
9.8 LinIng of Tanks The type of liquid to be stored should be consi-
—
24
IS: 3370( Part I). 1965
concrete. Provision of an impermeable protective lining should be consi-
dered for resistance to the effects of corrosive liquids. Certain natural
waters exhibit corrosive characteristics and in such cases it is important to
obtain a dense impermeable concrete and with a higher cement content.
An increased cover to the steel is also desirable. Use of sulphate resisting
portland cement, pozzolana cement, or blast-furnance slag cement may in
certain cases be advantageous.
10. TESTS ON STRUCTURE
10.1 In addition to the structural test of the structure, as given in 21.3 of
IS: 456.1964*, the tanks shall also be teste4 for watertightness at full
supply level as described in 10.1.1, 10.1.2 and 10.1.3.
10.1.1 In the case of tanks whose external faces are exposed such as
elevated tanks, the requirements of the test shall be deemed to be satisfied
if the external faces show no signs of leakage and remain apparently dry
over the period of observation of seven days after allowing a seven day
period for absorption after filling.
10.1.2 In the case of tanks whose external faces are submerged and are
not accessible for inspection, such as underground tanks, the tanks shall be
filled with water and after the expiry of seven days after the filling, the
level of the surface of the water shall be recorded. The level of the water
shall be recorded again at subsequent intervals of 24 hours over a period
of seven days. The total drop in surface level over a period of seven days
shall be taken as an indication of the watertightness of the tank. The
engineer-in-charge shall decide on the actual permissible nature of this
drop in the surface level, taking into account whether the tanks are open
or closed and the corresponding effect it has on evaporation losses. For
many purposes, however, underground tanks whose top is covered may be
deemed to be water-tight if the total drop in the surface level over a period
of seven days does not exceed 40 mm.
10.1.3 If the structure does not satisfy the conditions of test, and the
daily drop in water level is decreasing. the period of test may be extended
for a further seven days and if specified limit is then reached, the structure
may be considered as satisfactory.
25