E N V I R O N M E N TA L C O N T R O L

DataMate
60 Hz
New Wall Mount Display

ENGINEERING
MANUAL

0
900
ISO IFIED
T
CER PANY
COM
Table of Contents

Page
General Information — all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

11/2, 2, and 3 Ton Systems


Standard and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Air Cooled Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Water/Glycol Cooled Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
Guide Specifications (all 11/2, 2, and 3 Ton Systems) . . . . . . . . . . . . . . . . . . . 13-14
THE LIEBERT DATAMATE ENVIRONMENTAL
CONTROL SYSTEM

The Liebert DataMate Computer matched. Liebert Steam generating humidifier.


provides complete control systems are designed to create the The optional humidifier is pro-
environment required for comput- vided with an automatic flushing
of temperature, humidity
ers and other sensitive electronic circuit strainer, inlet and drain,
and air cleanliness on an equipment. DataMate provides solenoid valves and necessary
around the clock basis. complete control of temperature, control hardware.
humidity and air cleanliness on an
Air distribution fans. Direct drive
around the clock basis, as well as
centrifugal fans are located
the high sensible heat ratio re-
behind removable panels and
quired by sensitive electronic
are quiet in operation.
equipment.
Easy installation. All compo-
Space saving. Requires 5
nents of the DataMate are pre-
square feet or less.
charged and require no field
Reliable. The Liebert reputation brazing, evaluation or charging.
for quality and a nationwide Pre-charged refrigerant lines are
service network assures maximum available in 15 feet and 30 feet
uptime. lengths to connect evaporator
and condensing unit modules.
Designed to fit. Models avail-
able to fit any room without dis- Serviceability. The DataMate
rupting work-station layout. is designed with front service
access. Routine maintenance
and service can be performed
quickly and easily.
UL listed. Units are UL listed
and CSA (NRTL-C) certified.
NRTL-C meets both U.S. and
Canadian government safety
requirements, providing fast,
hassle-free inspection and
building code approvals.

The microprocessor control system, with its


user-friendly wall-mounted display, provides
precise control of all unit functions.

60 Hz 3
STANDARD FEATURES Standard Prop Fan Condensing Close-coupled Condensing
Unit: Includes scroll compressor, Unit: Include compressor,
The DataMate is a split system condenser coil, prop fan, high brazed plate condenser, 2-way
air, water or glycol cooled unit or head pressure switch, Lee-Temp water regulating valve, filter dryer
self contained chilled water unit. head pressure control, filter dryer and site glass. Design pressure is
and site glass. Unit is rated at 150 psi (1034 kPa).
The Evaporator Section. includes
95°F (35°C) ambient.
the evaporator coil, 2-speed cen- Remote Condensing Unit
trifugal blower assembly, tubular Centrifugal Fan Condensing (2 & 3 ton): Includes compressor,
reheat, cleanable filters and Unit: Includes compressor, con- coaxial condenser, 2-way water
microprocessor control. The unit denser coil, centrifugal blower regulating valve, filter dryer and
construction is galvanized steel assembly, high pressure switch, site glass. Design pressure is
with powder coated, removable electronic head pressure control, 150 psi (1034 kPa).
exterior panels. A reversible dis- filter dryer and site glass. Unit
Chilled Water Models include
charge grill provides the ability to must be mounted indoors. Duct
all the components described in
redirect airflow. The evaporator flanges are provided. Unit is
the evaporator section in addition
can be floor or wall mounted. rated for 95°F (35°C) ambient.
to a 2-way slow close motorized
Air Cooled Models include the Water/Glycol Cooled Models valve. Design pressure is 125 psi
evaporator section plus one of the include the evaporator section (1034 kPa).
following condensing units. plus one of the following

OPTIONAL FEATURES Auxilliary pump float automatically Water Detection Systems –


shuts off unit if pump discharge line Available in point, zone, and zone
Humidity control package: clogs or pump fails. measurments models.
Provides humidification and dehu-
Refrigerant- Line Sweat Adapter Prop Fan Condensing Units:
midification control and consists of
Kit – contains two suction and two Are available in several optional
a steam generator, steam distribu-
liquid line compatible fittings that configurations to satisfy various
tion tube, fill valve, drain valve and
allow field-supplied interconnecting application issues. They are:
electronic controls, located within
refrigerant lines to be used. 95°F (35°C) ambient with hot gas
the evaporator module. Maximum
bypass for low load conditions.
humidifier water supply pressure is 277 Volt Transformer – Required
105°F (40°C) ambient for high
150 PSIG. where 277 volt power is supplied to
ambient conditions.
the unit; one for evaporator module
Precharged line sets: Consist 105°F (40°C) ambient with hot gas
and one for condensing module
of one precharged liquid line and bypass for high ambient and low
(37.5 amps each). For self con-
one precharged insulated suction load conditions.
tained water/glycol system use one
line of soft copper tubing. Each 95°F (35°C) ambient Quietline for
37.5 amp transformer for 11/2, and
line has one male quick-connect low noise level conditions below
2 ton system and 50 amp for 3 ton
coupling and one female quick- 56 dba.
system. Epoxy encapsulated, suit-
connect coupling with an access
able for indoor/outdoor service. Remote Water Cooled
valve connection. Available in 15 ft.
Condensing Units: Are available in
(4.6m) and 30 ft. (9.1m) lengths for Monitoring and Control
several optional configurations to
interconnection of remote located Equipment – The following equip-
satisfy various application issues
condenser module. Maximum ment is available for monitoring or
They are:
recommended distance between control of the DataMate:
evaporator and condenser modules SiteScan Site Monitoring 2-way wrv with 300 psi
is 45 ft. (13.7m). System (2068 kPa) design pressure
Mini-Remote single unit
Condensate Pump – Has a 3-way wrv with 150 psi
monitoring
capcity of 69 GPH (260 I/h) at 10 (1034 kPa) design pressure
Dry Contact Monitors, 1-8
ft. (30kPa). Pump is complete with
point models 3-way wrv with 300 psi
integral float switch, pump, motor
Auto-changeover controls, (2068 kPa) design pressure
assembly and resevoir. Assembly
2-8 unit models
mounts on the right end of the
evaporator (indoor) module.

4 60 Hz
E N V I R O N M E N TA L C O N T R O L

DataMate

Air Cooled Systems


60 Hz

Outdoor Air Cooled. Suitable for roof or ground level site. Indoor Air Cooled. For high-rise and other applications
The condensing unit is designed for operation as low as where roof or ground level locations are impractical. May be
-30°F. located above the dropped ceiling ducted to the outside.
Designed for operation down to -20°F ambient.

EVAPORATOR
MODEL NUMBER DESIGNATIONS STANDARD SYSTEMS CONFIGURATIONS
DME 037 E- P H 3 Condensing Unit

Normal Evaporator Air Cooled Air Cooled


3 = Revision
Capacity Unit Centrifugal Fan Propeller Fan
Level
(Indoor) (Outdoor)

Nominal
11/2 TONS DME020E PFCO20A
capacity H = With Humidifier
in thousand & Reheat
BTU/H (Evaporator) 2 TONS DME027E MCD24A PFCO27A
O = With Reheat
(Evaporator) 3 TONS DME037E MCD36A PFCO37A
C = Cooling only
DME= (Evaporator)
DataMate CONDENSING UNITS
Evaporator Unit MODEL NUMBER DESIGNATIONS
P = 208/230 1- phase
PFC 0 37 A - P L 0
Rev #
PFC = prop fan
E- = Evaporator condensing Air Cooled
unit L = 95F Ambient
PFH = prop fan Lee-Temp
condensing - = Std Coil H = 105F Ambient
unit w/hgbp C = Coated Coil Lee-Temp
MMC= indoor 0 = 95F Ambient
centrifugal FSC
condensing P = 208/230 1ph 60hz
unit Y = 208/230 3ph 60hz

0 = Std Noise Level Nominal Capacity


Z = Quiet Line (1000 btu/hrs)
5
Evaporator
Section

Dimensions - Inches (mm)


MODEL Width Depth Height
46 /2
1
11 /8
7
32
DME020E
(1181) (300) (813)
641/8 117/8 32
DME027E
(1628) (300) (813) For component access and removal, clearance of 34” is recommended
641/8 117/8 32 in the front of the unit; 12” is recommended on each side. For
DME037E (1628) (300) (813) refrigerant line commections sizes, see page 8.

Remote
Propeller Fan
Air Cooled
Condensing
Unit (Outdoor)

Dimensions – Inches (mm)


MODEL Width Depth Height
PFC020A-PL0 40 (1016) 18 (457) 23 (584)
PFH020A-PL0 40 (1016) 18 (457) 23 (584)
PFC027A-PL0 40 (1016) 18 (457) 23 (584)
PFH027A-PL0 40 (1016) 18 (457) 23 (584)
PFC027A-PH0 48 (1219) 18 (457) 31 (787)
PFH027A-PH0 48 (1219) 18 (457) 31 (787)
PFCZ27A-PL0 48 (1219) 18 (457) 31 (787) Electrical and Piping Connections
A B C D
PFC037A-_L0 48 (1219) 18 (457) 31 (787)
7
PFH037A-_L0 48 (1219) 18 (457) 31 (787) /8” (22.2mm) and Suction Line Male Liquid Line Male 7
/8” (22.2mm) dia.
1- 1/8” (28.6mm) Quick Connect Quick Connect electrical entrance
PFC037A-_H0 53 (1346) 18 (457) 36 (914) dia. knock outs Location. Location. for low voltage
53 (1346) 18 (457) 36 (914) electrical entrance connection
PFH037A-_H0
for line voltage
PFCZ37A-_L0 53 (1346) 18 (457) 36 (914) connection

6 Air Cooled Systems


60 Hz
Remote Centrifugal Fan
Air Cooled Condensing Unit (Indoor)

Dimensions – Inches (mm)


MODEL A B C D
MCD24A
17/16 (37) 117/16 (290) 1
/2 (13) 207/16 (519)
MCD36A

Electrical and Piping Connections


E F G H I J
7 7
/8” (22.2mm) /8” (22.2mm) High Pressure Suction Line Liquid Line 1
/2” (13mm)
and and Switch Reset Male Quick Male Quick N.P.T. Drain
Dia.Electrical Dia.Electrical Button Connect Connect Connection
Entrance for Entrance for (For condenser
Low Voltage Line Voltage coil washdown
Connection Connection only).

Air Cooled Systems 7


60 Hz
CAPACITIES AND TYPICAL SPECIFICATIONS ELECTRICAL DATA
AIR COOLED Evaporator Section 208/230v, 1‘, 60 Hz
Nominal Tons 1 1/2 2 3 Nom. Tons 1 1/2 2 3
Evaporator DME020E DME027E DME037E DME020E DME027E DME037E
Net Capacity Data - BTU/H (kW) High Fan Speed COOLING ONLY
80°F (26.7°C)DB Total 18000 (5.3) 25600 (7.5) 35300 (10.3) FLA 1.4 1.5 2.2
50% RH Sensible 16100 (4.7) 22000 (6.4) 27800 (8.1) WSA 1.8 1.9 2.8
75°F (23.9°C)DB Total 16700 (4.9) 23500 (6.9) 32300 (9.5) OPD 15 15 15
50% RH Sensible 15500 (4.5) 21000 (6.2) 26500 (7.8) WITH REHEAT
72°F (22.2°C)DB Total 16000 (4.7) 22300 (6.5) 30700 (9.0) FLA 11.8 22.3 23
50% RH Sensible 15000 (4.4) 20400 (6.0) 25800 (7.6) WSA 14.8 27.9 28.8
Net Capacity Data - BTU/H (kW) Low Fan Speed OPD 15 30 30
80°F (26.7°C)DB Total 18000 (5.3) 25500 (7.5) 35300 (10.3) WITH REHEAT AND HUMIDIFIER
50% RH Sensible 15000 (4.4) 20400 (6.0) 26400 (7.7) FLA 18.8 29.3 30
75°F (23.9°C)DB Total 16700 (4.9) 23400 (6.9) 32400 (9.5) WSA 23.5 36.6 37.5
50% RH Sensible 14400 (4.2) 19500 (5.7) 25300 (7.4) OPD 25 40 40
72°F (22.2°C)DB Total 16000 (4.7) 22200 (6.5) 30800 (9.0)
50% RH Sensible 14000 (4.1) 19000 (5.6) 24700 (7.2) Propeller Fan Condensing Unit 208/230v, 60 Hz
Fan Data - Direct Drive PFC020A PFC027A PFC037A
High Speed CFM (CMH) 870 (1480) 1230 (2090) 1320 (2245) 1‘ 1‘ 1‘ 3‘
Low Speed CFM (CMH) 750 (1275) 1050 (1785) 1175 (2000) FLA 10.7 12.8 19.3 12.8
Fan Motor Hp (W) .16 (120) *.20 (150) *.27 (200) WSA 13 15.7 23.8 15.7
Compressor Data OPD 20 25 40 25
Refrigerant R-22 R-22 R-22 Centrifugal Fan Condensing Unit 208/230v, 60Hz
Evaporater Coil - Copper Tube/Aluminum Fin MCD24A MCD36A
Face Area ft 2 (m 2 ) 2.4 (0.22) 3.9 (0.36) 3.9 (0.36) 1‘ 1‘ 3‘
Rows of Coil 4 3 4 FLA 13.7 21.6 15.1
Reheat Data - Electric WSA 16.6 26.1 18.0
Capacity - BTU/H (kW) @230V OPD 25 40 25
9215 (2.7) 18082 (5.3) 18765 (5.5)
Includes fan motor
Humidifier Data - Steam Generator Type
Capacity - lbs/hr (kg/h) 3 (1.3) 3 (1.3) 3 (1.3)
Connection Sizes
1 3 3
Liquid Line - in. ⁄4 ⁄8 ⁄8
5 7 7
Suction Line - in ⁄8 ⁄8 ⁄8
Humidifier Supply - Comp Ftg 1
⁄4 1
⁄4 1
⁄4
UNIT WEIGHTS – NET
Humidifier Drain - Barb Ftg 1
⁄2 1
⁄2 1
⁄2 Evaporator Section
Evaporator Drain - OD 3
⁄4 3
⁄4 3
⁄4 DME020E 230 lbs (104 kg)
DME027E 330 lbs (150 kg)
DME037E 365 lbs (165 kg)
Propeller Fan Condensing Unit
Air Cooled Condensing Options
PFC020A 199 lbs (90 kg)
Outdoor Propeller Condenser Coil and Fan -95°F (35°C) Ambient
PFC027A 200 lbs (91 kg)
Condensing Module PFC020A PFC027A PFC037A
PFC037A 241 lbs (109 kg)
Face Area ft 2 (m 2) 4.1 (.38) 4.1 (.38) 7.7 (7.2)
Centrifugal Fan Condensing Unit
Rows of Coil 2 2 2
1 1 1
MCD24A 230 lbs (104 kg)
Motor Hp ⁄5 ⁄5 ⁄5
MCD36A 240 lbs (109 kg)
Indoor Centrifugal Condenser Coil and Fan -95°F (35°C) Ambient
Condensing Module MCD24A MCD36A
Air Volume –– CFM (CMH) 1000 (1698) 1650 (2802)
Face Area ft 2 (m 2) 4.6 (.43) 4.6 (.43)
Rows of Coil 2 3
1 1
Motor Hp ⁄3 ⁄2
ESP in H2O (pa) .5 (125) .5 (125)

* The 2 & 3 ton units each have 2 motors


2 ton – .08 & .12 hp
3 ton – .11 & .16 hp

8 Air Cooled Systems


60 Hz
E N V I R O N M E N TA L C O N T R O L

DataMate

Water Cooled and


Glycol Cooled Systems
60 Hz

Water/Glycol Cooled Remote. Utilizes an existing water or Water/Glycol Cooled Integral. Totally packaged. A single
glycol loop. Condensing unit is located under the raised floor power and water supply connection puts the unit in operation.
or above the dropped ceiling.

MODEL NUMBER DESIGNATIONS


SYSTEMS CONFIGURATIONS
DME 037 E- P H 3
Condensing Unit
3 = Revision
Level Normal Evaporater Remote Remote Integral/water
Water Glycol Glycol
Capacity Unit Cooled Cooled Cooled
Nominal
capacity H = With Humidifier
in thousand 11/2 TONS DME020E --- --- DMC022WG
& Reheat
BTU/H (Evaporator)
2 TONS DME027E MCD26W MCD26W DMC029WG
O = With Reheat
(Evaporator)
C = Cooling only 3 TONS DME037E MCD38W MCD38W DMC040WG

DME= (Evaporator)
DataMate Water or Glycol
Evaporator Unit (Condensing Units)
0 = 2-way 150 psi
H = 2-way 300 psi
MCD= 3 = 3-way 150 psi
Remote T = 3-way 300 psi
Condensing Unit
P = 208/230 1- phase
DMC= Y = 208/230 3 - phase
Integral
Condensing Unit WG = Water/Glycol Cooled
W- = Water Cooled
G- = Glycol Cooled
E- = Evaporator
9
Evaporator
Section

Dimensions - Inches (mm)


MODEL Width Depth Height
461/2 117/8 32
DME020E
(1181) (300) (813)
641/8 117/8 32
DME027E
(1628) (300) (813) For component access and removal, clearance of 34” is recommended
641/8 117/8 32 in the front of the unit; 12” is recommended on each side. For
DME037E (1628) (300) (813) refrigerant line commections sizes, see page 12.

Remote
Water
Cooled
and Glycol
Cooled
Condens-
ing Unit
(Indoor)

Electrical and Piping Connections


Model Tons A B C D
MCD26W 2 High Pressure Sight Glass Liquid Line Suction Line
Switch Reset Male Quick Male Quick
MCD38W 3 button Connect Connect

E F G H
3 3 7 7
⁄4” (19mm) N.P.T. ⁄4” (19mm) N.P.T. ⁄8” (22mm) N.P.T. ⁄8” (22mm) N.P.T.
Female Water/ Female Water/ Electrical Entrance Electrical Entrance
Glycol Outlet Glycol Inlet for Low Voltage for High Voltage
Connection Connection Connection Connection

10 Water Cooled and


Glycol Cooled Systems
Integral Water Cooled and Glycol Cooled ELECTRICAL DATA
Condensing Unit (Indoor) Evaporator Section 208/230v, 1‘, 60 Hz
Nom. Tons 1 1/2 2 3
DME020E DME027E DME037E
COOLING ONLY
FLA 1.4 1.5 2.2
WSA 1.8 1.9 2.8
OPD 15 15 15
WITH REHEAT
FLA 11.8 22.3 23
WSA 14.8 27.9 28.8
OPD 15 30 30
WITH REHEAT AND HUMIDIFIER
FLA 18.8 29.3 30
WSA 23.5 36.6 37.5
OPD 25 40 40

Optional Water/Glycol Condensing Unit 208/230v,


1‘, 60 Hz
Evap. Sect DME020 DME027 DME037
Cond. Unit DME022 DME029 DME040
COOLING ONLY
FLA 11.8 12.4 18.2
WSA 14.4 15.1 22.2
OPD 20 25 35
WITH REHEAT
FLA 22.2 33.2 39.0
WSA 27.4 41.1 48.2
OPD 35 45 50
WITH REHEAT AND HUMIDIFIER
FLA 22.2 33.2 39.0
WSA 27.4 41.1 48.2
OPD 35 45 50
Model Tons Width Depth Height
DMC022WG 1
1 ⁄2 14” 12” 32” Water Cooled/Glycol Cooled
(356mm) (305mm) (813mm) Condensing Unit 208/230v, 60 Hz
DMC029WG 2 MCD26W MCD38W
For refrigerant and water/glycol piping connection
DMC040WG 3 sizes, see page 12.
1‘ 1‘ 3‘
FLA 11.4 17.9 11.4
WSA 14.3 22.4 14.3
OPD 25 40 25

UNIT WEIGHTS – NET


Evaporator Section
DME020E 230 lbs (104 kg)
DME027E 330 lbs (150 kg)
DME037E 365 lbs (165 kg)
Integral Condensing Unit
DMC022WG 170 lbs (77 kg)
DMC029WG 170 lbs (77 kg)
DMC040WG 175 lbs (78 kg)
Remote Condensing Unit
MCD26W 175 lbs (79 kg)
MCD38W 190 lbs (86 kg)

Design Data: 40% Ethylene Glycol and Water 60Hz Power Supply;
75/50% Room Design

Water Cooled and 11


Glycol Cooled Systems
WATER COOLED GLYCOL COOLED
Nominal Tons 1 1/2 2 3 1 1/2 2 3
Evaporator Section DME020E DME027E DME037E DME020E DME027E DME037E
Net Capacity Data - BTU/H (kW) High Fan Speed
80°F (26.7°C)DB Total 21200 (6.2) 27300 (8.0) 38700 (11.3) 17700 (5.2) 22900 (6.7) 32500 (9.5)
50% RH Sensible 17300 (5.1) 22600 (6.6) 29000 (8.5) 16000 (4.7) 21100 (6.2) 26700 (7.8)
75°F (23.9°C)DB Total 19400 (5.7) 24900 (7.3) 35100 (10.3) 16200 (4.7) 22700 (6.7) 29700 (8.7)
50% RH Sensible 16500 (4.8) 21500 (6.3) 27700 (8.1) 15200 (4.5) 22700 (6.7) 25500 (7.5)
72°F (22.2°C)DB Total 18300 (5.4) 23600 (6.9) 33100 (9.7) 16500 (4.8) 21700 (6.4) 28000 (8.2)
50% RH Sensible 16000 (4.7) 20900 (6.1) 26900 (7.9) 16500 (4.8) 21700 (6.4) 24700 (7.2)
Net Capacity Data - BTU/H (kW) Low Fan Speed
80°F (26.7°C)DB Total 21000 (6.2) 27100 (7.9) 38500 (11.3) 17600 (5.2) 22900 (6.7) 32700 (9.6)
50% RH Sensible 16100 (4.7) 21000 (6.2) 27600 (8.1) 14800 (4.3) 19500 (5.7) 25400 (7.4)
75°F (23.9°C)DB Total 19100 (5.6) 24700 (7.2) 35100 (10.3) 16100 (4.7) 21100 (6.2) 29800 (8.7)
50% RH Sensible 15300 (4.5) 20100 (5.9) 26400 (7.7) 14100 (4.1) 18600 (5.4) 24300 (7.1)
72°F (22.2°C)DB Total 18100 (5.3) 23500 (6.9) 33100 (9.7) 15200 (4.5) 20100 (5.9) 28300 (8.3)
50% RH Sensible 14900 (4.4) 19500 (5.7) 25700 (7.5) 13700 (4.0) 18100 (5.3) 23600 (6.9)
Fan Data - Direct Drive
High Speed CFM (CMH) 870 (1480) 1230 (2090) 1320 (2245) 870 (1430) 1230 (2090) 1320 (2245)
Low Speed CFM (CMH) 750 (1275) 1050 (1785) 1175 (2000) 750 (1275) 1050 (1785) 1175 (2000)
Fan Motor Hp (W) .16 (120) *.20 (150) *.27 (200) .16 (120) *.20 (150) *.27 (200)
Compressor Data - Sealed Hermetic
Refrigerant R-22 R-22 R-22 R-22 R-22 R-22
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft 2 (m 2 ) 2.4 (0.22) 3.9 (0.36) 3.9 (0.36) 2.4 (0.22) 3.9 (0.36) 3.9 (0.36)
Rows of Coil 4 3 4 4 3 4
Reheat Data - Electric
Capacity - BTU/H (kW) @230V
9215 (2.7) 18082 (5.3) 18765 (5.5) 9215 (2.7) 18082 (5.3) 18765 (5.5)
Includes fan motor
Humidifier Data - Steam Generator Type
Capacity - lbs/hr (kg/h) @230v 3 (1.3) 3 (1.3) 3 (1.3) 3 (1.3) 3 (1.3) 3 (1.3)
Connection Sizes
1 3 3
Liquid Line - in. 1
⁄4 3
⁄8 3
⁄8 ⁄4 ⁄8 ⁄8
5 7 7
Suction Line - in. 5
⁄8 7
⁄8 7
⁄8 ⁄8 ⁄8 ⁄8
1 1 1
Humidifier Supply - Comp Ftg 1
⁄4 1
⁄4 1
⁄4 ⁄4 ⁄4 ⁄4
3 3 3
Humidifier Drain - Barb Ftg 1
⁄2 1
⁄2 1
⁄2 ⁄8 ⁄8 ⁄8
3 3 3
Evaporator Drain - OD 3
⁄4 3
⁄4 3
⁄4 ⁄4 ⁄4 ⁄4

Water Cooled Condensing Options * The 2 & 3 ton units each have 2 motors
2 ton – .08 & .12 hp
Condenser Water Requirements 85°F(29.4°C) EWT, 105°F(40.6°C) Cond. Temp
3 ton – .11 & .16 hp
Condensing Module DMC022WG DMC029WG DMC040WG
THR-BTU/HR (KW) @75°/50 24,800 (7.2) 32,500 (9.5) 46,000 (13.6)
Flow Rate - GPM (I/M) 4.8 (18) 5.1 (19) 8.4 (32)
Pressure Drop - psi (kPa) 4.2 (28.9) 2.3 (15.9) 4.2 (28.6)
5 7 7
Condenser Connection -in. ⁄8 ⁄8 ⁄8
Condenser Water Requirements 85°F(29.4°C) EWT, 110°F(43.3°C) Cond. Temp
Condensing Module MCD26W MCD38W
THR-BTU/HR (KW) @75°/50% 30,800 (9.0) 44,500 (13.0)
Flow Rate - GPM (I/M) 7.9 (30) 6.5 (25)
Pressure Drop - psi (kPa) 4.1 (12.1) 2.8 (8.4)
3 3
Condenser Connection -in. ⁄4 ⁄4

Glycol Cooled Condensing Unit Options


Condenser Glycol Cooled Requirements 110°F(43.3°C) EGT
Condensing Module DMC022WG DMCO29WG DMCO40WG
Flow Rate - GPM (I/M) 6 (23) 7 (27) 9 (34)
Pressure Drop - psi (kPa) 7.3 (50.3) 4.5 (31.0) 5.6 (38.6)
5 7 7
Condenser Connection -in. ⁄8 ⁄8 ⁄8
Condenser Glycol Requirements 110°F(43.3°C) EGT
Condensing Module MCD26W MCD38W
Flow Rate - GPM (I/M) 9 (34) 12 (46)
Pressure Drop - psi (kPa) 16.0 (47.7) 25.0 (74.6)
3 3
Condenser Connection -in. ⁄4 FPT ⁄4 FPT

12 Water Cooled and


Glycol Cooled Systems
E N V I R O N M E N TA L C O N T R O L

DataMate

Chilled Water Systems


60 Hz

Chilled Water. This unit simply connects to a chilled water


loop, for quick and easy installation.

MODEL NUMBER DESIGNATIONS SYSTEM CONFIGURATIONS


DME 044 C- P H 3 Nominal Evaporator Condensing
Capacity Unit Unit
3 = Revision
Level 3 TONS DME044C ---

Nominal
capacity H = With Humidifier
in thousand & Reheat
BTU/H (Evaporater)
O = With Reheat
C = Cooling only

DME=
DataMate
Evaporator Unit
P = 208/230 1- phase

C- = Chilled Water

13
Evaporator
Section

DataMate Evaporator Section


Dimensions - Inches (mm)
MODEL Width Depth Height Weight
641/8 117/8 32 364 lb
DME044C
(1628) (300) (813) (165 kg)

14 Chilled Water Systems


CAPACITIES AND TYPICAL SPECIFICATIONS ELECTRICAL DATA
CHILLED WATER Evaporator Section 1‘, 60 Hz
Nominal Tons 3 208/230v
Evaporator Sections DME044C DME044C
Capacity Data - BTU/H (kW) High Fan Speed COOLING ONLY
45°F (7.2°C) EWT, 10°F (5.6°C) FLA 2.2
80°F (26.7°C)DB Total 45100 (13.2) WSA 2.8
50% RH Sensible 32300 (9.5) OPD 15
Flow Rate – GPM (I/M) 9.0 (34) WITH REHEAT
Pressure Drop – PSI (kPa) 10.3(71.0) FLA 23
75°F (23.9°C)DB Total 32700 (9.6) WSA 28.8
50% RH Sensible 27700 (8.1) OPD 30
Flow Rate – GPM (I/M) 6.5 (25) WITH REHEAT AND HUMIDIFIER
Pressure Drop – PSI (kPa) 7.2 (49.6) FLA 30
72°F (22.2°C)DB Total 27600 (8.1) WSA 37.5
50% RH Sensible 24900 (7.3) OPD 40
Flow Rate – GPM (I/M) 5.5 (21)
Pressure Drop – PSI (kPa) 6.0 (41.4)
Capacity Data - BTU/H (kW) Low Fan Speed
45°F (7.2°C) EWT, 10°F (5.6°C)
80°F (26.7°C)DB Total 42100 (12.3)
50% RH Sensible 29800 (8.7)
Flow Rate – GPM (I/M) 8.4 (32)
Pressure Drop – PSI (kPa) 9.5(65.5)
75°F (23.9°C)DB Total 30300 (8.9)
50% RH Sensible 25400 (7.5)
Flow Rate – GPM (I/M) 6.0 (23)
Pressure Drop – PSI (kPa) 6.6 (45.5)
72°F (22.2°C)DB Total 25500 (7.5)
50% RH Sensible 22900 (6.7)
Flow Rate – GPM (I/M) 5.1 (19)
Pressure Drop – PSI (kPa) 5.5(37.9)
Fan Data –Direct Drive
High Speed CFM (CMH) 1320 (2245)
Low Speed CFM (CMH) 1175 (2000)
Fan Motor Hp (W) *.27 (200)
Chilled Water Coil – Copper Tube, Aluminum Fin
Face Area ft 2 (m2) 3.9 (0.36)
Rows of Coil 3
Chilled Water Controls
Maximum Design Pressure – PSI (kPa) 125 (862)
Slow Close
Valve Type
Solenoid
Valve Body 2-way
Valve Cv 8
Valve Close – Off Pressure – PSI (kPa) 8 (55)
3
Valve Sizes – Inches ⁄4
Reheat Data – Electric
Capacity* – BTU/H (kW)
18765 (5.5)
*includes fan motor
Humidifier Data – Steam Generating Type
Capacity – lbs/hr (kg/h) 3 (1.3)
Connection Sizes (inches)
Chilled Water 3
⁄4
Supply and Return – FPT
1
Humidifier Supply – Compr Ftg ⁄4
1
Evaporator Drain – Barb Ftg ⁄2
3
Evaporator Drain – OD ⁄4
*2 motors – .11 & .16 hp

Chilled Water Systems 15


GUIDE SPECIFICATIONS
1.0 General 2.1.2. Air Distribution 2.1.3.3.2 Common Alarm and
The air distribution system shall be Remote On/Off
1.1. Summary constructed with a quiet, direct-drive fan A common alarm relay shall be
These specifications describe assembly equipped with multiple provided to provide a contact closure
requirements for a computer-room double-inlet blowers, self-aligning sleeve to a remote alarm device. Two (2)
bearings, and lifetime lubrication. Fan terminals shall also be provided for
environmental control system. The system
motor shall be permanent-split capacitor, remote on/off control. Individual
shall be designed to maintain temperature high efficiency type, equipped with two alarms shall be "enabled" or "disabled"
and relative humidity conditions within the speeds for air flow modulation. from reporting to the common alarm.
room. Dehumidification shall utilize the lower fan
speed. 2.1.3.3.3 Setback Control
The manufacturer shall design and furnish Air filters shall be the cleanable foam type The control shall be programmable on
all equipment to be fully compatible with They shall be easily removable from the a daily basis or on a 5 day/2 day
front of the system by means of program schedule. It shall be capable
heat dissipation requirements of the site.
quarter-turn fasteners and shall not of accepting 2 programs per day.
1.2. Design Requirements require system shutdown for service.
2.1.3.3.4. Temperature
The computer room environmental control
system shall be a Liebert DataMate, 2.1.3 Microprocessor Control Calibration
factory assembled unit. The refrigeration The control system shall be microproces- The control shall include the
system shall be split, with the compressor sor based. The wall-mounted control capabilities to calibrate the temperature
located in a remote or close coupled enclosure shall include a 2-line by 16 char- and humidity sensors and adjust the
condensing unit. The evaporator section acter LCD display providing continuous sensor response delay time from 1 to
shall be specifically designed for floor or display of operating status and alarm con- 90 seconds. The control shall be
wall-mounted installation and serviceable dition. An 8-key membrane keypad for capable of displaying temperature
from the front of the system. Condensing setpoint/program control, unit on/off, and values in °F or °C.
units shall be designed for outdoor, below fan speed shall be located below the dis-
the raised floor, above-dropped-ceiling, play. 2.1.3.3.5. System Auto Restart
or in room installation. Refer to Section For start-up after power failure, the
Temperature and humidity sensors shall be
system shall provide automatic restart
2.3. located in the wallbox which shall be
with a programmable (up to 9.9
capable of being located up to 300 ft
Each system shall be capable of minutes in 6-second increments) time
(91.4m) from the evaporator unit. delay. Programming can be performed
delivering______CFM. The
circulating-air fan shall be two speed for either at the unit or from the central site
2.1.3.1 Monitoring
precise dehumidification control. The fan monitoring system.
The LCD display shall provide an on/off
motor horsepower shall be______ . The
indication, fan speed indication, operating 2.1.4 Alarms
system shall be designed for blow
mode indication (cooling, heating,
through air arrangement.
humidifying, dehumidifying) and current 2.1.4.1 Unit Alarm
The system shall have a total cooling day, time, temperature and humidity (if The control system shall monitor unit
capacity of______BTU/HR, and a applicable) indication. The monitoring operation and activate an audible and
sensible cooling capacity of______ system shall be capable of relaying unit visual alarm in the event of the
BTU/HR, based on the entering air operating parameters and alarms to the following factory preset alarm
condition of______°F dry bulb, and Liebert SiteScan® monitoring system. conditions:
______°F wet bulb. These units are to
be supplied with______volt, PH, 2.1.3.2 Control Setpoint • High Temperature
______HZ power supply. Parameters • Low Temperature
• High Humidity
1.3. Submittals • Temp. Setpoint 65-85°F (18 to 29°C) • Low Humidity
Submittals shall be provided with the • Temp. Sensitivity 1 to 5°F (1 to 3°C) • High Water Alarm - Lockout Unit
proposal and shall include: Single-Line • Humidity Setpoint 20-80% RH Operation
Diagrams; Dimensional, Electrical, and • Humidity Sensitivity 1 to 10% RH • High Head Pressure
Capacity data; Piping and Electrical • Loss of Power
Connection Drawings. 2.1.3.3 Unit Controls • Compressor Short Cycle

2.0 Product 2.1.3.3.1 Compressor


Short-Cycle Control
2.1. Standard Features/ The control system shall prevent 2.1.4.2 Custom Alarms (2x)
All Systems compressor short-cycling by a 3 minute
• Humidifier Problem
timer from compressor stop to the next
2.1.1. Evaporator Cabinet and • Filter Clog
start. • Water Detected
Frame Construction
• Smoke Detected
The cabinet and chasis shall be
constructed of heavy gauge, painted User customized text can be entered
furniture steel. The cabinet shall be for the two (2) custom alarms
be designed for easy installation and
service access from the front only.

16 60 Hz
2.1.4.3 Alarm Controls 2.2.2 Chilled Water Coil 2.3.1. Water or Glycol Cooled
Each alarm (unit and custom) shall be The cooling coil shall have a minimum of (Integral)
separately enabled or disabled, 2.6 sq.ft.(.24m 2) face area, 3 rows deep.
selected to activate the common alarm It shall be constructed of copper tubes Water or Glycol Cooled
(except for high head pressure). and aluminum fins and be mounted in a Condensing Unit
stainless steel condensate drain pan. The The water/glycol cooled condensing unit
coil shall be designed for a maximum face shall include the compressor and the
2.1.4.4 Audible Alarm velocity of 340 ft. per minute (1.73 m/s) at
The audible alarm shall water/glycol cooled condenser, and shall
______ CFM (CMH). The water circuit be remote from the evaporator module.
annunciate any alarm that is shall be designed to distribute water into The water/glycol cooled condenser shall
enabled by the operator. the entire coil face area. The coil shall be
be designed to balance the heat rejection
supplied with ______ °F (°C) entering
at______ ° F ( ° C) entering water/glycol
2.1.4.5 Common Alarm water temperature, with a ______ °F (°C) temperature with a flow rate of
A programmable common alarm temperature rise. The coil shall be ______ GPM (I/s). An adjustable water
shall be provided to interface user supplied with ______ GPM (I/s) of chilled regulating valve shall be included.
selected alarms with a remote water and the pressure drop shall not
alarm device. exceed ______ PSI (kPa). All components shall be factory
assembled, charged with refrigerant,
2.3. Standard Features/ sealed and be capable of being
2.1.4.6 Remote Monitoring Indlvldual Systems connected to the evaporator section using
All alarms shall be communicated pre-charged refrigerant line sets. No
to the Liebert site monitoring 2.3.1. Air Cooled piping, brazing, dehydration or charging
system with the following The air cooled system shall consist of an shall be required.
information: date and time of evaporator section and a condensing unit
occurrence, unit number, and Drycooler
section.
present temperature and humidity. The Liebert manufactured drycooler shall
A. Centrifugal Fan Condensing Unit be the low profile, slow speed,
2.1.5 Electric Reheat direct drive propeller fan type. The
The electric reheats shall be low-watt The condenser coil shail be constructed drycooler shall be constructed of
density, tubular elements and shall of copper tubes and aluminum fins, with aluminum and contain a copper tube
include agency approved safety switches a direct-drive centrifugal-type fan. aluminum fin coil with an integral electric
to protect the system from overheating. control panel. The drycooler shall be
The capacity of the reheat coils shall be The condensing unit shall be factory designed for______ °F (°C) ambient.
_____ BTU/HR, _____ KW, controlled in tested, charged with refrigerant, sealed
1 stage. and be capable of being connected to the GIycol Pump Package
evaporator secUon using pre-charged This system shall be provided with a
2.2. Direct Expansion System refrigerant line sets. No piping, brazing, centrifugal pump mounted in a
dehydration or charging shall be required.
Components Condenser shall be designed for 95°F
weatherproof and vented enclosure. The
pump shall be rated for GPM (I/s) at
2.2.1. Direct Expansion Coil (35°C) ambient and be capable of ______ ft. (m) of head, and operate on
The evaporator coil shall have _____ sq. ft. operation to -20°F (-29°C). ______ volt, 1 phase______HZ.
face area, _____ rows deep. It shall be
B. Propeller Fan Condensing Unit 2.4. Optional Equipment/AII
constructed of copper tubes and
aluminum fins and have a maximum The condenser coil shall be constructed Systems
face velocity _____ of ft. per minute at of copper tubes and aluminum fins with
_____ CFM. Refrigerant flow shall be a direct drive propeller fan and scroll 2.4.1. Condensate Pump
controlled by an externally equalized compressor. (Option) A hot gas bypass The condensate pump shall have the
thermostatic expansion valve. The coil circuit shall be provided to ensure opera- capacity of ____GPH (I/s) at____ft. (m) of
shall be provided with a galvanized steel tion under low load conditions. All com- head. It shall be complete with integral
drain pan. ponents shall be factory assembled, float switch, pump, motor assembly,
charged with refrigerant, sealed and check valve and reservoir.
2.2.2. Refrigeration System be capable of being connected to the
The refrigeration system shall consist of a evaporator section using pre-charged 2.4.2. Refrigerant Line Sets
(hermetic) (scroll) compressor with vibra- refrigerant line sets. No piping, brazing, Pre-charged refrigerant line sets shall be
tion isolating springs, high pressure safety dehydration or charging shall be required. provided by Liebert in proper lengths for
switch, liquid line filter/drier, and a com- application. Line set length shall be
pressor crankcase heater. Refrigeration Condensing unit shall be designed for _____feet (m).
components shall be located in remote or ______°F ( ____°C) ambient and be capable
close-coupled condensing unit. Refer to of operation to -30°F (-34°C). 2.4.3. Steam-Generating
section 2.3. Humidifier
(Option) The condensing unit shall be
Provide electronically controlled
designed to operate at a sound level less steam-generating humidifier factory
2.2. Chilled Water System than 58 dba. piped, mounted and wired to the integral
Components control system. The steam generator shall
provide dry steam to the bypass air
2.2.1 Chilled Water Control around the evaporator coil.
The water circuit shall include a 2-way
slow close motorized valve. Design
pressure shall be 125 psig (865.85 kPa).

60 Hz 17
Controls for the humidification system
shall include: High and low humidity
setpoints, automatic water feed and drain
valves. Capacity shall be ____ Ibs/hr
(_____ kg/hr).

2.4.4. Liebert SiteScan Site


Monitoring System
A Liebert SiteScan Site Monitoring System
Model __________ shall be provided for
remote monitoring of the DataMate unit
and monitoring of other Liebert support
equipment.

2.4.5. Liebert Site Monitoring or


Control Systems
Provide indicated quantities of the
following:
•______Water Detection System(s)
Model______
•______Remote Monitor(s)
Model______
•______Auto-changeover Control(s)
Model______

3.0 Execution
3.1. Installation of Computer-
Room Air Conditioning Units
3.1.1. General
Install computer room Air Conditioning
units in accordance with manufacturer's
installation instructions. Install units plumb
and level, firmly anchored in locations
indicated, and maintain manufacturer's
recommended clearances.

3.1.2. Electrical Wiring


Install and connect electrical devices
furnished by manufacturer but not
specified to be factory mounted. Furnish
copy of manufacturer's electrical
connection diagram submittal to electrical
contractor.

3.1.3. Piping Connections


Install and connect devices furnished by
manufacturer but not specified to be
factory mounted. Furnish copy of
manufacturer's piping connection
diagram submittal to piping contractor.

3.1.4. Supply and Drain Water


Piping
Connect water supply and drains to air
conditioning unit. Provide pitch and trap
as manufacturer's instructions and local
codes require.

3.2. Field Quality Control


Start up computer room air conditioning
units in accordance with manufacturer's
start up instructions. Test controls and
demonstrate compliance with
requirements.

18 60 Hz
60 Hz 19
Liebert Corporation

1050 Dearborn Drive Via Leonardo Da Vinci 8


P.O. Box 29186 Zona Industriale Tognana
Columbus, Ohio 43229 35028 Piove Di Sacco
800.877.9222 Phone Italy
614.841.6022 FAX 39-049-9719-111 Phone
upstech@liebert.com Email 39-049-5841-257 Fax

23/F Allied Kajima Bldg.


138 Gloucester Road
Wanchai
Hong Kong
852.2.572.2201 Phone
852.2.831.0114 Fax

Liebert Web Site


http://www.liebert.com
© Copyright 2000 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without
notice.

® Liebert and the Liebert logo are


registered trademarks of Liebert
Corporation.

Printed in U.S.A.
SL-11035 (R6/00)