Service Manual

Commercial Air Conditioning


4HP 5HP Universal Outdoor Unit air conditioning

AB36NACBEA+AU36NAIBEA
AC36NACBEA+AU36NAIBEA
AD36NAMBEA+AU36NAIBEA
AD36NAHBEA+AU36NAIBEA
AB42NACBEA+AU42NAIBEA
AC42NACBEA+AU42NAIBEA
AD42NAMBEA+AU42NAIBEA
AD42NAHBEA+AU42NAIBEA
AP42NACBEA+AU42NAIBEA

Features
Auto-Restart function
Group control(with a group controller)
Auto-changeover
The same outdoor unit can match with cassette \convertible\
duct type indoor unit
With new environment friendly refrigerant R407C
Remotoe control and Wired remote control(Optional)

Weekly timing(with a weekly timer)

Haier Group
MANUAL CODE: SYJS-006 -03 Rev.0 .
CONTENTS

CONTENTS

Contents……..............................................…...………...…….1
1. Description of Products & Features…………………...…….2
2. Specifications…………………………. ………………...……6
3. Safety precaution…………………………..………………….14
4. Net dimensions of indoor and outdoor unit………………...17
5. Installation instructions ……………………. ………………..20
6. Parts and functions …………………………..…… ..……….48
7. Remote controller functions………………………….………50
8. Refrigerant diagram…………………………..……………....71
9. Electrical control functions……………………………………72
10. Diagnostic information(trouble shooting)…………….……78
11. Electrical data.........................................…………….……85
12. Exploded views and parts lists...............……………. ……88
13. Perdormance curves……………............................... ……96
14. Noise level charts.....……………............................... ……104
15. Air velocity distribution …………............................... ……106

-1-
1. Description of product code and brief introduction of the series
a) Description of the coding rule of the models
A U 36 N A I B D A

Climate type:T1
Design serial number
Product type: heat pump R407C
Appearance features
Product series:one-tag-one
Adaptive voltage:380-400V/50Hz
Product specification:valid digit above kilobi

Outdoor unit

Air conditioner
A B 36 N A C B D A

Climate type:T1
Design serial number
Product type: heat pump R407C
Appearance features
Product series:one-tag-one
Adaptive voltage:380-400V/50Hz
Product specification:valid digit above kilobi
Product type:indoor unit
P:Cabinet typeC:Convertible type
B:Cassette type D:Duct type
Air conditioner

b). Standard working condition


Indoor Operating Mode Outdoor Operating Mode
No. Operating Mode
Temp. Humidity Temp. Humidity
1 Nominal Cooling DB:27 WB:19 DB:35 WB:24
2 Nominal Heating DB:20 WB:15 DB:7 WB:6

2
c)Brif introduction of the series:
Convertible type:
AC36NACBEA+AU36NAIBEA AC42 NACBDA+AU42NAIBEA
(1).Ceiling convertible,flexible installation,convenient
maintenance,saving the users' expenditures
(2).Adopting three-phase power supply,applicable for household
and commercial usage
(3).Dual air outlet design,floor air blowing,accelerating the indoor air
circulation, quick temperature adjustment
(4).Long-distance air blowing,large power,large cooling/heating
ratio
(5).Intelligent remote control,convenient and flexible control
(6).Super-slim indoor unit design,luxury and nice-looking,saving
space,harmonious and unitive with the indoor environment
(7).Adopting screw-fastening for the air inlet grill,firmly
fixed;adopting slipway insert-lock fastening method for the
filter screen,convenient cleaning or replacing the filter screen
without opening the air inlet grill.
(8).Group control,units up to 128 sets can be controlled .

Duct type :
AD36NAMBEA+AU36NAIBEA AD42NAMBEA+AU42 NAIBEA
Totally concealed machine body
All the machine body is to be installed inside the ceiling, having no effect on the
beauty of the room and without taking any room space.
Air intake via the rear air intake duct
This new design has changed the former unique pattern of air intake, and a larger
distance between air intake and air return cycles as well as better air quality can be
achieved.
Flexible and easier installation
The machine body is to be installed in a totally concealed way,its fan system has
a longer distance coverage so as to supply its airflow to several rooms, and the
indoor unit may be installed inside the ceiling of a room or corridor. The
installation is simple and flexible, and there is no need to have specified personnel
for management, thus cutting down the expenses; the machine is lighter and
smaller, and convenient for installation, it takes an extremely small building space,
thus lower the construction cost; the indoor unit is to be concealed inside the
ceiling, and hence the usable space can be saved and the room decoration will
not be affected.

3
Cassette type:
AB36NACBEA+AU36NAIBEA AB42NACBEA+AU42NAIB
E A
Products characteristic:
Completely invisible machine body:
The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither
breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air
conditioner allows it to blend right into ceiling.
Superbly efficient healthy filter:
Superbly efficient antibiotic materials are utilized and can prevent germs from
breeding efficiently .
Flexible and easy installation
Slim design with machine body, completely ceiling concealing and portable shape, all make it greatly
easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional
cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing
installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill,
the ceiling can be protected from pollution effectively and allow the airflow to fit people's
comfortable need much more.
Compensation function of power failure:
When meeting a power failure during running, no matter how long it will be, once the power is
restored, air conditioner will automatic restart with the previous status.
Safety and reliable control due to various signal controls
1 Inputting with press buttons on the panel
2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe
temperature sensors,
3 Piping pressure signals
4 Compressor current signals
5 Testing signals
6 System time-shorten signal
7 Water overflowing signal
8 Communication signals between indoor unit and front plate or between indoor unit and outdoor
unit .
Silent design
The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to
significantly decrease operating noise.
NEW When using remote-controlling mode, it is comfortable and convenient to operate.
Advanced wire-controller and convenient remote-controller
The new wired controller can connect with 16 indoor units without any device such as detectors.
The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient.
In addition, it can be compatible with the old remote controllers.
NEW Low ambient temperature cooling function (optional)
Equipped with high/low pressure protection switch

4
d). Brief Introduction for T1\ T2\ T3 working condition

Climate type
Type of Air Conditioner
T1 T2 T3
Cool only 18 43 0 10 35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52

5
2.Specifications
item Model AB36NACBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 36000 41000
Total power input W 4000 3800
Max. power input W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3N~ 380V-400V 50HZ
Running /Max.Running A/A cooling:7.5/9.5;heating:6.5/9.5;
Start Current A 45
Unit model (color) AB36NACBEA(WHITE)
Fan Type × Number Centrifugal*1
Speed(H-M-L) r/min 590+30/490+40/420+50
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 1980/-/-
Heat exchanger Type / Diameter mm TP2M/φ7
Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


Dimension External (L×W×H) mm×mm×mm 1230×840×280
Package (L×W×H) mm×mm×mm 1325×920×370
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) Remote
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 43/41/39
Weight (Net / Shipping) kg / kg 46/53
Dimension External (L×W×H) mm×mm×mm 1340×950×80
Panel

Package (L×W×H) mm×mm×mm 1400×995×115


Weight (Net / Shipping) kg / kg 8.4/12
Unit model (color) /
Compressor Model / Manufacture /
Type /
Fan Type × Number /
Speed r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Outdoor unit

Total area m² /
Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Refrigerant Type / Charge g R407C 3800
Recharge quantity g/m 65
Liquid mm φ9.52
PIPING

Pipe
Gas mm φ19.05
Connecting Method Falre
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

6
item Model AC36NACBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 36000 41000
Total power input W 4000 3800
Max. power input W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3pH,380V-400V 50HZ
Running /Max.Running A/A cooling:7.5/9.5;heating:6.5/9.5;
Start Current A 45
Unit model (color) AC36NACBEA(WHITE)
Fan Type × Number CentrifugalX4
Speed(H-M-L) r/min 1350+30/1280+30/1050+30
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 1600/1400/1200
Heat exchanger Type / Diameter mm TP2M/9.52
Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


Dimension External (L×W×H) mm×mm×mm 1920×715×235
Package (L×W×H) mm×mm×mm 1980×761×295
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) Remote
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 48/-/44
Weight (Net / Shipping) kg / kg 62/77
Dimension External (L×W×H) mm×mm×mm /
Panel

Package (L×W×H) mm×mm×mm /


Weight (Net / Shipping) kg / kg /
Unit model (color) /
Compressor Model / Manufacture /
Type /
Fan Type × Number /
Speed r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Total area m² /
Outdoor unit

Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Refrigerant Type / Charge g R407C 3800
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

7
item Model AD36NAMBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 36000 41000
Total power input W 4000 3800
Max. power input W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3N 380V-400V 50HZ
Running /Max.Running A/A cooling:7.5/9.5;heating:6.5/9.5;
Start Current A 45
Unit model (color) AD36NAMBEA(WHITE)
Fan Type × Number CentrifugalX3
Speed(H-M-L) r/min 1050/ 960/ 870/810
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 2040/1800/1600
Heat exchanger Type / Diameter mm TP2M/9.52
Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


Dimension External (L×W×H) mm×mm×mm 1410×645×350
Package (L×W×H) mm×mm×mm 1557×800×370
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) Wired
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 43/-/39
Weight (Net / Shipping) kg / kg 55/75
Dimension External (L×W×H) mm×mm×mm /
Panel

Package (L×W×H) mm×mm×mm /


Weight (Net / Shipping) kg / kg /
Unit model (color) /
Compressor Model / Manufacture /
Type /
Fan Type × Number /
Speed r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Total area m² /
Outdoor unit

Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Refrigerant Type / Charge g R407C 3800
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.D
MAX.Piping length m 50

8
item Model AD36NAHBEA
Function cooling heating
Capacity BTU/h 36000 41000
Capacity kW 10.55 12.01
Sensible heat ratio 79% /
Total power input W 4000 3800
Max. power input W 5500 5500
EER or COP W/W 2.64 3.16
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3PH 380V-400V 50HZ
Running /Max.Running A/A Cooling:7.5/9.5, Heating:6.5/9.5
Start Current A 45
Unit model (color) AD36NAHBEA (grey)
Type × Number centrifugal X2
Speed(H-M-L) r/min 1090/1000/930
Fan
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 2580/2070/1560
Type / Diameter mm TP2M/9.52
Heat exchanger Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


External (L×W×H) mm×mm×mm 1197×828×355
Dimension
Package (L×W×H) mm×mm×mm 1450×980×530
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) wired
Fresh air hole dimension mm /
Outlet distribution hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 48/46/44
Weight (Net / Shipping) kg / kg 62/77
Unit model (color) /
Model / Manufacture /
Compressor
Type /
Type × Number /
Speed r/min /
Fan
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Type / Diameter mm /
Heat exchanger Total area m² /
Outdoor unit

Temp. scope ℃ /
External (L×W×H) mm×mm×mm /
Dimension
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Type / Charge g R407C 3800
Refrigerant
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method flared
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
item Model AU36NAIBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 36000 41000
Total power input W 4000 3800
Max. power input W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3N380V-400V 50HZ
Running /Max.Running A/A cooling:7.5/9.5;heating:6.5/9.5;
Start Current A 45
Unit model (color) /
Fan Type × Number /
Speed(H-M-L) r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Total Area m² /
Indoor unit

Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Control type (Remote /wired) /
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) /
Weight (Net / Shipping) kg / kg /
Dimension External (L×W×H) mm×mm×mm /
Panel

Package (L×W×H) mm×mm×mm /


Weight (Net / Shipping) kg / kg /
Unit model (color) AU36NAIBEA(WHITE)
Compressor Model / Manufacture C-SBN303H8A(SANYO)
Type Scroll
Fan Type × Number Axial-flow×2
Speed r/min 840+30
Fan motor output power kW 0.15
Air-flow(H-M-L) m³/h 6000
Heat exchanger Type / Diameter mm TP2M/9.52
Total area m² 0.92
Outdoor unit

Temp. scope ℃ 43-60


Dimension External (L×W×H) mm×mm×mm 980×340×1250
Package (L×W×H) mm×mm×mm 1050×440×1375
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm Capiliary
Defrosting AUTO
Volume of Accumulator L /
Noise level dB(A) 64/-/-
Type of Four way valve DHF-12
material of reduce noise XPE
crankcase heater power W /
Weight (Net / Shipping) kg / kg 91/111
Refrigerant Type / Charge g R407C 3800
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

9
item model AB42NACBEA
Function Cooling Heating
Capacity BTU/h 42000 48000
Total power input W 4800 5000
Max. power input W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3N~ 380V-400V 50HZ
Running /Max.Running Cooling:8.3/10.2;Heating:9.5/12.6;
A/A
current
Start Current A 59.5
Unit model (color) AB42NACBEA(WHITE)
Fan Type × Number Centrifugal
Speed(H-M-L) r/min 590+30/490+40/420+50
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 1980/-/-
Heat exchanger Type / Diameter mm TP2M/φ7
Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


Dimension External (L×W×H) mm×mm×mm 1230×840×280
Package (L×W×H) mm×mm×mm 1325×920×370
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) Remote control
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 43/41/39
Weight (Net / Shipping) kg / kg 46/53
Dimension External (L×W×H) mm×mm×mm 1340×950×80
Panel

Package (L×W×H) mm×mm×mm 1400×995×115


Weight (Net / Shipping) kg / kg 8.4/12
Unit model (color) /
Compressor Model / Manufacture /
Type /
Fan Type × Number /
Speed r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
/
Outdoor unit

Total area m²
Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Refrigerant Type / Charge g R407C 4000
Recharge quantity g/m 65
Liquid mm φ9.52
PIPING

Pipe
Gas mm φ19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

10
Item model AC42NACBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 42000 48000
Total power input W 4800 5000
Max. power input W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3N380V-400V 50HZ
Running /Max.Running A/A Cooling:8.3/10.2;Heating:9.5/12.6;
Start Current A 49.5
Unit model (color) AC42NACBEA(WHITE)
Fan Type × Number CentrifugalX2
Speed(H-M-L) r/min 1350+30/1280+30/1050+30
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 1600/1400/1200
Heat exchanger Type / Diameter mm TP2M/9.52
Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


Dimension External (L×W×H) mm×mm×mm 1920×715×235
Package (L×W×H) mm×mm×mm 1980×761×295
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) Remote
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 48/-/44
Weight (Net / Shipping) kg / kg 62/77
Dimension External (L×W×H) mm×mm×mm /
Panel

Package (L×W×H) mm×mm×mm /


Weight (Net / Shipping) kg / kg /
Unit model (color) /
Compressor Model / Manufacture /
Type /
Fan Type × Number /
Speed r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Total area m² /
Outdoor unit

Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Refrigerant Type / Charge g R407C 4000
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

11
Item model AD42NAMBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 42000 48000
Total power input W 4800 5000
Max. power input W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10‐³×m³/h 5
Power cable 5X2.5mm 2

Power source N,V,Hz 3N380V-400V 50HZ


Running /Max.Running A/A cooling:8.3/10.2;heating:9.5/12.6;
Start Current A 49.5
Unit model (color) AD42NAMBEA(WHITE)
Fan Type × Number CentrifugalX3
Speed(H-M-L) r/min 1050/960/ 870/810
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 2040/1800/1600
Heat exchanger Type / Diameter mm TP2M/9.52
Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


Dimension External (L×W×H) mm×mm×mm 1410×645×350
Package (L×W×H) mm×mm×mm 1450×9800×530
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) Wired
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 42/36/30
Weight (Net / Shipping) kg / kg 55/75
Dimension External (L×W×H) mm×mm×mm /
Panel

Package (L×W×H) mm×mm×mm /


Weight (Net / Shipping) kg / kg /
Unit model (color) /
Compressor Model / Manufacture /
Type /
Fan Type × Number /
Speed r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Total area m² /
Outdoor unit

Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Refrigerant Type / Charge g R407C 4000
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

12
item Model AD42NAHBEA
Function cooling heating
Capacity BTU/h 42000 48000
Capacity kW 12.31 14.06
Sensible heat ratio 79% /
Total power input W 4800 5000
Max. power input W 5700 7200
EER or COP W/W 2.56 2.81
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3PH 380V-400V 50HZ
Running /Max.Running A/A Cooling: 8.3/10.2, Heating: 9.5/12.6
Start Current A 49.5
Unit model (color) AD42NAHBEA (grey)
Type × Number centrifugal X2
Speed(H-M-L) r/min 1090+30/-/930+50
Fan
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 2580/-/1560
Type / Diameter mm TP2M/9.52
Heat exchanger Total Area m² /
Indoor unit

Temp. scope ℃ 2-7


External (L×W×H) mm×mm×mm 1197×828×355
Dimension
Package (L×W×H) mm×mm×mm 1450×980×530
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) wired
Fresh air hole dimension mm /
Outlet distribution hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) 48/-/44
Weight (Net / Shipping) kg / kg 62/77
Unit model (color) /
Model / Manufacture /
Compressor
Type /
Type × Number /
Speed r/min /
Fan
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Type / Diameter mm /
Heat exchanger Total area m² /
Outdoor unit

Temp. scope ℃ /
External (L×W×H) mm×mm×mm /
Dimension
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm /
Defrosting /
Volume of Accumulator L /
Noise level dB(A) /
Type of Four way valve /
material of reduce noise /
crankcase heater power W /
Weight (Net / Shipping) kg / kg /
Type / Charge g R407C 4000
Refrigerant
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method flared
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
item Model AP42NACBEA
Function cooling heating
Capacity BTU/h 42000 50000
Capacity kW 12.31 14.65
Total power input W 5000 6000
Max. power input W 6000 7200
EER or COP W/W 2.46 2.44
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 1PH 380V-400V 50HZ
Running /Max.Running A/A Cooling:8.5/10.2 Heating:10.0/12.0;
Start Current A 49.5
Unit model (color) AP42NACBEA (white)
Type × Number centrifugalX1
Speed(H-M-L) r/min 590/400/350
Fan
Fan motor output power kW 0.06
Air-flow(H-M-L) m³/h 1560/-/-
Type / Diameter mm TP2M/9.52
Indoor unit

Heat exchanger Total Area m² 0.338


Temp. scope ℃ 2-7
External (L×W×H) mm×mm×mm 1820×530×310
Dimension
Package (L×W×H) mm×mm×mm 1952×660×455
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Control type (Remote /wired) wired control
Noise level (H-M-L) dB(A) 48/-/44
Weight (Net / Shipping) kg / kg 62/77
Type / Charge g R407C 4000
Refrigerant
Recharge quantity g/m /
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method flared
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
Item model AU42NAIBEA(SANYO)
Function Cooling Heating
Capacity BTU/h 42000 48000
Total power input W 4800 5000
Max. power input W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10‐³×m³/h 5
Power cable /
Power source N,V,Hz 3N380V-400V 50HZ
Running /Max.Running A/A Cooling:8.3/10.2;Heating:9.5/12.6;
Start Current A 49.5
Unit model (color) /
Fan Type × Number /
Speed(H-M-L) r/min /
Fan motor output power kW /
Air-flow(H-M-L) m³/h /
Heat exchanger Type / Diameter mm /
Total Area m² /
Indoor unit

Temp. scope ℃ /
Dimension External (L×W×H) mm×mm×mm /
Package (L×W×H) mm×mm×mm /
Drainage pipe (material , I.D./O.D.) mm /
Control type (Remote /wired) /
Fresh air hole dimension mm /
Electricity Heater kW /
Noise level (H-M-L) dB(A) /
Weight (Net / Shipping) kg / kg /
Dimension External (L×W×H) mm×mm×mm /
Panel

Package (L×W×H) mm×mm×mm /


Weight (Net / Shipping) kg / kg /
Unit model (color) AU42NAIBEA(WHITE)
Compressor Model / Manufacture C-SBN373H8A(SANYO)
Type Scroll
Fan Type × Number Axial-flow×2
Speed r/min 1180+30 840+30
Fan motor output power kW 0.15
Air-flow(H-M-L) m³/h 6000
Heat exchanger Type / Diameter mm TP2M/9.52
Total area m² 0.92
Outdoor unit

Temp. scope ℃ 43-60


Dimension External (L×W×H) mm×mm×mm 980×340×1225
Package (L×W×H) mm×mm×mm 1050×440×1375
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Refrigerant control method mm/mm Capiliary
Defrosting Auto
Volume of Accumulator L /
Noise level dB(A) 64/-/-
Type of Four way valve DHF-12
material of reduce noise XPE
crankcase heater power W 42
Weight (Net / Shipping) kg / kg 91/116
Refrigerant Type / Charge g R407C 4000
Recharge quantity g/m 65
Liquid mm 9.52
PIPING

Pipe
Gas mm 19.05
Connecting Method Flare
MAX.Drop m 30
Between I.D &O.
MAX.Piping length m 50

13
SAFETY PRECAUTIONS

3 SAFETY PRECAUTIONS
Please read these "Safety Precautions" first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, WARNING and
CAUTION those points which are related to the strong possibility of an installation done in error
resulting in death or serious injury are listed in the WARNING section. However, there is also a
possibility of serious consequences in relationship to the points listed in the CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please
explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's
manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.

WARNING
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior
environment such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned
countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,
and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold
concentration does occur,there is the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive
use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and
fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat
generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.

- 14-
SAFETY PRECAUTIONS

WARNING
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (please see nameplate) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refigerant leakage.
The position of indoor unit must be above the floor 2.5m.

CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone
ground wire.
Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not
installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.

-15
3 Net dimensionsof indoor unit and outdoor unit
1)Outdoor unit
185 580 185

70 30
18
38

52
380

340
88
18
38

Screw Hole
(M10)

950

Power wiring Terminal


1250

25

16
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

2)Indoor unit
Model: AB36NACBEA Cassette type Indoor unit

1250-1280 (ceiling hole)


1340 1070 (hanging position)
615

860-890
950

780
615

840 55 1230 55
295
300
50 280

220

220

155
135
160
20
30

260

1000mm
270
315
over
00
15
er
ov

ov
er
15
00
00
15
er
ov

ov
er
15
00

- 17 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

Model: AC36NACBEA Convertible Indoor unit

105 195 300 300

600 600 600


590
545

690
630
555
310

85 150
drainage pipe

1920
1800
100

R15
180

30
235

60
85
195
150

100

85
40
85
25
300

10 10
110

60
65 45

18
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

Model: AD36NAMBEA AD42NAMBEA

drainage pipe
liquid pipe

A-A
gas pipe

19
Model: AD36NAHBEA AD42NAHBEA
INSTALLATION INSTRUCTIONS

5 INSTALLATION INSTRUCTIONS
5.1 Cassette type
5.1.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner,
shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter
7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor
11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump
15 .Flat screwdriver

5.1.2 Standard accessories


Please check if your unit is delivered with following

Part name 1 Clamp 2 Washer 3 Clamp 4 Drain hose 5 Paper pattern 6 Screw(M5 size)

QTY 2 Piece 8 Piece 6 Piece 1 Piece 1 Set 3 Piece

For installation
of
Shape paper pattern

Part name 7 Insulator 8 Insulator 9 Dry battery 10Sealing pad 11 Sealing pad 12 Sealing pad
[Other]
QTY 1 Piece 1 Piece 2 Piece 1 Piece 1 Piece 2 Piece
Operation
For gas pipe For liquid pipe R03, 7# Large size Medium size Small size Manual
Shape Ornament
panel
Remote
controller

5.1.3 Installation of indoor unit


5.1.3.1 Before installation
Determine the way kto carry unit to installation place.
Don't remove packing until unit reaches installation place.
If unpacking is unkavoidable, protect unit properly.
5.1.3.2 Selection of installation place
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured.
No block to air flow.
Water drainage is smpoth.
Place strong enough to support unit weight.
Place where inclination is not evident on ceiling.
Enough space for mainenance.
Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)
Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This
is helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio
wave is strong)

- 20 -
INSTALLATION INSTRUCTIONS

(2) Ceiling height


Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to 8 Foeld setting and Installation
Manual of ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take
necessary measures in case it is not safe. (Distance between holes are marked on paper pattern.
Refer to paper pattern for place need be reinforced)
Installation space

260

260
2500 Over

Air outlet Air outlet Air outlet Air inlet


Air inlet Air inlet
1500 Over 1500 Over 1500 Over 1500 Over

5.1.3.3 Preparation

(1) Position of ceiling opening between unit and suspending bolt.Unit: mm

890(Ceiling opening)
1070 (Distance between suspending bolts)
515
780(Distance between suspending bolts)
860(Ceiling opening)

20 Over
515

(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before
installation.
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent
vibration. Contact your real estate dealer
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new
ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
<Installation example>
Roof
Anchor bolt
Long nut
50~100

Suspending bolt

Ceiling Note: All the above mentioned parts shall be prepared in field.

- 21 -
INSTALLATION INSTRUCTIONS

5.1.3.4 Installation
In the case of new ceiling
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.
Center of the hole is marked on the paper pattern.
Center of the unit is marked on the card in the unit and on the paper pattern.
Mount paper pattern 4 onto unit using 3 screws 5 . Fix the corner of the drain pan at piping outlet.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))
(4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using
horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem
may occur on floating switch, causing water leakage.)
(5) Remove the washer mounlting 7 , and tighten the nut above.
(6) Remove the paper pattern.
In the case of ceiling already exists
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the
bracket. Fix the bracket firmly.
(2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).
(3) Proceed with 3 and 4 of "In the case of new ceiling".
Scrtews at the piping outlet is fixed at the corner
of drain pan.

Center of ceiling hole Paper pattern Paper pattern 4

Level
Polythene pipe

Screw 5 Screw 5 (accessory)


(accessory)
[Fix the paper pattern]

5.1.3.5 Refrigerant piping


As for outdoor piping, please refer to installation Manual of outdoor unit.
Outdoor is precharged with refrigerant.
Be sure to see the Fig.1, when connecting and removing piping from unit.
For the size of the flare nut, please refer to Table 1.
Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.
Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).
Check piping joints for gas leakage. Insulate piping as shown in Fig. below.
Cover joint of gas piping and insulator 6 with seal 9 .
Table 1
Pipe Tighten
A(mm) Flare shape
size torque
Apple refrigerant oil Medium size seal pad 9 (accessory)
(Cover the piping joint with seal pad.) 9.52 3270~3990N.cm
12.0~12.4 R0.4 ~ 0.8
2

(333~407kgf.cm)
90 0.5
45
A

Torque spanner
Clip 3

9720~11860N.cm
Insulator (accessory) 7 19.05 22.9~23.3
spanner (990~1210kgf.cm)
(For liquid pipe)

Insulator (accessory) 6
Diameter of Pipe Tighten Torque
Piping joing Gas pipe (For gas pipe)
Liquid pipe Liquid Pipe 9.52mm 42N. m
Flare nut
Gas Pipe 19.5mm 60N. m

- 22 -
INSTALLATION INSTRUCTIONS

5.1.3.6 Installation of drainage pipe


(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
If downward slope can't be made, take other measures to lift it up.
Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.

1-1.5m

Slope over 1/100


Waterring can of plastic

Use the self-provided stiff pipe and clip 2 with unit. Insert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 8 . Large size seal pad 10
Insulate drain hose in the room. (accessory)
Clip 2
Clip 2
(accessory)

Tape (White) Self-provided stiff pipe


4mm below
<Cautions for the drain water lifting pipe>
Installation height shall be less than 280mm.
There should be a right angle with unit, 300mm from unit.

300mm below 1~1.5m Suspending bracket Self-provided stiff pipe

500 below
Drain hose 1 (accessory)
220 280 below

75 below
500 below

(accessory) drain water lifting pipe

Clip 2
(accessory)
(Note)
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Over 100

Specifieations of the water hoses shall meet the requirements for the unit running.
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Check water drainage in cooling operation. See also 11 test run.
When wiring is not complete
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper
part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.
Note, in this operation, fan will be running.
Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove short
connection of "CHECK" terminal. Indoor
1 2 3
Method of water charging
Self-provided stiff pipe Maintenance
H05RN-F 2
Connect with
outdoor unit Terminal block 4G 0.75mm
Water drainage port for
maintenance Inspecting hole
L N 1 2 3
(Drain water from
this hole) Outdoor
PCB on indoor Power
Terminal Indoor
H07RN-F2
3G 4mm 1 2 3
H05RN-F 2
100mm Charge water from 4G 0.75mm
inspecting hole

Watering can of plastic R S T N 1 2 3


pipe should be about Charge water from
100 mm long air outlet
Cover of controll box Power Outdoor
H07RN-F 2
- 23 - 5G 2.5mm
INSTALLATION INSTRUCTIONS

5.1.3.7 Wiring
All supplied parts. materials and wiring operation must in appliance with local code and regulations.
Use copper wire only.
When make wiring, please refer to wiring diagram also.
All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unit
Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,
tighten clamp A. Connect wires of correct pole to the terminal block inside.
Wind seal (12) around wires. (Be sure to do that, or, dew may occur).
Upon connecting, replace control box cover (1) and (2).

Connect with Terminal block Terminal block


outdoor unit Clip A

Cover of control box 2

• Don't fail to seal it, or, water may come in.

Grounding lead Rubber tube Note: Have it sealed, leaving no space.


Rubber tube A Seal pad (small size)(
12 )
(Wind around wire)
Cover of control box 1
In Out
Field wiring
Attach seal pad

<<WARNING>>
Connect wires of the sameDon't connect wires of the
Obscrve the following when connecting power supply terminal block: Don't connect wires of the
Don't connect wires of different specifications to the same specifications at two sides.same specifications at one side.
different specifications.
terminal block.
(Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in right Fig.

5.1.3.8 Wiring example


As for outdoor unit circuit, please see Installation Manual of outdoor unit.
Note: All electric wires have their own poles, poles must match that on terminal block.
5.1.3.9 Installation of ornament panel
Cautions for the installation
Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read also
the Installation Manual of indoor unit.
With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.

Accessory Pad Pad

1. Prepare ornament panel


Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither on an uneven object.
Don' t bend carelessly the swing flap, or, problem may occur.

(1) Remove air inlet grill from ornament panel:


1 Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
2 Lift it up for about 45 degree and remove it from ornament.
Tear off adhesive tape fixing air filter on the back of the air
inlet grill. (Refer to Fig. 2)
Bar

- 24 -
INSTALLATION INSTRUCTIONS

(2) Remove cover plate at corner


Tear off the adhesive tape,
and slide it off.
(Refer to Fig. 3) Slide
Adhesive tape

45
Fig. 3
2. Install ornament panel on indoor unit.
For indoor unit installation, please refer to Installation Manual. Fig. 2
Hook
(1) As shown in Fig . 7, match the position of Holding ring 1

swing flap motor with that of the indoor unit 2 Piping hole position
piping hole , so that ormament panel can be
placed on to indoor unit.
(2) Installation of ornament panel
1 Place the holding ring on swing flao motor 2

side teporarily on hooks of the indoor unit.


(2 pcs) Swing flap motor

2 Put the other two holding rings on the hooks at


3
both side of the indoor unit. (Care should be
taken not to push wiring of swing flap motor
into seals). 4
3 Screw in all 4 screws under holding ring for Fig. 7
about 15mm. (Pancl will rise).
4 Adjust the ornament panel as per Fig. 7 to Indoor unit Seal
cover opening on the ceiling. Ceiling material

5 Tighten screws to redrce the thickness of seals 5 _ 8mm


between ornament and indoor unit to 5- Ornament panel
8mm. Caution
If indoor unit is at horizontal level
If screws are not tighten tight, problems in Fig, 8 If there are still space after tightening
and water drainage is smooth,
might occur. Tighten screws properly. of screws, please readjust the height then, indoor unit height can be ad-
Gas leakage.
of indoor unit. (Refer to Fig. 9) justed throrgh holes at corners of
ornament panel.
Gas leakage from roof.

Contamination Mist exists and drop down.


Leave no space.
Fig. 8 Fig. 9

3. Mounting on high ceiling


(1) Ornament panel can be mounted on ceiling as high as 3 m.
(2) Please install pad as accessary.
1 Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)
2 Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.

Cutting line Leave no space.


Place it on the frame.

a b
50 100

Part a of the pad Fig. 6


Fig. 4 Part a of the pad

Swing flap motor Fig. 5

(3)Wiring on ornament panel Side of ornament panel


Connecting of wiring of the swing
flap motor on ornament panel. (2 places)
(Refer to Fit . 10)

If connecting is not made, error code


(A7) appears on remote controller. So,
make proper connecting. Fig. 10
Side of indoor unit
Wiring diagram

- 25 -
INSTALLATION INSTRUCTIONS

4. Installation of inlet grill and cover plate


(1) Installation of inlet grill
Install in reversed order of “Prepare ornament pandl”.
Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as
per customers request.
When installing inlet grill, take care not to twist wiring of swing flap motor.
bolt
(2) Install cover plate on the corner
1 As shown in Fig. 11 tie the
cover plate onto the bolt on
ornament plate.
2 Install cover plate onto ornament plate.

(Refer to Fig. 12) Slide all five hold rings


to let them drop in holes
on ornament plate,

Fig. 11 Fig. 12

5.1.3.10 Test running


Refer to
Take special care during installation, check after working Conduct test run before installing ornament panel
Upon installation of piping, water drainage and wiring
work, make test run to ensure proper unit operation. Procedure Operation
Conduct test run after installation of ornament panel
(1) Open check valve on gas pipe.
Proce-
dure Operation (2) Open check valve on liquid pipe.
(1) Open check valve on gas pipe. (3) Press ON/OFF button, select Cooling mode.
(2) Open check valve on liquid pipe. (4) Let it run for 3 min.
(3) Press ON/OFF button, select Cooling mode. Cut main power supply after operation.
(5)
(4) Let it run for 3 min.
(5) Press air flow adjust button to make unit run properly Note:
(6) Confirm unit functions according to Operation Manual. If unit doesn’t run due to certain problem, please see
‘‘Note to unit maintenance’’.

- 26 -
INSTALLATION INSTRUCTIONS

5.1.4 Installation of outdoor unit


5.1.4.1 Selection of installation place
Place strong enough to support the unit and will not cause vibration and noise.
Place where discharged wind and noise do not cause a nuisance to the neighbors.
Place where is less affected by rain or direct sunlight and is sufficiently ventilated, or to install a shield.
Place with enough space for smooth air flow.
The unit shall not be installed on an unspecifised metal frame (e.g. theft guard net).
If the outdoor unit is installed close to a street, it shall be no less than 2.5m from the ground.
5.1.4.2 Fixing of the unit
Fix outdoor unit using M10 bolt to concrete floor horizontally.
If installed on the wall or on top of a roof, bracket should be fixed securely to resist earthquake or storms.
Use rubber pad during installation against unit vibration.
Install the unit so that the angle of inclination must be less than 3 degrees.
380

185 580 185

Installation dimension of outdoor unit (mm)

5.1.4.3 Air purging method: To use vacuum pump


For those models which adopt R407C refriengerant shall only use vacuum pump to
purg air.
Liquid
(Thin)
1
Detach the service port's cap of 3-way valve, the valve rod's Gas
cap for 2-way valve and 3-way's, connect the service port 2way V. (Thick)
into the projection of charge hose (low) for gaugemanifold.
Then connect the projection of charge hose (center) for 3way V.
gaugemanifold into vacuum pump.
Gaugemanifold

2
Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low) 2 Open Vacuum pump
reach vacuum condition in a moment, check 1 again.

3
Vacuumize for over 15min. And check the level
gauge which should read -0.1 MPa (-76 cm Hg)
at low pressure side. After the completion of
vacuumizing, close the handle 'Lo' in gaugemanifold
and stop the operation of the vacuum pump.
Check the condition of the scale and hold it for
1-2min. If the scale-moves back in spite of
tightening, make flaring work again, the return
to the beginning of 3 .
INSTALLATION INSTRUCTIONS

4
Open the valve rod for the 2-way valve to and
2way V.
angle of anticlockwise 90 degree.
After 6 seconds later, close the 2-way valve and 3way V.
male the inspection of gas leakage. 90°
Service port
4 90° for 6 sec.

If it does not stop gas leakage, discharge whole


In case of gas leakage, tighten
5 parts of pipe connection. If leakage
refrigerants from the serice port. After flaring work
No gas leakage? again and vacuumize, fill up prescribed refrigerant
stops, then proceed 6 steps.
from the gas cylinder.

6 2way V.
Detach the charge hose from the service port, open 6
2-way valve and 3-way. Turn the valve rod 3way V.
anticlockwise until hitting lightly. 6
3
7
To prevent the gas leakage, turn the service port's
cap, the valve rod'd cap for 2-way valve and 3-way's
a lottle more than the point where the torque increases
suddenly.
2way V.

8 3way V.
After attaching the each caps, check the gas leakage
around the caps. 7 Valve rod cap

7 Valve rod cap

5 Service port cap

If needing to remove the refrigerant gas when installation or repair , please refer to the
following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure
pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After
powering on the unit again and switch to COOLING mode,perform refrigerant gas removing
according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals
of the low-pressure pressure-switch properly.

- 28 -
INSTALLATION INSTRUCTIONS

GAS LEAKAGE INSPECTION


CAUTION
After connecting the piping, check the joints for gas leakage with gas leakage detector.

HOW TO CONNECT WIRING TO THE TERMINALS


A. For solid core wiring (or F-cable)(Fig.28A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.

B. For strand wiring(Fig.28B)


(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.
(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 28
Screw with
B. Strand wire special washer
A. Solid wire
Round Round Screw with
terminal terminal special washer
Loop
Strip 10mm

Terminal Round
board terminal
Wire

Insulation Wire
Strip 25mm

HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29

Fig. 29
Insulation tube

Cord clamp

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

5.5 Pay special care to the following and check after installation
Item to the checked Unproper installation may cause Check
Is indor indoor unit firmly installed? Unit might fall down, make vibration or noise.
Is gas leakage dheck performed? This may lead to gas shortage.
Is unit properly insulated? Dew or water drop may occur.
Is water drainage smooth? Dew or water drop may occur.
Is power voltage meet that stipulated on the nameplate? Problem may occur or parts got burned.
Is wiring and piping correctly arranged? Problem may occur or parts got burned.
Is unit safely grounded? There might be a danger of electric shock.
Is wire size correct? Problem may occur or parts got burned.
Are there any obstacles on air inlet and outlet grill of This may cause poor cooling.
indoor and outdoor unit?
Is record made for piping length and refrigerant It is hard to control refrigerant charging
charging amount? amount.
INSTALLATION INSTRUCTIONS

5.2 INSTALLATION INSTRUCTIONS--Convertible type


For authorized service personnel only
WARNING
(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation manual.
(2) Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our
standard parts. This installation manual describes for the correct connections so that the installation set
available from our standard parts should be used.
(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(4) Never cut the power cord, lengthen or shorten the cord, or change the plug.
(5) Also, do not use an extension cord.
(6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(7) Do not turn on the power until all installation work is done.

Be careful not to scratch the room air conditioner when handing it.
After installation, explain correct operation to the customer, according to the operating manual.
Let the customer keep this installation manual because it will be used when the room air conditioner is serviced
or moved.
5.2.1SELECTING THE MOUNTING POSITION 2. OUTDOOR UNIT

WARNING WARNING
(1) Install the unit where it will not be tilted by more than 5•
Install at a place that can withstand the weight of the (2) When installing the outdoor unit where it may be
indoor and outdoor units and install positively so that exposed to the strong wind, fasten it securely.
the units will not topple or fall.
(1) If possible, do not install the unit where it will be
exposed to direct sunlight.(If necessary, install a
CAUTION blind that does not interfere with the air flow.)
(2) Install the outdoor unit in a place where it will be
(1)Do not install where there is the danger of com- free from being dirty or getting wet by rain as much
bustible gas leakage. as possible.
(2) Do not install near heat sources. (3) Install the unit where connection to the indoor unit
is easy.
(3) If children under 10 years old may approach the (4) During heating operation, drain water flows from
unit, take preventive measures so that they can- the outdoor unit. Therefore, install the outdoor unit
not reach the unit. in a place where the drain water flow will not be
obstructed.(Reverse cycle model only)
Decide the mounting position with the customer (5) Do not place animals and plants in the path of the
warm air.
as follows: (6) Take the weight of the air conditioner into account
1. INDOOR UNIT and select a place where noise and vibration are
small.
(1) Install the indoor unit level on a strong wall, floor, ceiling (7) Select a place where the warm air and noise from
the air conditioner do not disturb neighbors.
which is not subject to vibration.
(8) Provide the space shown in Fig.2 so that the air
(2) The inlet and outlet ports should not be obstructed: the flow is not blocked. Also for efficient operation, leave
air should be able to blow all over the room. open three of the four directions front, rear, and both
(3) Install the unit near an electric outlet or special branch sides.
circuit. L2
Air inlet L3
500
(4) Do not install the unit where it will be exposed to direct (Servicing
sunlight. Air
inlet
space)

(5) Install the unit where connection to the outdoor unit is Air outlet
L1
easy.
(6) Install the unit where the drain pipe can be easily installed.
Series 36 42
(7) Take servicing, etc. into consideration and leave the Case
spaces shown in Fig.1. Also install the unit where the filter Distance I II III I II III
L1 open open 500 open open
can be removed. 500
L2 300 0 open 300 0 open
NOTE: The appearance may be different from models. L3 100 300 150 150 300 150
INSTALLATION INSTRUCTIONS

Fig. 1 Fig. 2
Floor console
may be different
1.5m

Left Right

For series 36,42

Note: For series 36, 42 no floor console type, the function


30 cm 1.5m 30 cm
or more below about floor console is invalid to the series.
or more
Under ceiling

Indoor unit Right

Left

30 cm 30 cm
or more 1.5m or more
Ceiling

2 cm
or more
INSTALLATION INSTRUCTIONS

5.2.2 STANDARD PARTS


The following installation parts are furnished.
Use them as required.
ACCESSORIES
Name and shape Q'ty Application Name and shape Q'ty Application

Cover plate (left) Tapping screw For fixing the wall


For series 24,28, 36,42
1 ( 4x20) 6 bracket.
the two cover plate are
For series 24,28,36,42
not available
no this part.
Cover plate (right)
Coupler heat insulator(large) For indoor side pipe
1 1 joint (Large pipe)

Tapping screw
( 4x10) 2 Coupler heat insulator(small) For indoor side pipe
1
joint (Small pipe)

Installation For positioning the


1
template indoor unit
Nylon fastener For fixing the drain
For under ceiling type. 1
hose
Anchor bolt
4 For suspending the Drain hose
1
indoor unit from ceiling
Spring washer
4
Non-adhesive tape
1
Special nut
4

VT wire
For fixing the drain
1 hose L 280mm
Pipe hole cover For series 24,28,36,42
1
VT wire is not available

Wall hole cover Remote Use for air conditioner


controller 1
1 operation

Main pipes Battery For remote controller


2
1 unit

Connecting cables Optional parts


1 Mark Parts name
A Adhesive tape

Cushion B Saddle (L.S) with screws


4
Connecting electric cable
C for indoor and outdoor
Drain-elbow Only for the heat pump D Drain hose
1 type
E Heat insulation material

Wall bracket For suspending the indoor F Piping hole cover


2 unit on the wall.For series
G Putty
24,28,36,42 no this part.
H Plastic clamp
INSTALLATION INSTRUCTIONS

5.2.3CONNECTION PIPE REQUIREMENT


Table 1

Series
Diameter Maximum
Maximum height
(between indoor CAUTION
Liquid side Gas side length and outdoor)
Install the drain hose at the rear; it should not be installed
on the top or right side.
36
9.52 mm 19.05mm 50 m 15 m
When the directions are selected, drill 80mm and 50mm or 150mm
dia. hole on the wall so that the hole is tilted downward toward the
outdoor for smooth water flow.
42 9.52 mm 19.05mm 50 m 15 m
Wall
6mm
INSTALLATION PROCEDURE
Install the room air conditioner as follows:

PREPARING INDOOR UNIT 2. DRILLING HOLES FOR ANCHOR BOLTS AND

INSTALLATION INSTALLING THE ANCHOR BOLTS


With a concrete drill, drill four 12.7 mm dia. Holes.(Fig.15)
1. REMOVE THE INTAKE GRILL
Fig. 15
Open the intake grill and remove the three or four or six screws.
(Fig. 3)

60 to 70mm
Machine screw
Fig. 3 Tapping screw

Tapping screw

12.7mm

Insert the anchor bolts into the drilled holes, and drive the pins
completely into the anchor bolts with a hammer. (Fig. 16)
Intake grill Fig. 16

Remark: The main unit can be wired before the indoor unit is
installed. Select the most appropriate installation order.
For series36,42 not the power plug, but 3-core connecting cable.

A. UNDER CEILING TYPE-THE ONLY WAY


Using the installation template, drill holes for piping and anchor bolts(for
holes).(Fig.12) A
40 B 40
247mm
720mm
326mm
147mm

3. INSTALLING BRACKETS
53 85

87.5mm Install the brackets with nuts, washers and spring


series A B 100mm
washers.(Fig. 17)
36 1920 1840
42 1920 1840
Fig. 17
1. DRILLING FOR PIPING
Select piping and drain directions. only have rear side(Fig.13)

Fig. 13
Rear (Install the drain hose
in the direction.)

Right Spring washer


Bracket
Special nut
INSTALLATION INSTRUCTIONS
381
68 16 21 28 26.5
5. INSTALL THE DRAIN HOSE
Select whether the drain hose will be connected to the left or right

4-R
side.(Fig.5)

5
2-R2.5
7.5
10

Insert the drain hose into the drain pan, then secure the drain hose
18

26.5 232
with a nylon fastener.(Fig.8)
232 26.5
Wrap the insulation (drain hose)around the drain hose connection.

18
(Fig.9)

10
2-R2.5

7.5
Be sure to arrange the drain hose correctly so that it is leveled lower
4-R
5

26.5 28 21 16 68
than the drain hose connecting port of the indoor unit.(Fig.20)
381
Fig. 20 Remove the hole cover.
4. INSTALLING INDOOR UNIT

Reset the hex bolts as shown in Fig.18.

Fig. 18
Hex bolt

Indoor unit 8 to 13mm

Arrange the drain hose Drain hose


lower than this portion
OK NO
When drain hose is arranged backward.Secure the drain hose with
Apply the indoor unit to the brackets.(Fig.19) the VT wire. (Fig. 21)

Fig. 19 Fig. 21
Piping hole
VT wire hole

Bracket Drain hose


Bolt

Indoor unit

Now, securely tighten the hex bolts in both sides.

5.2.4 GAS LEAKAGE INSPECTION


CAUTION
After connecting the piping, check the joints for gas leakage with gas leakage detector.

HOW TO CONNECT WIRING TO THE TERMINALS


A. For solid core wiring (or F-cable)(Fig.28A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.

B. For strand wiring(Fig.28B)


(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.
(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 28
INSTALLATION INSTRUCTIONS

Fig. 28
Screw with
B. Strand wire special washer
A. Solid wire
Round Round Screw with
special washer
Strip 25mm

terminal terminal
Loop

Strip 10mm
Terminal Round
board terminal
Wire

Insulation Wire

HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29

Fig. 29
Insulation tube

Cord clamp

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

Fig. 30

ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 5

Series 36 42

Connection MAX 3.5 3.5 Electric component box


cord
(mm2) MIN 2.5 2.5

Fuse capacity(A) 30 30

INDOOR UNIT SIDE


ELECTRICAL WIRING

CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit. Fig. 31
Erroneous wiring may cause burning of the electric Electric component box
parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection
cord with the cord clamp.(If the insulator is chafed,
electric leakage may occur.)
(4) Always connect the ground wire.

1. INDOOR UNIT SIDE Remove the four tapping


screws.
(1) Remove the electric component box.

CAUTION
Do not remove the screws. If the screws
are removed, the electric component
box will fall.
INSTALLATION INSTRUCTIONS

(2) Pull out the electric component box. ELECTRICAL WIRING

Fig. 32 WARNING
(1) Always use a special branch circuit and install a special
receptacle to supply power to the room air conditioner.
(2) Use a circuit breaker and receptacle matched to the
capacity of the room air conditioner.
(3) The circuit breaker is installed in the permanent wiring.
Always use a circuit that can trip all the poles of the
Electric component box
wiring and has an isolation distance of at least 3mm
between the contacts of each pole.
(4) Perform wiring work in accordance with standards so
(3) Remove the electric component box cover. that the room air conditioner can be operated safely
Fig. 33 and positively.
(5) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company
standards.

CAUTION
(1) The power source capacity must be the sum of the
room air conditioner current and the current of other
Base electrical appliances. When the current contracted
capacity is insufficient, change the contracted capacity.
Electric component box cover (2) When the voltage is low and the air conditioner is dif-
ficult to start, contact the power company the voltage
Remove the three tapping screws.
raised.

CAUTION 5.2.5TEST RUNNING


Be careful not to pinch the lead wires 1. CHECK ITEMS
between the electric component box
and base. (1) INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?


(4) Wiring
(2) Does each lamp light normally?
(1) Remove the cord clamp.
(3) Do not air flow direction louvers operate normally?
(2) Process the end of the connection cords to the
(4) Is the drain normal?
dimensions shown in Fig.34.
(3) Connect the end of the connection cord fully into the (2) OUTDOOR UNIT
terminal block.
(4) Fasten the connection cord with a cord clamp. (1) Is there any abnormal noise and vibration during operation?
(5) Fasten the end of the connection cord with the screw. (2) Will noise, wind, or drain water from the unit disturb the neighbors?
(6) The power cable and connecting are self-provided (3) Is there any gas leakage?

5.2.6 CUSTOMER GUIDANCE


Indoor Explain the following to the customer in accordance with the
1 2 3 unit
operating manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control
unit operations.
(2) Air filter removal and cleaning, and how to use air louvers.
Outdoor (3) Give the operating and installation manuals to the customer.
unit R S T N 1 2 3 Outdoor
unit
INSTALLATION INSTRUCTIONS

5.3 INSTALLATION INSTRUCTIONS-Duct type

Installation place
Avoid installing the air conditioner Install the unit at well ventilated Install the air conditioner firmly
near the place where possibility of place. on the foundation that can fully
inflammable gas leakage exists. support the weight of the unit.

Explosion (Ignition) may occur. If some obstacle exist, it may cause If not, it may cause vibration or noise.
capacity reduction or noise increase.

Select the place so as not to Snow protection work is It is advisable not to install the air con-
annoy neighbor with the hot air necessary where outdoor unit is ditioner at the following special place.
or noise. blocked up by snow. It may cause malfunction, consult the
sales dealer when you have to install
the unit on such a place.
The place where corrosive gas generates
(Hot spring area etc.)
The place where salt breeze blows
(Seaside etc.)
The place where dense soot smoke exists
The place where humidity is extraordina-
rily high
The place where near the machine which
radiates the electromagnetic wave
For details consult your sales dealer. The place where voltage variation is con-
siderably large

Electric work

The electric work must be burden on the authorized engineer with qualification for electric work and
grounding work, and the work must be conducted in accordance with electric equipment technical standard.
The power source for the unit is to be of exclusive use.
An earth leakage breaker should be installed.(This is necessary to prevent electric shock.)
The unit must be grounded.

When you change your address or the installation place

Special technology is required for removal or reinstallation of air conditioner, consult the sales
dealer. Besides, construction expense is charged for removal or reinstallation.

For inspection and maintenance


The capacity of air conditioner will decrease by contamination of inside of unit when it is used for
about three years although depending upon the circumstances under which it is used, and so in
addition to the usual maintenance service, special inspection/maintenance service is necessary.
It is recommended to make a maintenance contract (charged) by consulting your sales dealer.
INSTALLATION INSTRUCTIONS

5.3.1 Installation of the wired remote controlller


a. Remove upper part of wire PCB is mounted on lower part of wire
Remove upper part of wire controller controller, be careful not to damage
Upper part of wire
controller

Lower part of wire


controller

b. Install wire
(1) For exposed installation, use 2 wood screws(accessory).
(2) For recessed installation, use 2 wood screws(accessory).
Note: Try as far as possible a flat surface for installation. Don't use excessive
c. Indoor unit wiring Hint:
Connect terminals (A,B,C,D) on lower When make wiring, please
part of wire controller to terminals (A, keepa distance between wires
and power supply cord.
B,C,D) on PCB of indoor unit.
wiring from here Wire size
AB CD

Lower part of Cord kind Shield wire (4 core) (refer to Hint 3,4)
wire controller
Size 0.33mm2

Use shielede wires for telecommunication


between wire controller and indoor unit;
indoor unit and outdoor unit. Ground the
shield on one side.
Otherwise misoperation because of noise
may occur.
Signal wire is self-provided.
Upper part of Shielded wire
wire controller ground

Hint: Tread surface of the terminal well so that shielding may not contact other part.
d. Replace the upper part of wire controller
Be careful not to press the wiring.
Hint: 1. Switch box and cord for wiring are not supplied.
2. Don't touch PCB with hand.
INSTALLATION INSTRUCTIONS

5.3.2 Installation of outdoor unit


<Heat Pump model/Cooling Only model >
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING
INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS
INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.

a. Accessories Edging
"Edging" for protection of electric wires from an
opening edge.
b. Selection of the place of installation
Select the place of installation satisfying the following conditions and, at the same time, obtain
a consent from the client or user.
Place where air circulates.
Place free from heat radiation from other heat sources.
Place where drain water may be discharged.
Place where noise and hot air may not disturb the neighborhood.
Place where there is not heavy snowfall in the winter time.
Place where obstacles do not exist near the air inlet and air outlet .
Place where the air outlet may not be exposed to a strong wind.
Place surrounded at four sides are not suitable for installation. A 1m or more of overhead
space is needed for the unit.
Mount guide-louvers to place where short-circuit is a possibility.
When installing several units, secure sufficient suction space to avoid short circuiting.
(1) Open space requirement around the unit
Unit: mm
Air inlet •L3 Case I II III
Distance
• L2 •500
L1 open open 500
Air (Servicing L2 300 0 open
inlet space)
Air outlet L3 150 300 150
•L1

(2) Installation where the area with strong winds.


Install the unit so that the air outlet section of the unit must NOT be faced
toward wind direction.

c. Installation of outdoor unit


(1) Installation
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
(a) Concrete foundation
Unit Foundation anchor
Unit
Anchor bolt Concrete foundation

To fix by bolts

Note (1) Give enough room for the Note (1) Place the concrete foundation deep
concrete foundation to fix by anchor bolts. enough.
Install the unit so that the angle of inclination must be less than 3 degrees.
INSTALLATION INSTRUCTIONS

d. Refrigerant piping Flare connection Check joint


Service valve
Gas pipe
(1) Outline piping
Indoor Outdoor
unit unit
(2) Piping size Liquid
pipe Flare connection

Model 36 series 42 series

Gas piping 19.05(3/4")x1.0mm 19.05(3/4")x1.0mm


Liquid piping 9.52(3/8")x0.8mm 9.52(3/8")x0.8mm

_0.5
90+
Install the removed flared nuts to the pipes to be connected,
then flare the pipes.
(3) Limitations for one way piping length and vertical height difference.
One way piping length:less than 50m (for 36,42 series)

Vertical height difference:less than 30m (for 36,42 series).

Precautions for refrigerant piping


Do not twist or crush piping.
Be sure that no dust is mixed in piping.
Bend piping with as wide angle as possible.
Keep insulating both gas and liquid piping.
Check flare-connected area for gas leakage.
(4) Purging method ( the refrigerant is R407C)
To use vacuum pump 2-way valve
1 3-way valve
Detach the service port's cap of 3-way valve, the
valve rod's cap for 2-way valve and 3-way's, connect Gaugemanifold
the service port into the projection of charge hose For series 36,42
(low) for gaugemanifold. Then connect the projection
of charge hose (center) for gaugemanifold into
vacuum pump.
Vacuum pump

2
Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low) 2 Open
reach vacuum condition in a moment, check 1 again.

Vacuumize for over 15min. And check the level gauge


which should read -0.1 MPa (-76 cm Hg) at low
pressure side. After the completion of vacuumizing,
close the handle 'Lo' in gaugemanifold and stop the 3 Close
operation of the vacuum pump.
Check the condition of the scale and hold it for 1-2min.
If the scale-moves back in spite of tightening, make
flaring work again, the return to the beginning of 3 .
2-way valve

4 3-way valve

Open the valve rod for the 2-way valve to and angle
ofanticlockwise 90 degree.
Open Service port
After 6 seconds later, close the 2-way valve and 90•
90• 4 90• for 6 sec.
malethe inspection of gas leakage.
For series 36,42
INSTALLATION INSTRUCTIONS

5 If it does not stop gas leakage, discharge


In case of gas leakage, tighten
parts of pipe connection. If whole refrigerants from the serice port.
No gas leakage? After flaring work again and vacuumize,
leakage stops, then proceed 6
fill up prescribed refrigerant from the gas
steps.
cylinder.
6 2-way valve
Liquid pipe 9.52mm
Detach the charge hose from the service port, open 3-way valve
Gas pipe 19.05mm
2-way valve and 3-way. Turn the valve rod
anticlockwise until hitting lightly.
6
6 For series 36,42

7
To prevent the gas leakage, turn the service port's
cap, the valve rod'd cap for 2-way valve and 3-way's
a lottle more than the point where the torque
increases suddenly.

8
2-way valve
After attaching the each caps, check the gas
leakage around the caps. 3-way valve

For series 36,42


CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to
7 Valve rod cap
make all the refrigerant out, then charge the liquid refrigerant
7 Service port cap
into air conditioner according to the amount marked on the
name plate.

If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again
and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure
pressure-switch properly.

e. Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.

Precautions for Electric wiring


Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped
terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length
wires with less than 2% voltage drop.)

Item Circuit breaker Power source Earth leakage breaker


Phase Switch breaker Overcurrent protector wire size Switch Leak
Model (A) rated capacity (A) (minimum) breaker current

36,42 series
30 20 2.5mm2 30 30mA
(380-400V,3N~,50Hz) 3
INSTALLATION INSTRUCTIONS

(2) Wiring connection


Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is
supplied by 1 and 2 terminals.
Circuit breaker
Outdoor Earth leakage Indoor
unit breaker unit
TB1
R
S
T
N

TB2 HIGH VOLTAGE TB


1 1
2 2
3 3

2
Interconnecting
wires

(For 36,42 series(380-400V,3N~,50Hz))

WARNING
DO NOT CONNECT THE NEUTRAL WIRE N TO R , S OR T PHASE. INTERCONNECT-
ING WIRES MUST BE WIRED WITH SAME SYMBOLS ON THE TERMINALS OF BOTH
INDOOR AND OUTDOOR UNIT.INCORRECT WIRING CAUSE EQUIPMENT DAMAGE
OR FIRE.

(3) Wiring procedure


1) Remove set screws on the side before taking off the front panel toward the direction shown
in figure.
2) Connect wires to the terminal block correctly and fix the wires with a wire clamp equipped
near by the terminal block.
3) Route the wires in a proper way and penetrate the wires through the opening for electric
wiring on the side panel.

e. Test run

CAUTION
THIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION WHEN ELECTRIC
POWER IS SUPPLIED.
BE SURE TO EXECUTE "OFF" OPERATION BEFORE ELECTRIC POWER IS
DISCONNECTED FOR SERVICING.
This unit has a function of automatic restart system after recovering power stoppage.

(1) Before starting test run (for all Heat pump models)
Confirm whether the power source breaker (main switch) of the unit has been turned on for
over 12 hrs to energize the crankcase heater in advance of operation.
(2) Test run
Run the unit continuously for about 30 minutes, and check the following.
Suction pressure at check joint of service valve for gas pipe.
Discharge pressure at check joint on the compressor discharge pipe.
Temperature difference between return air and supply air for indoor unit.
INSTALLATION INSTRUCTIONS

5.3.3 Installation of indoor unit

(1) Preparation of indoor unit


Before or during the installation of the unit, assemble necessary optional panel etc. depending
on the specific type.
(2) Select places for installation satisfying following conditions and at the same time obtain
the consent on the part of your client user.
(a) Places where chilled or heated air circulates freely.
When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases,
suggest your client users to install air circulators.
(b) Places where perfect drainage can be prepared and sufficient drainage.
(c) Places free from air disturbances to the suction port and blowout hole of the indoor unit,
places where the fire alarm may not malfunction or short-circuit.
(d) Places with the environmental dew-point temperature is lower than 28 and the relative
humidity is less than 80%. (When installing at a place under a high humidity environment, pay
sufficient attention to the prevention of dewing such as thermal insulation of the unit.)
(e) Ceiling height shall have the following height.
Installation space

100 or 100 or
36series 42 series more
1000 or more
more

50 or more
Combination
with silent 416mm 416mm
panel
Obstacle Unit: mm

(a) Size of hole at ceiling and position of hanging bolts


<Combination with silent panel>
Unit: mm
(Hanging bolt position)

wrap dimensions) (Panel dimensions)

Dimensions
(Ceiling hole size)
70

A B C
nnection side)

Model
(Pipe co-

545

690

750

36 series 1406 1600 1660


75

(Ceiling ~ panel
30

57 A 137 42 series 1406 1600 1660


(Hanging bolt position)
B 30
(Ceiling hole size)
C
(Panel dimensions) (Ceiling ~ panel Hole-in anchor
wrap dimensions) Insert
Hole-in plug
(b) Hanger bolts installation
Use care of the piping direction when the unit is
installed.

Concrete

Hanging bolt M10


INSTALLATION INSTRUCTIONS

(5) Installation of indoor unit Hanging bolt


M10 nut
M10 washer
Fix the indoor unit to the hanger bolts.If required, it is
possible to suspend the unit to the beam, etc.
Directly by use of the bolts without using the hanger bolts. M10 spring washer
Main unit

Note
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with
the slot holes of hanging bracket.
Piping side
Adjusting to the levelness
Supply water
(a) Adjust the out-of levelness using a level or
Water level
by the following method.
Make adjustment so that the relation between 0~5 mm PVC hose
the lower surface of the unit proper and water (0~0.2")
Bring the piping side slightly lower.
level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the
float switch may occur.
Tap selection on blower unit (When the high performance filter is used.)
Taps of blower unit are set at the standard selection at the shipping from factory. Where
the static pressure is raised by employing such option as the high performance filter,
etc., change the connection of connectors provided at the flank of control box as shown
below.
Standard tap (at shipping) High speed tap
White White White Black
Control box side

Connector white
Connector white

Moter side

Moter side
Blue Blue Blue White
Red
White

Yellow Yellow Yellow Blue


Red Red Red Red

(6) Drain Piping


(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across
an elevation or making traps.
Good piping Inproper piping
Suspension
bolts 1.5m ~ 2m Avoid riding across an elevation

Air vent Keep free from traps

Do not pipe under water


Heat A downhill grade
insulation of 1/100 or more

(b) When connecting the drain pipe to unit, pay


suffcient attention not to apply excess force to Stage
the piping on the unit side. Also, fix the piping difference Drain hose
Drain socket part
at a point as close as possible to the unit.
Drain socket
(c) For drain pipe, use hard PVC general purpose VP 25 joint
Pipe cover(large) (field purchased)
pipe VP-25(I.D.1") which can be purchased [for insulation]
(accessory)
locally. When connecting, insert a PVC pipe Main unit

end securely into the drain socket before


VP 25
tightening securely using the attached drain Drain hose
Clamp (accessory)
(field purchased)
hose and clamp. Adhesive must not be used (accessory) Adhesion Pipe cover
connection of the drain socket and drain hose Pipe cover(small)
[for insulation]
(field purchased)
[for insulation]
(accessory). (accessory)
INSTALLATION INSTRUCTIONS

(d) When constructing drain piping for several units, position Secure the elevation as high as possible
(approx. 100 mm)

the common pipe about 100 mm below the drain outlet


of each unit as shown in the sketch. Use VP-30(11/4")
or thicker pipe for this purpose. A downhill grade of
1/100 or more
VP 30

(e) Be sure to provide heat insulation to hard PVC pipes of


indoor placement. 290~325mm

(Maximum local drain up dimension)


(f) Do not ever provide an air vent.
(g) The height of the drain head can be elevated up to a Drain hose
Right overhead

point 500 mm above the ceiling, and when an obstacle

600
exists in the ceiling space, elevate the piping to avoid
the obstacle using an elbow or corresponding gadget.
When doing this, if the stretch for the needed height is Joint for VP 25
(Local procurement)
higher than 500 mm, the back-flow quantity of drain at
the event of interruption of the operation gets too much
and it may cause overflow at the drain pan. Therefore,
make the height of the drain pipe within the distance
(h) given in the sketch below.
Avoid positioning the drain piping outlet at a place where
generation of odor may be stimulated. Do not lead the
drain piping direct into a sewer from where sulfur gas

Drainage Test

1 Conduct a drainage test after completion of the electrical work.


2 During the trial, make sure that drain flows properly through the piping and that no water
leaks from connections.
3 In case of a new building, conduct the test before it is furnished with the ceiling.
4 Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

1 Supply about 1000 cc of water to the unit through the air outlet using a feed water
2 pump.

Pour water into a convex joint.

Insert water supply hose


for 20 mm ~ 30 mm to
supply water.
(Insert hose facing
toward bottom.)
(In the electrical work has not been
Remove grommet.
Attached drain hose clamp
completed, connect a convex joint in the
Make sure to install
it back after test. Main unit Drain piping
drain pipe connection to provide a water
inlet. Then, check if water leaks from the
piping system and that drain flows through
Drain situation can be checked with transparent socket

- 45 -
INSTALLATION INSTRUCTIONS

(7) Installation work for air outlet ducts

Air conditioner main unit

Heat inlet duct


insulation (optional or Suction panel
Ceiling surface marketat item) (Silent panel)
B Special blowout A Blowout duct C special inlet (option)
(Option) (Optional or marketed item) (with air filter)

Hole for check

Calculate the draft and external static pressure and select the length, shape and blowout.
A Blowout duct

2-spot, 3-spot and 4-spot with 200 type duct are the standard specifications. Determine
the number of spots based on following table.
Note (1) Shield the central blowout hole for 2-spot.
(2) Shield the blowout hole around the center for 3-spot.
Limit the difference in length between spots at less than 2:1.
Reduce the length of duct as much as possible.
Reduce the number of bends as much as possible. (Corner R should be as larger as
possible.)
Bad example Bad example Good example

Use a band. etc. to connect the main unit and the blowout duct flange.
Conduct the duct installation work before finishing the ceiling.

(8) Connection of suction, exhaust ducts


State seeing from top of unit
Exhaust hole

Side fresh air inlet

(a) Duct connection position Rear fresh air inlet

i) Fresh air inlet Fig.1 Fig.2

Inlet can be selected from the side or rear faces depending on the working conditions.
Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted.
(Side inlet cannot be used.)
ii) Exhaust (Make sure to use also the suction.)
Use the side exhaust port.

- 46 -
INSTALLATION INSTRUCTIONS

5.4 Pay special care to the following and check after installation

Item to the checked Unproper installation may cause Check


Is indor indoor unit firmly installed? Unit might fall down, make vibration or noise.
Is gas leakage dheck performed? This may lead to gas shortage.
Is unit properly insulated? Dew or water drop may occur.
Is water drainage smooth? Dew or water drop may occur.
Is power voltage meet that stipulated on the nameplate? Problem may occur or parts got burned.
Is wiring and piping correctly arranged? Problem may occur or parts got burned.
Is unit safely grounded? There might be a danger of electric shock.
Is wire size correct? Problem may occur or parts got burned.
Are there any obstacles on air inlet and outlet grill of This may cause poor cooling.
indoor and outdoor unit?
Is record made for piping length and refrigerant It is hard to control refrigerant charging
charging amount? amount.

- 47 -
High static pressure duct unit:

3. Preparation before installation


(1) The position relation among hoisting screw (unit: mm)

360 1270
250
853

794
Down side

Up side 1103

(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling)
Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire
(wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that
after installation, they can be immediately connected with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even
and flat and prevent the ceiling from vibration. For details, please consult to the builder.

(3) Hanger bolts installation


Use care of the piping direction when the unit is installed.
(Use M10 screw bolt)
Hole-in anchor Insert
In order to bear the weight of the unit, for existed Hole-in plug
ceiling, using foundation screw bolt, for new ceiling,
using burying embedded screw bolt, burying screw
bolt or spot supplied other parts.
Concrete
Before going on installation, adjust the gaps with ceiling.
Hanging bolt M10
4. Installation of indoor unit Hanging bolt
M10 nut
M10 washer
Fix the indoor unit to the hanger bolts.
If required, it is possible to suspend the unit to the beam, etc.
Directly by use of the bolts without using the hanger bolts.
Main unit M10 spring washer

Note
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot
holes of hanging bracket.

Adjusting to the levelness Piping side


Supply water
(a) Adjust the out-of levelness using a level or by
the following method. Water level

Make adjustment so that the relation between 0~5 mm PVC hose


the lower surface of the unit proper and water (0~0.2")
Bring the piping side slightly lower.
level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float
switch may occur.

5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an
elevation or making traps.

Good piping Inproper piping


Suspension Avoid riding across an elevation
bolts 1.5m ~ 2m
Air vent Keep free from traps

Do not pipe under water


Heat A downhill grade
insulation of 1/100 or more

(b) When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping
on the unit side. Also, fix the piping at a point as close as possible to the unit.

Stage
difference Drain hose
(c) For drain pipe, use hard PVC general purpose pipe Drain socket part
VP-25(I.D.1") which can be purchased locally. When
Drain socket
connecting, insert a PVC pipe end securely into the VP 25 joint
Pipe cover(large) (field purchased)
drain socket before tightening securely using the [for insulation]
Main unit (accessory)
attached drain hose and clamp. Adhesive must not
be used connection of the drain socket and drain
Drain hose VP 25
hose (accessory). Clamp (accessory)
(field purchased)
(accessory) Adhesion Pipe cover
[for insulation]
Pipe cover(small) (field purchased)
[for insulation]
(accessory)
(d) When constructing drain piping for several units, Secure the elevation as high as possible
position the common pipe about 100 mm below (approx. 100 mm)

the drain outlet of each unit as shown in the sketch.


Use VP-30(11/4") or thicker pipe for this purpose.

(e) The stiff PVC pipe put indoor side should be heat insulated. A downhill grade of VP 30
1/100 or more

(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain
hose directly into drainage, where the gas with sulfur may be generated.
(g) Backwater bend
Because the drain spout is at the position, which negative pressure may occur. So with the rise of water
level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a
backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint.
The backwater bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
2H 1H

H1=100mm or the static pressure of air sending motor


H2=1/2H1 (or between 50~100mm)
Drainage Test

1 Conduct a drainage test after completion of the electrical work.


2 During the trial, make sure that drain flows properly through the piping and that no water leaks
from connections.
3 In case of a new building, conduct the test before it is furnished with the ceiling.
4 Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

1 Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
2 Check the drain while cooling operation.

6. Installation of air suction and discharging duct

muffler cavity (air sending)


Enlarging chart of
Sacking joint profile chart A
Vibration resistance hook
Insulation A Air volume adjuster

Air conditioner Ceiling


Air outlet main unit
Air suction grille with air filter
Checking meatus

Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation
of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing
and outer static pressure, and choose the discharging duct with proper length and shape.
The length difference among every duct is limited below 2:1.
Reduce the length of duct as possible as can.
Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main unit and the flare part of air
discharging duct. Perform duct installation work, before the fitment of ceiling.

Bad example Bad example Good example

7. Calculation method of the dimension of the simple quadrate air duct


Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of
the air duct is fixed as 250mm, as shown below:
Air volume Duct(mmxmm) Air volume Duct(mmxmm)
Air conditioner 1200m3/h
A A 2400m /h
3
250x560 250x310
(40m3/min) (20m3/min)
300m3/h
B 600m /h
3

(10m3/min)
250x190 (5m3/min) 250x120

B HDU-42H03/H HDU-24H03/H
A
A Static pressure box Equipped with HDU-28H03/H
air filter (bought)

The calculation of duct resistance (the simple calculation is as follow table)

Straight part Calculate as per 1m length 1Pa, 1Pa/m


Bend part Each bend takes as a3~4m long straight duct
Air out part Calculate as 25Pa
Static pressure box Calculate as 50Pa/each
Air inlet grille (with air filter) Calculate as 40Pa/each

The chosen chart of simple duct


Note:1Pa/m=0.1mmAg/m

Shape Square duct Shape Square duct


Item Item
Dimension Air volume Dimension
Air volume
3 3 3 3
m /h(m /n) (mmxmm) m /h(m /n) (mmxmm)
100 250 x 60 1,800(30) 250 x 430
200 250 x 90 2000 250 x 470
300 250 x 120 2400 250 x 560
400 250 x 140 250 x 650
3,000(50)
500 250 x 170 3,500 250 x 740
600(10) 250 x 190 4,000 250 x 830
800 250 x 230 4,500 250 x 920
1,000 250 x 270 5,000 250 x 1000
1,200(20) 250 x 310 5,500 250 x 1090
1,400 250 x 350 6,000(100) 250 x 1180
1,600 250 x 390
8. The attentive matters in installation of air suction and discharging duct
Recommend to use anti-frost and sound-absorbing
duct. (locally bought) Special air discharging outlet
The duct installation work should be finished Use screw bolt to fix
before the fitment of ceiling.
The duct must be heat insulated.

The specific air-discharging outlet should be installed at Duct


the place where the airflow can be reasonably distributed.
The surface should leave a checking meatus for checking
and maintenance. Air
Air

9. The examples of improper installation


Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular
outer air mass, strong wind and sunshine, the humidity is increased.
There may be water drop on the outside of duct. For cement and other new constructions, even if
not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber
to perform heat preservation to the whole. (use iron net to bind the glass fiber)
Maybe exceeding the unit operation limit (for example: when indoor dry bulb temperature is 35 C,
wet bulb temperature 24 C), it may lead to overload of compressor.
Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction,
when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow,
leading to water leakage.

Air discharging fan


Improper example
10. The operation method of fan controller
Through the fan controller switch in the electric box, the air volume of this unit can be continuously
adjusted.
It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment).
The air volume set should be in the operation air volume range.
Figure I shows the position of fan controller in the electric box and operation method.
After finishing the electric work, perform test run. According to the main points in Figure II making the
chosen switch No. accordant. And confirm if it reaches the needed air volume.
Note:
1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the
power supply.
2) Do not set the dial at the position less than 1.
3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity
number may exceed the permitted operation capacity range, so it is impossible to operate.
4) When delivering from factory, the capacity number of fan controller is set at “No.5”.

Rotate this switch


High Condition of standard air volume
(capacity number
setting: Low (air volume 100Pa)
No. 1 ~ No. 8)
200 • •

• •

• • Example of
• duct
150 •
Outer static pressure Pa


Once the fan controller 100


has trouble, this linker
can perform emergency •
assistant control. When
this linker is connected
to the linker from the 50
PCB, it can operate with
total load.

When this linker is 0


26 30 34 35 40 43
connected to the linker
from the PCB, through Lower limit Upper limit
the fan speed adjustment
panel to adjust speed.
Figure 1 Standard air volume(m3/min) Figure 2

The example of the method of choosing capacity number:


3
1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m /min
as working condition point, according to Figure II “The characteristic chart of air volume”, the capacity number
of fan controller is No. 2.
3
2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m /min as
working condition point, according to Figure II “The characteristic chart of air volume”, the capacity number
of fan controller is No. 4.
11. Refrigerant pipe
[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause
water leakage.]
The outdoor unit has been charged with refrigerant.
When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,
use spanner and torque spanner together.
When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use
hand to twist 3-4 rings, then fasten with spanner.
Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.
Only use seal cushion to bind the joint part of air pipe and heat insulation parts.

Paste the refrigerant oil here Middle size seal cushion (accessory)
(Use seal cushion to
bind the pipe joint)

Torque spanner
Clamp

Heat insulation (accessory)


Spanner
(for liquid pipe)
Heat insulation (accessory)
Pipe joint (for gas pipe)
Cone nut Gas pipe
Liquid pipe

Liquid pipe Gas pipe Electric box


Upper

Air inlet Air outlet


310

Down side
30

Drain hose connection mouth


VP25 PVC pipe

Specification of pipe Tighten torque Cone dimension Cone


(mm) A (mm)

9.52 3270~3990 N.cm 45 2


12.0~12.4
(333~407 kgf.cm)
90 0.5
A
15.88 9720~11860 N.cm
22.9~23.3
(990~1210 kgf.cm)
Other instruction
1. Power supply
The air conditioner must use a special power circuit. The user should provide by himself with
special switch (25A~30A), grounding wire. The wiring should be done by a qualified electrician
according to the wiring rules specified by national standard
An creepage breaker should be installed.
The grounding wire and null wire of the power cord should be strictly separated. It is incorrect to
connect the null wire with grounding wire.

2. Cut and flaring method Flarer


A
Use pipe cutter to cut the pipe, the burrs must be removed.
After inserting the flarer, perform flared nut.

Pipe diameter Dimension A (mm)


Liquid pipe 9.52mm (3/8”) 1.0-1.2
Gas pipe 19.05mm (3/4”) 1.4-2.2
Gas pipe 15.88mm (5/8”) 1.4-2.2

Correct Incorrect

Slant Broken Burrs Uncompleted Too long

Test run
The following items must be noticed carefully during installation. After finishing installation,
performing checking.

After installing the refrigerant pipe, drain hose and electric wire properly, perform test run to ensure
the system not have trouble.

Test run

(1) Open the stop valve of gas pipe.


(2) Open the stop valve of liquid pipe.
(3) Press ON/OFF button to start operation, use wire controller to set to Cooling operation.
(4) Confirm the function of the unit according this manual.
PARTS AND FUNCTIONS

6.Parts and functions


Cassette type Indoor unit :
Discharge unit (built in)
In cooling operation,to
discharge the water Drain Hose
from inside the room.

Swing fender
(located in the outlet)

Refrigerant pipe
Cable line
Outlet Earthing line

Air filter
(located in the suction grill)
Remote Controller

Suction grill

Convertible type Indoor unit :

Remote control PCB


Outlet grill assy

Inlet grill assy 1320X715X235(AXBXC)


Electric box assy

- 48 -
PARTS AND FUNCTIONS

Duct type(mid static pressure)

Duct
Air outlet

Air inlet

For series 36, 42

Outdoor unit

Air inlet

Air outlet
Compressor (inside)

Compressor
(Inside of unit)

For series 36, 42

- 49 -
High static pressure

Air outlet

Duct

Duct

Drainpipe

Air inlet
7.Remote controller functions

Remote controller 4.Operation MODE


28
29 27 Used to select operation mode.
30 26 Every time you press MODE button, operation mode
25
changes according to following sequence:
31 B A

32 24
33 23 AUTO COOL DRY HEAT FAN
34 22
A
U
T
35 O
21
36
M D
OFF

20
5.HEALTH Button
19
Used to set health mode, if the unit has the negative ion function
1 TEMP
and oxygen bar function.
ON
2
SWING
OFF FAN
18 6.CLOCK Button
3 Used to set correct time.
4
MODE SLEEP
17 7.CLOCK Button
HEALTH FRESH
16 Used to select TIMER ON, TIMER OFF.
5
CLOCK SET (Note: if time of TIMER ON is the same as TIMER
6 15 OFF,TIMER ON/OFF cannot be set)
TIMER HIGH/SO
7 14
8. FILTER Button
FILTER
8 13 Used to set up/down function of filter.
RESET CODE LIGHT LOCK
12 9. CODE Button
9 11 Used to select code A or B, for this unit, the code is A.
10 10.RESET Button
Press this button by using a sharp article to resume
the correct operation of the remote controller in case
of need, i.e. for example in case of malfunctions due
to electromagnetic noise.
11.LOCK Button
Used to lock operation button and LCD display
1.TEMP Setting Button contents: by pressing this button, other buttons comes
(Used to set temperature. Setting ranges: out of function and lock state display appears; if you press
16 C to 30 C) it again, lock state will be no more active and lock state
In Up/Down function, for controlling up and display will disappear.
down filter. 12.LIGHT Button
Used to light the control panel (only for cabinet unit)
2.SWING Button
If you press this button once, auto swing will 13.Up and down Button
be activated. Used to set TIMER and CLOCK up or down.
If you press this button again, the louver will 14.HIGH/SO Button
fix in the present position. Used to select HIGH or SOFT operation.
3.Power ON/OFF Button 15.SET Button
Used to confirm TIMER and CLOCK settings.
Used for unit start and stop
16.FRESH Button
After power on, the LCD of remote controller Used to set fresh mode, the unit will draw in fresh air.
will display the previous operation state (except 17.SLEEP Button
for TIMER,SLEEP and SWING state). (The clock must be corrected before setting sleep
function)
Used to set sleep mode.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating.
2.HIGH/SO button
This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high
functon" will be cancelled automatically after 15 minutes running.
18.FAN Button The distance between the remote controller and the receiver
should be max 7m and there should be no obstacle between them.
Used to select fan speed:LOW,MID,HIGH,AUTO. Do not throw the remote controller; prevent it from being
19.TIMER OFF Display damaged.
20.CLOCK Display When operating the remote controller in an area where
electronically controlled lights are installed or wireless handsets
21.FILTER Display are used, please move closer to the indoor unit as the function
22.TEMPERATURE Display of the remote controller might be affected by signals emitted
23.AUTO SWING Display by the above mentioned equipments.
24.HIGH/SO Display
25.SIGNAL SENDING Display Battery loading
26.FRESH AIR Display Battery loading
27.ELECTRICAL HEATING Display

*
Batteries are fitted as follows:

*
*
28.Some other buttons

*
Remove the battery compartment lid
All these functions are not available now. Slightly press and disengage the battery compartment lid marked
with ì î and then hold the remote controller by the upper
29.HEALTH Display
section and then remove the battery compartment lid by pressing
Displays when healthy run function is set. in the direction of the arrow as shown in the figure above.
30.DEHUMIDIFICATION Display
Loading the battery
31.Operation MODE Display Ensure that batteries are correctly placed in the compartment
as required for positive and negative terminals.
AUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN

Replacing the battery compartment lid


The battery compartment lid is reinstalled in the reverse
32.SLEEP State Display sequence.
33.BATTERY Energy Display
Display review
Notify the user when it is time to change Press the button to see if batteries are properly fitted. If
the batteries. no display appears, refit the batteries.
34.LOCK State Display Confirmation indicator
35.FAN SPEED Display
If no indication is displayed after press ON/OFF button,
LO
reload the batteries.
MID Caution:

HI
If the remote controller does not operate as designed after
fitting new batteries of the same
AUTO
type, press the Reset button (marked ) with a pointed article.
AUTO
Note:
It is recommended that the batteries be removed from the
36.TIMER ON Display compartment if the remote controller is not used for an extended
period.
Remote Controller' Operation The remote controller is programmed for automatic test of
When in use, direct signal transmission operation mode after the batteries are replaced. When the test
head to the receiver placed on the indoor is conducted, all icons will appear on the screen and then
disappear if the batteries are properly fitted.
unit

Clock Set MODE SLEEP

When unit is started for the first time and after replacing batteries in remote HEALTH FRESH

controller, clock should be adjusted as follows: CLOCK SET

1.Press CLOCK button, clock indication of " AM " or " PM " flashes. 1 TIMER 2 HIGH/SO 3
2.Press or to set correct time. Each press will increase or decrease FILTER

1 min. If the button is kept pressed, time will increase or decrease quickly.
RESET CODE LIGHT LOCK

3.After time setting is confirmed, press "SET" : AM or PM stop flashing,


while clock starts working.
Note:AM means morning and PM means afternoon.
Fan Operation 1.Unit start
Press ON/OFF button to start your air conditioner.
Previous operation status appears on LCD (except for
TIMER, SLEEP, and SWING setting).

2.Select operating mode


Press MODE button. At each press, operation mode
changes as follows:
A

AUTO COOL DRY HEAT FAN

A
U
T
O
Then select FAN

TEMP 3. Adjust fan speed


ON
Press FAN button. At each press, fan speed changes as
SWING 4 OFF FAN
3 follows:
MODE
1 SLEEP

HEALTH FRESH
2
LOW MID HIGH
CLOCK SET

TIMER HIGH/SO
Air conditioner will run at the selected fan speed.
FILTER When in AUTO mode, unit will adjust fan speed
RESET CODE LIGHT LOCK
according to room temperature automatically.

4. Unit stop
Press ON/OFF button to stop unit.

About FAN mode


When the air conditioner runs in FAN mode,
it is not possible to select AUTO FAN or to
set temperature.
AUTO, COOL , HEAT and DRY Operation
1. Unit start
A
Press ON/OFF button,unit starts.
Previous operation status appears on LCD (except for TIMER,
SLEEP and SWING setting)
A
U
T
O
2.Select operation mode
Press MODE button. At each press, operation mode changes
as follows:
TEMP

3 ON AUTO COOL DRY HEAT FAN


3
SWING
OFF FAN
5 1 4
MODE SLEEP Then select AUTO run or select COOL operation or
2 HEALTH FRESH
select DRY operation or select HEAT operation
CLOCK SET
3.Temperature setting
TIMER HIGH/SO Press TEMP button.
FILTER
Every time the button is pressed, temp. setting increases
1 C; if the button is kept pressed, temp. setting will increase
LIGHT LOCK
quickly.
RESET CODE

Every time the button is pressed, temp. setting decreases


1 C, if the button is kept pressed, temp. setting will decrease
quickly.
Set proper temperature
4.Adjust FAN button
Press FAN button. At each press, fan speed changes as follows:
A
U
T
O

AUTO LOW MID HIGH


COOL operation starts
when room temp.is
higher than temp. Air conditioner will run at the selected fan speed.
setting.
Ultra-low air flow
5. Unit stop
Temp. setting +2 C Press ON/OFF button,unit stops.
Temp.setting

On reaching temp.setting
+2 C, unit will run in mild
DRY mode.

In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner
will select COOL, HEAT or FAN mode automatically according to the room temperature.
In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently
at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will
only run FAN operation.
In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.
Adjusting air flow direction

AUTO SWING AUTO SWING

Press SWING button.


Up and down airflow varies upwards When the automatic swing louver moves to the proper
and downwards. Left and right airflow angle, press SWING button can fix the airflow direction.
varies left and right sides.

Always use SWING button on the remote


controller to adjust flaps. Adjusting them by hand
A may result in air conditioner's abnormally running.

In COOL or DRY mode, do not leave the louver in


A
U
T
O downward position for a long time, as the water
vapor close to the grille may condense and water
may drop from the air conditioner.
TEMP

ON
OFF
SWING FAN Please carefully set temperature when children,
MODE SLEEP old or infirm people ues the air conditioner.
HEALTH FRESH

CLOCK SET
In case of great humidity, If the vertical flaps
TIMER HIGH/SO are completely turned towards left or right, the
louver will drop water.
FILTER

RESET CODE LIGHT LOCK


Never adjust the louver directly by hand, as this
could make it work abnormally.If the louver work
abnormally, stop unit, restart and adjust the louver
by remote controller.

After unit stops:


Displays on the LCD disappear.
All indicators on the indoor unit go out.
Swing louver automatically close the air outlet.

Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful
for a better air circulation
As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for
a better air circulation.
Be careful not to catch a cold when cold air blows downward directly.
Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make
you sleep more comfortably.
Before using this function, the clock must be set.

Use of SLEEP function


After the unit's start, set running mode and then press SLEEP button once to make the air conditioner
have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button
/ : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1
hour: "xh" and "OFF" indications appear on the display.

Operation Mode
1.In COOL, DRY mode SLEEP RUN BEGINS SLEEP RUN STOPS
One hour after sleeping operation start, the temperature about 6 hrs
is 1 C higher than the setting one. After another hour,
temperature rises 1 C: sleep run continuously for another increase 1 C
6 hours and then stops. The actual temperature is higher
than the setting one which is to prevent from being too 1 hrs increase 1 C
cold to your sleep.
SETTING T SHUT DOWN
2.In HEAT mode
One hour after sleeping operation start, the temperature In COOL,DRY mode
is 2 C lower than the setting one. After another hour,
temperature decreases by 2 C more. Temperature will
automatically rise by 1 C after another 3 hours'
continuous operation. The actual temperature is lower SETTING T SHUT DOWN
than the setting one which is to prevent from being too
1 hrs decrease 2 C
hot to your sleep.
1 hrs
decrease 2 C
3.In AUTO mode. about 6 hrs
The air conditioner will run in corresponding sleep 3 hrs increase 1 C
operation according to the automatically selected
operation mode. SLEEP RUN STOPS
SLEEP RUN BEGINS
In HEAT mode

A
U
T
O

OFF

Notes:
TEMP

After setting SLEEP function, it is not possible to set clock. ON


OFF
SWING FAN

If set-sleep time does not reach 8 hours, unit will automatically stop operation MODE SLEEP

after set time is reached. HEALTH FRESH

CLOCK SET

Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first, TIMER HIGH/SO

then set SLEEP. After set SLEEP function, the TIMER function cannot be FILTER

set. RESET CODE LIGHT LOCK


Timer ON/OFF Function
Set clock correctly before starting TIMER operation

1.Unit start
A After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:

ON OFF ON OFF blank


TEMP AM
12:00 PM 12:00 AM
12:00 PM 12:00
ON TIMER ON TIMER OFF TIMER ON-OFF
SWING
OFF FAN
1 Then select TIMER mode as needed (TIMER ON or TIMER OFF).
MODE SLEEP Now ON or OFF will flash.
HEALTH FRESH
3.TIMER setting (press time adjust buttons )
CLOCK SET Every time the button is pressed, time increases 10 minuts.
If the button is kept pressed, time changes quickly.
TIMER 3 HIGH/SO 4
Every time the button is pressed, time decreases 10 minuts.
2 FILTER If the button is kept pressed, time changes quickly.
It can be adjusted within 24 hours at will.
LIGHT LOCK
RESET CODE
4.Confirm setting
After setting correct time, press SET button to confirm time. Now
ON or OFF stop flashing.
Time displayed: unit starts or stops at X hour X min (TIMER ON
or TIMER OFF)
5.Cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.

Hints:
After replacing batteries or if a power failure occurs, TIMER setting
must be reset.
Remote controller has memory function. When you use TIMER
mode next time, just press SET button after mode selection if timer
setting is the same as the previous one.

Note:
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time,
just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you
can adjust clock). 5 seconds later, the display will show TIMER time again.
Timer ON-OFF Function
Set clock correctly before starting TIMER operation
1.Unit start
After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
A
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:

ON OFF ON OFF blank


OFF
AM
12:00 PM 12:00 AM
12:00 PM 12:00
TIMER ON TIMER OFF TIMER ON-OFF
TEMP

ON Then select TIMER ON-OFF mode. ON will flash.


SWING
OFF FAN
1 3.Time setting for TIMER ON
MODE SLEEP
Press time button
HEALTH FRESH
Every time the button is pressed, time increases 10 minuts.
If the button is kept pressed, time will changes quickly.
CLOCK SET

Every time the button is pressed, time decreases 10 minuts.


2 TIMER
3HIGH/SO
6 If the button is kept pressed ,time will changes quickly.
It can be adjusted within 24 hours at will.
4FILTER 5 AM refers to morning and PM refers to afternoon.
RESET CODE LIGHT LOCK
4.Timer confirming for TIMER ON
After setting correct time, press TIMER button to confirm time. Now
ON stops to flash, while OFF starts flashing.

Time displayed : unit starts at X hour X min.


5.Timer setting for TIMER OFF
Press time buttons and follow the same procedures in " Time setting
for TIMER ON"

6.Time confirming for TIMER OFF


After time setting, press SET button to confirm time. OFF stops to flash.
Time displayed: unit starts at X hour X min.

7.Canel TIMER mode


Just press TIMER button several times until TIMER mode disappears.
According to the time setting sequence of TIMER ON and TIMER OFF,
either start-stops or stops-start can be realized.
If the time setting of TIMER ON is the same as TIMER OFF, TIMER
ON-OFF function cannot be set.
Filter Up/Down
(Only for AB182ACBEA)
After the air conditioner has operated for a certain period, dust has
accumulated on the filter, and the filter up/down function can be used
to clean it.
A

1.Whether unit starts or stops, continuously press FILTER


button for 3 seconds, and enter the filter up/down waiting
status (when unit stops, the yellow TIMER indicator flashes,
and filter and clock indication are displayed on the remote
controller. Only the FILTER button, the temperature buttons
" " " " and time buttons are active).
TEMP
2.Press temperature " " button or time " " button in filter
ON up/down waiting status: the up/down mechanism makes
SWING
OFF FAN the filter moving downward and does not stop until it has
reached the maximum limit.
MODE SLEEP

HEALTH FRESH
3.Press temperature " " button or time " " button in filter
up/down waiting status: the up/down mechanism makes
CLOCK SET the filter to moving upward till near the surface board and
then automatically adjusts it to reset (when adjusting to reset,
TIMER HIGH/SO
it will not be controlled by the remote controller till the adju-
FILTER
stment is finished).

RESET 1
CODE LIGHT LOCK

4.During moving downward, press temperature " " button


or time " " button: moving stops.

5.During moving downward, press temperature " " button


or time " " button: moving stops.

6.Continuously press FILTER button 3 seconds again to


cancel the filter up/down waiting mode (unit stops, the
yellow timer indicator stops flashing, the filter goes back to
the original position, the remote controller goes back to off
status and only clock is displayed).

Note:
If the filter does not thoroughly go back to the original position, only needs to
operate several times repeatedly.
" High mode " Operation
Outline of operation in "High Mode"
This function is suitable when the set temperature must be
reached in the shortest delay.
A The button "HIGH/SO", referred to this function, is effective
in Cooling/Heating mode (not in Auto/Dry/Fan modes).

A
U
T
O

ON
TEMP

ON Press the HIGH/SO button noce


SWING
OFF FAN The indication appears on the display of the remote
controller and operation in "High Mode" starts.
MODE SLEEP
The AUTO fan speed is automatically set and the corresponding
HEALTH FRESH indication is also displayed.
CLOCK SET

TIMER HIGH/SO

FILTER 1
RESET CODE LIGHT LOCK
OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is displayed
on the remote controller. If you press the button once again,
the indication disappears, regular operation is restored and fan
speed goes back to the mode set before "High Mode" operation.

NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature
may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular
operation is automatically restored.
" Soft mode " Operation

Outline of operation in "Soft Mode"


A
U
T
O
Operation in "Soft Mode", more silent, is suitable when noises
OFF
should be reduced, e.g.. for reading or sleeping.
The button "HIGH/SO", referred to this operation, is effective
in Cooling/Heating mode (not in Auto/Dry/Fan modes).
TEMP

ON
SWING
OFF FAN
ON
MODE SLEEP
Press the HIGH/SO button twice
HEALTH FRESH
The indication appears on the display of the remote
CLOCK SET controller and operation in "Soft Mode" starts.
The AUTO fan speed is automatically set and the corresponding
TIMER HIGH/SO
indication is also displayed.
FILTER 1
RESET CODE LIGHT LOCK

OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is disappears
from the remote controller's display. If you press the button
once again, regular operation is restored and fan speed goes
back to the mode set before "Soft Mode" operation.

NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature
may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular
operation is automatically restored.
Wired controller YR-E12 functions:
Buttons and functions of the wired controller

CLOCK MODE
Used to adjust time. Used for select
indoor operation
TIMER mode.
Used to set timer
mode. FAN SPEED
CHECK Used for select indoor
Auto-diagnostic air flow.
button. SWING
Used for setting
indoor swing mode.
HEALTH

HEALTH
C
F SET RECOVERY
Used for setting
indoor health
CHECK function.

TEMP + -
Used for changing
+- set temperature.
stands for time plus/minus,
used to adjust time. RECOVERY
used to switch
FILTER over air-
Filter-cleaned button. exchanging mode.

RESET
POWER ON/OFF Reset correct
Used for unit start and mode button.
stop.

Cautions: Note:
On cooling only unit, heating The above information is the explanation of
mode is not available. the displayed information therefore varies
with those displayed in actual operation.
Buttons function:
MODE:used for select indoor operation mode.
FAN:used for select indoor air flow.
SWING:used for setting indoor swing mode.
HEALTH:used for setting indoor health function.
TEMP + -:used for changing set temperature.
CLOCK:used to adjust time.
+、-:stands for time plus/minus, used to adjust time.
TIMER:used to set timer mode.
RECOVERY:used to switch over air-exchanging mode.
CHECK:auto-diagnostic button.
FILTER:filter-cleaned button.
RESET:reset correct mode button.

Display description:
[MODE] [AUTO]:auto operation mode
[MODE] [FAN ONLY]:air-throwing mode
[MODE] [COOL]:Cooling operation mode
[MODE] [DRY]:Dehumidification mode
[MODE] [HEAT]:Heating operation mode
[MODE] [HEAT] [TES]:In heating mode, auxiliary electric heater is running. Only when the unit
with auxiliary electric heater is in auxiliary electric heating mode, it will display.
[FAN] [AUTO]:auto fan running
[FAN] [HIGH]:high fan speed
[FAN] [MED]: medium fan speed
[FAN] [LOW]: low fan speed
[FAN] [FIX]: fixed fan speed, it will display only when fixed fan speed is requested to main indoor
unit.
[CENTRAL]: central control mode
[OPERATION] :running mode
[STAND BY] : waiting mode
[PRE-HEAT] : pre-heating mode
[DEFROST]: defrosting mode
[FILTER] : request of filter to be cleaned
[HEALTH]:health function
[UNIT NO.]
[CEN.ADD]:central control address, the address number will display on “88”
[SYS.ADD.]:system address, the address number will display on “88”
[CHECK]:auto-diagnostic, trouble shooting
[DEMAND]:compulsory operation function, when it works, [CENTRAL] will flash
[SWING]:swing mode
[ROOM TEMP.]:indoor ambient temperature
[SET TEMP.]:set admired temperature
[TIMER][ON] :timer function is on, it will switch over in the sequence below:
[ON][OFF] → [ON][OFF][DAILY] →[ ]
[TIMER][OFF] :timer function is off
[TIMER][ON][OFF] :timer function ON-OFF
[TIMER][ON][OFF][DAILY]:timer ON-OFF will switch over in turn daily
[CLOCK]:clock display, the displaying time is the current time of the clock.
[UP]、[DOWN]:indicator of filter elevating
[VENTILATION][AUTO]:auto ventilation mode
[VENTILATION][RECOVERY]:fully heat exchanging ventilation mode
[VENTILATION][NORMAL]:normal ventilation mode

FAN ONLY OPERATION:


1)Start up operation: press the button of ON/OFF, the system will start up, and will display
[MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”.
2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch
over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY].
Select [FAN ONLY].
3)Select fan speed: press FAN button, then you see in the display section [FAN] switch over in
below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed.
4)Power off: press ON/OFF button, indoor unit will be powered off, there are only time and the
ambient temperature in the screen.
AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation

1) Start up operation: press the button of ON/OFF, the system will start up, and will display
[MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”.
2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch
over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY]. Select
[FAN ONLY].
3) Change set temperature: press TEMP + or – every time, [SET] will display, and set
temperature will increase/reduce 1℃(F).
4) Select fan speed: press FAN button, then you see in the display section [FAN] switch over in
below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed.
5) Select [SWING]: press [SWING] button,swing function is valid. Press again, swing function is
invalid.
6) Set [HEALTH]: used to set the indoor health function. Press it once, [HEALTH] will display in
the display section, then indoor health function is valid. Press it again, [HEALTH] will disappear,
then the health function is invalid.
This function is valid only for the unit with health function.
7) Power off: press ON/OFF button, indoor unit is powered off. There are only time and the
ambient temperature in the screen.

Set TIMER operation:

Adjust clock: when powered on, for the first time to set timer function, the clock will be adjusted.
Press “CLOCK” button, and set the current clock. Now, “CLOCK” will flash at the frequency of
2Hz every minute. Press the clock +/- button; the current clock can be adjusted. Until the proper
time comes, press [SET].

TIMER ON operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below
sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [ON], then
[TIMER] [ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press [SET]
button.

TIMER OFF operation:


Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below
sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [OFF], then
[TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET]
button.

TIMER ON-OFF operation:


Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below
sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [ON] [OFF].
Firstly, [TIMER][ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press
[SET]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button
to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will
determine the mode is [TIMER] [ON] →[OFF] or [TIMER] [OFF] →[ON].
Note: 1. If the two times are the same, the unit will adjust the state after set time arrives according
to the current state. If current state is in running mode, after set time arrives the unit will switch to
“power off“ state. If current state is in “power off” mode, after set time arrives, the unit will switch to
running mode.
2. When in TIMER setting state, if you do not input any button in continuous 10 seconds, the unit
will think [SET] pressed.

Cancel TIMER operation:


In the timer operation state, press [TIMER] button, the unit will quit from the current timer
operation state, and the set data will be memorized, then enter the next timer mode.
After timer be set, press ON/OFF to cancel timer mode. When in running again, timer mode will
be continuous (without timer).

[FILTER] function
When the wired controller receives the filter-cleaned signal from indoor unit, [FILTER] will display.
After finishing clean, press [FILTER], the sign [FILTER] disappears, and the controller will send
the filter reset signal to indoor unit.
When the sign [FILTER] not display, it is invalid to press [FILTER] in short time.

FILTER ELEVATING function: (only for the unit with elevating function)
In power off state, press [FILTER] for 5 seconds to enter filter elevating set state. In this state, the
sign [FILTER] will flash at the frequency of 2Hz. By pressing [+] TEMP [-], filter can go up or down.
Press TEMP [+], in timer section [UP] will display, while press TEMP [-], in timer section [DOWN]
will display. Press [FILTER] button to quit the mode.

DEMAND operation function:


In the stop state of cooling mode, press [ON/OFF] button for 5 seconds to enter [DEMAND]
cooling operation state, the sign [DEMAND] will display. In the 7-segmet liquid crystal screen of
set temp. section, “0” will display in first position, which shows that No. 0 indoor unit has enter
demand operation. In the second position, “L” will display, in the meantime, [COOL] will flash,
[FAN][AUTO] is constant on. Press TEMP [+] [-] to set different indoor unit. Press [ON/OFF] to
cancel [DEMAND] operation.
In the stop state of heating mode, press [ON/OFF] button for 5 seconds to enter [DEMAND]
heating operation state, the sign [DEMAND] will display. In the 7-segmet liquid crystal screen of
set temp. section, “0” will display in first position, which shows that No. 0 indoor unit has enter
demand operation. In the second position, “H” will display, in the meantime, [HEAT] will flash,
[FAN][AUTO] is constant on. Press TEMP [+] [-] to set different indoor unit. Press [ON/OFF] to
cancel [DEMAND] operation.

VENTILATION mode (only for the unit with fresh air function or heat recovery function)
Press [RECOVERY] button, then the unit will switch over the ventilation mode:
[ ] → [VENTILATION][AUTO] → [VENTILATION][RECOVERY] → [VENTALATION][NORMAL]
→[ ], please select appropriate ventilation mode.

Query indoor malfunction history:


In the state of power on or power off, press [CHECK] button, enter the malfunction-querying
mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual
indoor numbers will be displayed in some sequence (unit number is in decimals). At the same
time, in the time region, there will be the current malfunction and the latest time malfunction, the
displaying format is [XX:YY], in which XX stands for the current malfunction, if normal, it will
display “――”; YY stands for the latest time malfunction. The failure code of every unit will display
for 3 seconds. After the failure codes of all indoor units in the whole group are displayed, the
mode will quit automatically.

Clear abnormal state and malfunction history:


In normal state, press [CHECK] button for 5 seconds to clear abnormal states, at the same time,
wired controller will send the data of “clear abnormal state”, but the malfunction history still
retains.
In normal state, press [CHECK] button for 15 seconds, except for malfunction states, the
malfunction history in wired controller will be cleared.

Query indoor performance state:


In normal state, press both buttons of [CHECK] and [FILTER] for 5 seconds, in the set
temperature region in the screen, [XX] will display, XX is indoor number, which can be selected by
pressing [TEMP] [+] [-]. In the timer region in the screen, [YZZZ] will display, in which Y stands for
data type, ZZZ stands for the corresponding data. which can be selected by pressing [CLOCK] [+]
[-].

Y ZZZ Type
A Indoor capacity (W) Nominal cooling
capacity/10, decimal
B Request of indoor capacity(Hz) Actual value, decimal
C Temperature of indoor ambient Actual value, decimal
temp. sensor TA
d Temperature of indoor gas pipe Actual value, decimal
sensor TC1
E Temperature of indoor liquid pipe Actual value, decimal
sensor TC2
F Open degree of indoor PMV Actual value, decimal
g Preset ―――
H Outdoor total capacity Actual value, decimal
In check mode, press [CHECK] to quit the check mode, and go into normal running mode.
How to change the function switches?
No. Type State of Function description
switch
J01 Changeover of Wired Connected Central controller
controller and central Cut off Wired controller
controller
J02 Changeover of type of Connected Set as simple controller
wired controller Cut off Set as standard controller
J06 Selection of room temp. Connected Use the sensor in the wired
sensor controller
Cut off Use the sensor in the indoor unit
J07 Auto reset after power Connected Common control
failure Cut off Auto reset after power failure
J03 Display of room Connected Yes
temperature Cut off No
SW01 Changeover of master or ON Set as slave controller
① slave controller OFF Set as master controller
SW01 ℃ or ℉ ON ℉
② OFF ℃
D1 Shorten time function Connected Indoor unit in shorted time
function
Cut off Common control
D2 Compulsorily defrost Connected Send compulsorily defrost signal
to indoor unit
Cut off Common control
Note: The switches in grey can be operated after opening the cover of wired
controller.
Electrical functions of wired controller:
1.Switch over method: wired control master unit/wired control slave
unit/remote control unit
Control method Wired control Wired control Remote control unit
Socket master unit slave unit
/jumper
CN23 Short circuit Not short circuit Not short circuit
CN30 Short circuit Short circuit Not short circuit
CN21 Blank Blank To remote receiver
board
J19 Short circuit Short circuit Cut circuit
Signal terminal block A,B,C connected B,C connected to A,B,C not connected
to wired controller wired controller to wired controller

Function difference between master wired controller and slave one:


Contrastive items Master wired controller Slave wired controller
Function All of functions Only with below functions:
ON/OFF, MODE, FAN SPEED,
SET TEMP., SWING

2. Wiring connections of wired controller:

A indoor 1 indoor 2 indoor N indoor 15 indoor 16


(master unit)

wired controller wired controller wired controller wired controller wired controller

control wiring of wired controller, polar.


A
B
C

wired controller

B indoor 1 C indoor 1
wired controller wired controller
1
2
3
1
2
3

polar wire
polar wire
polar wire
A
B
C

A
B
C
A
B
C

wired controller wired controller


wired controller

There are three methods to connection wired controller and the indoor
units:
A. One wired controller can control max. up to 16 sets of indoor units, and

1
3 pieces of polar wire must connect the wired controller and the master
unit (the indoor unit connected with wired controller directly), the others
connect with the master unit through 2 pieces of polar wire.
B. One wired controller controls one indoor unit, and the indoor unit
connects with the wired controller through 3 pieces of polar wire.
C. Two wired controllers control one indoor unit. The wired controller
connected with indoor unit is called master one, the other is called slave
one. Master wired controller and indoor unit; master and slave wired
controllers are all connected through 3 pieces of polar wire.
3. Communication wiring:
The wired controller is equipped with special communication wiring in the
accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the
terminal A、B、C of wired controller respectively.
The communication wiring is 4 meter long; if the actual length is more than
it, please distribute wiring according to below table:

Communication wiring length(m) Dimensions of wiring


<100 0.3mm2X3-core shielded wire
≥100 and <200 0.5mm2X3-core shielded wire
≥200 and <300 0.75mm2X3-core shielded wire
≥300 and <400 1.25mm2X3-core shielded wire
≥400 and <600 2mm2X3-core shielded wire

※ One side of the shielded sheet of communication wire must be earthed.

2
REFRIGERANT DIAGRAM

8 REFRIGERANT DIAGRAM

Piping Systematic Diagram for Cooling/Heating Type Air Conditioner


Cooling Operation Outdoor Unit
Indoor Unit
Stop Heating Operation
Valve
Filter

One-way Valve
Capillary Tube
Reversing Valve
Heat Exchanger

Heat Exchanger
Quieter
Stop
Compressor

Valve

- 71-
ELECTRICAL CONTROL FUNCTIONS

9 ELECTRICAL CONTROL FUNCTIONS


9.1 Control Features
The brief introduction includes those for each item of various types of air conditioners and
their electric control functions.
7.1 Brief introduction of electric control
(1) Automatic run
a. Cooling-heating type
After the machine being started and running mode changes to AUTO, the system will
decide running mode according to difference between the present room temperature and
setting temperature, then runs as the decided mode. In the following selections, Tr means
room temperature and Ts means setting temperature.
Select running mode according to the following conditions at the first time to enter Auto
mode:
Tr Ts-3 to select cooling mode (with setting temperature being Ts +3)
Tr<Ts-3 to select heating mode (with setting temperature being Ts)
After the system entering auto run mode, the running mode can convert automatically
according to variation of room temperature between cooling, blowing and heating in the way
shown as the chart below:
f t R
a e o
o
l m
Cooling
l p m
Ts+3
i e
n r
g a
t
u rising
temperature
Room
r
e
Cooling Blowing
Ts-3
Ts-3
Heating
b. Single Cooling Type
Select running mode according to the following conditions at the first time to enter Auto
mode:
Tr Ts + 3 to select cooling mode
Tr < Ts + 3 to select blowing mode
After the system entering auto run, the running mode can convert automatically
according to variation of room temperature between cooling and blowing functions in the way
shown as the chart below:
f t R
a e o
o
l m
Cooling
l p m
i e
n r
g a
t
u
r Ts+3
rising
temperature
Room

e
Cooling
Blowing
Blowing
Ts-3

-72 -
ELECTRICAL CONTROL FUNCTIONS

(2) Auto Selection of Wind Speed


In the following, Tr means room temperature while Ts means setting temperature.
a. During cooling program conversion of wind speed from the low to high won’t work until
the present speed has continued for 3 minutes while conversion from the high to low needs
no time delay. The chart below is the sketch map of conversion:
falling
Temperature

High speed
Ts 3
High speed
Ts 2 Medium speed

Medium speed Ts 1

rising
Temperature
Low peed
Ts
Low speed

b. During heating program applicable for cooling-heating type , conversion of wind speed
from the low to high won’t work until the present speed has continued for 3 minutes while
conversion from the high to low needs no time delay. The hart below is the sketch map of
conversion:
falling
Temperature

Low speed

Low speed Ts

Ts 1 Medium speed

Medium speed Ts 2
rising
Temperature

Ts 3 High speed

High speed

(3) Dehumidifying program


In the following, Tr means room temperature while Ts means setting temperature.
a. After the system entering dehumidifying program, the compressor, outdoor and indoor
blowing fans run according to the following rules:
(1) Tr > Ts + 2 , the compressor and outdoor blowing fan run continuously while indoor

- 73 -
ELECTRICAL CONTROL FUNCTIONS

blowing fan runs at setting wind speed. This working area is defined as area A.
(2) Ts Tr Ts + 2 , the compressor and outdoor blowing fan run for 10 minutes then
pause for 6 minutes, while indoor blowing fan runs at low wind speed. This working
area is defined as area B.
(3) Tr < Ts, the compressor and outdoor blowing fan stop working while outdoor blowing
fan runs at low wind speed. This working area is defined as area C.

a. After dehumidifying program starting, the system converts between A, B and C areas
according to variations of room temperature with running mode being shown as the chart
below:
falling
temperature
Room

Area A
Area A Ts 3
Ts 1
Area B

rising
temperature
Room
Area B Ts
Ts 1
Area C
Area C

(4) Cutoff protection against overload and overheat


During heating program, if the indoor blowing fan has been started and the compressor
has been running more than 2 minutes, and the temperature of indoor coil pipe (Ticp)
> 64 , the outdoor blowing fan will stops running; If Ticp ≤ 50 and the outdoor
blowing fan has kept stop state for 45 seconds, then it will restore rotation; If Ticp > 67
and such temperature has last for 10 seconds, the compressor will stop running and
indoor blowing fan run according to conditions as it reaches setting temperature. When
Ticp < 58 , and the compressor has kept stop state over 3 minutes, then the
compressor and outdoor blowing fan will restore normal running.
Cutoff protection for heating current
After 60 seconds from the compressor being started, if CT current exceeds I1 (9.2A) and
such case has kept 5 seconds, the outdoor blowing fan will stop. If 45 seconds has passed
after the outdoor blowing stops and the current of the compressor is less than I2 (7.5A), the
blowing fan will restore running. If CT current exceeds I3 (14.3A) and such case lasts for 3
seconds, the compressor and outdoor blowing fan will stop. The compressor will not restore
running until 3 minutes passes with CT current less than 12A.
(5) Cool wind prevention during heating program
At the first time entering heating program or after ending the latest frost removal, if the
temperature of indoor coil pipe (Ticp) < 28 , the indoor blowing fan will stop running; If
28 Ticp < 38 , the indoor blowing fan will run at low speed; If Ticp > 38 or the
compressor has been running for more than 4 minutes, the indoor blowing fan will run at

- 74-
ELECTRICAL CONTROL FUNCTIONS

setting wind speed.


(6) Afterheat blowing during heating program
During heating program, the compressor will stop running (except overheat protection or
frost removal) while the indoor blowing fan will firstly run for 50 seconds at low speed then
stop.
(7) Frost removal control (applicable for cooling-heating type)
Starting conditions for frost removal:
A The indoor unit is in overload protection and outdoor blowing fan stops. The outdoor
blowing fan does not enter overheat mode in 10 minutes after it is restarted, the
compressor has run over 45 minutes totally while 20 minutes continuously, and the
temperature of indoor coil pipe is lower than 43 ;
B After the compressor continuously running for 20 minutes, the temperature of indoor
coil pipe falls 1 every 6 minutes and such case continuously appears three times,
and the temperature of indoor coil pipe is less than 40 , and 5 minutes have passed
after the compressor is restarted;
C The compressor has run totally over 3 hours while 20 minutes continuously, and the
temperature of indoor coil pipe is less than 40 ;
D The difference between room temperature and the one of indoor coil pipe is less than
16 and the compressor has totally run over 45 minutes while 20 minutes
continuously;
Frost removal will start if any one of the above conditions is satisfied.
Ending conditions for frost removal:
1 Time of frost removal has exceeded 9 minutes;
2 CT current exceeds I4(8.2A)
Actions of each load after the frost removal starts:
The compressor and outdoor blowing fan stop, and indoor blowing fan also stops.
55 seconds later the reversal valve is closed and next 5 seconds later the compressor is
started.
Actions of each load after the frost removal ends:
The compressor stops running while outdoor blowing fan immediately runs at high
speed, 55 seconds later the reversal valve is opened and next 5 seconds later the
compressor restores running and indoor blowing fan runs as conditions for cool wind
prevention.
(8) Freeze protection
After the compressor has run for 9 minutes, the system will check temperature of
indoor coil pipe (Ticp). If Ticp is less than -1 , the compressor and outdoor blowing
fan will stop. They will run again after the compressor stops if both the following
conditions are satisfied:
1) 3 minutes have passed since compressor stops.
2) Ticp exceeds 7 .

(9) 3 minutes protection for compressor


After compressor stops, it cannot be started until 3 minutes later. During the machine’s
running, if time after loosing power not exceeds 3 minutes, the compressor cannot be

- 75-
ELECTRICAL CONTROL FUNCTIONS

restarted until 3 minutes later after it is reenergized.


10 Power breakdown memory
If the machine suddenly loses power while running, or stops for maintenance or trouble
shooting, it will restart running as the status when it stops after the power is restored.
Note: 1. Function setting: Continuously press sleep button on the remote controller 10
times in 5 seconds and buzzer on control panel shall beep 4 times.
2. Memory content: Running mode, wind speed setting, temperature setting,
swing status.
3. Cancel: Press sleep button on the remote controller 10 times and buzzer on
control panel beeps 2 times.

(11) Control of water pump


a. In cooling (including automatic cooling mode) and dehumidifying modes, the water
pump works if the compressor runs while stops 5 minutes later after the compressor
stops.
b. When water tank is fully filled, the float switch will be off. The water pump will start
to work after a controller has detected this signal and it will continue working for 5
minutes after the float restores to normal state.
c. If the full water signal is detected continuously over 5 minutes, the water pump
indicator lamp will flash to alarm and compressor stops running. The water pump
will run 5 minutes, then pause for 5 seconds before next 5 minutes’ running, ... until
the float restores to normal state, after which the pump will run for 5 minutes then
stop.

(12) Monitoring of remote network


Through preset interface, the air conditioner is connected to remote control detector
(made by Haier) with 2-core cables for wire communication, to execute instructions sent
from computer or centralized controller via remote control detector and meanwhile send
present running status and trouble information of the machine to remote control detector.
Connection between air conditioner and remote control detector:

CN11
PC board A-
1
A+
2

Interface for remote


control detector
(13) Trial run
Under shut-down state, hold pressing mandatory button. The buzzer will beep once,
then twice after 5 seconds. Release the button to enter mandatory cooling mode, under
which the indoor blowing fan runs at high speed with both the compressor and outdoor
blowing fan working. Press the mandatory button again can end the mandatory mode.

- 76 -
ELECTRICAL CONTROL FUNCTIONS

9.3 Defrost operation flow chart

Come to defrost

Compressor Open outdoor fun


ON

Compressor
Condition off or 55s?
E-Heat off for 30s?
for
compressor Return
OFF Operation indoor
fun motor
Return

4-way value
ON
Turn off compressor Return
outdoor fun
OFF
compressor
Compressor
ON ?
Turn off for
55s?
Return

Turn off Clear the sign of


4-way value defrosts
Return

Compressor Return
ON

Return

B
10. Diagnostic information
10.1 Failure code
remote control type unit:
indoor running
failure description
lamp flash times
indoor ambient temp. sensor failure 1
indoor coil temp.sensor failure 2
outdoor ambient temp. sensor failure
3
or 4-way valve broken down in heating mode
outdoor coil temp. sensor failure 4
over-current protection failure or phase sequence fault 5
refrigerant system pressure too high or low 6
communication between indoor PCB and receiver panel failure 8
communication between indoor PCB and outdoor PCB 9
drainage failure 10
Note: For convertible type unit, drainage failure is not available.

Wired control type unit failure code:for old wired controller

Failure description Failure code on wired


controller
Indoor ambient temp. sensor abnormal E1
Indoor coil temp. sensor abnormal E2
Outdoor ambient temp. sensor abnormal E3
Outdoor coil temp. sensor abnormal E4
Over current protection E5
Over high or low pressure protection E6
Communication between panel and indoor E8
abnormal
Communication between indoor and outdoor E9
abnormal
Water pump failure E0
Failure code with wired controller YR-E12:
For Failure For central Failure description Reason
remote code on control,
type, flash wired failure code
times controller
10 08 21 Drainage system failure Float switch broken down for more than
25m continuously
1 01 01 Indoor ambient temp. sensor sensor broken down or short circuit for
failure more than 2m continuously
2 02 02 Indoor coil temp. sensor failure sensor broken down or short circuit for
more than 2m continuously
3 4A 11 Outdoor ambient temp. sensor sensor broken down or short circuit for
failure more than 2m continuously
4 49 12 Outdoor coil temp. sensor Sensor broken down or short circuit for
failure (compressor more than 2m continuously
discharging temp. sensor)
5 48 10 Over-current protection CT check abnormal 3 times in 30m
6 53 14 High pressure abnormal High pressure switch acts 3 times in 30m
8 07 06 Communication between wired Communication abnormal for more than
controller and indoor abnormal 4m continuously
9 06 05 Communication between Communication abnormal for more than
indoor and outdoor abnormal 4m continuously
11 0B 30 Outside alarm signal input Outside signal broken down for more than
10s
12 03 20 Gas pipe temp. sensor Sensor broken down or short circuit for
abnormal more than 2m continuously
13 0D 31 Solenoid valve abnormal Solenoid valve act incorrectly 3 times
continuously
15 05 17 EEPROM abnormal EEPROM data missing
sensor resistance value

R(25℃)=10K (Indoor unit Pipe sensor)

Therameter Sensor
temperature(℃) resistance(KΩ) temperature(℃) resistance(KΩ)
-15 66.53 45 4.549
-20 87.42 50 3.788
-25 116.0 55 3.170
-10 51.8 60 2.660
-5 39.55 65 2.223
0 30.88 70 1.912
5 24.30 75 1.630
10 19.20 80 1.395
15 15.38 85 1.200
20 12.36 90 1.035
25 10.00 95 0.8967
30 8.141 100 0.7796
35 6.668 105 0.6802
40 5.492 110 0.5955

R(25℃)=23K (Indoor unit ambinent sensor)


Therameter Sensor
temperature(℃) resistance(KΩ) temperature(℃) resistance(KΩ)
-10 139.5 60 5.243
-5 105.3 65 4.336
0 80.14 70 3.603
5 61.51 75 3.008
10 47.58 80 2.522
15 35.36 -20 251.8
20 27.93 -19 235.9
25 23.00 -18 223.1
30 18.30 -17 210.1
35 14.65 -16 197.9
40 11.79 -15 186.5
45 9.556 -14 176.9
50 7.780 -13 165.9

79

10.2 Trouble Shooting - Detailed for engineer
Malfunction flow chart: analyze and diagnose
If the air-condition fails to cooling or heating function and other functions, please check
the system as follows:

1.Cooling 

begining

fails in cooling

the enactment TEMP. Y change the designed


right or not TEMP.

the cooling load


Y use arange is right Y
beyond the allowable redesign the TEMP.
or not
arange

condensate Y change the


fault in 4-way vavle
flowage failure 4-way vavle

quantity of condensate Y superaddition condensate


charge is not enough

Y
compressor fault replacing compressor

airiness circle fan speed at Y enact fan speed of


improperly low-speed high or middle speed

air entrance filter Y


clear the filter
obstruct

heat insulation of condensate Y insulate the two


pipeline between indoor unit pipeline respective
and outdoor unit is normal

Figure 9-1

80
2. Heating

begining

fails in heating

the enactment TEMP. Y change the designed


right or not TEMP.

the heating load Y


beyond the allowable use arange is right Y
or not redesign the TEMP.
arange

condensate Y change the


fault in 4-way vavle
flowage failure 4-way vavle

quantity of condensate Y superaddition condensate


charge is not enough

Y
compressor fault replacing compressor

airiness circle fan speed at Y enact fan speed of


improperly low-speed high or middle speed

air entrance filter Y


clear the filter
obstruct

heat insulation of condensate Y insulate the two


pipeline between indoor unit pipeline respective
and outdoor unit is normal

Y replacing the
blowing cold air fault in 4-way vavle 4-way vavle

prevent cold air pipe sensor of Y replacing the


failure indoor unit is fault 4-way vavle

Figure 9-2

81
10.3 Malfunction and Solution of Wired controller

1) There is nothing on display of wire control organ, and the air-conditioner failure to
operate
begining

if the diode on indoor


unit is lumines

'
if there'e DC 12V
if there s voltage Y between the four N
on the primary side ports:A,B,C and D which
of tranaformer on wire control organ

if there's AC 220V Y
if power supply and N
check the port row of Y repacing the wire
communication line are of power suplay on
power supply control organ
connected correctly PCB. of indoor unit

redo the N if the transform of N if the fuse of indoor


connection work PCB.socket is normal unit PCB.is normal

Y
Y

if the primary side of N


power supply
replacing the N if there's AC 15V on transformer is short
transformer transformer subside
of indoor unit PCB. Y
replacing the transformer replacing the PCB.
of indoor unit

Figure 9-3

82
2) The wire control organ displays the alarm signal with “E0”
“E0” means the floater switch of indoor unit is abnormal 
begining

the alarm signal of wire


control organ is E0

if the floater swith is N amend the oritation of


orientated correctly the floater switch

if the function of the


floater is normal

N
replacing the switch

Figure 9-4

3) The wire control organ displays the alarm signal with “E1”
“E1” means indoor ambient temperature sensor is abnormal

begining

wire control organ displays


the alarm signal with E1

N amend the
if the indoor ambient sensor
position of the
is orientated correctly
sensor

if the resistance of
sensor is right

N
replacing the sensor

Figure 9-5

Notation: The resistance of indoor ambient sensor is 23K

83
4) The wire control organ displays the alarm signal with “E2”
 “E2” means indoor piping temperature sensor is abnormal

begining

the alarm signal of wire


control organ is E2

if the position of piping N amend the position


Temp.sensor is right of sensor

if the resistance of
the sensor is right

N
replacing the sensor

Figure 7-6
Notation: The resistance of piping temperature sensor is 10K 

8) The wire control organ displays the alarm signal with “E8”
 “E8” means malfunction of communication between control panel and indoor units
begining

N replacing the wire


if the wire control organ can
matches the PCB of indoor units control organ

if the four ports on wire control N


connected corresponding connect the
with the port on PCB of indoor unit wire correctly

if the ports:A,B,C and N connect the


D are connected well wire correctly

if the potrs A and B,or N connect the


C and D are short wire correctly

 
Figure 9-7
11. Electrical Data
11.1 Wiring Diagram
11.1.1 Outdoor unit
single phase outdoor wiring diagram

NOTE:
1. Dashed parts is not available for only Cooling type
2. Dashed parts is optional for Low Ambient Temp. Cooling,and there is
no relay in only Cooling type

3-phase outdoor wiring diagram

NOTE:
1. Dashed parts is not available for Cooling capacity below 42000Btu/h

2. Dashed parts are not available for only Cooling type

3. Dashed parts is optional for Low Ambient Temp. Cooling,and there is


no relay in only Cooling type
11.1.2 Indoor unit
over 24000BTU/h convertible type wiring diagram

NOTE:
1. Dashed parts are not availble in convertible type
2. Dashes part is not avaliable below Cooling capacity 42000Btu
type
3. Remote central controller is optional
4. P16 and P17 are used for room card function

over 24000BTU/h cassette type wiring diagram

NOTE:
1. Parts in dashed frame are not available for cassette type
unit
2. Central controller is optional
3. P16 and P17 are used for room card function
over 24000BTU/h mid ESP duct type wiring diagram

W
Y
R

Note:
1.Dashed parts are not available in duct type.
2. Dashed part is ont avaliable below Cooling capacity 28000Btu type
3.Remote central controller is optional.
4.P16 and P17 are used for room card function

Wiring Diagram For 24000/42000BTU/h cabinet Unit


PIPING
TRANS. TEMP ROOM
TEMP.

CONTROLLER
CN6 CN3
TERMINAL
CN12
TO OUTDOOR UNIT

BLOCK
Y/G
R Y/G

CN5 CN11
R

B
W B

CN8
W
DOOR
CN9 SWITCH

N S(N-W) CN7 CN1


FUSE
T3.15A/250VAC

SWING FAN MOTOR


MOTOR

FAN MOTOR CAP.


High ESP duct type wiring diagram

W
Y
R

Note:
1.Dashed parts are not available in duct type
2.Dashed part is fan speed controller kit.
3.Remote central controller is optional
4.P16 and P17 are used for room card function
Circuit for 3-phase outdoor unit:
1 2 3 4 5 6

+12
N C16 C3
22uF/250V 103
250 JK1
R5 JQ1P
33K +5 fan motor
R1
D 200K D
R12 1
D2 2 L
560 3 H
IC1 TLP371 +5
4007 JK2
L1 CN9
D1 R2 OJE-SS-112DM B3B-VH-W
250 4007 62K/3W R7
TLP521-1 10K
R3 C2 R6 IC2 R8
62K/3W 103 2.2K
R4 D3 1K
62K/3W 4007
C4 103
+5
R15

10K/0.5W +5
R27 R17 R18 R19 R20
R16 10K 10K 10K 10K 10K C5
D4 IC3
S
104
4007 MC68HC908JL3ECP
250 10K/0.5W 1
IRQ RST
28
JK5
CN10 2
2
PTA0 PTA5
27 IC4 compressor
C TEST ULN2003A OJE-SS-112DM C
1 1
VHB2B 3 26 1 16
R9 1M VSS PTD4 A1 Q1 2
2 15
A2 Q2
4 25 3 14
OSC1 PTD5 A3 Q3 CN7
CN2 C27 103 4 13
2 A4 Q4 B2B-VH-B
5 24 5 12
VHB2B 1 4MHz OSC2/PTA6 PTD2 A5 Q5
6 11
A6 Q6
+5 6 23 7 10
OSC1 PTA1 PTA4 A7 Q7
D5
C10 103
7 22 +12
4148 VDD PTD3
D15 D14 8 9 JK7 4-way valve wind
GND VCC
C12 103 8 21
PTA2 PTB0
OJE-SS-112DM 1
CT1 R10
C11 103 9 20 2
PTA3 PTB1
0057W +5
R11
1K 10 19
PTB7 PTD1
D12 D13 R34 33K/2W CN5
R13 1K C6 11 18 B2B-VH-W
PTB6 PTB2 R29 R31 L2
470 104 560 5.6K
12 17 +5 250
PTB5 PTB3
+5 D6
R23 13 16
RW PTD7 PTD0 R21 10K 4148
C21 560
B 102 LED1 14 15 B
PTD6 PTB4
470UF/16V C18

103 R35 33K/2W


R26 C25 IC6 TLP521-1
47K 104 +5
CN3 R24
EX TH TEMP TH

XHB2B C17
5.1K CN11 2 R32 33K/2W
+5 4.7UF/50V
2 1 R28 R30 L3
XHB2B
1 1K 5.6K
250
D7
2 4148
1
R25
C22
CN12 C19
N
XHB2B C20 5.1K
4.7UF/50V 103
104 IC7 TLP521-1 R33 33K/2W 250

FUSE
CN1 CN4
D9 D10 T3.15A/250V L1
XHB2P3 RTB-1.5-2P
+5 RG1 7805 +12 1 1 250
A 3 1 LX102 A
Vout Vin VR
C7 LX1
GND

2 2 Title
104
C8
D8 D11 C23 C24
S14K350
N
AU42NABCEA
104 250 Size Number Revision
2

2200UF/35V
C1 0.1UF/250V 0.1UF/250V
B 0010451295
Date: 5-Nov-2003 Sheet of
File: C:\Documents and Settings\zhanjie\×ÀÃæ\0010451429.DDB
Drawn By:
1 2 3 4 5 6
Circuit for single-phase outdoor unit (capacity is over 24000BTU/h):
1 2 3 4 5 6

+12
N C16 C3
22uF/250V 103
250 JK1
R5 JQ1P
R1 33K +5 fan motor
D 200K D
R12 1
D2 2 L
560 3 H
IC1 TLP371 +5
4007 JK2
L1 D1 OJE-SS-112DM CN9
R2 B3B-VH-W
250 4007 62K/3W R7
TLP521-1 10K
R3 C2 R6 IC2 R8
62K/3W 103 2.2K
R4 D3 1K
62K/3W 4007
C4 103
+5
R15

10K/0.5W +5
R27 R17 R18 R19 R20
S D4 R16 10K 10K 10K 10K 10K IC3 C5
4007 MC68HC908JL3ECP 104
250 10K/0.5W 1
IRQ RST
28
JK5 compressor
2 27 IC4
C CN10 2 TEST PTA0 PTA5
ULN2003A OJE-SS-112DM C
1 1
VHB2B 3 26 1 16
R9 1M VSS PTD4
2
A1 Q1
15
2
A2 Q2
4 25 3 14
CN2 C27 103 OSC1 PTD5 A3 Q3 CN7
4 13
2 A4 Q4 B2B-VH-B
5 24 5 12
VHB2B 1 4MHz OSC2/PTA6 PTD2 A5 Q5
6 11
A6 Q6
+5 6 23 7 10
D5 OSC1 PTA1 PTA4 A7 Q7
C10 103
7 22 +12
4148 VDD PTD3
JK7
D15 D14 8 9 4-way valve wind
GND VCC
C12 103 8 21
PTA2 PTB0
+5 OJE-SS-112DM 1
CT1 R10 C11 103 R31 5.6K
9 20 2
PTA3 PTB1
0057W 1K R11
10 19
PTB7 PTD1
D12 D13 CN5
R13 1K C6 11 18 R30 5.6K B2B-VH-W
PTB6 PTB2
+5
470 104 10K
12 17
PTB5 PTB3
+5
R23 13 16 R21
RW PTD7 PTD0
102 C21 560
B LED1 14 15 B
PTD6 PTB4
470UF/16V

R26 C25
47K 104
CN3 R24
EX TH TEMP TH

XHB2B C17
5.1K 4.7UF/50V CN11 2
+5
2 1
XHB2B
1

2
1
R25
CN12 C22
XHB2B C20 5.1K 4.7UF/50V
104

FUSE
CN1 CN4
D9 D10 XHB2P3 RTB-1.5-2P T3.15A/250V L1
+5 RG1 7805 +12 1 1 250
A 3 1 LX102 A
Vout Vin VR
C7 LX1
GND

2 2 Title
104
C8
D8 D11 C23 C24
S14K350
N
AU242ACBEA
104 250 Size Number Revision
2

2200UF/35V
C1 0.1UF/250V 0.1UF/250V
B 0010451293
Date: 5-Nov-2003 Sheet of
File: C:\Documents and Settings\zhanjie\×ÀÃæ\0010451293.DDB
Drawn By:
1 2 3 4 5 6
0010451167 PCB information – circuit diagram
+5 +12 W1 VDD D1-D4
R5 33K 104 103 100uF W2
R2 +5
T1 0.1UF/275V 0.1UF/275V 187
IC6 C29 C22 E4 470uF/16V
LED3 10K/0.5W TLP371
OUT IN OUT IN 1 P2-P6
P15 C4 103 C33 7805 7812
1
LB1
330
R3 10K/0.5W 5 6 1
E1
1 104 E3 2200uF C34 104
RV1
187 4 2 R10 4 C1
D10 CN23 CN22 CN10
4.7K CN1 T3.15A/250V
+5 R30 +5 R41 10K D12
CN4 C2
1N4007 1 2 1 TRAN1-2 FUSE1
2 1 2 R36 R43 N1 9013 C21 R64 R34
4148
10K N9 10K D13 187
1 P1
C3 1K LED2 103 56K 4.7K 4148 +12
2.2K TLP521 IC7 4 R24
1 1K
D9 103 1K RL6
2 3 R21 C8 JQ1AP-A
102 1 A
R4 R58 187
B 1 P14
+5 103 C
IC10
R63 C24 CN5 JQ1P-A
RL8
R11 330 LED4
CN14 +12 +5 4.7K 27K 187
1 P13
D16
4 D18 R55 R31
N3
+5
TLP741/541 4148 RC3
9013 R8 10 R7 10 0.033uF+120

1N4148
+5 CN20 RL7
JQ1P-A

1
2
3
4
5
1 9013 +5 R32
N6 4.7K D15
10K R39 10K 4.7K 187
R54 10K R28 4148 1 P12
R33 IC9 D14 R25 2.4K
CN19
R53 10K N8 RC1

1
2
3
4
5
E9 1K 4148 VDD 0.033uF+120
9013 9013 C27 R22 1K RL5
N7 4.7K JQ1AP-A
C7
R29 104 N2 IC1
1uF 102 9013 187
TLP521 1 16 1 P11
LED5 2 15
3 14 RC2
4 13 0.033uF+120
+5 IC3 RL4
5 2003 12 JQ1AP-A
CN13 R23 1K 1 64 6 11
LED1 187
2 63 7 10 1 P10
+5V 1 C23 IRQ/50Hz
C5 102 3 62 8 9
GND R19 R12 103 RESET
4 61 +12 RL3
560 NOP 104 JQ1AP-A
1K 5 60 C32
6 59
OSC1 XT1 187
7 58 IC2 1 P9
BEEP OSC2
8 57 C28 104 1 16
7 C6 IR CGMXFC R66
9 56 2 15 RL2
102 VSSA 1M JQ1AP-A
10 55 3 14
VDDA +5
11 54 4 13
VREFH 8.00M 187
12 53 5 12 1 P8
487 2003
13 52 6 11
NET-O
14 51 7 10 RL1
NET-I JQ1AP-1
R51 10K 15 50 8 9
9013 10K 16 P/G 49 +12
2 N10 +5 R59 187
10K 17 P/G 48 C31 104 1 P7
R56
1 D19 R57 4.7K C26 104
18
NOP
47
CN17 4148 R52 19 46 R49 10K
NOP
+12 IC5 R50 10K 20
NOP AVss
45 R27 4.7K C35
CN7
1 8 21 44 104 BUZ1
Vss VDDAREF +5
24C01A

2 7 10K 22 43 1
+5 Vdd N5
3 6 23 42
SCL 9013
4 5 24 41
SDA +12
25 40
IC4 MAX487 C36 R67 100 R35 4.7K
26 39
CN16 5 4 A
GND DI 27 38
2
DL1 6
A DE
3 EEPROM 28
B
37
R48
R47
10K
10K R26 4.7K
104
+5
DL2 7 2 C
1 B /RE 29 36 R40 10K N4
8 1 D R65
VCC RO 30 35 9013 680 1N4007
+5 200K
31 34 R6 D11
32 33 1
C25 104
AB32 NOP C14 103 R9 220 IC8 187
P16
C15 103
R20
C16 103 1K E8 R1
C20 100K/1W
C9 2.2uF TLP521-1
103 1

1K R15

1K R14

1K R13
103 C10 187
+5 103 C11 P17
CN12 R44 10K 103 C12
R18 1K 103
R61 20K J1 J2 J3 J4 J5 J6 J7 J8 J9 J10
C17 R62 20K
RB1 RB2 RB3 RB4 RB5
1 103 D17 R60 20K
C13
CN11 R45 10K 103 4.7uF 4.7uF
R17 1K E5 1N4148 E6 E7 +5
2
1 C18
R46 10K 103 4.7uF
CN15 +5v +5v
R16 1K SW2 SW1
1
C19 CN8 CN6
2
1

1
CHECK
1/60
J10
J9
J8
J7

J6
J5

J4
J3
J2
J1

103
0010451167 PCB information – characters on board(horizontal)
0010451167 characters on board(vertical)
0010451167 PCB information – port and definition
P1——connect to external power supply, live line: L (220VAC)

P2——connect to external power supply, neutral line: N (0VAC)

P3、4、5、6——control external load, neutral line: N1、N2、N3、N4(0VAC)

P7——control external load, electrical heat: HEAT (control output 220VAC)

P8——control external load, health function: OXYGEN (control output 220VAC)

P9——control external load, humidification: HUMI (control output 220VAC)

P10——control external load, SWING(control output 220VAC)

P11——control external load, WATER PUMP(control output 220VAC)

P12——control external load, indoor fan motor low speed: L(control output

220VAC)

P13——control external load, indoor fan motor mid speed: M(control output

220VAC)

P14——control external load, indoor fan motor high speed: H(control output

220VAC)

P15 — — communication with fixed frequency single outdoor unit:

COMM(0~220VAC)

P16——input control, signal live line: L’(220VAC)

P17——input control, signal neutral line: N’(0VAC)

CN1——input port of transformer (220VAC)

CN2——input port 1 of transformer (no use)

CN3——input port 2 of transformer (no use)


CN4——input port 3 of transformer (1-2、14VAC,3-4、12VAC)

CN5——input control, connecting port to wired controller: CONTROLLER(1.

power supply: 12VAC, 2. power supply: 0VAC, 3. communication: COMM.)

CN6 — — input control, ambient temp.-coil temp. sensor connecting port:

ROOM/PIPE(1-2、ROOM,3-4、PIPE。

CN7——control external load, fresh air control: FRESH(1. blank, 2. power

supply 0VDC, 3. control output: 12VDC.)

CN8——input signal: FREEZE(no use)

CN9——input control(no use)

CN10——communication with fixed frequency single outdoor unit: (0~12VDC)

CN11——input signal, door switch: DOOR(1-2 short circuit is normal, cut off

P8 output)

CN12——input signal, external alarm input: ALARM(1-3 short circuit is normal,

if cut off, air conditioner stops work.)

CN13——input signal, wiring port of remote receiver board: RECEIVE BOARD

(1. power supply 5VDC, 2. power supply 0VDC, 3. remote signal, 4. signal output of

running lamp 0VDC, 5. signal output of timer lamp 0VDC,6. signal output of power

lamp 0VDC, 7. signal output of water pump running lamp 0VDC)

CN14——control external load, elevating function (1. signal of door switch

close, 2. output of elevating direction control 0VDC, 3. output of elevating power

control 0VDC, 4. power supply 12VDC)

CN15——input signal, water level of float switch (1-3 short circuit is normal, cut
off shows that level exceeds the limitation)

CN16——input control, wiring port of central controller: REMOTE(1、RS485-B,

2、RS485-A。

CN17——output signal, output signal of failure alarm, control external load,

12V/ALM(1. control output 0VDC, 2. power supply 12VDC)

CN18——output signal (no use)

CN19——control external load, swing 1(1、16VDC,2、0VDC,3、0VDC,4、

0VDC,5、0VDC.)

CN20——control external load, swing 2(1、16VDC,2、0VDC,3、0VDC,4、

0VDC,5、0VDC.)

CN21——input signal, spring switch, CHECK(1、input signal of earthing, 2.

power supply 0VDC)

CN22——short circuit means selecting single split communication type.

CN23——short circuit means selecting multi split communication type.


0010451167 PCB information – function selection(ON is 1, OFF is 0)
The standard condition for PCB in factory

SW1:4 bits are OFF

SW2:4 bits are OFF

SW3:4 bits are ON

SW4:2 bits are ON

SW5:4 bits are ON

SW1-1——address selection of central controller 0, address selection of wired

controller 0

SW1-2——address selection of central controller 1,address selection of wired

controller 1

SW1-3——address selection of central controller 2,address selection of wired

controller 2

SW1-4——address selection of central controller 3,address selection of wired

controller 3

SW2-1——address selection of central controller 4

SW2-2——address selection of central controller 5

SW2-3——address selection of central controller 6

SW2-4——logistic relationship of control function(door card control and remote/

wired control)0 means logistic relationship is “and”, 1 means the later coming is

preferential.

J1,SW3-1——function selection-control type: 1 means remote control, 0 means


wired control.

J2,SW3-2——function selection-temperature compensation in heating mode:

1means “yes”, 0means “no”.

J3,SW3-3——function selection-outdoor communication: 1means “yes”, 0means

“no”. This PCB must be 1.

J4,SW3-4——function selection-heat pump unit: 1means “heat pump”, 0means

“cooling only”.

1/60——test in short circuit, but in operation short circuit mustn’t be permitted.

CHECK — — short spring switch control, it also can be used as switch of

convertible type except for testing.

J5,SW4-1——function selection-elevating function: 1means “yes”, 0means “no”.

J6,SW4-2——function selection –health function: 1means common (indoor fan

motor running); 0 means special (indoor, outdoor running).

J7,SW5-1——function selection –swing mode: 1 means common(simultaneous

motor), 0 means special (swing motor).

J8,SW5-2——function selection – system combination: 1means fixed frequency

single unit, 0 means fixed frequency multi split.

J9,SW5-3——function selection –group control: 1 stands for the master unit (its

address in wired controller is 0), 0 stands for the slave units (the address should be

set by the dip switch, their addresses only can be in the range: 1~15)

J10,SW5-4——function selection –preset: 1 no meaning, 0 no meaning


0010451167 PCB information- control type
Control type selection between remote and wired: select by dip switch J1, SW3-1

(1 means remote control;0means wired control).

For remote control type, please use remote controller YR-H71, and a remote

receiver is equipped with indoor unit. For wired control type, wired controller

YR-E12 will be used, 3-core shied wire is equipped with indoor unit.

Door card control: controls ON/OFF, the start up setting will comply with last time

request memorized according to condition memorize function. Its difference with

emergency switch of convertible type unit lies: the emergency switch control will

perform in the condition: 24degrees, auto fan speed in auto mode.

The function combination between door card and remote/wired control type: select

by dip switch: SW2-4(0 means “and”, 1 means later coming is preferential.)

Dip switch position in wired control type: Only one indoor unit of all indoor units

connected with wired controller is the master unit, whose address is 0, function

selection switch(J9,SW5-3)is 1. The others are slave units, and the quantity can be

0~15, whose addresses are(SW1:1~4)from 1 ~15, and cannot repeat.

Wiring request in wired control type: the wired controller ports A-B-C are

connected with indoor port CN5(1-2-3) through 3-core shield wire. Requirements:

1. Port A only connects with either of indoor port CN5(1)

2. Port B connects with port CN5 (2) of all indoor units.

3. Port C connects with port CN5 (3) of all indoor units.


Dip switch position in central control type: the addresses (SW1:1~4;SW2:1~4)

of indoor units connected with central controller can not repeat. In principle, they

should be in the order from small to big.

Wiring request in central control type: port A-B is connected with indoor port

CN16(A-B)through 2-core shield wire. Requirements:

1. Port A connects with port CN16(A)of all indoor units.

2. Port B connects with port CN16(B)of all indoor units.

When only use remote control type, please select remote control unit, and install

according to installation manual, there is no other special request.

When only use wired control type, please select wired control unit, and install

according to installation manual. When control multi indoor units, take care the

requirements of dip switch and wiring, there is no other special request.

When only use central control type, please firstly install according to air conditioner

requests and set the dipswitch, there is no other special request.

When central control type(128×)and remote control type are used simultaneously,

set the dip switch according to central control type, there is no other special request.

When central control type(128×)and wired control type (16×)are used

simultaneously, max. indoor units sets: 128×16 can be controller. Address setting of

central controller can be met firstly, and then modulate the address setting of slave unit

wired controlled.
10. Exploded view
cassette type: AB36NACBEA and AB42NACBEA are the same.
Parts list
the proportion of
Spare parts description in Failure the spare-part
No. Spare parts number english Qty. Model rate stock Remark
1 001A1232307 Electrical box cover2 1 AB42NACBEA 0.00% 0.000% ×
2 001A1232306 Electrical box cover1 1 AB42NACBEA 0.00% 0.000% ×
3 0010451265 Terminal block 1 AB42NACBEA 0.00% 0.000% ×
4 001A3600232 fan mortor capacitor 1 AB42NACBEA 0.04% 0.048% *
5 0010451262 Transformer 1 AB42NACBEA 0.01% 0.012%
6 0010451167 Indoor PCB 1 AB42NACBEA 0.02% 0.024% *
7 001A1232305 Electrical box 1 AB42NACBEA 0.00% 0.000% ×
8 001A1301815 fan motor filter 1 AB42NACBEA 0.00% 0.000% ×
9 001A1231308 Wind ring 1 AB42NACBEA 0.00% 0.000% ×
10 001A1434927 Drin pan accessory 1 AB42NACBEA 0.00% 0.000% ×
11 001A0900066 Drin pan assy. 1 AB42NACBEA 0.00% 0.000% ×
12 001A5102015 Flange screw nut 1 AB42NACBEA 0.00% 0.000% ×
13 001A1301710 Fan in-built part 1 AB42NACBEA 0.00% 0.000% ×
14 0010250212 Centrifugal fan 1 AB42NACBEA 0.02% 0.024% *
15 001A3000195 Indoor fan motor 1 AB42NACBEA 0.02% 0.024% *
16 001A1301668 Motor bracket 1 AB42NACBEA 0.00% 0.000% ×
17 001A1301669 Motor holder 1 AB42NACBEA 0.00% 0.000% ×
18 001A1301679 Evaporator holder 2 AB42NACBEA 0.00% 0.000% ×
19 0010752260 Heat exchanger assy. 1 AB42NACBEA 0.01% 0.012%
20 001A0100507 Bottom plate assy. 1 AB42NACBEA 0.00% 0.000% ×
21 001A1101187 Swing 4 AB42NACBEA 0.00% 0.000% ×
22 001A3900006 Pipe temp. sensor 1 AB42NACBEA 0.00% 0.000% ×
23 001A1301677 pump Bracket 1 AB42NACBEA 0.00% 0.000% ×
24 001A3400160 Float Switch 1 AB42NACBEA 0.00% 0.000% ×
25 001A01001096 Evaporator holded plate 1 AB42NACBEA 0.00% 0.000% ×
26 001A1434920 Drainage hose 1 AB42NACBEA 0.00% 0.000% ×
27 001A3000197 Water pump 1 AB42NACBEA 0.00% 0.000% ×
28 001A1301659 pipe holder plate 1 AB42NACBEA 0.00% 0.000% ×
29 001A3900159 nvironment temperature sens 1 AB42NACBEA 0.00% 0.000% ×
30 001A1439315 collar clamp 1 AB42NACBEA 0.00% 0.000% ×
31 0010451255 Remote Controller 1 AB42NACBEA 0.01% 0.012%
32 001A1734260 Heat insulation pipe1 1 AB42NACBEA 0.00% 0.000% ×
33 001A1734261 Heat insulation pipe2 1 AB42NACBEA 0.00% 0.000% ×
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-
parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the
actual quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts
warehouse,and should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may
stock in the spare-part warehouse accord with the actual case,should be marked with " ".

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The
spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
Convertible type
AC36NACBEA and AC42NACBEA are the same
Parts list
the proportion
Failure of the spare-
No. Spare parts number Spare parts description in english Qty. Model rate part stock Remark
1 001A1231278 inlet grill assy 3 AC42NACBEA 0.00% 0.000% ×
2 001A2400108 air filter 3 AC42NACBEA 0.00% 0.000% ×
3 001A1101167 front panel assy 1 AC42NACBEA 0.00% 0.000% ×
4 001A17341009 pad 1 AC42NACBEA 0.00% 0.000% ×
5 001A13011280 Eletrical box 1 AC42NACBEA 0.00% 0.000% ×
6 001A1301379 Eletrical box cover 1 AC42NACBEA 0.00% 0.000% ×
7 0010451167 PCB 1 AC42NACBEA 0.02% 0.024% *
8 0010451262 transformer 1 AC42NACBEA 0.01% 0.012%
9 001A3600098 capacitor 2 AC42NACBEA 0.04% 0.048% *
10 0010451265 termonal block 1 AC42NACBEA 0.00% 0.000% ×
11 001A5701062 Power line clip 1 AC42NACBEA 0.00% 0.000% ×
12 001A3900159 environment temp. Sensor indoor 1 AC42NACBEA 0.00% 0.000% ×
13 001A1301580 motor bracket 4 AC42NACBEA 0.00% 0.000% ×
14 001A1301582 scroll case right 2 AC42NACBEA 0.00% 0.000% ×
15 001A1200325 drain pan assy 1 AC42NACBEA 0.00% 0.000% ×
16 001A1101172 mounting plate 1 AC42NACBEA 0.00% 0.000% ×
17 0010751099 air pipe 1 AC42NACBEA 0.00% 0.000% ×
18 0010752148 liquid pipe 1 AC42NACBEA 0.00% 0.000% ×
19 001A1301588 partition plate 1 AC42NACBEA 0.00% 0.000% ×
20 001A1301577 plate assy right 1 AC42NACBEA 0.00% 0.000% ×
21 001A1301579 right wallboard 1 AC42NACBEA 0.00% 0.000% ×
22 001A1231277 Ornamental plate right 1 AC42NACBEA 0.00% 0.000% ×
23 001A1301574 left scroll case 2 AC42NACBEA 0.00% 0.000% ×
24 001A2331071 centrifugal fan 4 AC42NACBEA 0.02% 0.024% *
25 001A1301581 motor bracket 2 AC42NACBEA 0.00% 0.000% ×
26 0010450626 Indoor fan motor 2 AC42NACBEA 0.02% 0.024% *
27 001A1301578 left wallboard 1 AC42NACBEA 0.00% 0.000% ×
28 001A1231276 ornamental plate (left) 1 AC42NACBEA 0.00% 0.000% ×
29 001A3900006 Pipe temp. sensor indoor 1 AC42NACBEA 0.00% 0.000% ×
30 001A1431878 Indicator light cover 1 AC42NACBEA 0.00% 0.000% ×
31 0010400410 receive panel 1 AC42NACBEA 0.02% 0.024% *
32 001A1231279 ornamental plate of panel(left) 1 AC42NACBEA 0.00% 0.000% ×
33 001A1231280 middle ornamental plate 4 AC42NACBEA 0.00% 0.000% ×
34 001A1101169 Long blade assy 1 AC42NACBEA 0.00% 0.000% ×
35 001A1431800 fixing bracket left 1 AC42NACBEA 0.00% 0.000% ×
36 001A0100431 left fixing bracket 1 AC42NACBEA 0.00% 0.000% ×
37 001A1231272 left top cover assy 1 AC42NACBEA 0.00% 0.000% ×
38 001A1231274 front top cover assy 3 AC42NACBEA 0.00% 0.000% ×
39 001A1231281 Ornamental plate of panel right 1 AC42NACBEA 0.00% 0.000% ×
40 001A0100435 outlet grill hold middle 3 AC42NACBEA 0.00% 0.000% ×
41 001A1231275 top cover assy 3 AC42NACBEA 0.00% 0.000% ×
42 001A1101170 long blade 2 1 AC42NACBEA 0.00% 0.000% ×
43 001A0100432 outlet grill hold right 1 AC42NACBEA 0.00% 0.000% ×
44 001A1231273 right top cover assy 1 AC42NACBEA 0.00% 0.000% ×
45 001A1431746 fixing bracket right 1 AC42NACBEA 0.00% 0.000% ×
46 001A1443745 prompting pole 1 AC42NACBEA 0.00% 0.000% ×
47 001A3000198 Synchromotor 1 AC42NACBEA 0.02% 0.024% *
48 0010451255 Remote Controller 1 AC42NACBEA 0.01% 0.012%
49 001A1734260 Heat insulation pipe1 1 AC42NACBEA 0.00% 0.000% ×
50 001A1301575 plate assy left 1 AC42NACBEA 0.00% 0.000% ×
51 0010752258 evaporator 1 AC42NACBEA 0.01% 0.012%
52 001A1101171 Rear guard plate 1 AC42NACBEA 0.00% 0.000% ×
Duct type
AD36NAMBEA\AD42NAMBEA
Parts list
the proportion of
Spare parts Failure the spare-part
No. number Spare parts description in English Qty. Model rate stock Remark
1 001A1101223 Guard plate 1 1 AD42NAMBEA 0.000% 0.000% X
2 001A1101226 Guard plate 2 1 AD42NAMBEA 0.000% 0.000% X
3 0010752912 Evaporator assembly 1 AD42NAMBEA 0.010% 0.012%
4 001A0100744 Right fixing plate assembly 1 AD42NAMBEA 0.000% 0.000% X
5 001A1101203 Supporting plate assembly(right) 1 AD42NAMBEA 0.000% 0.000% X
6 001A1301988 Seal ring for scroll case 3 AD42NAMBEA 0.000% 0.000% X
7 001A2331089 Centrifugal fan 3 AD42NAMBEA 0.020% 0.024% *
8 001A17621153 Cushion 1 AD42NAMBEA 0.000% 0.000% X
9 001A17621151 Cushion 1 AD42NAMBEA 0.000% 0.000% X
10 001A17341291 Cushion 4 AD42NAMBEA 0.000% 0.000% X
11 001A14311066 Air outlet 4 AD42NAMBEA 0.000% 0.000% X
12 001A17341292 Cushion 4 AD42NAMBEA 0.000% 0.000% X
13 001A1101227 inlet wind connect frame 1 AD42NAMBEA 0.000% 0.000% X
14 001A17341156 Cushion 1 AD42NAMBEA 0.000% 0.000% X
15 001A17341269 Cushion 1 AD42NAMBEA 0.000% 0.000% X
16 001A1101228 Long fixing tendon 1 AD42NAMBEA 0.000% 0.000% X
17 001A1101224 Enclosure 1 AD42NAMBEA 0.000% 0.000% X
18 001A1101225 Inlet wind connect frame 1 AD42NAMBEA 0.000% 0.000% X
19 0010451262 Transformer 1 AD42NAMBEA 0.010% 0.012% *
20 001A1101206 Electrical box 1 AD42NAMBEA 0.010% 0.012%
21 001A1452909 Rubber ring 1 AD42NAMBEA 0.000% 0.000% X
22 001A1452861 Rubber ring 1 AD42NAMBEA 0.000% 0.000% X
23 0010451167 indoor PCB 1 AD42NAMBEA 0.020% 0.024% *
24 0010451265 Terminal block 1 AD42NAMBEA 0.020% 0.024% *
25 001A3600134 Fan capacitor 1 AD42NAMBEA 0.040% 0.048% *
26 001A3600237 Fan capacitor 1 AD42NAMBEA 0.040% 0.048% *
27 001A1301796 Electrical box cover assembly 1 AD42NAMBEA 0.000% 0.000% X
28 001A5002256 Fixing bolt 3 AD42NAMBEA 0.000% 0.000% X
29 001A1309785 W ater pump fixing stand 1 AD42NAMBEA 0.000% 0.000% X
30 001A17511246 Damping pad 3 AD42NAMBEA 0.000% 0.000% X
31 001A3000250 Dual shaft electric motor 1 AD42NAMBEA 0.020% 0.024% *
32 0010450169 Water pump motor 1 AD42NAMBEA 0.020% 0.024% *
33 001A1301786 Floater fixing stand 1 AD42NAMBEA 0.000% 0.000% X
34 001A14341141 Water drain pipe assembly 1 AD42NAMBEA 0.000% 0.000% X
35 001A1301783 Connecting plate 2 1 AD42NAMBEA 0.000% 0.000% X
36 001A1301784 Water pump support 1 AD42NAMBEA 0.000% 0.000% X
37 001A1301782 Connecting plate 1 1 AD42NAMBEA 0.000% 0.000% X
38 001A3400076 Float switch 1 AD42NAMBEA 0.000% 0.000% X
39 001A1301789 Fixed handle 1 2 AD42NAMBEA 0.000% 0.000% X
40 001A1301790 Fixed handle 2 2 AD42NAMBEA 0.000% 0.000% X
41 001A3000251 Single shaft electric motor 1 AD42NAMBEA 0.000% 0.000% X
42 001A1101205 Scroll case 3 AD42NAMBEA 0.000% 0.000% X
43 001A0100743 Left fixing plate assembly 1 AD42NAMBEA 0.000% 0.000% X
44 001A0900094 Water collecting pan assembly 1 AD42NAMBEA 0.000% 0.000% X
45 001A17621350 Cushion 1 AD42NAMBEA 0.000% 0.000% X
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first
time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3
months later.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and
should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in
the spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare
parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
Parts list
Spare parts Failure the proportion of the
No. number Spare parts description in English Qty. Model rate spare-part stock Remark
1 0010850776 Guard plate 1 1 AD36NAMBEA 0.000% 0.000% X
2 001A1101226 Guard plate 2 1 AD36NAMBEA 0.000% 0.000% X
3 0010752257 Evaporator assembly 1 AD36NAMBEA 0.010% 0.012%
4 001A0100744 Right fixing plate assembly 1 AD36NAMBEA 0.000% 0.000% X
5 001A1101203 Supporting plate assembly(right) 1 AD36NAMBEA 0.000% 0.000% X
6 001A1301988 Seal ring for scroll case 3 AD36NAMBEA 0.000% 0.000% X
7 001A2331089 Centrifugal fan 3 AD36NAMBEA 0.020% 0.024% *
8 001A17621153 Cushion 1 AD36NAMBEA 0.000% 0.000% X
9 001A17621151 Cushion 1 AD36NAMBEA 0.000% 0.000% X
10 001A17341291 Cushion 4 AD36NAMBEA 0.000% 0.000% X
11 001A14311066 Air outlet 4 AD36NAMBEA 0.000% 0.000% X
12 001A17341292 Cushion 4 AD36NAMBEA 0.000% 0.000% X
13 001A1101227 inlet wind connect frame 1 AD36NAMBEA 0.000% 0.000% X
14 001A17341156 Cushion 1 AD36NAMBEA 0.000% 0.000% X
15 001A17341269 Cushion 1 AD36NAMBEA 0.000% 0.000% X
16 001A1101228 Long fixing tendon 1 AD36NAMBEA 0.000% 0.000% X
17 001A1101224 Enclosure 1 AD36NAMBEA 0.000% 0.000% X
18 001A1101225 Inlet wind connect frame 1 AD36NAMBEA 0.000% 0.000% X
19 0010451262 Transformer 1 AD36NAMBEA 0.010% 0.012% *
20 001A1101206 Electrical box 1 AD36NAMBEA 0.010% 0.012%
21 001A1452909 Rubber ring 1 AD36NAMBEA 0.000% 0.000% X
22 001A1452861 Rubber ring 1 AD36NAMBEA 0.000% 0.000% X
23 0010451167 indoor PCB 1 AD36NAMBEA 0.020% 0.024% *
24 0010451265 Terminal block 1 AD36NAMBEA 0.020% 0.024% *
25 001A3600134 Fan capacitor 1 AD36NAMBEA 0.040% 0.048% *
26 001A3600237 Fan capacitor 1 AD36NAMBEA 0.040% 0.048% *
27 001A1301796 Electrical box cover assembly 1 AD36NAMBEA 0.000% 0.000% X
28 001A5002256 Fixing bolt 3 AD36NAMBEA 0.000% 0.000% X
29 001A1309785 W ater pump fixing stand 1 AD36NAMBEA 0.000% 0.000% X
30 001A17511246 Damping pad 3 AD36NAMBEA 0.000% 0.000% X
31 001A3000250 Dual shaft electric motor 1 AD36NAMBEA 0.020% 0.024% *
32 0010450169 Water pump motor 1 AD36NAMBEA 0.020% 0.024% *
33 001A1301786 Floater fixing stand 1 AD36NAMBEA 0.000% 0.000% X
34 001A14341141 Water drain pipe assembly 1 AD36NAMBEA 0.000% 0.000% X
35 001A1301783 Connecting plate 2 1 AD36NAMBEA 0.000% 0.000% X
36 001A1301784 Water pump support 1 AD36NAMBEA 0.000% 0.000% X
37 001A1301782 Connecting plate 1 1 AD36NAMBEA 0.000% 0.000% X
38 001A3400076 Float switch 1 AD36NAMBEA 0.000% 0.000% X
39 001A1301789 Fixed handle 1 2 AD36NAMBEA 0.000% 0.000% X
40 001A1301790 Fixed handle 2 2 AD36NAMBEA 0.000% 0.000% X
41 001A3000251 Single shaft electric motor 1 AD36NAMBEA 0.000% 0.000% X
42 001A1101205 Scroll case 3 AD36NAMBEA 0.000% 0.000% X
43 001A0100743 Left fixing plate assembly 1 AD36NAMBEA 0.000% 0.000% X
44 001A0900094 Water collecting pan assembly 1 AD36NAMBEA 0.000% 0.000% X
45 001A17621350 Cushion 1 AD36NAMBEA 0.000% 0.000% X
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first
time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3
months later.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should
be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the
spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts
may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be
marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
High static pressure duct unit
Parts list
the proportion of
Spare parts description in the spare-part
No. Spare parts number english Qty. Model Failure rate stock Remark
1 001A01001000 connection frame of inlet air 1 AD42NAHBEA 0.000% 0.000% x
2 0010151123 hanging 4 AD42NAHBEA 0.000% 0.000% x
3 0010851049 boarding assy. of liquid pipe 1 AD42NAHBEA 0.000% 0.000% x
4 001A0100999 fix blot assy. 1 AD42NAHBEA 0.000% 0.000% x
5 001A01001002 bottom plate assy. 1 AD42NAHBEA 0.000% 0.000% x
6 001A1301205 air discharge framework 1 AD42NAHBEA 0.000% 0.000% x
8 0010800284 cover board assy. 1 1 AD42NAHBEA 0.000% 0.000% x
9 0010800282 fix tendon assy. 1 1 AD42NAHBEA 0.000% 0.000% x
10 0010800285 cover board assy. 2 1 AD42NAHBEA 0.000% 0.000% x
11 001A13011050 bracket of floater 1 AD42NAHBEA 0.000% 0.000% x
12 0010800290 evaporator fixing plate 3 1 AD42NAHBEA 0.000% 0.000% x
13 0010752259 evaporator assy. 1 AD42NAHBEA 0.000% 0.000% x
14 0010800286 cover board assy. 3 1 AD42NAHBEA 0.000% 0.000% x
15 0010800283 fix tendon assy. 2 1 AD42NAHBEA 0.000% 0.000% x
16 0010800289 evaporator fixing plate 2 1 AD42NAHBEA 0.000% 0.000% x
17 0010451262 transformer 1 AD42NAHBEA 0.020% 0.024% *
18 0010400298 relay 3 AD42NAHBEA 0.030% 0.036% *
19 001A3600254 fan motor capacitor 1 AD42NAHBEA 0.040% 0.048% *
20 001A13011035 electrical box cover 1 AD42NAHBEA 0.010% 0.012%
21 001A3300352 Fan Speed Controller 1 AD42NAHBEA 0.020% 0.024% *
22 001A5745116 Power line clip 1 AD42NAHBEA 0.000% 0.000% x
23 0010451470 wiring harness 1 AD42NAHBEA 0.000% 0.000% x
24 0010451167 indoor PCB 1 AD42NAHBEA 0.020% 0.024% *
25 0010451265 termianl block 1 AD42NAHBEA 0.020% 0.024% *
26 0010800287 electrical box assy. 1 AD42NAHBEA 0.000% 0.000% x
27 0010752120 liquid pipe assy. 1 AD42NAHBEA 0.000% 0.000% x
28 0010700869 air pipe assy. 1 AD42NAHBEA 0.000% 0.000% x
30 0010800290 evaporator fixing plate 3 1 AD42NAHBEA 0.000% 0.000% x
31 001A3400160 float switch 1 AD42NAHBEA 0.000% 0.000% x
32 001A13011045 motor fixing bolt 1 AD42NAHBEA 0.000% 0.000% x
33 001A13011045 motor fixing bolt 1 AD42NAHBEA 0.000% 0.000% x
34 001A13011039 motor bracket 1 AD42NAHBEA 0.000% 0.000% x
35 001A13011040 snail shell 1 1 AD42NAHBEA 0.000% 0.000% x
36 001A2301102 fan 1 1 AD42NAHBEA 0.020% 0.024% *
37 001A13011044 hermitic circle of snail shell 1 AD42NAHBEA 0.000% 0.000% x
38 001A13011044 hermitic circle of snail shell 1 AD42NAHBEA 0.000% 0.000% x
39 001A2301103 fan 2 1 AD42NAHBEA 0.020% 0.024% *
40 001A13011041 snail shell 2 1 AD42NAHBEA 0.000% 0.000% x
41 001A5401035 washer 1 AD42NAHBEA 0.000% 0.000% x
42 001A3000291 indoor motor 1 AD42NAHBEA 0.020% 0.024% *
43 0010800329 drain pan assy. 1 AD42NAHBEA 0.000% 0.000% x
44 0010800280 guarding plate assy.2 1 AD42NAHBEA 0.000% 0.000% x
45 0010800281 guarding plate assy.1 1 AD42NAHBEA 0.000% 0.000% x

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first
time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3
months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and
should be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in
the spare-part warehouse accord with the actual case,should be marked with " ".

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare
parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
Parts list
Spare parts description in the proportion of the
No. Spare parts number english Qty. Model Failure rate spare-part stock Remark
1 001A01001000 connection frame of inlet air 1 AD36NAHBEA 0.000% 0.000% x
2 0010151123 hanging 4 AD36NAHBEA 0.000% 0.000% x
3 0010851049 boarding assy. of liquid pipe 1 AD36NAHBEA 0.000% 0.000% x
4 001A0100999 fix blot assy. 1 AD36NAHBEA 0.000% 0.000% x
5 001A01001002 bottom plate assy. 1 AD36NAHBEA 0.000% 0.000% x
6 001A1301205 air discharge framework 1 AD36NAHBEA 0.000% 0.000% x
8 0010800284 cover board assy. 1 1 AD36NAHBEA 0.000% 0.000% x
9 0010800282 fix tendon assy. 1 1 AD36NAHBEA 0.000% 0.000% x
10 0010800285 cover board assy. 2 1 AD36NAHBEA 0.000% 0.000% x
11 001A13011050 bracket of float 1 AD36NAHBEA 0.000% 0.000% x
12 0010800290 evaporator fixing plate 3 1 AD36NAHBEA 0.000% 0.000% x
13 0010752259 evaporator assy. 1 AD36NAHBEA 0.000% 0.000% x
14 0010800286 cover board assy. 3 1 AD36NAHBEA 0.000% 0.000% x
15 0010800283 fix tendon assy. 2 1 AD36NAHBEA 0.000% 0.000% x
16 0010800289 evaporator fixing plate 2 1 AD36NAHBEA 0.000% 0.000% x
17 0010451262 transformer 1 AD36NAHBEA 0.020% 0.024% *
18 0010400298 relay 3 AD36NAHBEA 0.030% 0.036% *
19 001A3600254 fan motor capacitor 1 AD36NAHBEA 0.040% 0.048% *
20 001A13011035 electrical box cover 1 AD36NAHBEA 0.010% 0.012%
21 001A3300352 Fan Speed Controller 1 AD36NAHBEA 0.020% 0.024% *
22 001A5745116 Power line clip 1 AD36NAHBEA 0.000% 0.000% x
23 0010451470 wiring harness 1 AD36NAHBEA 0.000% 0.000% x
24 0010451167 indoor PCB 1 AD36NAHBEA 0.020% 0.024% *
25 0010451265 termianl block 1 AD36NAHBEA 0.020% 0.024% *
26 0010800287 electrical box assy. 1 AD36NAHBEA 0.000% 0.000% x
27 0010752120 liquid pipe assy. 1 AD36NAHBEA 0.000% 0.000% x
28 0010700869 air pipe assy. 1 AD36NAHBEA 0.000% 0.000% x
30 0010800290 evaporator fixing plate 3 1 AD36NAHBEA 0.000% 0.000% x
31 001A3400160 float switch 1 AD36NAHBEA 0.000% 0.000% x
32 001A13011045 motor fixing bolt 1 AD36NAHBEA 0.000% 0.000% x
33 001A13011045 motor fixing bolt 1 AD36NAHBEA 0.000% 0.000% x
34 001A13011039 motor bracket 1 AD36NAHBEA 0.000% 0.000% x
35 001A13011040 snail shell 1 1 AD36NAHBEA 0.000% 0.000% x
36 001A2301102 fan 1 1 AD36NAHBEA 0.020% 0.024% *
37 001A13011044 hermitic circle of snail shell 1 AD36NAHBEA 0.000% 0.000% x
38 001A13011044 hermitic circle of snail shell 1 AD36NAHBEA 0.000% 0.000% x
39 001A2301103 fan 2 1 AD36NAHBEA 0.020% 0.024% *
40 001A13011041 snail shell 2 1 AD36NAHBEA 0.000% 0.000% x
41 001A5401035 washer 1 AD36NAHBEA 0.000% 0.000% x
42 001A3000291 indoor motor 1 AD36NAHBEA 0.020% 0.024% *
43 0010800329 drain pan assy. 1 AD36NAHBEA 0.000% 0.000% x
44 0010800280 guarding plate assy.2 1 AD36NAHBEA 0.000% 0.000% x
45 0010800281 guarding plate assy.1 1 AD36NAHBEA 0.000% 0.000% x
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first
time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3
months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should
be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the
spare-part warehouse accord with the actual case,should be marked with " ".

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts
may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be
marked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
Parts list
the proportion of
Spare parts Spare parts description in Failure the spare-part
No. number english Qty. Model rate stock Remark
1 001A1231233 Inlet grill 1 AP42NACBEA 0.00% 0.000% ×
2 001A1301502 Inlet grill insert 2 AP42NACBEA 0.00% 0.000% ×
3 0010850578 Front panel 1 AP42NACBEA 0.00% 0.000% ×
4 001A0600657 Operation panel 1 AP42NACBEA 0.00% 0.000% ×
5 001A1432687 Horizontal blade 6 AP42NACBEA 0.00% 0.000% ×
6 001A1734970 Vertical air outlet pad 2 AP42NACBEA 0.00% 0.000% ×
7 001A1431689 Vertical blade 1 AP42NACBEA 0.00% 0.000% ×
8 001A1734832 Air damper pad 1 AP42NACBEA 0.00% 0.000% ×
9 001A1301508 Air damper 1 AP42NACBEA 0.00% 0.000% ×
10 0010751945 Heat exchanger assembly 1 AP42NACBEA 0.01% 0.012%
11 001A1301847 Evaporator left mounting plate 1 AP42NACBEA 0.00% 0.000% ×
12 001A1301848 Evaporator right mounting plate 1 AP42NACBEA 0.00% 0.000% ×
13 0010150194 Left board 1 AP42NACBEA 0.00% 0.000% ×
14 001A17341222 Left board pad 1 AP42NACBEA 0.00% 0.000% ×
15 001A1301846 Top cover plate 1 AP42NACBEA 0.00% 0.000% ×
16 001A1431994 Cover 1 AP42NACBEA 0.00% 0.000% ×
17 001A17561372 Side board horizontal pad 1 AP42NACBEA 0.00% 0.000% ×
18 0010150195 Right board 1 AP42NACBEA 0.00% 0.000% ×
19 001A0100787 Back guard 1 AP42NACBEA 0.00% 0.000% ×
20 001A1101145 Wiring plate 1 AP42NACBEA 0.00% 0.000% ×
21 001A1734842 Thermal insulation pipe 1 AP42NACBEA 0.00% 0.000% ×
22 001A5002078 Special nut 1 AP42NACBEA 0.00% 0.000% ×
23 001A0100575 Bottom plate 1 AP42NACBEA 0.00% 0.000% ×
24 001A1745106 Plastic cushion 1 AP42NACBEA 0.00% 0.000% ×
25 001A3000249 Motor 1 AP42NACBEA 0.02% 0.024% *
26 001A5739020 Mounting wiring clamp 1 AP42NACBEA 0.00% 0.000% ×
27 001A1101146 Pipe press plate 1 AP42NACBEA 0.00% 0.000% ×
28 001A1752911 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×
29 001A1452695 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×
30 0010250163 Drain pan 1 AP42NACBEA 0.00% 0.000% ×
31 001A1452695 Fan pad 1 AP42NACBEA 0.00% 0.000% ×
32 001A5102050 Nut 1 AP42NACBEA 0.00% 0.000% ×
33 001A2300095 Centrifugal fan 1 AP42NACBEA 0.02% 0.024% *
34 001A1742931 Down shell press plate cushion 1 AP42NACBEA 0.00% 0.000% ×
35 001A1301445 Down shell press plate 1 AP42NACBEA 0.00% 0.000% ×
36 001A1431647 Wiring clamp (plasticizing) 1 AP42NACBEA 0.00% 0.000% ×
37 001A1301437 Filter guide AP42NACBEA 0.00% 0.000% ×
38 0010200026 Air ring 1 AP42NACBEA 0.00% 0.000% ×
39 001A0100385 Down shell 1 AP42NACBEA 0.00% 0.000% ×
40 001A2400102 Filter 1 AP42NACBEA 0.00% 0.000% ×
41 001A0100075 Door lock 1 AP42NACBEA 0.00% 0.000% ×
42 001A1734967 Sealing plate 1 AP42NACBEA 0.00% 0.000% ×
43 001A17621241 Sealing plate 1 AP42NACBEA 0.00% 0.000% ×
44 001A1757833 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×
45 001A3000016A Synchro-motor 1 AP42NACBEA 0.02% 0.024% *
46 001A1301448 Wring cover 1 AP42NACBEA 0.00% 0.000% ×
47 001A1431647 Wire clamp 1 AP42NACBEA 0.00% 0.000% ×
48 001A4000107 Terminal block(6 colume) 1 AP42NACBEA 0.00% 0.000% ×
49 0010450450 Transformer 1 AP42NACBEA 0.01% 0.012%
50 001A3600134 Fan capacitor 1 AP42NACBEA 0.04% 0.048% *
51 001A1452695 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×
52 0010401369 Indoor PCB 1 AP42NACBEA 0.02% 0.024% *
53 / / AP42NACBEA
54 001A1301447 Electric box 1 AP42NACBEA 0.00% 0.000% ×
55 001A1301444 Mounting beam 1 AP42NACBEA 0.00% 0.000% ×
56 001A1734967 Sealing plate 1 AP42NACBEA 0.00% 0.000% ×
57 001A1752840 Supporting plate 1 AP42NACBEA 0.00% 0.000% ×
58 001A3900006 Pipe temp. sensor 1 AP42NACBEA 0.00% 0.000% ×
59 001A0100407 Splint 1 AP42NACBEA 0.00% 0.000% ×
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-
parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with
the actual quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts
warehouse,and should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may
stock in the spare-part warehouse accord with the actual case,should be marked with " ".

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The
spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
Outdoor
Model: AU36NAIBEA\AU42NAIBEA
Parts list
the proportion of
Spare parts Spare parts description in Failure
the spare-part
No. number English Qty. Model rate
stock Remark
1 001A0100122 Front grille 2 AU42NAIBEA 0.0000% 0.0000% X
2 001A1301707 service panel assy 1 AU42NAIBEA 0.0000% 0.0000% X
3 001A1301640 Front panel 2 AU42NAIBEA 0.0000% 0.0000% X
4 001A5402022 Axial fan 2 AU42NAIBEA 0.0200% 0.0240% *
5 0010450279 Fan motor 2 AU42NAIBEA 0.0200% 0.0240% *
6 001A0100740 Bracket for fan motor 1 AU42NAIBEA 0.0000% 0.0000% X
7 0010751389 Condenser assy. 1 AU42NAIBEA 0.0100% 0.0120%
8 0010451291 AC contactor 1 AU42NAIBEA 0.0100% 0.0120%
9 001A3600018 Capacitor for fan motor 2 AU42NAIBEA 0.0400% 0.0480% *
10 001A4000158 connection block 1 AU42NAIBEA 0.0100% 0.0120%
11 0010451346 Resumable transformer 1 AU42NAIBEA 0.0500% 0.0600% *
12 0010451295 outdoor PCB 1 AU42NAIBEA 0.0200% 0.0240% *
13 001A3900110 ambient temp. sensor 1 AU42NAIBEA 0.0100% 0.0120% *
13 0010451314 coil temp. sensor 1 AU42NAIBEA 0.0100% 0.0120% *
13 0010450398 discharging temp. sensor 1 AU42NAIBEA 0.0100% 0.0120% *
14 001A5736055 clip for sensor 1 AU42NAIBEA 0.0000% 0.0000% X
15 0010451265 Terminal block 1 AU42NAIBEA 0.0100% 0.0120%
17 001A0100827 Top cover assy. 1 AU42NAIBEA 0.0000% 0.0000% X
18 001A0100733 Slide plate(right) 1 AU42NAIBEA 0.0000% 0.0000% X
19 001A1303642 Back grille 1 AU42NAIBEA 0.0000% 0.0000% X
20 0010400127 High pressure switch 1 AU42NAIBEA 0.0000% 0.0000% X
21 001A21111254 segregator 1 AU42NAIBEA 0.0000% 0.0000% X
22 0010850850 4-way valve 1 AU42NAIBEA 0.0000% 0.0000% X
23 001A2500121 coil of4-way valve 1 AU42NAIBEA 0.0200% 0.0240% *
24 001A2400128 muffle 1 AU42NAIBEA 0.0000% 0.0000% X
25 0010750471 Compressor 1 AU42NAIBEA 0.0600% 0.0720% *
26 0010451431 wiring harness 1 AU42NAIBEA 0.0100% 0.0120%
27 001A2500149 2-way stop valve 1 AU42NAIBEA 0.0000% 0.0000% X
28 001A2500150 3-way stop valve 1 AU42NAIBEA 0.0000% 0.0000% X
29 001A1301762 Valve pedestal 1 AU42NAIBEA 0.0000% 0.0000% X
30 001A0100735 Bottom cover assy. 1 AU42NAIBEA 0.0000% 0.0000% X
31 001A5701062 Power line clip 1 AU42NAIBEA 0.0000% 0.0000% X
32 001A0100734 Partition plate 1 AU42NAIBEA 0.0000% 0.0000% X
33 001A17561212 Partition plate tray 1 AU42NAIBEA 0.0000% 0.0000% X
34 001A1436160 handle 1 AU42NAIBEA 0.0000% 0.0000% X
35 001A1301763 cover 1 AU42NAIBEA 0.0000% 0.0000% X
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-
parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with
the actual quantity 3 months later.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts
warehouse,and should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may
stock in the spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The
spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-
part warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
Parts list
Spare parts Spare parts description in Failure the proportion of the
No. number English Qty. Model rate spare-part stock Remark
1 001A0100122 Front grille 2 AU36NAIBEA 0.0000% 0.0000% X
2 001A1301707 service panel assy 1 AU36NAIBEA 0.0000% 0.0000% X
3 001A1301640 Front panel 2 AU36NAIBEA 0.0000% 0.0000% X
4 001A5402022 Axial fan 2 AU36NAIBEA 0.0200% 0.0240% *
5 0010450279 Fan motor 2 AU36NAIBEA 0.0200% 0.0240% *
6 001A0100740 Bracket for fan motor 1 AU36NAIBEA 0.0000% 0.0000% X
7 0010850975 Condenser assy. 1 AU36NAIBEA 0.0100% 0.0120%
8 0010451291 AC contactor 1 AU36NAIBEA 0.0100% 0.0120%
9 001A3600018 Capacitor for fan motor 2 AU36NAIBEA 0.0400% 0.0480% *
10 001A4000158 connection block 1 AU36NAIBEA 0.0100% 0.0120%
11 0010451346 Resumable transformer 1 AU36NAIBEA 0.0500% 0.0600% *
12 0010451295 outdoor PCB 1 AU36NAIBEA 0.0200% 0.0240% *
13 001A3900110 ambient temp. sensor 1 AU36NAIBEA 0.0100% 0.0120% *
13 0010451314 coil temp. sensor 1 AU36NAIBEA 0.0100% 0.0120% *
13 0010450398 discharging temp. sensor 1 AU36NAIBEA 0.0100% 0.0120% *
14 001A5736055 clip for sensor 1 AU36NAIBEA 0.0000% 0.0000% X
15 0010451265 Terminal block 1 AU36NAIBEA 0.0100% 0.0120%
17 001A0100827 Top cover assy. 1 AU36NAIBEA 0.0000% 0.0000% X
18 001A0100733 Slide plate(right) 1 AU36NAIBEA 0.0000% 0.0000% X
19 001A0100767 Back grille 1 AU36NAIBEA 0.0000% 0.0000% X
20 0010400127 High pressure switch 1 AU36NAIBEA 0.0000% 0.0000% X
21 001A21111254 segregator 1 AU36NAIBEA 0.0000% 0.0000% X
22 0010850850 4-way valve 1 AU36NAIBEA 0.0000% 0.0000% X
23 001A2500121 coil of4-way valve 1 AU36NAIBEA 0.0200% 0.0240% *
24 001A2400128 muffle 1 AU36NAIBEA 0.0000% 0.0000% X
25 0010750196 Compressor 1 AU36NAIBEA 0.0600% 0.0720% *
26 0010451431 wiring harness 1 AU36NAIBEA 0.0100% 0.0120%
27 001A2500149 2-way stop valve 1 AU36NAIBEA 0.0000% 0.0000% X
28 001A2500150 3-way stop valve 1 AU36NAIBEA 0.0000% 0.0000% X
29 001A1301762 Valve pedestal 1 AU36NAIBEA 0.0000% 0.0000% X
30 001A0100735 Bottom cover assy. 1 AU36NAIBEA 0.0000% 0.0000% X
31 001A5701062 Power line clip 1 AU36NAIBEA 0.0000% 0.0000% X
32 001A0100734 Partition plate 1 AU36NAIBEA 0.0000% 0.0000% X
33 001A17561212 Partition plate tray 1 AU36NAIBEA 0.0000% 0.0000% X
34 001A1436160 handle 1 AU36NAIBEA 0.0000% 0.0000% X
35 001A1301763 cover 1 AU36NAIBEA 0.0000% 0.0000% X
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-
parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with
the actual quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts
warehouse,and should be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may
stock in the spare-part warehouse accord with the actual case,should be marked with " ".

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The
spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
PERFORMANCE CURVES

13 Performance curves
a)performance curves
1)AD36NAMBEA+AU36NAIBEA
Cool capacity graph

14
13
12 20
Capacity(KW)

11 22
25
10
27
9
30
8 32
7
Indoor
6 DB( )
-7 5 15 25 35 43
Outdoor DB( )

EER graph

3.5
20
3 22
25
EER

2.5
27
2 30
32
1.5
Indoor
DB( )
1
-7 5 15 25 35 43
Outdoor DB( )

- 96 -
Heat capacity graph (only heat type available)

13

12
16
11
18
Capacity(KW)

10 20
22
9 24
8 26
28
7
Indoor
6 DB( )
-7 -5 0 6 10 15
Outdoor DB( )

COP graph (only heat type available)

3.5
16
3 18
20
COP

2.5 22
24
2 26
28
1.5
Indoor
1 DB( )
-7 -5 0 6 10 15
Outdoor DB( )

- 97 -
PERFORMANCE CURVES

2)AB36NACBEA+AU36NAIBEA

a Cooling capacity graph

14
13
12 20
Capacity(KW)

11 22
25
10
27
9
30
8 32
7
Indoor
6 DB( )
-7 5 15 25 35 43
Outdoor DB( )
b EER graph
4

3.5
20
3 22
25
EER

2.5
27
2 30
32
1.5
Indoor
DB( )
1
-7 5 15 25 35 43
Outdoor DB( )

- 98 -
PERFORMANCE CURVES

3)AB42NACBEA+AU42NAIB
E A
a Cooling capacity graph

18
16
14 20
Capacity(KW)

12 22
10 25
8 27
6 30
4 32
2 Indoor
0 DB( )
-7 5 15 25 35 43
Outdoor DB( )

b EER graph

5
4.5
20
4
22
3.5 25
EER

3 27
2.5 30
2 32
1.5
1 Indoor
DB( )
-7 5 15 25 35 43
Outdoor DB( )

- 99-
PERFORMANCE CURVES

4)AC36NACBEA+AU36NAIBEA
Cool capacity graph

14
13
12 20
Capacity(KW)

11 22
25
10
27
9
30
8 32
7
Indoor
6 DB( )
-7 5 15 25 35 43
Outdoor DB( )

EER graph

3.5
20
3 22
25
EER

2.5
27
2 30
32
1.5
Indoor
DB( )
1
-7 5 15 25 35 43
Outdoor DB( )

- 100 -
PERFORMANCE CURVES

5)AC42NACBEA+AU42NAIBEA
Cool capacity graph

18
16
14 20
Capacity(KW)

12 22
10 25
8 27
6 30
4 32
2 Indoor
0 DB( )
-7 5 15 25 35 43
Outdoor DB( )

EER graph

5
4.5
20
4
22
3.5 25
EER

3 27
2.5 30
2 32
1.5
1 Indoor
DB( )
-7 5 15 25 35 43
Outdoor DB( )

- 101 -
b)Ambient temperature range for cooling operation:

50
outdoor ambient temperature ( C)

40

consecutive operation

unload period
35

30

25

20

15
0 15 20 23 25 28 30
indoor ambient temperature ( C)
Ambient temperature range for heating operation:
outdoor ambient temperature ( C)

20

15
consecutive operation

10
unload period

-5

-10

5 7 10 15 20 25 27 30
indoor ambient temperature ( C)

102
c). Capability modification curver
AU42NAIBEA (Cold producing/Heat producing)
Alteration curve of outdoor air dry-bulb temperature

capability modification(kw)
15

20 30 35 40 43

Outdoor air dry-bulb temperature( )

Alteration curve of outdoor air wet-bulb temperature


15
capability modification(kw)

13
12
11

8
7
-10 -5 0 5 10 15

103
14. NOISE LEVEL CHARTS
1)Convertible Type
Cooling

Heating

22

- 104 -
2)Cassette type
Cooling

Heating

-105 -
AIR VELOCITY DISTRIBUTION

15.Air Velocity Distribution

1)AB36NACBEA AB42NACBEA
a. Cooling / Air Velocity Distribution
Cooling
Blowy angle:40
Air Velocity Distribution

m/s m/s

0
4 2 1 0 1 2 4

b. Cooling / Temperature Distribution


Cooling
Blowy angle:40
Temperature Distribution

22
22

25
25
27
27

0
4 2 1 0 1 2 4

- 106-
AIR VELOCITY DISTRIBUTION

2) AC36NACBEA
a. Cooling / Air Velocity Distribution
Cooling
Blowy angle:25
Air Velocity Distribution

2.4

0 5.5

b. Cooling / Temperature Distribution


Cooling
Blowy angle:25
Temperature Distribution

2.4
27
25
22

0 5.5

- 107-
AIR VELOCITY DISTRIBUTION

3)AD36NAMBEA\ AD42NAMBEA

cooling
air discharge angle 5
Air Velocity distribution

2.4

1.8
0.5

0 5.5

cooling
air discharge angle 5
Temperature distribution
2.4

1.8
25 27
22

0 5.5

- 108 -