This worker is supported by Foundation of Liaoning Province Education Fig.1 Geometrical structure of main insulation for transformer
Bureau under Grant 05L279.
4427
The electric field calculation combined with boundary 3mm and 4 mm in the main insulation structures. The distance
condition for the solved region are given by from high voltage coils to yoke core is 70mm and the distance
⎧ from high voltage coils to bottom yoke core is 70mm .The
⎪ 1 ∂ ∂ϕ ∂ 2ϕ square ring is not put on the terminal of high voltage coils.
⎪ (r )+ 2 = 0
⎪ r ∂r ∂r ∂z
⎪ϕ (CDEF ) = 0
⎪
⎨ϕ ( AB) = 0 (4)
⎪ ∂ϕ
⎪ =0 (BC、 AF )
⎪ ∂n
⎪ ∂ϕ1 ∂ϕ
⎪ε1 = ε2 2 (GH )
⎩ ∂n ∂n
4428
Fig.7 Electric intensity curves around high voltage coils
Fig.5 Potential distribution of the old type main insulation The manufacture costs have been reduced by main insulation
The potential distribution for the new type main insulation structure improved. The costs of old and new type transformer
structures and the are shown in Fig.6 It is concluded from are given in Table I. We can know from Table I that the copper
calculation results that the maximum of electric intensity is weight has been reduced 142kg, the iron weight has been
7.861 kV/mm. The maximum of electric intensity can be found reduced 811kg and the oil weight has been reduced 525kg. The
in inner side of angle ring next to the terminal of high voltage
valid costs has been reduced 6.2%. It is saved ¥120,000 if a
coils. It is well known that electric field is concentrative overly
transformer’s price is ¥2000,000.
if the main insulation distance has been reduced from 40mm to
TABLE I
38mm.
THE MAXIMUM OF ELECTRIC INTENSITY AT ANGLE RING TURNING
Width of main Copper weight Iron weight
insulation ( mm ) ( kg ) (kg)
40.00 4878 9816
38.00 4736 9005
V. EXPERIMENTS RESULTS
The distance of new type main insulation structure of 110kV
power transformer has been reduced largely, so the
measurement and experiments must be taken to insure the
reliability of insulation design for power transformer. The
Fig.6 Potential distribution of the new type main insulation condition and results for applied over-voltage test is shown in
It can be derived from calculation that the shape of angle Table II and the condition and results for induced over-voltage
ring should keep the same as possible as shape of the equal test is also given in Table III.
potential curves. Otherwise, the slip discharge may happen due TABLE II
to the action of the tangential component of electric intensity. RESULTS FOR APPLIED OVER-VOLTAGE TEST
Fig .7 shows the electric intensity vector curves around high
Position of applied Test voltage Test time Results
voltage coils. It can be seen that the higher intensity occurs voltage ( kV) (s)
around the terminal of the high voltage coils.
Comparing the manufacturing cost of the two examples, the High voltage to ground 140 60 Pass
or low voltage
advantages and practicability of the new main insulation
structure are feasible. Low voltage to ground 25 60 Pass
or high voltage
4429
TABLE III
Upk=-479.58kV T1=1.48us T2=49.01us
RESULTS FOR INDUCED OVER-VOLTAGE TEST Tested
50% lightning wave
Product
Position of switching Applied voltage Induced voltage
voltage (kV) (kV)
5 L.V. H.V.
12.6 200
2 200 30 Pass
REFERENCES
[1] Lu Changbai, “Experiments Studies on main Insulation Structures for
10kV, 35kV power transformers,” Transformer, 2004, 41(9):18-22.
[2] Guo Zhenyan, “35kV Analysis of technology and economy for 35kV
power transformers,” Transformer, 2000, 37(5): 1-5.
[3] Takahashi E,Shirasaks Y,Okuyama, “Analysis of an anisotropic nonlinear
electric field with a discussion of dielectric tests for converter transformer
and smoothing reators,” IEEE Trans. on PD, 1994, 9(3): 1480-1486.
[4] Kurita A , Takahashi E , Ozawa J et al, “DC flashover voltage
characteristics and their calculation method for oil-immersed insulation
systems in HVDC transformers,” IEEE Trans. On PD, 1986, 1(3)
:184-190.
b) Tested wave for 100% lightning over-voltage at T2=48.9us [5] Takahashi E, Tsutsumi Y, Okuyama K et al, “Partial discharge
characteristics of oil-immersed insulation systems under DC combined
DC-AC and DC reversed polarity voltage,” IEEE Trans.on PAS, 1976, 95
VI. CONCLUSIONS (1):411-420.
1) The maximum of electric intensity is 8.354kV/mm for [6] Y.M.Li, Y.Qiu, L.L.Li, G.S.Jiang, E.Kuffel, “New Approach to
Calculation of Electric Field in Three-core Power Cable,” IEEE Trans. on
improved transformer. It is less than the intensity permissible Power Delivery, Vol.5, No.2, April 1990, pp866-872.
value 8.5kV/mm. [7] Liang Z G,Tang R Y,Wang C C,Hu Y, “A software package of 3D
2) 6.2% manufacturing costs of power transformer is saved transient eddy current field analysis for transformer ,” Procceedings of
by reducing insulation distance from 40mm to 38mm. ICEF’2000, Beijing, China, International Academic Publisher,
2000:300-30.
4430