Sei sulla pagina 1di 14

Relay symbols and device

numbers; selection from


1MRK 590 006-BEN
IEC 617-, IEEE C37.2-1991 and Page 1
Issued June 1999
IEEE C37.2-1979 Changed since July 1998
Data subject to change without notice

Symbols and Symbols and designations, I Earth fault current


designations based on the IEC 617-series,
IEC 617-7 (1983) and others I Current to frame

Block symbols and qualifying symbols IN Current in the neutral conductor

1. General block symbols IN-N Current between neutrals of two


Protection relay polyphase systems
The asterisk must be Iub Current unbalance
replaced by one or more
letters or qualifying
U Voltage
symbols indicating the
parameters of the device
dP/dt Power derivative
Protection relay with
enabling input Q Reactive power

R Resistance
Protection relay with
blocking input X Reactance

Z Impedance

2. Parameters and functions


f Frequency
I Current

n Rotational speed
I Reverse current

F Magnetic flux
Id Differential current

j Phase angle
Id/I Percentage differential current
(current restraint)
Q Temperature

Inf Current of nth harmonic


Thermal effect

I1, (Ip) Positive sequence current


component
Flash-over, Fault

I2, (In) Negative sequence current


component
Delay

I0, (Ih) Zero sequence current


component t Delay at transition to ON-state,
pick-up delay

Irsd Residual current


Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 2
and IEEE C37.2-1979

Symbols and Relay with make contact,


designations (cont’d) SYNC Synchronizing (check) delayed when the relay is
energized.
BLOCK Blocking device Pick-up delay

LO Lock-out Relay with brake contact,


delayed when the relay is
deenergized.
TCS Trip circuit supervision Drop-out delay

X/Y Translation of signal


Overcurrent relay with
U short-circuiting connector
A/D or /# Analog to digital conversion

> Operation above a set value,


e.g. overcurrent Coils

< Operation below a set value, Relay with one winding


e.g. underimpedance

>> Operation above a high set Relay with two windings


stage

Examples of protection relays Operate and reset coil


R

Relays and relay parts

Relay contacts

Make contact

Auxiliary relay with mechanical contacts Brake contact

Change-over contact
(break before make)

Auxiliary relay, block symbol


Change-over contact,
delayed when releasing

Change-over contact,
delayed when operating

Switch contacts
Static relay with terminals for external auxiliary
Push-button operated
voltage supply
contact with automatic
return
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 3
and IEEE C37.2-1979

Test switch contacts Indications


Indicator with self reset, indi-
cates when coil is energized.
Annunciator element (target)

Indicator light, lamp or led

Hand reset indication, indicates


1. Break-contact (voltage supply circuit), late
when the coil is energized and
opening and early closing upon insertion
remains visible even when the
and withdrawal, respectively, of the test han-
coil is not energized
dle. Note that the test switch contacts
number 1 and 18 (12) will not be opened
when the test handle RTXH 18 (24) is Components
inserted.
2. Break-contact (trip circuits), early opening Capacitor, general symbol
and late closing upon insertion and with-
drawal respectively, of the test handle.
3. Make before break contacts with shorting Polarized capacitor
connection (CT secondary circuits), late
opening and early closing upon insertion
and withdrawal respectively, of the test Resistor, general symbol
handle.

Potentiometer
Resistor with two fixed end
terminals and one movable
terminal
Varistor
Voltage dependent non-linear
resistor
Fixed trimming resistor
Resistor with two fixed end
terminals and one movable
terminal for fixed setting
(trimming)

Diode, semiconductor

Reference diode
Zener diode
Voltage regulator diode
Single-phase transformer with
two windings
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 4
and IEEE C37.2-1979

Symbols and
designations (cont’d) Designations Divider (by 5)
Ir, Ur Rated current, voltage

Band-pass filter
I b, Ub Base current, voltage

Is, Us Set current, voltage


Time element delayed
on pick-up, 200 ms
L1, L2, L3, N Phase designations

Alternating current, ac
Time element delayed
Direct current, dc on drop-out, 70 ms

Ac and dc

Adjustable time
UL Auxiliary tripping voltage
element delayed on
pick-up
EL Auxiliary electronic voltage

RL Auxiliary relay voltage

Time element non


re-triggable pulse
Logic elements
Logic setting signal
DIR
(including on-off)
LOOPDELAY Loop delay output
(T) = input (T-1)

BC Binary input signal


Light emitting diode
(LED)
AND gate
C=AxB
Earth fault over-
current dependent
time function
OR gate
C=A+B

Input inverted

Output inverted Directional earth fault


overcurrent function

Signal summation
circuit
C = A + (-B) EF UCH
Level detector, earth
fault voltage check
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 5
and IEEE C37.2-1979

IEEE device IEEE device numbers and func- Device Definition


numbers and tions for switchgear apparatus number and function
functions The devices in switching equipments are 6 Starting circuit breaker is a device
referred to by numbers, with appropriate suf- whose principal function is to connect
fix letters when necessary, according to the a machine to its source of starting
functions they perform. voltage.

These numbers are based on a system adopted 7 Rate-of-rise relay is a relay that func-
as standard for automatic switchgear by tions on an excessive rate of rise of
IEEE, and incorporated in American current.
Standard C37.2-1979. This system is used in
connection diagrams, in instruction books, 8 Control power disconnecting
and in specifications. device is a disconnecting device,
such as a knife switch, circuit breaker,
or pull-out fuse block, used for the
Device Definition
purpose of respectively connecting
number and function
and disconnecting the source of
1 Master element is the initiating control power to and from the control
device, such as a control switch, bus or equipment.
voltage relay, float switch etc., that
serves either directly, or through such
9 Reversing device is used for the
permissive devices as protective and
purpose of reversing a machine field
time-delay relays, to place an equip-
or for performing any other reversing
ment in or out of operation.
functions.

2 Time-delay starting or closing relay


10 Unit sequence switch is used to
is a device that functions to give a
change the sequence in which units
desired amount of time delay before or
may be placed in and out of service in
after any point of operation in a switch-
multiple-unit equipment.
ing sequence or protective relay sys-
tem, except as specifically
provided by device functions 48, 62 11 Multifunction device is a device that
and 79 described later. performs three or more comparatively
important functions that could only be
designated by combining several of
3 Checking or interlocking relay is a
these device function numbers. All of
device that operates in response to
the functions performed by device 11
the position of a number of other
shall be defined in the drawing legend
devices, (or to a number of predeter-
or device function list.
mined conditions), in an equipment to
allow an operating sequence to pro-
ceed, to stop, or to provide a check of 12 Overspeed device is usually a direct-
the position of these devices or of connected speed switch that functions
these conditions for any purpose. on machine overspeed.

4 Master contactor is a device, 13 Synchronous-speed device, such as


generally controlled by device No. 1 or a centrifugal speed switch, a slip
equivalent, and the required permis- frequency relay, a voltage relay, an
sive and protective devices, that serve undercurrent relay, or any other type
to make and break the necessary con- of device that operates at approxi-
trol circuits to place an equipment into mately the synchronous speed of a
operation under the desired conditions machine.
and to take it out of operation under
other or abnormal conditions. 14 Underspeed device functions when
the speed of a machine falls below a
5 Stopping device is a control device pre-determined value.
used primarily to shut down an equip-
ment and hold it out of operation. [This
device may be manually or electrically
actuated, but excludes the function of
electrical lockout (see device function
86) on abnormal conditions.]
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 6
and IEEE C37.2-1979

IEEE device numbers Device Definition Device Definition


and functions (cont’d) number and function number and function
15 Speed or frequency matching 23 Temperature control device func-
device functions to match and hold tions to raise or to lower the tempera-
the speed or the frequency of a ture of a machine or other apparatus,
machine or of a system equal to, or or of any medium, when its tempera-
approximately equal to, that of another ture falls below or rises above a pre-
machine, source, or system. determined value.
Note: An example is a thermostat that
16 Reserved for future application switches on a space heater in a
switchgear assembly when the
17 Shunting or discharge switch temperature falls to a desired value
as distinguished from a device that is
serves to open or to close a shunting
circuit around any piece of apparatus used to provide automatic tempera-
(except a resistor), such as a machine ture regulation between close limits
and would be designated as 90T.
field, a machine armature, a capacitor,
or a reactor.
Note: This excludes devices that 24 Volts per hertz relay is a relay that
perform such shunting operations as functions when the ratio of voltage to
may be necessary in the process of frequency exceeds a preset value.
starting a machine by devices 6 or 42, The relay may have an instantaneous
or their equivalent, and also excludes or a time characteristic.
device 73 function that serves for the
switching of resistors. 25 Synchronizing or synchronism-
check device operates when two ac
18 Accelerating or decelerating circuits are within the desired limits of
device is used to close or to cause the frequency, phase angle, or voltage to
closing of circuits that are used to permit or to cause the paralleling of
increase or decrease the speed of a these two circuits.
machine.
26 Apparatus thermal device functions
19 Starting-to-running transition when the temperature of the protected
contactor is a device that operates to apparatus (other than the load-
initiate or cause the automatic transfer carrying windings of machines and
of a machine from the starting to the transformers as covered by device
running power connection. function number 49) or of a liquid or
other medium exceeds a predeter-
mined value; or when the temperature
20 Electrically operated valve is an
of the protected apparatus or of any
electrically operated, controlled, or
medium decreases below a pre-
monitored valve used in a fluid, air,
determined value.
gas, or vacuum line.
Note: The function of the valve may be
indicated by the use of the suffixes, see 27 Undervoltage relay is a relay that
page 11. operates when its input voltage is less
than a predetermined value.

21 Distance relay is a relay that func-


tions when the circuit admittance, 28 Flame detector is a device that
impedance, or reactance increases or monitors the presence of the pilot or
main flame in such apparatus as a gas
decreases beyond a predetermined
value. turbine or a steam boiler.

22 Equalizer circuit breaker is a breaker 29 Isolating contactor is used expressly


that serves to control or to make and for disconnecting one circuit from
another for the purposes of emer-
break the equalizer or the current bal-
ancing connections for a machine gency operation, maintenance, or test.
field, or for regulating equipment, in a
multiple unit installation.
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 7
and IEEE C37.2-1979

Device Definition Device Definition


number and function number and function
30 Annunciator relay is a nonautomati- 38 Bearing protective device functions
cally reset device that gives a number on excessive bearing temperature or
of separate visual indications upon the on other abnormal mechanical condi-
functioning of protective devices and tions associated with the bearing,
that may also be arranged to perform such as undue wear, which may
a lock-out function. eventually result in excessive bearing
temperature or failure.
31 Separate excitation device
connects a circuit, such as the shunt 39 Mechanical condition monitor is a
field of a synchronous converter, to a device that functions upon the occur-
source of separate excitation during rence of an abnormal mechanical
the starting sequence; or one which condition (except that associated with
energizes the excitation and ignition bearings as covered under device
circuits of a power rectifier. function 38), such as excessive vibra-
tion, eccentricity, expansion, shock,
32 Directional power relay is a relay tilting, or seal failure.
that operates on a predetermined
value of power flow in a given direction 40 Field relay functions on a given or
or upon reverse power flow such as abnormally low value or failure of
that resulting from the motoring of a machine field current, or on an exces-
generator upon loss of its prime sive value of the reactive component
mover. of armature current in an ac machine
indicating abnormally low field exci-
33 Position switch makes or breaks tation.
contact when the main device or piece
of apparatus that has no device func- 41 Field circuit breaker is a device that
tion number reaches a given position. functions to apply or remove the field
excitation of a machine.
34 Master sequence device is a device
such as a motor operated multicontact 42 Running circuit breaker is a device
switch, or the equivalent, or a pro- whose principal function is to connect
gramming device, such as a computer, a machine to its source of running or
that establishes or determines the operating voltage. This function may
operating sequence of the major also be used for a device, such as a
devices in an equipment during start- contactor, that is used in series with a
ing and stopping or during other circuit breaker or other fault protecting
sequential switching operations. means, primarily for frequent opening
and closing of the circuit.
35 Brush-operating or slip-ring short-
circuiting device is used for raising, 43 Manual transfer or selector device
lowering or shifting the brushes of a is a manually operated device that
machine; short-circuiting its slip rings; transfers the control circuits in order to
or engaging or disengaging the modify the plan of operation of the
contacts of a mechanical rectifier. switching equipment or of some of the
devices.
36 Polarity or polarizing voltage device
operates, or permits the 44 Unit sequence starting relay is a
operation of, another device on a relay that functions to start the next
predetermined polarity only or that available unit in multiple unit equip-
verifies the presence of a polarizing ment upon the failure or nonavaila-
voltage in an equipment. bility of the normally preceding unit.

37 Undercurrent or underpower relay 45 Atmospheric condition monitor is a


functions when the current or power device that functions upon the occur-
flow decreases below a predeter- rence of an abnormal atmospheric
mined value. condition, such as damaging fumes,
explosive mixtures, smoke, or fire.
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 8
and IEEE C37.2-1979

IEEE device numbers Device Definition Device Definition


and functions (cont’d) number and function number and function
46 Reverse-phase or phase-balance 53 Exciter or dc generator relay is a
current relay is a relay that functions relay that forces the dc machine field
when the polyphase currents are of excitation to build up during starting or
reverse phase sequence or when the that functions when the machine volt-
polyphase currents are unbalanced or age has built up to a given value.
contain negative phase-sequence
components above a given amount.
54 Turning gear engaging device is an
electrically operated, controlled, or
47 Phase-sequence or phase-balance monitored device that functions to
voltage relay functions upon a pre- cause the turning gear to engage (or
determined value of polyphase disengage) the machine shaft.
voltage in the desired phase
sequence, or when the polyphase volt-
55 Power factor relay is a relay that
ages are unbalanced, or when the
operates when the power factor in an
negative phase-sequence voltage
ac circuit rises above or falls below a
exceeds a given amount.
predetermined value.

48 Incomplete sequence relay is a relay


56 Field application relay is a relay that
that generally returns the equipment
automatically controls the application
to the normal, or off, position and
of the field excitation to an ac motor at
locks it out if the normal starting,
some predetermined point in the slip
operating, or stopping sequence is
cycle.
not properly completed within a pre-
determined time. If the device is used
for alarm purposes only, it should pref- 57 Short-circuiting or grounding
erably be designated as 48A (alarm). device is a primary circuit switching
device that functions to short circuit
or ground a circuit in response to auto-
49 Machine or transformer thermal
matic or manual means.
relay is a relay that functions when the
temperature of a machine armature
winding or other load-carrying winding 58 Rectification failure relay is a device
or element of a machine or power that functions if a power recitifier fails
transformer exceeds a predetermined to conduct or block properly.
value.
59 Overvoltage relay is a relay that
50 Instantaneous overcurrent relay is a operates when its input voltage is
relay that functions instantaneously on higher than a predetermined value.
an excessive value of current.
60 Voltage or current balance relay is a
51 Ac time overcurrent relay is a relay relay that operates on a given differ-
with either a definite or inverse time ence in voltage, or current input or out-
characteristic that functions when the put, of two circuits.
ac input current exceeds a predeter-
mined value, and in which the input 61 Density switch or sensor is a device
current and operating time are inde- that operates on a given value, or a
pendently related or inversely related given rate of change, of gas density.
through a substantial portion of the
performance range.
62 Time-delay stopping or opening
relay is a time-delay relay that serves
52 Ac circuit breaker is a device that is in conjunction with the device that
used to close and interrupt an ac initiates the shutdown, stopping, or
power circuit under normal conditions opening operation in an automatic
or to interrupt this circuit under fault or sequence or protective relay system.
emergency conditions.

63 Pressure switch is a switch that oper-


ates on given values, or on a given
rate of change, of pressure.
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 9
and IEEE C37.2-1979

Device Definition Device Definition


number and function number and function
64 Ground detector relay is a relay that 69 Permissive control device is gener-
operates upon failure of machine or ally, a two-position device that in one
other apparatus insulation to ground, position permits the closing of a circuit
or on flashover of a dc machine to breaker, or the placing of an equip-
ground. ment into operation, and in the other
Note: This function is assigned only to position prevents the circuit breaker or
a relay which detects the flow of current the equipment from being operated.
from the frame of a machine or enclos-
ing case or structure of a piece of 70 Rheostat is a variable resistance
apparatus to ground, or detects a device used in an electric circuit which
ground on a normally ungrounded wind- is electrically operated or has other
ing or circuit. It is not applied to a device electrical accessories, such as auxil-
connected in the secondary neutral of a iary, position, or limit switches.
current transformer, or in the secondary
neutral of current transformers, con-
nected in the power circuit of a normally 71 Level switch is a switch that operates
on given values, or on a given rate of
grounded system.
change, of level.

65 Governor is the assembly of fluid,


electrical, or mechanical control 72 Dc circuit breaker is used to close
equipment used for regulating the flow and interrupt a dc power circuit under
normal conditions or to interrupt this
of water, steam, or other media to the
prime mover for such purposes as circuit under fault or emergency condi-
starting, holding speed or load, or tions.
stopping.
73 Load-resistor contactor is used to
shunt or insert a step of load limiting,
66 Notching or jogging device func-
tions to allow only a specified number shifting, or indicating resistance in a
of operations of a given device or power circuit, or to switch a space
heater in circuit, or to switch a light, or
equipment, or a specified number of
successive operations within a given regenerative load resistor of a power
time of each other. It is also a device rectifier or other machine in and out of
circuit.
that functions to energize a circuit
periodically or for fractions of specified
time intervals, or that is used to permit 74 Alarm relay is a relay other than an
intermittent acceleration or jogging of annunciator, as covered under device
a machine at low speeds for mecha- function 30, that is used to operate, or
nical positioning. that operates in connection with, a
visual or audible alarm.
67 Ac directional overcurrent relay is a
relay that functions on a desired value 75 Position changing mechanism is a
of ac overcurrent flowing in a predeter- mechanism that is used for moving a
mined direction. main device from one position to
another in an equipment; for example,
shifting a removable circuit breaker
68 Blocking relay is a relay that initiates
a pilot signal for blocking of tripping on unit to and from the connected, dis-
external faults in a transmission line or connected, and test positions.
in other apparatus under predeter-
mined conditions, or that cooperates 76 Dc overcurrent relay is a relay that
with other devices to block tripping or functions when the current in a dc
to block reclosing on an out-of-step circuit exceeds a given value.
condition or on power swings.
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 10
and IEEE C37.2-1979

IEEE device numbers Device Definition Device Definition


and functions (cont’d) number and function number and function
77 Telemetering device is a transmitter 86 Lockout relay is an electrically
used to generate and transmit to a operated hand or electrically reset
remote location an electrical signal auxiliary relay that is operated upon
representing a measured quantity, or a the occurrence of abnormal conditions
receiver used to receive the electrical to maintain associated equipment or
signal from a remote transmitter and devices out of service until it is reset.
convert the signal to represent the
original measured quantity.
87 Differential protective relay is a
protective relay that functions on a
78 Phase-angle measuring or out-of- percentage, or phase angle, or other
step protective relay is a relay that quantitative difference between two
functions at a predetermined phase currents or some other electrical
angle between two voltages, or quantities.
between two currents, or between
voltage and current.
88 Auxiliary motor or motor generator
is a device used for operating auxiliary
79 Ac reclosing relay is a relay that equipment, such as pumps, blowers,
controls the automatic reclosing and exciters, rotating magnetic amplifiers,
locking out of an ac circuit interrupter. etc.

80 Flow switch is a switch that operates 89 Line switch is used as a disconnect-


on given values, or on a given rate of ing, load interrupter, or isolating switch
change, of flow. in an ac or dc power circuit. (This
device function number is normally
81 Frequency relay is a relay that not necessary unless the switch is
responds to the frequency of an electrically operated or has electrical
accessories, such as an auxiliary
electrical quantity, operating when
the frequency or rate of change of switch, a magnetic lock, etc.)
frequency exceeds or is less than a
predetermined value. 90 Regulating device functions to
regulate a quantity or quantities, such
as voltage, current, power, speed,
82 Dc load-measuring reclosing relay
is a relay that controls the automatic frequency, temperature, and load,
closing and reclosing of a dc circuit at a certain value or between certain
(generally close) limits for machines,
interrupter, generally in response to
load circuit conditions. tie lines, or other apparatus.
91 Voltage directional relay is a relay
83 Automatic selective control or that operates when the voltage across
transfer relay is a relay that operates an open circuit breaker or contactor
exceeds a given value in a given direc-
to select automatically between
certain sources or conditions in an tion.
equipment or that performs a transfer
operation automatically. 92 Voltage and power directional relay
is a relay that permits or causes the
84 Operating mechanism is the com- connection of two circuits when the
plete electrical mechanism or servo- voltage difference between them
exceeds a given value in a predeter-
mechanism, including the operating
motor, solenoids, position switches, mined direction and causes these two
etc., for a tap changer, induction regu- circuits to be disconnected from each
other when the power flowing between
lator, or any similar piece of apparatus
that otherwise has no device function them exceeds a given value in the
number. opposite direction.

85 Carrier or pilot-wire receiver relay is 93 Field-changing contactor functions


to increase or decrease, in one step,
a relay that is operated or restrained
by a signal used in connection with the value of field excitation on a
carrier-current or dc pilot-wire fault machine.
directional relaying.
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 11
and IEEE C37.2-1979

Device Definition Suffix numbers


number and function If two or more devices with the same function
number and suffix letter (if used) are present
94 Tripping or trip-free relay functions
to trip a circuit breaker, contactor, or
in the same equipment, they may be distin-
equipment, or to permit immediate guished by numbered suffixes as for example,
tripping by other devices; or to prevent 52X-1, 52X-2 and 52X-3, when necessary.
immediate reclosing of a circuit inter-
rupter if it should open automatically, Suffix letters
even though its closing circuit is main- Suffix letters are used with device function
tained closed. numbers for various purposes. In order to pre-
vent possible conflict each suffix letter should
95 Used only for specific applications on have only one meaning in an individual
96 individual installations where none of equipment. All other words should use the
97 the assigned numbered functions from abbreviations as contained in American
98 1 to 94 is suitable. Standard Z32.13-1950, or latest revision
99 thereof, or should use some other distinctive
Supervisory control and indication. abbreviation, or be written out in full each
A similar series of numbers, prefixed time they are used. The meaning of each
by the letters RE (for “remote”) shall single suffix letter, or combination of letters,
be used for the interposing relays should be clearly designated in the legend on
performing functions that are con- the drawings or publications applying to the
trolled directly from the supervisory
equipment. In cases where the same suffix
system. Typical examples of such
device functions are: RE1, RE5 and
(consisting of one letter or a combination of
RE94. letters) has different meanings in the same
equipment, depending upon the device func-
tion number with which is used, then the
Note: The user of the “RE” prefix for
this purpose in place of the former
complete device function number with which
200 series of numbers now makes it it is used, the complete device function
possible to obtain increased flexibility number with its suffix letter or letters and its
of the device function numbering sys- corresponding function name should be listed
tem. For example, in pipeline pump in the legend in each case, as follows: 90V,
stations, the numbers 1 through 99 Voltage regulator.
are applied to device functions that
are associated with the over-all station Lower case (small) suffix letters are used in
operation. A similar series of numbers, practically all instances on electrical dia-
starting with 101 instead of 1, are
grams for the auxiliary, position, and limit
used for those device functions that
are associated with unit 1; a similar
switches. Capital letters are generally used
series starting with 201 for device for all other suffix letters.
functions that are associated with unit
2; and so on, for each unit in these The letters should generally form part of the
installations. device function designation, are usually writ-
ten directly after the device function number,
Devices performing more than one as for example, 52CS, 71W, or 49D. When it
function is necessary to use two types of suffix letters
If one device performs two relatively impor- in connection with one function number, it is
tant functions in an equipment so that it is often desirable for clarity to separate them by
desirable to identify both of these functions, a slanted line or dash, as for example,
this may be done by using a double function 20D/CS or 20D-CS.
number and name such as:
The suffix letters which denote parts of the
50/51 Instantaneous and Time Overcurrent main device, and those which cannot or need
relay. not form part of the device function designa-
tion, are generally written directly below the
device function number on drawings, as for
52 43
example, ---------
CC
or ------ .
A
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 12
and IEEE C37.2-1979

IEEE device numbers Auxiliary devices Main devices


and functions (cont’d) Separate auxiliary devices These letters denote the location of the main
X device in the circuit, or the type of circuit in
Y – Auxiliary relay 1) which the device is used or the type of circuit
or apparatus with which it is associated, when
Z
this is necessary, such as:
R – Raising relay
L – Lowering relay A – Alarm or Auxiliary power
O – Opening relay or contactor AN – Anode
C – Closing relay or contactor B – Battery, or Blower, or Bus
CS – Control switch BK – Brake
CL – Auxiliary relay, open (energized when BL – Block (Valve)
main device is in open position)
BP – Bypass
OP – Auxiliary relay, open (energized when
BT – Bus tie
main device is in open position)
C – Capacitor, or Condenser, or Compen-
U – “Up” position-switch relay
sator, or Carrier current, or Case, or
D – “Down” position-switch relay Compressor
PB – Push button CA – Cathode
CH – Check (Valve)
1) In the control of a circuit breaker with so-called
D – Discharge (Valve)
X-Y relay control scheme, the X relay is the
device whose main contacts are used to ener- E – Exciter
gize the closing coil or the device which in F – Feeder, or Field, or Filament, or Filter,
some other manner, such as by the release of or Fan
stored energy, causes the breaker to close.
G – Generator, or Ground2)
The contacts of the Y relay provide the anti-
pump feature for the circuit breaker. H – Heater, or Housing
L – Line, or Logic
Actuating quantities
M – Motor, or Metering
These letters indicate the condition or
electrical quantity to which the device N – Network, or Neutral 2)
responds, or the medium in which it is P – Pump, or Phase comparison
located, such as: R – Reactor, or Rectifier, or Room
S – Synchronizing, or Secondary, or
A – Air or Amperes or Alternating Strainer, or Sump, or Suction (Valve)
C – Current T – Transformer, or Thyratron
D – Direct or Discharge
TH – Transformer (high-voltage side)
E – Electrolyte TL – Transformer (low-voltage side)
F – Frequency, or Flow, or Fault TM – Telemeter
H – Explosive U – Unit
J – Differential
L – Level, or Liquid 2) Suffix “N” is generally used in preference to “G”
for devices connected in the secondary neutral
P – Power, or Pressure
of current transformers, or in the secondary of
PF – Power factor a current transformer whose primary winding is
Q – Oil located in the neutral of a machine or power
transformer, except in the case of transmission
S – Speed, or Suction, or Smoke line relaying, where the suffix “G” is more com-
T – Temperature monly used for those relays which operate on
ground faults.
V – Voltage, Volts, or Vacuum
VAR – Reactive power
VB – Vibration
W – Water, or Watts
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 13
and IEEE C37.2-1979

Main device parts Standard reference positions of some


These letters denote parts of the main typical devices are as follows:
device, divided in the two following Standard
categories: Device reference position
Power circuit breaker Main contacts open
1. All parts, except auxiliary contacts, position
switches, limit switches, and torque limit Disconnecting switch Main contacts open
switches. Load-break switch Main contacts open
BK – Brake Valve Closed position
C – Coil, or Condenser, or Capacitor Gate Closed position
CC – Closing coil Clutch Disengaged position
HC – Holding coil Turning gear Disengaged position
M – Operating motor Power electrodes Maximum gap position
MF – Fly-ball motor Rheostat Maximum resistance
ML – Load-limit motor position
MS – Speed adjusting, or Synchronizing Adjusting means 1) Low or Down position
motor Relay 2) Deenergized position
S – Solenoid Contactor 2)
Deenergized position
SI – Seal-in Relay (latched-in Non-latched-in position
TC – Trip coil type)
V – Valve Contactor (latched-in Main contacts open
type)

2. All auxiliary contacts and positioning and Temperature relay 3) Lowest temperature
limit switches for such devices and equipment as 3)
Level detector Lowest level
circuit breakers, contactors, valves and rheostats
Flow detector 3) Lowest flow
and contacts of relays. These are designated as
follows: Speed switch 3) Lowest speed
a – Contact that is open when the main Vibration detector 3) Minimum vibration
device is in the standard reference 3)
Pressure switch Lowest pressure
position, commonly referred to as the
nonoperated or deenergized position, Vacuum switch 3) Lowest pressure, i.e.,
and that closes when the device highest vacuum
assumes the opposite position.
b – Contact that is closed when the main The simple designation “a” or “b” is used in all
device is in the standard reference cases where there is no need to adjust the
position, commonly referred to as the contacts to change position at any particular point
nonoperated or deenergized position, in the travel of the main device or where the part
and that opens when the device of the travel where the contacts change position is
assumes the opposite position. of no significance in the control or operating
scheme. Hence the “a” and “b” designations
aa – Contact that is open when the operating
usually are sufficient for circuit breaker auxiliary
mechanism of the main device is in the
switches.
nonoperated position and that closes
when the operating mechanism Note: If several similar auxiliary switches are
assumes the opposite position. present on the same device, they should be des-
ignated numerically 1, 2, 3, etc. when necessary.
bb – Contact that is closed when the operat-
ing mechanism of the main device is in
the nonoperated position and that
opens when the operating mechanism
assumes the opposite position.
Relay symbols and device numbers;
selection from IEC 617-, IEEE C37.2-1991 1MRK 590 006-BEN
Page 14
and IEEE C37.2-1979

IEEE device numbers D – Decelerating, or Detonate, or Down, or


and functions (cont’d) Standard Disengaged
Device reference position
E – Emergency, or Engaged
1) These may be speed, voltage, current, load, or
F – Failure, or Forward
similar adjusting devices comprising rheostats,
springs, levers, or other components for the H – Hot, or High
purpose. HR – Hand reset
2) These electrically operated devices are of the HS – High speed
non-latched-in type, whose contact position is
dependent only upon the degree of energiza- L – Left, or Local, or Low, or Lower, or
tion of the operating or restraining or holding Leading
coil or coils which may or may not be suitable M – Manual
for continuous energization. The deenergized
OFF – Off
position of the device is that with all coils
deenergized. ON – On
3) The energizing influences for these devices are P – Polarizing
considered to be, respectively, rising R – Right, or Raise, or Reclosing, or
temperature, rising level, increasing flow, rising Receiving, or Remote, or Reverse
speed, increasing vibration, and increasing
pressure. S – Sending, or Swing
T – Test, or Trip, or Trailing
TDC – Time-delay closing
TDO – Time-delay opening
U – Up

Other switches
These letters cover all other distinguishing
features or characteristics or conditions,
which serve to describe the use of the device
or its contacts in the equipment such as:

A – Accelerating, or Automatic
B – Blocking, or Back-up
C – Close, or Cold

Potrebbero piacerti anche