Liebert

Liebert Series 610 UPS P ow er A v a i l a bi l it y

THE ULTIMATE RELIABILITY SOLUTION FOR


LARGE-SCALE, MISSION-CRITICAL APPLICATIONS

High Power, On-Line UPS Protection

For Critical Sites Including Computer

Rooms, Telecommunications Centers,

Industrial Process Control Facilities

And Other Locations Housing

Sensitive Electronic Systems


CONTINUOUS IMPROVEMENT:
BUILDING UPON THE BEST
The Liebert Series 610 UPS system is The Liebert Series 610 retains the The Standard For
built on the reliability record of the proven, robust high power topology Performance And Efficiency
of the original Series 600 product line The Liebert Series 610 includes
Series 600 UPS that is unequalled in the
while adding significant output several new features that are all
power protection industry. Now, this
performance and reliability designed to enhance performance,
latest generation product line brings
2 improvements over previous models. efficiency, application flexibility —
dependability to yet another level. Unlike typical large UPS inverters and above all — reliability.
then, and even now, this design These latest updates provide
provides industry-leading further improvements to the unit's
performance without the need to overload and critical output bus fault
parallel inverter IGBTs or inverter management, further ensuring that
power subassemblies — which the connected load is powered by the
means fewer critical parts. UPS rather than being transferred to
New Features, The Liebert Series 600 has bypass…or suffering a loss of power to
Renowned Reliability proven itself to be the most durable the critical bus. Other improvements
Building the most reliable power system UPS in the industry with year after include the addition of an easy-to-
possible can only be accomplished year of continuous improvement read system display panel to provide
since its introduction. Based on detailed operating information and
through a dedication to making it better
actual field performance of systems control capabilities.
and better. The Liebert Series 610 is a
shipped since the original product Liebert's Series 610 UPS is an
culmination of past improvements and introduction, Series 600 equipment industry leader in every key respect,
outstanding new features that has demonstrated a critical bus MTBF including demonstrated reliability in
maximize reliability. (mean time between failure) of field operation, compact footprint,
greater than 2.8 million hours. This is efficiency, operator controls and the
significantly better than any other widest range of choices for dual-load-
competitive UPS product. bus system configurations.

Mean Time Between Failures (MTBF) 1989-2003

3,000,000 MTBF

1.36 M 1.79 M
2,000,000 MTBF

1.0 M
• •
1,000,000 MTBF •
1985

1989 1990 1992 1993 1994 1995 1996
First 750 kVA, 180 Advanced battery Intro of Series 600; Industry-best Power-Tie introduced. First UPS product Introduction of IGBT 1100 kVA rating.
cell module introduced; status monitoring robust PWM SCR 1000 kVA UPS. First practical use of family to hit and exceed models — first large Improved AC and
auxiliary-commutated developed; first inverter; digital Full 0.9 load pf fiber optics in UPS to 1,000,000 hours critical model IGBT-based UPS DC capacitor reliability.
inverter; no module true high-current controls; industry- product family. provide system-to- bus field-documented models without need
output switch required. 3 ph continuous first ASIC; first system signal fault MTBF. Static Transfer to parallel devices.
duty static bypass agency-listed isolation. Switch (STS) introduced. Major size reduction.
switch in one large UPS
package.
No-Compromise Reliability In
High Power Applications
There are certain operations and processes in this world that are so critical to the
existence of a business, institution, government agency or other
organization...that even the mere thought of them shutting down due to a power
failure is unthinkable.

It is at this point that a solution is required that leaves no room for failure, no room
for compromise of any kind — a solution that actually goes beyond "High 9's"
reliability. This is when to turn to a Liebert Series 610 UPS system.

Documented Performance with a new design every few years.


The Liebert Series 610 delivers 100% The Series 610 features the safest and 3
protection with its true on-line, most reliable design for high power Improved System Control Panel
double-conversion topology that applications with years of proven For Easier Operation
provides complete input to output performance in the field. The Liebert Series 610 UPS includes a redesigned
isolation with totally regenerated Another key to reliability is to get operator interface control panel located on the front
power. This is a level of protection the job done with a reduced number of the unit. It features a backlit display that is easy to read.
unmatched by single-conversion UPS of operating parts. Fewer components The display panel enables the user to quickly identify
products including line-interactive and mean fewer individual items that can the current status of the UPS system and to perform
others that call themselves "on-line." malfunction, thereby reducing the risk most manual control operations. Designed for intuitive
A true double conversion UPS is the of a critical bus failure due to a operation, the display screen is driven by an easy-to-use,
only way to guard against the full component failure. user-prompted menu program.
spectrum of power disturbances. Other factors that contribute to the
Anything less is a compromise that can remarkable reliability of this product
lead to serious problems. line are the use of conservatively
Liebert's primary goal in UPS design rated components, minimizing
is delivering high output reliability. A transfers to bypass by managing fault
key strategy for achieving this goal is conditions, making operator controls
the continuous improvement of the understandable, and providing easy
Field-observed "MTBF" refers to Series 600 installed base and critical bus
Series 610 UPS, building on what’s access for maintenance and repair. outages reported to Liebert. MTBF reflects the performance of the Liebert-
known to work well. The best products The Liebert Series 610 UPS systems produced UPS product only when viewed as a component of a well-designed
and maintained system. User-observed end-to-end system MTBF
simply don’t come from starting over leads the industry in all these areas. performance will differ significantly from these values due to many per-site
variables, including ancillary equipment performance, power distribution
system configuration and user on-site maintenance practices.

2.73 M 2.88 M 2.9 M

2.12 M 2.22 M
2.57 M
• • • • •
1.87 M
• •

1997 1998 1999 2000 2001 2002 2003 2004


Trench-gate IGBTs 65 and 80 kVA models 100 and 125 kVA Redundant Vsat for Control logic refine- Developed computer- Added improved, Liebert Series 610
(more efficient, introduced. Improved models introduced. IGBTs. Test facility ments; improved based, comprehensive more comprehensive introduced; improved
reliable); Single self-test and battery Production process expansion, power reliability; improved UPS system dynamic critical output bus user interface, fault
Module System auto charging functions; enhancements for and instrumentation easy-to-service features. performance models. overload and fault management;
restart; System Control first use of system improved reliability. expansion. current management redundant IGBT
Cabinet integrated into simulation for functions. STS2 Vsat improvement.
standard switchgear. reliability and launched.
fault analysis.
Overload And Fault Management:

IT'S ALL ABOUT MAINTAINING THE CRITICAL BUS

Designed For Critical BUS Management


Maximum Reliability The system offers three levels of protection to keep the critical bus operating
Reliability starts with the ability to while maintaining operation within industry recommended limits. Voltage
keep your critical load on-line and levels outside these limits can cause erratic or incorrect operation of critical
protected. The enhanced fault current customer equipment. The system is designed to better discriminate between
management capabilities of the Liebert undervoltage conditions — due to an external or internal overload fault event —
Series 610 are designed to do just that. that can be managed without a transfer to bypass.
4
The Series 610 is designed for
immediate response to utility outages
Pulse-Parallel Operation
“plus” high overload capacity “plus” Current versus Time Curve of Overload Capacity
<1000% Load
adaptive response to other critical bus 1000
The curve represents
fault conditions. The system will UPS overload capability 500
manage faults occurring upstream and as a function of time. No Transfer Transfer
The inverter remains 400
downstream from the UPS as well as Liebert 100%
Output Voltage
on-line providing Regulation Point
180% Load 150% Load 125 % Load
internal to the UPS. 300
%Load

regulated power
output at full voltage 200
The fault handling capabilities of the Liebert Series 610 — at every point of the
104 %
especially when used in multi-module installations — are overload/ time curve. 100
designed to keep the critical load on the UPS, no matter
what the condition of the incoming power.
40ms 1s 30s 10 min.
Time
A fault is managed in this order of priority:
The overload handling characteristics of the Series 610 are also enhanced
Single Module System Multi-Module System
through the use of pulse-parallel operation. When an overload condition, such
First priority First priority
Manage an internal fault Manage an internal fault as magnetic inrush current or a branch load circuit fault, exceeds 155% of the
within the UPS module within the UPS module full load current rating, the static bypass switch pulses on. This allows up to
without the critical bus without the critical bus
exceeding voltage limits exceeding voltage limits 1000% rated full load current from the bypass line to clear the overload without
and without transfer and without transfer
to bypass. to bypass.
a full transfer to bypass, while keeping your critical load operations still
connected to the UPS inverter.
Second priority Second priority
If the fault or overcurrent If the fault cannot be The bypass source is in parallel with the UPS output, permitting the bypass
cannot be handled handled internally to the
internally by the module, module and redundant source to carry the initial overload current. If the overload clears, a complete
then transfer the critical modules are present, load transfer to bypass is not made. If the overload condition exceeds the
bus to the bypass source disconnect that module
without exceeding from the critical inverter capacity, the automatic transfer is completed, maintaining the load
voltage limits. bus without exceeding
voltage limits and without
voltage within specified limits. The use of pulsed static switch operation provides
transfer to bypass. a simple, reliable response to brief output bus dynamic overload conditions and
Third priority reduces nuisance transfer/retransfer cycles for short-term conditions. Not all
If fault or overcurrent
cannot be handled by the UPSs use motor-operated current breakers for this function. Liebert does.
remaining modules on-line,
then transfer the critical Digital Control Accuracy
bus to the bypass source
without exceeding The reliability and performance of the Liebert Series 610 UPS is enhanced
voltage limits.
through the use of digital control and Application-Specific Integrated Circuits
(ASICs) for key control logic functions. These computer-tested controls provide self
diagnostics and greatly reduce the parts count and number of interconnect points.
What's the "real world" performance standard you expect
from your power protection? Protecting the operation of the
critical bus no matter what.

HERE'S HOW THE LIEBERT SERIES 610 DOES IT

The Liebert Series 610 will meet your highest output Other features include:
performance expectations. This includes the ability to •Connected Load Compatibility — The Liebert Series
handle both balanced and unbalanced loads, high crest 610 supports all normally-expected load configurations
factor loads, dynamic loads and overloads, as well as both and performance characteristics without the need for
external and internal faults. special provisions.

Proven Advantages That Have Made The •Smaller Footprint — All of the Series 610 models have
5
Liebert Series 610 The Standard Of Reliability an exceptionally small footprint, even those with input
The Liebert Series 610 continues to meet all industry isolation transformers. In some cases, two Liebert UPS

performance standards for large, high-reliability UPS modules can be installed in the space formerly required

systems with the most robust inverter in the industry. by just one competitive unit.

It can manage overloads and faults without the need for a •Higher DC Bus Utilization — Provides higher AC/AC and

static switch on the UPS inverter output. It can handle DC/AC efficiency and allows a relatively smaller battery.

dynamic loading and non-linear loads. The Series 610 also •High Performance PWM Inverter — The most robust

costs less to operate thanks to >93% operating efficiency inverter in the industry, it meets all industry performance

and a leading power factor of greater than 0.92 for all units standards with the lowest parts count. Handles most

with input filters. overloads while meeting voltage waveform requirements


and minimizing the use of a static bypass source.
•Lower Parts Count — Continuous improvement
dramatically improves reliability by reducing the
potential points of failure within the system.
•Higher Operating Efficiency — The Series 610 has
excellent operating efficiency in all configurations and
with all types of loads. Even with an input isolation
transformer and a 12-pulse rectifier, the 610 is better
than 92.5% efficient from 50% through 100% load.
Versions with the standard 6-pulse rectifier are
approximately 94% efficient throughout this range.
•Lower Operating Costs — The higher AC/AC efficiency
of the Series 610, along with its high input power
factor and long life reduce operating costs over the
life of the systems.
•Lower Heat Output — The low BTU output of the 610
reduces the need for complex air cooling arrangements.
Liebert Series 610 Configurations:

MORE WAYS TO Single-Module Configuration


ACHIEVE THE LEVEL Single-module systems provide a basic protection
configuration. The critical bus is powered by a single UPS
OF PROTECTION AND system with bypass capability.

RELIABILITY YOU NEED Single Module System


Static Switch

Bypass
AC Input
Output
Isolation System
Technology Designed For Bypass
6 Rectifier Inverter Transformer
Breaker Critical Bus
Reliability Rectifier AC Output
AC Input UPS Output
Thanks to digital controls and a CBI
Breaker
unique inverter topology, the Liebert
Series 610 can be used in all of the
Battery
conventional single-bus system
configurations: single module,
parallel-redundant or isolated Multi-Module Configuration AC Input
redundant.
Source
In addition, the Series 610 is The need for maximum reliability has driven customers to
Battery
uniquely well suited for high- add redundant UPS modules to their critical power systems.
availability, multi-module system Multi First, a redundant UPS module improves maintainability
System System
Module
configurations and for configurations Units
since one UPS moduleBypass
at a time can be taken
Controloff-line for
Cabinet
using Load Bus Sync™ (LBS) and Breaker
service without shutting down the whole system. Second,
Static Switcha

Liebert Power-Tie™ technologies. Battery


redundant UPS module adds fault management capability
Static Switch
Unlike some competitive products, by preventing a single module or single battery failure from
Bypass
UPSInput
AC Output UPS AC Output
which are optimized for one or two bringing down the critical
Output bus. To Load
Output
Isolation System
Breaker Bypass
particular configurations, the 610 can Rectifier Inverter Transformer Critical Bus
Breaker
AC Output
be used reliably in a wide variety of Parallel Redundant
Rectifier
AC Input UPS Output
CBI
custom applications and with custom Breaker
The most common multi-module configuration is parallel
switchgear to meet the requirements
redundant, in which the system has one UPS module more
of your facility.
than is required to carry the rated critical Battery
load.

Multi-Module System
AC Input
Source

Battery

Multi
System System
Module
Bypass Control
Units
Cabinet
Breaker

Battery
Static Switch

UPS Output UPS AC Output


Output To Load
Breaker
Dual-Bus Configuration Static Switch
Distributed Redundant
Configurations
Distribution Options
For Dual-Bus Systems
After choosing a dual-bus system,
Distributed Redundant
Static Switch UPS LBS UPS
Unit
your next task is configuring your power
1 2
While both parallel and
Output isolated redundant systems
System
distribution system to best meet
Isolation
er Inverter Bypass your needs.
improveTransformer
the ability ofBreaker
the critical busBus
Critical to survive LBS
AC Output UPS UPS 1 The first arrangement provides
Unit 2
disturbances
Output
created outside the facility — their redundancy 1
UPS Output
System a high level of fault tolerance. A
Isolation
Inverter ends Transformer
where the critical
Bypassbus begins. All the critical load
Breaker
Liebert STS2 ahead of the PDU provides
Breaker Critical Bus
equipment is somewhere downstream, AC Output with two or more Static uninterrupted transfers between UPS
UPS Output 1 Transfer
circuit breakers in series systems. The fast-switching capability of
Breaker between UPS output and load Switch
Battery the static switch provides protection
input. For maximum reliability, an even better solution is a
StaticPDU
dual-bus, distributed redundant system, which takes Transfer
against “fast” power system failures, 7
Switch such as source failures, breaker trips
Battery
redundancy all the way out to the critical load equipment. Load and even operator error. The limitation
AC Input PDU
The simplest way
Sourceto build a dual-bus system is with our
here is that you still can’t service the
PDU when the load is on-line.
exclusive Load Bus Sync™ (LBS) option, which keeps two
y LoadStatic 2 The second arrangement has a single-
or more UPSACsystems
Input
in a synchronized state even when 2 PDU Transfer PDU
input load receiving power from a static
Source Switch
operating on batteries or out-of-synch generator sets.
System switch on the output of two PDUs. The
System
Control StaticLoad static switch can take power from either
Each
BypassUPS powers its own downstream distribution
Cabinet PDU Transfer PDU
Breaker Switch PDU. This enables you to service one UPS
equipment, so that each piece of load equipment can be
System System and one PDU at a time, while remaining on
connected
Bypass to Switch
Static both. With proper transfer devices, such
Control
Load Dual UPS power from the other PDU.
Cabinet 3 PDU Input PDU
Breaker
asUPS
a static transfer switch,
AC Outputany connected load can be Load 3 Another option is to connect a dual
Output
switched transparently To Load
between UPS sources so that one power cord device to two different PDUs.
Breaker Static Switch Dual Everything is now serviceable while the
complete UPS and distribution system can be de-energized PDU Input PDU
UPS AC Output Load load is on-line. This option is only available,
for maintenance To
Output orLoad
expansion. The LBS can be used to however, if your load equipment has dual
Breaker
synchronize any two Liebert Series 610 UPS systems or power cords and if the equipment has
the 610 to a genset or to another vendor’s UPS. 100% functionality with either input.

Utility Source Utility Source


No. 1 No. 2
Power-Tie ® Power-Tie™ Configuration
UPS LBS
Another approach to a dual-bus system is Liebert's Utility Source UPS UPS
Utility Source UPS
1A1 1B Unit 2A2 2B
No. No.
Power-Tie configuration, which uses a tie breaker to
Tie Controls UPS
LBS
transfer loads between UPS systems in order to facilitate UPS UPS
Tie Breaker 2A
UPS
1A 1B Unit 2B
maintenance. The Power-Tie can be used between any
two identical Liebert Series 610 systems, either Single Tie Controls
Tie Breaker
Module or Multi-Module.

Static Transfer Switch2


Liebert Static Transfer
In addition to the LBS and Power-Tie options, the Liebert
Switch 2 connects to dual
Load or
Static Transfer Switch 2 (STS2) makes the redundancy truly Distribution bus power distribution
system, making nearly
usable. The STS2 connects to dual bus power distribution
instant transfer of its
network and makes a nearly instant (less than quarter- Load or connected load from one
Distribution power source to the other.
cycle) transfer of its connected load from one power
source to the other. The STS2 can be used with a power
distribution unit (PDU) or dedicated to a specific piece of
load equipment to provide dual power cord functionality.
THERE IS A LIEBERT MONITORING SOLUTION
DESIGNED TO MEET YOUR NEEDS
Liebert has built advanced Liebert SiteScan™ Web Stand-Alone Monitoring
monitoring and communications Enterprise Monitoring Solutions
capabilities into the Series 610 UPS Systems
Critical Load shutdown Software, as
system. Liebert monitoring and control
The Liebert SiteScan™ Web is a well as autonomous microprocessor
products allow you to take full
comprehensive critical systems controlled modules, are available to
advantage of these features. You will
8 monitoring solution dedicated to provide supervision, control and
find a full range of monitoring and
ensuring reliability through graphics, remote alarm notification for Liebert
control systems, communications
event management and data power equipment.
modules and other equipment
extrapolation. The standard Web
designed to interface with a variety of
interface allows users easy access from
communication protocols, operating
"anywhere" at "anytime."
platforms and building management
•Single and multi-site applications.
systems. Knowing what is happening
•Event management and unit control.
with your power equipment, so you
•Trend and historical data captures
can keep it at peak operating Liebert
and reporting.
efficiency, is vital to system reliability. MultiLink™
•Full ASHRAE BACnet compatibility.
Automated
•Java based.
Important facility operational and Shutdown Software
•Windows 2000 and XP compatible.
status information needs to be Liebert MultiLink will monitor UPS
Network-Based Monitoring
communicated by different means with status and perform user-specified
Systems
varying levels of importance. This is why actions to execute notifications and
The Liebert OpenComms™ Nform provide automated, unattended critical
Liebert gives you so many ways to
family of monitoring software and load shutdown to protect critical data
supervise your enterprise:
communications hardware solutions during extended power outages.
combines the coverage of facility
Liebert Universal Monitor
monitoring with the efficiency of a
network-based system. They provide a All-purpose microprocessor-
cost-effective, centralized monitoring based alarm and notification unit
solution flexible enough to support that allows a variety of Liebert
your critical system configurations equipment to be monitored and
while utilizing your existing controlled both remotely and locally
distributed infrastructure. from a single point.
Critical Space
Services From Liebert
Global Services
Liebert Global Services has the necessary resources Total Service Capability Remote Monitoring —
and expertise to support the critical power and Always There, Always Alert
Service Excellence programs from
environmental infrastructure that supports your Liebert Global Services provide a The key to providing proper service
9
mission-critical computing and communications systems. simple and easy to understand for your critical power systems is
strategy for meeting all of your critical being aware of that equipment's
space service and maintenance needs. operating status at any given time.
Basic, Essential and Preferred levels Our Remote Monitoring Service is
allow you to select the complement of designed to maximize the capabilities
critical power and environmental of your Liebert equipment by
system services that best fits your maximizing the effectiveness its
requirements. These programs monitoring capabilities.
include guaranteed four-hour Continuous 24-hour remote
response time, emergency service and monitoring of UPS/power conditioning
preventive maintenance. equipment, environmental products,
With over 300 Liebert-employed fire and water detection, and other
Customer Engineers and a network facility systems is available through
of over 900 factory authorized service Liebert Global Services' Remote
personnel, our technical capabilities, Monitoring Service. No matter where
geographical coverage and ability to your facilities are located, Liebert's
respond are second to none. These Remote Monitoring can provide
factory-trained service professionals continuous oversight of a wide range
have direct access to the most of critical installations from our
comprehensive factory authorized Customer Response Center.
parts network in the industry. We Combining the capabilities of your
also provide them with immediate Liebert monitoring systems with
online access to detailed schematics our Remote Monitoring Service
and your equipment's complete provides you with a seamless rapid-
service record from the time it was response system.
started up.
Liebert Series 610 Specifications

10
LOAD AC INPUT/ %EFFICIENCY AT NOMINAL BATTERY MAXIMUM HEAT DIMENSIONS APPROXIMATE
UPS RATING POWER OUTPUT VARIOUS LOADS1 REQUIREMENTS DISSIPATION (BTU/HR) WxDxH2 (INCHES) WEIGHT 2
KVA KW FACTOR VOLTAGE 50% 75% 100% (CELLS) FULL LOAD TOP ENTRY ONLY TOP & BOTTOM ENTRY SMS MMU
65 52 0.8 480/480 92.5% 93.5% 93.5% 240 12,350 N/A 34X32X68 1,500 1,470
65 52 0.8 480/208 92.5% 93.0% 93.0% 240 13,350 N/A 34X32X68 1,700 1,670
65 52 0.8 208/208 92.0% 92.0% 92.0% 240 15,450 N/A 34X32X68 1,900 1,870
80 64 0.8 480/480 92.5% 93.5% 93.5% 240 15,200 N/A 34X32X68 1,700 1,670
80 64 0.8 480/208 92.5% 93.0% 93.0% 240 16,450 N/A 34X32X68 1,950 1,920
80 64 0.8 208/208 92.0% 92.0% 92.0% 240 19,000 N/A 34X32X68 2,100 2,070
100 80 0.8 480/480 92.5% 93.5% 93.5% 240 19,000 48X33X78 56X33X78 2,500 2,465
100 80 0.8 480/208 92.5% 93.0% 93.0% 240 20,550 48X33X78 56X33X78 2,800 2,765
100 80 0.8 208/208 92.0% 92.0% 92.0% 240 23,750 48X33X78 56X33X78 3,100 3,065
125 100 0.8 480/480 92.5% 93.5% 93.5% 240 23,750 48X33X78 56X33X78 2,600 2,565
125 100 0.8 480/208 92.5% 93.0% 93.0% 240 25,700 48X33X78 56X33X78 2,900 2,865
125 100 0.8 208/208 92.0% 92.0% 92.0% 240 29,700 48X33X78 56X33X78 3,250 3,215
150 120 0.8 480/480 93.0% 94.0% 94.0% 240 26,150 48X33X78 56X33X78 2,850 2,800
150 120 0.8 480/208 93.0% 93.5% 93.5% 240 28,450 N/A 56X33X78 3,050 3,000
150 120 0.8 208/208 93.0% 92.5% 92.5% 240 33,200 N/A 56X33X78 3,320 3,270
225 180 0.8 480/480 93.0% 94.0% 94.0% 240 39,200 48X33X78 56X33X78 3,190 3,140
225 180 0.8 480/208 93.0% 93.5% 93.5% 240 42,700 N/A 56X33X78 3,475 3,425
225 180 0.8 208/208 93.0% 92.5% 92.5% 240 49,800 N/A 56X33X78 3,870 3,820
300 240 0.8 480/480 93.0% 94.0% 94.0% 240 52,300 N/A 72X35X78 4,200 4,150
300 240 0.8 480/208 93.0% 93.5% 93.5% 240 56,950 N/A 72X35X78 4,450 4,400
300 240 0.8 208/208 93.0% 92.5% 92.5% 240 66,400 N/A 72X35X78 5,400 5,350
400 320 0.8 480/480 93.0% 94.0% 94.0% 240 69,700 N/A 72X35X78 4,900 4,850
400 320 0.8 480/208 93.0% 93.5% 93.5% 240 75,950 N/A 72X35X78 5,150 5,100
400 320 0.8 208/208 92.5% 92.0% 92.0% 240 94,950 N/A 96X35X78 8,400 8,350
400 360 0.9 480/480 93.0% 94.0% 94.0% 240 78,450 N/A 72X35X78 5,100 5,050
450 360 0.8 480/480 93.0% 94.0% 94.0% 240 78,450 N/A 72X35X78 5,100 5,050
500 (6P) 400 0.8 480/480 93.0% 94.0% 94.0% 240 87,150 N/A 72X39X78 5,775 5,710
500 (12P) 400 0.8 480/480 92.5% 93.0% 93.0% 240 94,910 N/A 96X39X78 8775 8710
500 (6P) 450 0.9 480/480 93.0% 94.0% 94.0% 240 98,050 N/A 72X39X78 5,795 5,730
500 (12P) 450 0.9 480/480 92.5% 93.0% 93.0% 240 106,770 N/A 96X39X78 8795 8730
625 (6P) 500 0.8 480/480 93.5% 94.5% 94.5% 240 99,300 N/A 108X39X78 7,500 7,405
625 (12P) 500 0.8 480/480 93.0% 93.5% 93.5% 240 118,650 N/A 120X39X78 10,580 10,485
750 (6P) 600 0.8 480/480 93.5% 94.5% 94.5% 240 119,200 N/A 108X39X78 8,100 8,005
750 (12P) 600 0.8 480/480 93.0% 93.5% 93.5% 240 142,350 N/A 120X39X78 11,580 11,485
750 (12P) 675 0.9 480/480 93.0% 93.5% 93.5% 240 160,150 N/A 120X39X78 11,880 11,785
1000 (12P)3 900 0.9 480/480 92.5% 93% 93% 240 231, 200 N/A 177X44X82 16,700 16,555

1 Efficiency measured at rated load power factor and non-linear load without input filter. Input filter loss is less than 0.5%.

2 Dimensions and weights do not include System Control Cabinet furnished with Multi-Module Systems. Weights are for the standard configurations; top-entry
models will be 200 pounds less.

3 1000 kVA unit is SCR-based inverter. See also separate 1000 kVA Series 610 brochure.
Specifications
See separate brochure for 1000 kVA

Input •Voltage Distortion: For linear loads, Standard Features


•Voltage: 480, 208 or 600 VAC, less than 4% THD. Maximum of 2% •Easy-to -read backlit LCD monitor/
3-phase, 3-wire plus ground RMS for any single harmonic. Less control display panel
•Voltage Range: +10, -15% (no than 5% THD for 100% nonlinear •Self-diagnostics
battery discharge down to -20%) loads without kVA/kW derating •Output isolation transformer
•Power Factor: 0.92 lagging with •Phasing Balance: 120° ±1° for •2-stage battery charge current limit
input filter (0.85 without) balanced load. 120° ±3° for 50% •2-stage input AC current limit
11
•Frequency Range: 60 Hz, ±5% unbalanced load •Internal wrap-around bypass
•Current Distortion: 7% reflected THD •Frequency Regulation: ±0.1% •Automatic and programmable retransfer
at full load with input filter. 4% •Load Power Factor Range: Unity to •Automatic line-drop compensation
reflected THD at full load with rated lagging load factor without •Battery overdischarge protection
optional 12-pulse rectifier and derating •Battery-time-remaining display and
input filter (for 500-750 kVA) •Overload: 125% of full load for ten battery statistics
•Subcycle Magnetizing Inrush: 2-3 minutes. 150% for 30 seconds. 104% •Automatic equalize charge timer
times normal full load current; 5-8 continuous •Emergency Power Off (EPO)
times normal for units with optional •Fault-Clearing Current: Up to 1,000% •Front access only for service and
input isolation transformer or for 16 milliseconds. Up to 500% for maintenance
12-pulse rectifier 40 milliseconds
•Configurable walk-in of 20% to 100% Options and Accessories
over 15 seconds Environmental •Input filter/power factor correction
•Operating Temperature: 0° to 40°C •12-pulse rectifier input (for 500-750 kVA)
Output and Bypass without derating •Load Bus Sync™ (for dual load
•Voltage: 480, 208 or 600 VAC, •Non-Operating Temperature: -20°C bus systems)
3-phase, 3-wire or 4-wire to 70°C •Power-Tie®Dual-Bus System
•Voltage Adjustment: ±5% •Humidity: 0-95% relative humidity •Input isolation transformer
•Voltage Regulation: ±0.5% for without condensation •Bypass isolation transformer
balanced load; ±2% for 50% •Operating Altitude: Up to 4,000 feet •Maintenance bypass cabinet,
unbalanced load (1200 meters) without derating matching or panelboard
•Dynamic Regulation: ±5% deviation •Non-Operating Altitude: Up to •Power distribution unit (single or
for 100% load step. ±4% deviation for 15,000 meters dual input)
50% load step. ±1% for loss or return •Audible noise 65-72 dBA typical, •Standard and custom
of AC input. Manual return of load to depending on kVA rating; measured switchgear packages
UPS: ±4% 5 ft. from the unit •Valve-regulated lead-acid
•Transient Response Time: Recover to battery packs
±1% of steady state within 16 Physical •Flooded rack-mounted
milliseconds (1 cycle) with •ETL listed to UL 1778 UPS standard battery systems
connected battery and CSA certified. Meets requirements •SNMP capabilities
for safe high-performance UPS •Remote monitor panel
operation •Communications interfaces
•Alarm status contacts
•Customer alarm inputs
TOTAL CONFIDENCE IN
THE DECISION YOU'VE MADE.

Liebert Series 610 UPS Po wer A v a il a b i li t y

No organization in the world today has a better understanding of exactly what it takes to keep critical L I E B E R T CO R P O R AT I O N
1050 DEARBORN DRIVE
information and industrial processes operating continuously than Liebert. P.O. BOX 29186
COLUMBUS, OHIO 43229
It starts with your local Liebert Representative, Distributor or Reseller. We are the only 800.877.9222 PHONE (U.S. &
CANADA ONLY)
company in this business that maintains such a strong local presence on a national and 614.888.0246 PHONE (OUTSIDE U.S.)
international basis. This resource, coupled with our broad product line, gives Liebert the ability 614.841.6022 FAX

to create a "tailored solution" that will meet your protection needs precisely and efficiently.
VIA LEONARDO DA VINCI 8
ZONA INDUSTRIALE TOGNANA
With your purchase of a Liebert product, you are buying into a company that stands behind its 35028 PIOVE DI SACCO (PD)
products. You are also aligning yourself with an organization that has a reputation for quality ITALY
39 049 9719 111 PHONE
and reliability that is second to none. 39 049 5841 257 FAX

In the systems protection business it's when you need someone to count on that you find out EMERSON NETWORK POWER ASIA PACIFIC
whether you’ve made the right choice. Liebert customers — many of them with us for over three 7/F., DAH SING FINANCIAL CENTRE
108 GLOUCESTER RD, WANCHAI
decades — already know how good their decision was. HONG KONG
852 25722201 PHONE
852 28029250 FAX

LIEBERT WEB SITE


http://www.liebert.com

24 X 7 TECH SUPPORT
800 222 5877 PHONE
614 841 6755 (OUTSIDE U.S.)

No matter where your needs for Due to continuing product improvement, specification are subject
to change without notice. Liebert Corporation assumes no
protecting the infrastructure of responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
your facility are heading — Liebert
© 2004 Liebert Corporation. All rights reserved throughout
is the one source that can deliver the world. Specifications subject to change without notice.
the high-availability solution. All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
® Keeping Business in Business is a registered trademark
of the Liebert Corporation.
The Emerson logo is a trademark and service mark
of Emerson Electric Co.

SL-30500 (2/04)
Printed in USA

That Is
The Liebert Experience