Sei sulla pagina 1di 24

Distance Protection

Distance Protection

Overview

The module distance protection allows the user


• to enter distance protection relays with their settings or characteristics
respectively,
• to get all voltage, current and impedance values (primary or secondary) seen
by a relay due to a short circuit,
• to check the relay settings,
• to set the relay automatically and
• to enter the tripping schedules.

All impedance values shown in the module are calculated with a short circuit
calculation according to the superposition method with or without load flow (see
chapter "Short Circuit").

The module distinguishes two types of relays


• user-defined or general relay (relay type given by the user)
• predefined relay type (relay type predefined by the program)

The characteristic of a general relay can be entered in a R/X-diagram. The user in


the dialog distance protection can enter the type of the relay.
When selecting the relay type from a predefined list, the user will be able to enter
the relay dependent setting parameters in a special dialog. The program will build
up the characteristic. The predefined list will be displayed, when pressing the
button "…" beside “Predefined type” in the dialog distance protection.

The tripping schedules are built-up by the user. This can be done in NEPLAN
menu option “Analysis-Distance protection-Tripping schedules”.

With menu option “Analysis-Distance protection-Protection device” the relay


characteristic and the impedances seen by the relay in case of short circuits on
nodes or lines are displayed in a R/X-diagram.

The evaluation or check of the relay settings can be done with a short circuit
calculation. The tripping time of the relays are displayed in the single line diagram.

NEPLAN User's Guide V5 10-1


Distance Protection

Starter

The following starter systems can be entered:


• pure over current starter
• under impedance starter (U-/I-limits)
• R/X-characteristic

The starter system can be selected in the dialog “Starter” of the distance
protection relay. All starter systems can be defined for line-line and line-earth
faults. The selection of the fault type will be done with “Data input” (“L_L” or “L-E”)
in the dialog “Parameter” of the relay.

With the starter system coupled are


• the directional end time and
• the non-directional end time.

The pure over current and the under impedance starter can be defined for user-
defined relays as well as for predefined relays. On the other hand the starter R/X-
characteristic cannot be defined for predefined relays, because it is determined by
the setting parameters.

Pure Over current


The input data are:

U / Ur

Starting area

I / Ir

I1/Ir

Fig. 10.1 Pure Over current starter

10-2 NEPLAN User's Guide V5


Distance Protection

The relay will start if the measured line current is larger than I1/Ir independent of
the voltage. Ir is the nominal current at primary side of the current transformer. A
current limit can be defined for line-line and line-earth faults.

Under Impedance
The data are entered according to fig. 10.2 and 10.3:

U / Ur

U2/Ur
U1/Ur

Starting area

I / Ir

I1/Ir I2/Ir

Fig. 10.2 Phase-independent under impedance starter

U / Ur

U2/Ur=
U1/Ur

Starting area

I / Ir

I1/Ir I2/Ir I3/Ir

Fig. 10.3 Phase-dependent under impedance starter

In case of under impedance starter not only the line current, but also the voltage
will be considered. The relay will start if the line current and the line-earth voltage
are in the starting area.

NEPLAN User's Guide V5 10-3


Distance Protection

The value I3/Ir should set to zero for phase-independent under impedance
starters. The input of "Phi1" and "Phi2" is then unimportant.

The value I3/Ir must be defined for a phase-dependent under impedance starter.
The values U1/Ur and U2/Ur must be set equal. In case of a short circuit and if the
angle between line current and line-earth voltage is between Phi1 and Phi2, the
current limit I3/Ir is considered instead of I2/Ir.

R/X-Characteristic
The following characteristics can be entered
• a polygon defined by a table of R/X values or
• a circle defined by a centre and a radius

If the measured impedance is inside the polygon or inside the circle the relay will
start.

Starting area
R

Fig. 10.4 Starter with R/X-characteristic

A characteristic for line-line and for line-earth faults can be defined. The
characteristic for predefined relays is defined by the setting parameters.

10-4 NEPLAN User's Guide V5


Distance Protection

Measurements

The following zones can be entered:


• Zones 1 – 4
• Overreach zone (zone 1 ext.)
• Backward zone
• Auto-reclosure zone

The zones are defined by a characteristic (polygon or circle). For predefined


relays the characteristic is determined by the relay setting parameters. The
characteristics can be given as primary or secondary values. A characteristic for
line-line and line-earth faults can be entered. The type of input can be selected by
the parameter „Data input“ in the relay dialog.

A measurement direction can be assigned to each zone. The measurement


direction is normally given by the proper entry of the characteristic. The definition
of the measurement direction is only necessary, if a simplified characteristic is
entered, e.g. a circle around zero point (0/0) or a rectangular in all forth
quadrants. With the input of a direction the circle or the rectangular will be divided
through a diagonal in the 2. and 4. quadrants. The diagonal changes the
characteristic.

To each zone a tripping time or time delay in seconds must be assigned. The
input of the delay time is also done for line-line and line-earth faults.

Each zone can be activated or de-activated. Zones, which are not active, are not
considered during the calculations.

Setting Parameters for Predefined Relays


The following relay types are predefined
• ABB REL316
• Siemens 7SA511/7SA513
• AEG PD551/PD531 and SD36

A special dialog will be created for each relay after having selected a predefined
relay. If a predefined relay has an over current or a under impedance starter the
parameters has to be entered according to the sections above.
The setting parameters are explained in the corresponding manual.

NEPLAN User's Guide V5 10-5


Distance Protection

ABB REL316
Starter characteristic:

X
XA

RLoad

RB R

AngleLoad RA

-RLoad

XB

Tripping characteristic (only for 1st stage)


X
X

27°

-X / 8 RR R
27° RRE
-RR / 2
-RRE / 2

For each stage the compensation factor k0 and for parallel lines also the
compensation factor k0m has to be entered.

Siemens 7SA511, 7SA513


Starter characteristic:

10-6 NEPLAN User's Guide V5


Distance Protection

X
X+A

RAE RA2 RA1 RA2 R


RA1 PHIA RAE

X-A

Tripping characteristic (only for 1st stage)


X

X1

R1 RE1 R
RE1 R1 45°

AEG PD531, PD551, SD36


Starter characteristic (only for PD551):

NEPLAN User's Guide V5 10-7


Distance Protection

X
110°

Xv

Zv

R
Beta Rv L-E
Rv L-L
Zr

70°

Tripping characteristic polygon (only for 1st stage)

-135°

-RL-E Alpha R
RL-L
-RL-L
RL-E

-X

Tripping characteristic circle with or without arc compensation (only for 1st stage)

10-8 NEPLAN User's Guide V5


Distance Protection

Delta

-135° Arc compensation

Alpha
Phi R

The function to get the arc compensation circle is:

Z
Zcor =
1 + sin(delta)

Delta is in the range -45° < phi < alpha:


delta = alpha - phi
and in the range 135° < phi < (alpha + 180°):
delta = alpha - phi + 180°

For the overreach stage the factor ku for L-L and L-E faults must be entered.

Backup Protection

The distance protection relay can also be defined as an over current relay with
two definite time stages

NEPLAN User's Guide V5 10-9


Distance Protection

t2

t1

I / Ir

I1/Ir I2/Ir

Fig. 10.5 2 definite time stages

I1/Ir and I2/Ir are the setting values for the two stages. Ir is the nominal current of
the CT at primary side. The delay times t1 and t2 are tripping time of the two
stages.

When evaluating the relay settings and if the relay has not been started by the
distance protection part of the relay, the values of the backup protection are
checked (see relay evaluation). If there is no over current functionality in the relay
no values have to be entered here.

Automatic Impedance Setting

The threshold impedance values or the characteristics of the stages 1 to 4 are


automatically calculated by the program with the help of the tripping schedules,
which are entered by the user.
The tripping schedules are generated in the NEPLAN menu option „Analysis-
Distance protection-Tripping schedule“. A relay can belong to any number of
tripping schedules. The arbitrary numbers of schedules are reduced to a single
schedule with the smallest impedances. In the minimum impedance path contains
only relay nodes. In the dialog “Setting” and at “Decisive nodes for relay setting”
the smallest impedance path, that means the nodes and the corresponding
impedances, are displayed. The displayed impedances are positive sequence
impedances, which the present relay will measure, if a 3phase short circuit at the
nodes takes place. The impedances are calculated according to the superposition
method with or without load flow (see short circuit parameters).

10-10 NEPLAN User's Guide V5


Distance Protection

There are two methods to set the relays:


• Relative
• Absolute

These methods can be selected in the dialog „Setting“. The two methods are
explained below. The base for both methods is the minimum impedance path.
The figure below shows an example for the creation of a minimum impedance
path.

Relay location A
R

R
User defined tripping
schedules
R

1. 2. 3. Zone
R Minimum impedance path
B C D
Z / Ohm

Fig. 10.6 Getting the minimum impedance path in meshed networks

With the minimum impedance path the relay in location R will be set.

Setting according to relative method


This is the usual method to set the stages of a relay.

NEPLAN User's Guide V5 10-11


Distance Protection

b2

b1

a b Z

Fig. 10.7 Setting according to relative method

The rules are:


Z1 = p1 * a
Z2 = p2 * (a + b1)
Z3 = p3 * (a + b2)

Z1ext = p1ext* a (overreach zone or zone 1 ext.)

Z1, Z2, Z3 are the setting values at the relay. The parameter p1 for 1. zone, p2 for
2. zone, p3 for 3. zone, etc. are input values, which can be entered in the dialog
„Zone settings”. The rule for setting zone 4 is accordingly.

Impedance corrections due to infeeds are considered in the lines b1 and b2.

Setting according to absolute method


This method is used to set the last zone. For example, if the last zone has to
cover 50% of the transformer impedance.

10-12 NEPLAN User's Guide V5


Distance Protection

b1

Z
a b

Fig. 10.8 Setting according to absolute method

The rules are:


Z1 = p1 * a
Z2 = a + p2 * b b1 = p2*b

The zone (impedance) is calculated absolutely to the impedance of the


corresponding zone.

Impedance corrections due to infeeds are considered in the line b.

Setting of relay considering the minimum reach


If the parameters „Minimum zone setting“ for zone 2 and/or zone 3 are activated,
the program will check after the automatic setting if a minimum impedance value
for zone 2 or zone 3 is reached. If not, the set values will be corrected.

t
(a + k * blg) / p2

a / p1

a blg Z

Fig. 10.9 Minimum reach

NEPLAN User's Guide V5 10-13


Distance Protection

The minimum reach is calculated as follows:


For zone 2: Z1min = a / p1
For zone 3: Z2min = pmin * a (for parallel lines)
Z2min = (a + b lg) / p2

blg means the longest adjacent line. The user can consider the infeed factor for
calculating the impedance blg. To calculate the impedance blg it is maybe
necessary to switch off or to reduce the infeed. The calculation of impedance blg
at the present stage of the network is done by pressing the button „Get longest
line for zone 3“ in dialog „Setting“. For the normal setting of the relay the infeed
must be considered in full.

Considering Arc resistance


The calculated impedance values are corrected with the arc resistance and the
resistance for tower footing path. These values can be entered in the relay
specific parameters.

Correction for line-line faults:


RR = RR + RfL-L / 2

Correction for line-earth faults:


RR = RR + RfL-E + RM
with:
RfL-L: Arc resistance for line - line faults
RfL-E: Arc resistance for line - earth faults
RM: Tower resistance for tower footing earth path

If no characteristic has been assigned to the relay the following rectangle will be
assigned:

P1 = -RR, -XR (R, X)


P2 = -RR, XR
P3 = RR, XR
P4 = RR, -XR

XR and RR are the reactance and resistance calculated from the impedances Z1,
Z2, Z3, etc. of each zone. If defining a direction, the characteristic will be modified
by the “direction line” into the 2. and 4. quadrant.

10-14 NEPLAN User's Guide V5


Distance Protection

In case that a characteristic has already been assigned to the relay, the
characteristic will be reduced or enlarged proportional.

The relay setting parameters are assigned to the predefined relays directly.

Tripping schedule

The user can define any number of tripping schedules with NEPLAN menu option
„Analysis-Distance protection-Tripping schedules“. After having selected this
option the following items are available
• Tripping schedule
with add, delete, edit, display graph and print
• View
with zoom out, zoom out all, edit, trace mouse position, trace curve, colors,
etc.
The option „Tripping schedule-Edit“ allows the user to define a tripping schedule.
A tripping schedule is described by the relay Z/t-characteristic and the node
impedances measured from the relay. Any number of nodes can be displayed.
Important is only, that the relay location nodes are displayed. The relay location
nodes are starting points for the Z/t-characteristic.

The following parameters are available:


Fig. No. An arbitrary figure number can be entered.
Title A description of the schedule can be entered.
Relays A new relay will be inserted. The node, in which the selected
Insert relay has been built-in, will also be added to the list of displayed
nodes.
Relays Parameters of the selected relay are displayed in a dialog.
Edit Characteristic or setting parameters can be changed directly.
Relays This function allows deleting a relay from the present schedule.
Delete
Nodes A new node will be inserted in the list of nodes to be displayed.
Insert A node can only be inserted once.
Nodes This function allows deleting a node from the present schedule.
Delete Relay location nodes cannot be deleted.
Recalculate The dialog will be closed and the tripping schedule recalculated
and Close or regenerated. A tripping schedule is generated by intersection
of the relay characteristic and the node impedances (see
below). This button has to be pressed, if relay data has

NEPLAN User's Guide V5 10-15


Distance Protection

changed.
Close The dialog will be closed without regeneration of the schedule.

The items „View-Zoom out“ and „View-Zoom out all“ allow changing the view of
the diagram. These items are only active, if a “Zoom” has taken place. Holding the
left mouse button and selecting the section to be zoomed the user can do a
„Zoom“. The colors for the Z/t-characteristics and the nodes can be selected in
“View-colors”. Up to six different colors are available.

The items of menu option „View“ can also be displayed by pressing the right
mouse button on the diagram.

A footer or header can be displayed.

10-16 NEPLAN User's Guide V5


Distance Protection

Structure of tripping schedule


Relays can measure the impedance of the same node distort, because of infeeds
and parallel lines. The following example illustrates that.

t t
K1 K2 K1 K2

A B A B

Z Z
a b a b1

Fig. 10.10 a) Without infeed b) With infeed

The relay A measures the impedance of node K2 without infeed as:


ZK2 = a + b;
The relay A measures the impedance of node K2 with infeed as:
ZK2 = a + b1 = a + k*b; k > 1.0;
However relay B measures the impedance of node K2 always as:
ZK2 = b;

Obviously relays A and B have different impedance coordinate systems caused


by the infeed. It is therefore important to relate all Z/t-characteristics and node
impedances to one common coordinate system. The common coordinate system
is given by the first relay in the tripping schedule. The conversion factor(s) are the
infeed factor(s). The infeed factor is calculated as:

A IA ‘ B IA‘+IB‘

IB‘

NEPLAN User's Guide V5 10-17


Distance Protection

Fig. 10.11 Calculation of the infeed factor

I A '+ I B '
k= >= 1.0
IA'

The calculation of the impedance values from the R/X- to Z/t-diagram is done with
the help of the complex node impedance. The distance of the intersection
between the node impedance and the characteristics (polygon or circle) from the
origin (0,0), represents the impedance, which is shown in the Z/t-diagram:

X /O h m
N o d e im p e d a n c e

1. zone
P2 P3

R /O h m
Phi L P4
P1

t/s

1. zone

Z /O h m

Fig. 10.12 Calculation of the impedance values from the R/X- to the Z/t-diagram

Display of impedances and relay characteristics

Relay characteristics and short circuit impedances measured by the relay can be
displayed in a R/X diagram. The short circuits can be defined on nodes and lines.
After having selected option „Analysis-Distance protection-Protection devices“ all
relays are listed at the left side of the screen. The following options are available:
• Protection devices
with Display relay characteristic, Show relay dialog, Edit parameters, Show
impedance list, Show relay documentation, etc.
• View
with Zoom out, Zoom out all, Trace mouse position, Trace curve, etc.

10-18 NEPLAN User's Guide V5


Distance Protection

Impedances to be displayed in the diagram can be selected with option „Edit


parameters“. The dialog can also be called by a double click on the diagram. The
dialog contents the following parameters:

Fault type The fault type can be selected here. The same types are
available as in the SC calculation (see short circuit calculation
parameters). The calculation method has to be set in the SC
calculation parameters (superposition with or without load flow).
Impedances The impedances to be displayed in the diagram can be chosen.
The calculation of the loop impedances is explained below. The
displayed impedances are secondary or primary values
according to the parameter set by the user.
Faults on The buttons „Insert“ and „Delete“ allows the user to define the
nodes faulted nodes. The impedances measured by the relay are
displayed in the diagram. All faulted nodes are listed. A node in
the list can be activated or de-activated. Parameter “Faults on
nodes-Active“ allows activating or de-activating all nodes in the
list.
Faults on lines The buttons „Insert“ and „Delete“ allows the user to define the
faulted lines. The impedances measured by the relay are
displayed in the diagram. All faulted lines are listed. A line in the
list can be activated or de-activated. Additionally the user can
define the fault location as the distance in percentage from the
“From node” of the line. The parameter “scanning” indicates if
the fault location will scan over the line in a given distance. In
this case not only one set of impedances will be calculated, but
a quantity of impedance sets (trajectory). Parameter “Faults on
lines-Active“ allows activating or de-activating all lines in the list.
Characteristic The relay characteristic for line-line and/or line-earth faults can
be selected here.
Recalculate The dialog will be closed and the impedances recalculated. This
and Close button has to be pressed, if relay or node data has changed.
Close The dialog will be closed without recalculation of impedances.

The items „View-Zoom out“ and „View-Zoom out all“ allow changing the view of
the diagram. These items are only active, if a “Zoom” has taken place. Holding the
left mouse button and selecting the section to be zoomed the user can do a
„Zoom“.

The items of menu option „View“ can also be displayed by pressing the right
mouse button on the diagram.

NEPLAN User's Guide V5 10-19


Distance Protection

A footer or header can be displayed.

Menu item „Protection devices-Show impedance list“ lists all calculated


impedances. The impedance values can be exported to a file RDS. The fields are
separated by tabs.

Calculated relay impedances


The following impedances are measured by the relay:
• Impedance of the positive sequence system
This impedance is only reasonable, when making 3phase faults.
• Loop impedances
Loop impedances are in practice measured impedances by the relay.

Loop impedances are calculated as follows:

with compensation with compensation for


parallel lines
UR UR UR − US
ZR = ZR = Z RS =
I R + 3 I 0 k0 I R + 3I 0 k0 + k0 m I Em IR − IS
US US U S − UT
ZS = ZS = Z ST =
I S + 3 I 0 k0 I S + 3I 0k0 + k0 m I Em I S − IT
UT UT UT − U R
ZT = ZT = ZTR =
IT + 3I 0 k0 I T + 3I 0k0 + k0 m I Em IT − I R
Z 0 − Z1 Z0m
k0 = k0 m =
3 ⋅ Z1 3 ⋅ Z1

with
UR, US, UT Line-earth voltage in phase R, S, T or L1, L2, L3
IR, IS, IT Line currents in phase R, S, T or L1, L2, L3
3I0 Three times zero sequence system current or earth current IE
Z1, Z0 Line impedance of positive and zero sequence system
Z0m Zero sequence coupling impedance of two parallel lines
IEm Earth current of parallel line
k0 Compensation factor for zero sequence system (input value)
k0m Compensation factor for parallel line coupling (input values).
The line, which is in parallel to the line with the present relay,
can be entered in the dialog of relay.

10-20 NEPLAN User's Guide V5


Distance Protection

NEPLAN User's Guide V5 10-21


Distance Protection

Procedure for Entering a Relay

For the input and setting of a relay the following procedure has to be done:

• Step: Insert all distance protection relay in the network. This can be done
graphic- or list-oriented. Each relay has to be named (predefined or user-
defined relay). Characteristics can also be imported.
• Step: Insert to each DP-relay current (CTs) and voltage transformers (VTs).
The VTs are assigned to a node. This is only necessary, if secondary values
are considered. It is also possible to enter the impedance ratio directly.
• Step: Define all tripping schedules, even when no relay characteristics are
entered at this point and thus the schedules not displayable. This step is very
important for the automatic setting of the relays.
• Step: To each relay a starter system can be assigned and the parameter or
characteristic can be entered for the zones. The relays can also be set
automatically.
• Step: Sometimes it is necessary to define a node as a distance protection
node, when this node is important for the automatic setting of a relay. This
can be done in the dialog of the node (see remark above).
• Step: To evaluate the relay settings short circuits can be calculated in the
network. The tripping time of the relays are displayed in the single line
diagram.

Remark:
Although in node B there is no relay located, node B can be important for the
automatic setting of the relay DP. This is the case, if for example node B is the
end of a feeder or if in node B there is a over current protection.

B C

DP

The parameter „Distance protection node“ in the node dialog indicates if the node
is relevant for the automatic relay setting.

10-22 NEPLAN User's Guide V5


Distance Protection

Relay Documentation

After having selected option „Analysis-Distance protection-Protection


devices“ all relays are listed at the left side of the screen. A relay will be
documented by choosing “Protection devices-Relay documentation”. Beside the
relay parameters the node impedances, which are important for the relay setting,
are displayed.

Relay location

Z / Ohm
1. 2. 3. Zone

Impedance Impedance Impedance


zone 1 zone 2 zone 3

Fig. 10.13 Impedances of relay zones

The impedance values of stage 1 represent the line impedance or the impedance
to the next relay node. The impedance values are given for the positive system. In
order to get the line impedance between stage 1 and 2 a subtraction of the
impedance values of stage 2 and 1 must be done.

The documentation shows the setting values for a general (user-defined) relay
with consideration of the arc resistances.

The relay documentation can be exported to a file with extension DDS. The fields
are separated by tabs.

NEPLAN User's Guide V5 10-23


Distance Protection

Checking the Relay Settings

All relays can be checked by calculating several variants (different fault locations,
faults on lines, arbitrary fault types). The program calculates the tripping times of
the relays. The tripping times are displayed in the single line diagram. It is
recommended to select only one fault location and to set in return the fault
distance (see SC calculation parameters) to a large number. With it all
voltages and currents at the relays are calculated.

10-24 NEPLAN User's Guide V5

Potrebbero piacerti anche