The Ingress Protection (IP) for The first character numeral The second character numeral
all low voltage enclosures up indicates the degree of indicates the degree of
to 1000 V a.c. and 1500 V d.c. protection provided by the protection provided by the
is defined in identical fashion enclosure with respect to enclosure with respect to
by the standards EN 60529 - persons, also to the equipment harmful ingress of water; a
IEC 529 it comprises the inside the enclosure. third character may be used
letters IP followed by two to indicate mechanical
character numerals: strength. An x signifies that no
test has been carried out.
312
Type Tested Assemblies
As there are no diversity factors applied to consumer units, the Form 1 - No separation
incoming circuit and the bus-bar system must be able to carry
their full rated current without exceeding the temperature rise Form 2 - Separation of bus-bars from the functional units
limits.
Form 3 - Separation of bus-bars from the functional units and
separation of all functional units from one another, but
not their outgoing terminals.
313
Type Tested Assemblies
For example, an enclosure with an index IP20 would provide All Invicta panel boards have been independently tested at a UK
protection against solid bodies greater than 12mm but offer no ASTA approved test laboratory.
protection against water; however an index IP31 would provide
protection against solid bodies greater than 2.5mm and in additi- To assist in the selection of the correct panelboard, suitable for
on against vertically dripping water. use on systems having prospective fault levels ranging from 15
to 50kA, Hager have prepared the following simple charts.
Sometimes the letter ‘X’ is used in place of the first or
second numeral to indicate that tests have not been made or are Invicta 250 Panelboard
not considered relevant. For example IP4X provides protection Enclosure - Degree of protection (door closed) IP3X
against a 1mm probe but has not been tested for the ingress of
water. Refer to page 312 for ingress protection chart. Internal Separation Form 3
Bus-bar rated current 800A
Invicta 125 Panelboard Bus-bar rated short-time withstand current 35kA for 1s
Rated conditional short circuit current 40kA - direct
Enclosure - Degree of protection (door closed) IP3X connected
Internal Separation Form 3 with 250A
Bus-bar rated current 400A MCCB
Bus-bar rated short-time withstand current 35kA for 1s outgoing
direct connected
(unconditional) Incoming - Main Terminals 800A
Non-Auto MCCB 800A
Incoming - Main Terminals 400A MCCB 800A
Non-Auto MCCB 400A
MCCB 400A Outgoing - H125 MCCBs 16 to 125A
H250 MCCBs 160 to 250A
6 way
Outgoing - H125 MCCBs 16 to 125A 8 way
4 way 12 way
6 way 18 way
8 way Maximum Prospective Short-circuit level at point of
12 way application with
Maximum Prospective Short-circuit level
at point of application with • Incomer - main terminals - outgoing H125 15kA
• Incomer - main terminals - outgoing only H250 40kA
• Incomer - non-auto MCCB - outgoing H125 15kA
• Incomer - main terminals - outgoing H125 15kA • Incomer - non-auto MCCB - outgoing only H250 40kA
• Incomer - non-auto MCCB - outgoing H125 15kA • Incomer - H400 MCCB - outgoing H125 25kA
• Incomer - H400 MCCB - outgoing H125 25kA • Incomer - H400 MCCB - outgoing only H250 35kA
• Incomer - H800 MCCB - outgoing only H250 50kA
Table 1
314
Invicta 125
- Dimensions
Dimensions
Cat Ref. Height Width Depth
JN304P / JN304P1 976 710 156
JN306P / JN306P1 1053 710 156
JN308P / JN308P1 1130 710 156
JN312P / JN312P1 1284 710 156
Terminals
No. of Neutral Earth
TP Ways
4 2 x 6 x 50mm 2 x 9 x 25mm
6 2 x 9 x 50mm 2 x 12 x 25mm
8 2 x 12 x 50mm 2 x 15 x 25mm
12 2 x 18 x 50mm 2 x 21 x 25mm
Main M12 M10
connection
Extension Boxes
Cat Ref. Height Width Depth
JN201E / JN201E1 250 710 156
JN203E / JN203E1 400 710 156
JN205E 250 710 156
JN206E 400 710 156
JN301A 400 710 156
250 710 156
Invicta
315