Weishaupt Monarch oil burners 1/2002 CA

Sizes 1 and 3
Description

Weishaupt Monarch oil burners are of Fuels The flame safeguard is mounted on the
the fully automatic pressure atomizing Light oil #2 to Medium heavy oil #4. burner on all standard L and M burners,
type. Their design has been carefully Viscosity: but can be supplied loose if requested.
considered down to the smallest Types Monarch L and RL - Together with the control panel, each
detail and has been proven to be < 6 cSt (6 mm2/s) at 68F (20°C) burner forms one complete unit. On the
successful over and over again. They
meet all the demands for safety, Type Monarch M - RL burner, the flame safeguard is
reliability and low cost operation. ≤ 75 cSt (75 mm2/s) at 122F (50°C) supplied loose for installation in the
control panel.
The burners are distinguished by a Regulation
variety of excellent features: On L and M type burners, the regulation There is no interference with radio and
of oil and air takes place as follows: television reception, as radio interference
■ Range of application 1.75 - 19 GPH ■ two stage, nozzle head with two noz- created during ignition is below the
(240 - 2,645 MBH) zles and a motor controlled, quickly permitted limits specified by the relevant
■ Automatic sequence of operations opening air damper. EMC standards and regulations.
■ Stable fan characteristics – good ■ three stage, with three nozzles and a
combustion results motor controlled, slowly opening air Quiet operation
■ Air regulation on pressure side damper. Weishaupt burners operate quietly. All air
■ Air damper closed on burner shut- handling burner parts have been
down The RL burners control fuel and air ratio aerodynamically designed, the fuel / air
■ Quiet operation in compound. The burner can, depending mixing noise is reduced to a minimum
■ Complete pre-wired integral on the controller and servomotor, be and rotors and fan wheels are
switchgear either: dynamically balanced. For installations
■ Hinged burner casing ■ sliding two stage (20 s running time) where special emphasis is placed on
■ Combustion head can be pulled out or burners with low noise levels, sound
when the burner is hinged open ■ modulating (42 s running time) absorbers, which considerably reduce
■ The design of the burner makes burner noise, are available as an option.
installation, adjustment and servicing With sliding two stage regulation, the low
easy and high fire positions are fixed within the Oil temperature regulation
burner operating range. The burner Medium/ heavy oil burners are equipped
Construction slides to one position or the other, with oil preheater. The oil is quickly
All the components are assembled in one depending on the appliance demand, heated to the required atomizing
unit. The motor drives the fan and the fuel and there are no rapid changes of fuel temperature, due to the large heat
pump. All the equipment used for the throughput. exchanger surface combined with a
regulation of fuel and air is clearly relatively small oil volume. Fast and
arranged and easily accessible. The By utilizing a suitable controller into the evenly heat distribution prevents local
burners can be hinged to the left or right, control panel, the burner can be overheating and carbonization of the oil.
which simplifies service work on the operated in modulating mode.
combustion head, diffuser, nozzles and Modulating burners operate at any point Heated nozzle head and nozzle
ignition electrodes. within the capacity range, depending on recirculation system on medium/
the heat demand. heavy oil burners
Application All medium/ heavy oil burners are fitted
The burners can be used on hot water On sliding two stage burners and with a heated nozzle head system. After
boilers, steam boilers, air heaters and for modulating burners, the slow capacity the oil temperature in the nozzle head has
various heating processes. The burners alteration ensures a particularly good been reached, the burner is released for
are used in particular on modern, high matching to the demand of the heating operation by a thermostat. During
efficient boilers, as they are capable of appliance. prepurge, heated oil flows through the
overcoming high combustion chamber nozzle head and oil line system. This
pressures. RL burners are preferably Flame safeguard ensures that evenly heated oil is available
used where there is a continually The burner flame safeguard automatically for good combustion.
changing heat demand. sequences the operations and monitors
the flame optically via the flame sensor.

2
Monarch L light oil burner, two stage

Integral switchgear (light oil burner) Monarch M medium heavy oil burner, preheater side

Pressure side air regulation Monarch RL light oil burner, compound regulator side

Combustion head removable from behind Monarch RL light oil burner, regulating system
3
Scope of delivery

Scope of delivery L1Z-B L3Z-A L1T-B M1Z-B RL3-A


L3T-A M3Z-A
Burner casing with integral air inlet, hinged flange, hinge interlock switch, flange gasket, ● ● ● ● ●
Weishaupt burner motor, fan, pump, oil hoses, nozzle assembly, combustion head, ignition
transformer, ignition cables, ignition electrodes, fixing screws, air damper on fan pressure side.
Oil solenoid valve(s) ● ● ● ● ●
Additional safety valve(s) ● ● ● ● ●
and oil pressure switch (on burners > 8 GPH/ 30 kg/h) – – – ● ●
Nozzle(s) ● ● ● ● ●
Burner flame safeguard with flame sensor
– Type LAL for burners ● ● ● ● ●
Terminal strip or ● ● ● ● ●
Integral switchgear ● ● ● ● –
Servomotor for air regulation ● ● ● ● –
Servomotor for oil / air regulation with regulating cam (sliding two stage burners – – – – ●
type SQM 10.15561, 20 s running time; modulating burners type SQM 10.16561,
42 s running time), oil regulator, spill type nozzle
Oil preheater, heated nozzle head and nozzle recirculation system, – – – ● –
filter

Parts supplied with integral Nomenclature of burner type


switchgear (ISG version) 1 contactor for oil preheater on burner R L 3 Z – A version ZMD
The integral switchgear version includes type M1Z-B (2 on burner type M3Z-A)
E = Single phase AC
all the parts required for operation. D = Three phase AC
1 stage 1 control switch with indicating
lamp Type of regulation
1 stage 2 control switch with indicating ZM = sliding two stage
Code for burner series
lamp Z = two stage, T = three stage
1 contactor (motor) Size
1 overload relay L = #2 light oil, M = #4 medium heavy oil
R = modulating burner
(three phase burners only)

Monarch L light oil burner, two stage Cover

4
Model overview
Types of regulation

Weishaupt Monarch oil burners

quick regulation slow (sliding) regulation

#2 light oil burners #2 heavy medium oil burners #2 light oil burners

sliding
two stage three stage two stage modulating
two stage

L1Z-B and L3Z-A L1T-B and M1Z-B and


RL3-A
L3T-A M3Z-A

Two stage and three stage SV1 SV2 HF


regulation (Z/T)
Standard burner version 110V 110V IF
■ Oil is released at start when solenoid SV3 LF
valves 1 and 2 open. The burner runs
at low fire. 110V
■ High fire is reached when solenoid SV4 on off
valve 3 / 4 opens.
■ The capacity is regulated by opening 110V
and closing solenoid valve 3 or 3
and 4
(Standard burner version)

Sliding two stage and modulating HF


regulation (ZM)
■ For burner start the oil regulator goes 55V 55V
into the ‘ignition’ position. LF
■ A slow running oil / air compound
servomotor adjusts the oil quantity up IGN
55V 55V
to high fire. The servomotor regulates P M on off
the burner capacity between low and
high fire.
■ The difference between sliding two HF
stage and modulating burners is that
on the modulating version the servo-
motor on the burner has a running LF
time of 42 s and on the sliding two IGN
stage burner a running time of 20 s.
In addition a special controller should on off
be fitted into the control panel for
modulating operation.
HF = High fire, IF = Med. fire, Upper graph: sliding two stage
LF = Low fire, IGN = ignition position Lower graph: modulating

5
Size 1 burner selection
Burner rating / combustion chamber pressure

Burner type _______ L1Z-B and L1T-B


Version ____________________ E and D “WC
Combustion head type
L1Z-B _____ M1/5a-105Kx33
L1T-B _____ M1/5a-105Kx36 3.0
Rating GPH ____________ 1.7 - 8.4 2.5
MBH _________ 239 - 1,177 2.0
1.5
1.0
0.5
0.0
-0.5
-1.0
MBH 0 200 400 600 800 1,000 1,200 1,400 1,600
GPH 0 2 4 6 8 10

Burner type _______ L1Z-B and L1T-B


Version ____________________ E and D “WC
Combustion head type
L1Z-B _____ M1/5a-100Kx33
L1T-B _____ M1/5a-100Kx36 3.0
Rating GPH ___________ 2.9 - 10.1 2.5
MBH _________ 410 - 1,416 2.0
1.5
1.0
0.5
0.0
-0.5
-1.0
MBH 0 200 400 600 800 1,000 1,200 1,400 1,600
GPH 0 2 4 6 8 10

Burner type ________________ M1Z-B


Version ____________________ E and D “WC
Combustion head type
M1Z-B ____ M1/5a-105Kx33
Rating GPH ____________ 2.2 - 8.1 3.0
MBH _________ 307 - 1,177 2.5
2.0
1.5
1.0
0.5
0.0
-0.5
-1.0
MBH 0 200 400 600 800 1,000 1,200 1,400 1,600
GPH 0 2 4 6 8 10

6
Burner type ________________ M1Z-B
Version ____________________ E and D “WC
Combustion head type
M1Z-B ____ M1/5a-100Kx33
Rating GPH ____________ 2.9 - 9.8 3.0
MBH _________ 410 - 1,416 2.5
2.0
1.5
1.0
0.5
0.0
-0.5
-1.0
MBH 0 200 400 600 800 1,000 1,200 1,400 1,600
GPH 0 2 4 6 8 10

The capacities in relation to Shut off devices


combustion chamber resistances are All burners with an oil throughput > 8
maximum values, which were GPH (30 kg/h) are equipped with a
measured on idealized test flame second solenoid valve (safety valve) as
tubes. standard.

All ratings data given relate to an air Voltages and frequencies


temperature of 68F (20°C) and an The burners are supplied with single
installation height above sea level of phase 110 V, 60 Hz supply (E), or three
1,640ft (500m). phase 460 V, 60 Hz supply (D) as
standard. Other voltages and
The oil throughput information refers frequencies are available upon request.
to a calorific value of
140,000 BTU/Gallon for #2 oil Burner motor standard version
145,000 BTU/Gallon for #4 oil Btrop class insulation, to IP54. Motors
can also be supplied to F class
insulation.

7
Size 3 burner selection
Burner rating / combustion chamber pressure

Burner type ____ L3Z-A, L3T-A, M3Z-A


Version “WC
L-Burner _________ E, D, E-C and D-C 3.0
M-Burner _______________ D and D-C
Combustion head type__ M2/1a-116x40
Rating GPH #2 oil ______ 2.9 - 12.7 2.0
GPH #4 oil ______ 2.8 - 12.4
MBH__________ 410 - 1,792 1.0

0.0

-1.0
MBH 0 400 800 1,200 1,600 2,000 2,400 2,800
GPH [#2] 0 2 4 6 8 10 12 14 16 18 20
GPH [#4] 0 2 4 6 8 10 12 14 16 18 20

Burner type ____ L3Z-A, L3T-A, M3Z-A


Version “WC
L-Burner _________ E, D, E-C and D-C 3.0
M-Burner _______________ D and D-C
Combustion head type__ M5/2a-116x40
Rating GPH #2 oil _______4.6 - 18.8 2.0
GPH #4 oil _______4.5 - 18.4
MBH ___________648 - 2,645 1.0

0.0

-1.0
MBH 0 400 800 1,200 1,600 2,000 2,400 2,800
GPH [#2] 0 2 4 6 8 10 12 14 16 18 20
GPH [#4] 0 2 4 6 8 10 12 14 16 18 20

8
Burner type _________________ RL3-A
Version ______________ ZME and ZMD “WC
Combustion head type __ M2/1a-116x40
Rating GPH ____________2.9 - 12.7
MBH __________410 - 1,792 3.0

2.0

1.0

0.0

-1.0
MBH 0 400 800 1,200 1,600 2,000 2,400 2,800
GPH [#2] 0 2 4 6 8 10 12 14 16 18 20

Burner type _________________ RL3-A


Version ______________ ZME and ZMD “WC
Combustion head type__M5/2a-116x40
Rating GPH ___________ 4.6 - 18.8
MBH _________ 648 - 2,645 3.0

2.0

1.0

0.0

-1.0
MBH 0 400 800 1,200 1,600 2,000 2,400 2,800
GPH [#2] 0 2 4 6 8 10 12 14 16 18 20

The capacities in relation to Shut off devices Modulating burners


combustion chamber resistances are All burners with an oil throughput The modulating RL3-A burner is based
maximum values, which were > 8 GPH (30 kg/h) are equipped with a on the sliding two stage burner. The
measured on idealized test flame second solenoid valve (safety valve) as modulating feature is obtained by fitting a
tubes. standard. suitable modulating controller into the
panel.
All ratings data given relate to an air Voltages and frequencies
temperature of 68F (20°C) and an The burners are supplied with single
installation height above sea level of phase 110 V, 60 Hz supply (E), or three
1,640ft (500 m). phase 460 V, 60 Hz supply (D) as
standard. Other voltages and
The oil throughput information refers frequencies are available upon request.
to a calorific value of
140,000 BTU/Gallon for #2 oil Burner motor standard version
145,000 BTU/Gallon for #4 oil Btrop class insulation, to IP54. Motors
can also be supplied to F class
insulation.

9
Order numbers, technical information

Description L1Z-B L1T-B L3Z-A L3Z-A


Version E / D➁ Version E / D➁ Version E / D➂ Version E-C / D-C
Order numbers - Version E or EC with integral switchgear 211 163 03 211 193 03 211 363 01 711 365 01
Version E or EC without integral switchgear ➀ 211 163 04 211 193 04 211 363 02 711 365 02
Version D or DC with integral switchgear 211 164 03 211 194 03 211 364 01 711 366 01
Version D or DC without integral switchgear ➀ 211 164 04 211 194 04 211 364 02 711 366 02
Version ZME without integral switchgear ➀ – – – –
Version ZMD without integral switchgear ➀ – – – –
Version E Version E Version E Version E–C
Burner motor 1~ 110V, 60 Hz Type EC90/50–2 EC90/50–2 EC90/90–2 EC90/90–2
Motor horse power HP/ kW 0.67/ 0.5 0.67/ 0.5 2/ 1.5 2/ 1.5
Full Load Amps (FLA) A 8 8 18 18
Speed rpm 3400 3400 3450 3450
Capacitor µF 16 16 32 32
Version D Version D Version D Version D–C
Burner motor 3~ 460V, 60 Hz Type D90/50-2 D90/50-2 D90/50-2 D90/50-2
Motor horse power HP/ kW 1.13/ 0.85 1.13/ 0.85 1.13/ 0.85 1.13/ 0.85
Full Load Amps (FLA) at 460V A 2.3 2.3 2.3 2.3
Speed rpm 3400 3400 3400 3400
Burner flame safeguard Type LAL 2.25 LAL2.25 LAL2.25 LAL2.25
Servomotor Type –w– 1055/23 – W – 1055/80 –w– 1055/23 –w– 1055/23
Pump Type AE67 AE67 AE97 AE97
Fan galvanized galvanized galvanized galvanized
Ignition transformer V 2 x 5000 2 x 5000 2 x 5000 2 x 5000
Oil hoses DN 8 8 8 8
Length in inches and (mm) 39” (1000) 39” (1000) 39” (1000) 39” (1000)
Connection 3/8” 3/8” 3/8” 3/8”
Oil preheater Type – – – –
Heating capacity in BTUh and (kW) – – – –
Weight lbs/ kg (approx.) 64 (29) 64 (29) 88 (40) 88 (40)

➀ On burners without integral switchgear, the ➁ L1Z-B and L1T-B burners, versions E and D, can ➂ L3Z-A burners, versions E and D, can be used
burner flame safeguard is supplied loose. As an be used with this specification up to with this specification up to 8 GPH (30 kg/h).
option it can be mounted on the burner (see 8 GPH (30 kg/h). Over 8 GPH (30 kg/h) the Over 8 GPH (30 kg/h) L3Z-A burners versions
page 12). A terminal strip is provided in both additional prices for “Solenoid valve as addition- E-C or D-C should be used (see page 11).
cases. al shut off device” apply (see special equipment, These burners are fitted with an LAL 2.25
page 12). burner flame safeguard and an additional safety
solenoid valve as standard.

10
L3T-A RL3-A M1Z-B M3Z-A M3Z-A
Version E-C, D / D-C Version ZME / ZMD Version E / D Version D Version D-C
711 395 01 – – – –
711 395 02 – 212 163 04 – –
711 396 01 – – 712 364 03 712 366 03
711 396 02 – 212 164 04 712 364 04 712 366 04
– 711 373 02 – – –
– 711 374 02 – – –
Version E Version ZME Version E – –
EC90/90–2 EC90/90–2 EC90/50–2 – –
2/ 1.5 2/ 1.5 0.67/ 0.5 – –
18 18 8 – –
3450 3450 3400 – –
32 32 16 – –
Version D–C Version ZMD Version D Version D Version D–C
D90/50-2 D90/50-2 D90/50–2 D90/50–2 D90/50–2
1.13/ 0.85 1.13/ 0.85 1.13/ 0.85 1.13/ 0.85 1.13/ 0.85
2.3 2.3 2.3 2.3 2.3
3400 3400 3400 3400 3400
LAL2.25 LAL2.25 LAL2.25 LAL2.25 LAL2.25
-w- 1055/80 SQM 10... –w– 1055/23 –w– 1055/23 –w– 1055/23
AE 97 AJ6 E4 E4 E4
galvanized galvanized galvanized galvanized galvanized
2 x 5000 2 x 5000 2 x 5000 2 x 5000 2 x 5000
8 8 8 13 13
39” (1000) 39” (1000) 20” (500) and 31” (800) 27” (700) and 39” (1000) 27” (700) and 39” (1000)
3/8” 3/8” 1/2” 1/2” 1/2”
– – EV1B EV2B EV2B
– – 6,100 (1.8) 15,350 (4.5) 15,350 (4.5)
88 (40) 104 (47) 80 (36) 121 (55) 121 (55)

11
Special equipment

Item Description L1… L3…


No. M1… M3…
Order No. Order No.
1 Hours counter in integral switchgear 1 x L…Z + T 210 000 69 210 000 69
2 x L…Z 210 000 70 210 000 70
2 x M…Z 210 000 70 210 000 70
2 Heating for pump E M…Z 110 004 74 110 004 74
3 Pressure gauge with isolating valve L…Z + T 110 006 63 110 006 63
RL – 210 000 92
M…Z 110 008 82 110 008 82
4 Vacuum gauge with isolating valve L…Z + T 110 006 64 110 006 64
RL – 110 006 64
M…Z 110 005 70 110 005 70
5 Potentiometer fitted in servomotor (ZM) RL 220 Ohm – 110 002 86
RL 1000 Ohm – 110 003 03
6 Solenoid valve as additional shut off device ➀ M…Z 210 000 47 210 000 49
7 Solenoid valve for continuous run L…Z without E. 210 005 99 210 005 92
to relieve pressure L…Z with E. 210 007 15 210 005 92
L…T without E. 210 006 20 210 007 07
L…T with E – 210 007 07
RL – 210 000 52
M…Z 210 000 88 210 000 54
8 Magnetic clutch for continuous run L…Z without E. 210 003 25 210 001 75
to relieve pressure L…Z with E. 210 003 90 210 001 75
L…T without E. 210 004 92 210 005 19
L…T with E. – 210 005 19
RL without E. – 210 001 44
M…Z without E. 210 003 26 210 003 01
M…Z with E. 210 003 91 –
9 Combustion head extensions L1Z 4” (100 mm) 210 003 22 –
(for standard burner versions) 8” (200 mm) 210 003 23 –
L1T 4” (100 mm) 210 004 76 –
8” (200 mm) 210 004 77 –
M1Z 4” (100 mm) 210 003 30 –
8” (200 mm) 210 003 31 –
L3Z 4” (100 mm) – 210 000 19
8” (200 mm) – 210 000 21
L3T 4” (100 mm) – 210 004 79
8” (200 mm) – 210 004 80
RL3 4” (100 mm) – 210 000 23
8” (200 mm) – 210 000 25
M3Z 4” (100 mm) – 210 002 29
8” (200 mm) – 210 002 30
10 Oil meter fitted L1Z 210 005 30 –
L1T 210 004 86 –
L3Z – 210 004 30
L3T – 210 005 27
11 Oil hoses 51” (1300) in lieu of 39” (1000 mm) L…Z + T 210 003 00 210 003 00
39” (1000 mm), rubber, heated M…Z 210 002 02 210 002 04
51” (1300 mm), rubber, heated M…Z 210 002 03 210 002 05
12 Flame safeguard LAL 2.25 L…Z Vers. E 210 006 07 –
(in combination with LAL 2.25 L…Z Vers. D 210 002 62 –
integral switchgear) LAL 2.25 M…Z Vers. D 210 006 05 –
13 Flame safeguard LAL 2.25 L…Z Vers. E + D 210 002 54 210 002 54
(loose, for fitting into
control panel)
14 Air intake flange RL… Vers. ZME – 210 003 97
RL… Vers. ZMD – 210 003 35
15 Intake flange for connection of air duct. 210 000 67 210 000 67
16 Type of protection IP54/Industrial version L…Z 210 003 19 210 002 47
L…T 210 006 02 210 006 03
RL… – 210 004 17
M…Z 210 006 04 210 003 77
Price reductions
17 Oil preheater EV2A in lieu of EV2B M…Z Vers. D and E – 210 004 68
EV2A in lieu of EV2B M…Z Vers. D – 210 000 85
EV2A in lieu of EV2B M…Z Vers. D-C and E – 210 004 69

➀ The additional price applies only to burners with ➁ Additional price applies to burners
oil throughputs up to 8 GPH (30 kg/h). For burn- L3Z-A / M3Z-A.
ers > 8 GPH (30 kg/h) this solenoid valve is fit-
ted as standard.

12
Burner fuel systems

Monarch L1Z-B and L3Z-A burners Monarch L1T-B and L3T-A burners Monarch RL3-A sliding two stage and
modulating burner without shut off
device

1 4 4 12 1 4 4 12 1 5 6 13

110V 110V 110V 110V 55V 55V

110V 110V 55V 55V


P M

110V

4 4 5a 9 10 6a

Monarch M1Z-B and M3Z-A burners Monarch M1Z-B and M3Z-A burners
< 8 GPH (30 kg/h) > 8 GPH (30 kg/h)

1 3 14 1 5 3 14

55V
110V 110V
P

55V

110V 110V

7 8 5a 9 7 8

1 Pump without inbuilt solenoid valve 6 Normally closed solenoid valve 11 Nozzle head with one nozzle, without
2 Pump with two inbuilt solenoid valves (2nd shut off device in supply line 55 shut off device
3 Oil preheater V, electrically connected in series) 12 Nozzle head with two / three nozzles,
4 Normally closed solenoid valve 6a Normally closed solenoid valve without shut off device
4a Normally open solenoid valve (2nd shut off device in return line 13 Nozzle head R, without integral shut
5 Normally closed solenoid valve (1st 55 V, electrically connected in off device
shut off device in supply line 55 V, series - fitted against direction of 14 Nozzle head M, with integral shut off
electrically connected in series) flow) device
5a Normally closed solenoid valve (1st 7 Normally open solenoid valve
shut off device in return line 55 V, (stage 1)
electrically connected in series - 8 Normally closed solenoid valve
fitted against direction of flow) (stage 2)
9 Pressure switch in return
10 Oil regulator

13
Dimensions

Monarch L and M Monarch RL

Size Size 3
1 and 3

Monarch L and M, sizes 1 and 3


Size Dimensions in inches and (mm)
h1 h2 h4 h5 h6 d1 d2 d3 d4 d5 d6 ➁ b1 b2 b3 ➀
1 15.3 5.9 11.4 16.5 7.7 5.3 6.3–6.7 4.7 6.3/6.9➀ 5.0 20.7/20➀ 6.0 10.1/9.4➀
M8
(388) (150) (290) (420) (195) (135) (160–170) (120) (161/175) (128) (526/507) (153) (257/239)
3 17.1 6.7 12.8 18.1 8.7 6.5 7.3 5.1/5.9➁ 6.3/6.9➀ 5.5/6.3➁ 23.3/21➀ 6.0 12.3/10➀
M10
(435) (170) (325) (460) (220) (165) (186) (130/150) (161/175) (140/160) (592/533) (153) (312/253)

b4 b6 b7 l1 l2 l3 l4 ➁ l5 l6 l7 r1 r2
1 9.8 7.7 8.3 1.3 3.1 0.3 4.8 7.7 6.6 21.2 21.9➀ 23.6
(248) (195) (210) (32) (80) (8) (122) (195) (168) (538) (555) (600)
3 11.0 8.7 8.6 1.9 3.9 0.3 4.9/5.3➁ 7.8 7.4 25.4 26.2/25.6➀ 26.6
(280) (220) (218) (47) (100) (8) (124/134) (198) (188) (645) (665/650) (675)

Monarch RL, Size 3


Size Dimensions in inches and (mm)
h1 h2 h3 h4 h6 d1 d2 d3 d4 d5 d6 b1 b2 b3 ➀
3 17.1 6.7 5.9 12.8 8.7 6.5 7.3 5.1/5.9➁ 6.3/6.9➀ 5.5/6.3➁ 24.1/21.8➀ 6.0 12.3/10➀
M10
(435) (170) (150) (325) (220) (165) (186) (130/150) (161/175) (140/160) (612/553) (153) 312/253)

b4 b5 b6 b7 l1 l2 l3 l4 l5 l6 l7 l8 r1 r2
3 11.0 15.2 8.7 8.6 1.9 3.9 0.3 4.9/5.3➁ 7.8 7.4 25.4 8.7 26.2/25.6➀ 25.6
(280) (385) (220) (218) (47) (100) (8) (124/134) (198) (188) (645) (220) (665/650) (650)
➀ For version E/ version D ➁ For combustion head M2/1a, M5/2a

14
Weishaupt control panels
and burner control system

Weishaupt control panels for


• two stage burners
• three stage burners
• sliding two stage burners
and modulating burners

The basic control panels contain all


burner controls, necessary for the
operation of a burner.

Description
Weishaupt control panels conform to
applicable national/international
standards.

Switching includes
• Power supply
• Burner control
• Fan control
• Start-up/regulation
• Door mounted switches
• Door mounted indicating lamps

Individual customer requirements can be


met at any time.

Weishaupt control technology for


• Boiler units
• Thermal process equipment
• Marine versions
• Building management systems

Together with its core business of


burners and heating systems, Weishaupt
are able to offer complex control tech-
nology up to BMS level with SPS and
DDC systems.

From planning to handover, tailor made


solutions are available from one supplier.

15
Product and customer service -
Weishaupt Corporation
6280 Danville Road
Mississauga, ON L5T 2H7
Ph: (905) 564 0946, Fax: (905) 564 0949

the complete Weishaupt range www.weishaupt-corp.com

Print No. 83002716, July 2002


Printed in Germany. All rights reserved.

Regular maintenance reduces heating Weishaupt customer service is there for


costs and environmental pollution. Only you all year round. Whenever you need
a properly adfusted burner can save help, be it the supply of spare parts,
enegy end be environmentally friendly. technical advice or a site visit. We are
Behind each Weishaupt customer there when you need us.
service organisation. The outstanding
efforts made in maintenance and service
justify the enormous trust places in
Weishaupt’s burners, for at Weishaupt
product and customer service belong
together.