Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
This work was supported in part by CAPES Grant BEX1640-02-0 Type E Type F
(Ministry o Education of Brazil).
R.C. Leborgne is with Chalmers University, Göteborg, SE-412 96 Sweden
(e-mail: roberto.leborgne@chalmers.se).
J.M. Carvalho Filho is with Itajuba Federal University, 37500-903 Brazil,
(e-mail: jmaria@unifei.edu.br).
E.G.C. Novaes is with Grupo Rede, Sao Paulo, Brazil (e-mail:
eder.novaes@gruporede.com.br)
J.P.G. de Abreu is with the Itajuba Federal University, 37500-903 Brazil,
(e-mail: polica@unifei.edu.br).
2
The ABC classification can be seen as an intuitive way to propagation of the voltage sags [5]. One of the proposals is the
relate the fault with the generated sag. For example, a SLG use of a sag propagation index (SPI)
fault generates a voltage sag type B and a LL fault generates a N
voltage sag type C as shown in Table II. SPI = Bi (1)
In order to understand the vertical propagation of voltage %V N
Bt
sags it is necessary to analyze how the voltage sag type
where %V is a voltage threshold (50%, 70%, 90%), NBi is the
changes from the primary to the secondary side of a
number of buses experiencing voltage sag with magnitude less
transformer. When a voltage sag propagates through a
than %V, and NBt is the total number of monitored buses.
transformer, the relation of the phasors of the secondary side is
The SPI is similar to the well-known SARFI (System
not the same as the relation of the phasors of the primary side.
Average Rms variation Index)
For example, in a delta/wye transformer, a phasor at the
secondary side is the subtraction of two phasors of the primary N
SARFI = i
side. The consequences are that the zero sequence component (2)
X% N
is filtered and the positive and negative sequences are rotated T
by a multiple of +/-30 degrees respectively. where Ni is the number of customers experiencing sags with
Table II shows the voltage sag classification for different magnitude below X% and NT the total number of customers.
fault types and how the sag type changes when propagates However, the SARFIX represents the average number of
through a Dy transformer. For example, when a SLF fault specified voltage sags that occurred over the assessment period
occurs at bus I the sag seen at this bus is type B. However, per customer as it was proposed in [8], where the specified
after a Dy transformer, at bus II the sag seen is type C. After disturbances are those with a magnitude less than X%.
another Dy transformer, the sag seen at bus III is type D. It is A new interpretation of the SARFIX consists in the number
interesting to remark that the sag type alternates from C to D of voltage sags with magnitude less than X% in a given
type and from D to C type each time that the sag propagates location during a period of time (normally one year) [4]. This
trough a Dy transformer. A detailed analysis of the change in interpretation of SARFI gives it a quite different meaning
voltage sag type due to other transformer winding connections compared with the propagation index SPI.
can be found in the references [6][7].
III. MONITORED SYSTEM
TABLE II The system used in the case study is shown in Figure 1. The
THE CHANGE ON VOLTAGE SAG CLASSIFICATION THROUGH DELTA-WYE
TRANSFORMERS network contains 67 transmission lines (138 and 230 kV) with
a total length of 6619 km. There are 93 substations with a
Location / Voltage sag type
transformer-installed capacity of 2076 MVA. The generation
Fault
Bus I Bus II Bus III capacity is larger than the present demand. The excess of
type
generated power is exported to another regional grid through
LLL A A A the RND substation.
UHE
210MW SNP
SLG B C D 138kV
P3
RND SIN Y Y
230kV COX NOB 230kV ∆
P2
LL C D C P1
188 Km
P6 ∆ Y ∆ Y
247 Km
IVM
254 Km
P11
horizontal and vertical propagation have to be addressed. 77 Km
P12
The analysis of the horizontal propagation is more complex Y ∆ UTE
150 MW
and requires computer simulation. It can be assumed that the UTE
230,0 kV
138,0 kV
voltage sag type is not changing. However, its magnitude and 480 MW 34,5 kV
13,8 kV
duration may be affected by the proximity of generation plants Figure 1. Diagram of the monitored power system.
and large induction machines that behave as generators at the
beginning of the sag. The topology of the network and the A total of 12 buses located at 5 substations were selected
impedance of the line also play an important role on the for voltage sag monitoring. The measured buses (P1…P12) are
voltage sag dumping as shown in section IV. indicated in Figure 1. The criteria for the bus choice included:
Few attempts have been done in order to quantify the network topology, load concentration, sensitive-loads location,
3
Frequency (%)
located at the utility control and operation room. The 30%
communication between the substations PQ-monitors and the 24%
20%
centralized server is established using the mobile telephone 13%
network. This communication was adopted because some of 10% 7%
4%
the substations were not remote-controlled or there were not 2%
0%
free communication channels available in the existing 20 - 100 101 - 200 201 - 300 301 - 500 501 - 1000 1001 - 3000
communication network. A second server located at the Sag duration (ms)
university was updated daily from the utility server. The
Figure 3. Histogram of voltage sag durations.
communication was established using standard internet
connection.
The measurements included: rms voltage, voltage phasors, B. SPI (Sag Propagation Index)
and sag duration at each phase. The time resolution of the rms In order to characterize the severity of the events
values and phasors were 8.33 ms (half cycle). The selected sag considering the propagation of the voltage sags the SPI was
threshold was 0.85 per unit in order to neglect the most estimated. The SPI was calculated considering the number of
shallows sags and not to overload the communication system. PQ-monitors that triggered, normalized by the total number of
installed PQ-monitors. The index for the 30 faults is shown in
IV. RESULTS Figure 4.
1.00
A. Voltage sag indices 0.90
After six months of measurements, 30 events were selected 0.80
for the propagation analysis. The 30 fault-events generated a 0.70
total of 89 voltage sags on the 12 monitored buses. The 0.60
SPI-85%
pu. However, 48% of the sags have a magnitude below 0.70 0.20
0.10
per unit. These sags may cause malfunction on many sensitive
0.00
electronic loads, such as ASDs and PLCs, as related in
previous studies [1].
1
11
13
15
17
19
21
23
25
27
29
Event
60%
of the faults were considerable more severe. For example, one
50% 48%
40%
of the events triggered 11 PQ-monitors (SPI=0.91).
30% 27% 25%
C. Fault location
20% 13%
11%
10% 3% 7%
9% The analysis of the SPI permits the localization of the fault
0% positions that cause more damage to the system from the
<0.1 0.1-0.2 0.2-0.3 0.3-0.4 0.4-0.5 0.5-0.6 0.6-0.7 0.7-0.8 0.8-0.85 voltage sag point of view. For instance, it could be interesting
Sag magnitude (pu)
to investigate the events 10, 14, 24, and 30 that produced
Figure 2. Distribution of voltage sag magnitudes. voltage sags in at least half of the monitored buses, as shown
in Table III.
The histogram of the voltage sag durations is shown in The four events with the largest SPI (E10, E14, E24, and
Figure 3. Approximate 50% of the sags have a duration of less E30) are located in Figure 5. It is observed that faults located
than 100 ms. These sag durations agree with the protection near generation units produced voltage sags at a large number
setting used by the utility, where the fault-clearing time for the of buses. Here, three of the four highlighted events are located
first zone is about 100 ms. in lines that are connected to the bus COX, one of the main
generation buses.
4
TABLE III approximate half of the SPI obtained for LLL faults.
CHARACTERISTICS OF THE EVENTS WITH LARGE SPI
It is interesting to see that there is a compensation between
Event # PQ-Monitors triggered Fault Characteristics the SPI value and the number of faults. For example, the
LL at radial line from number of SLG faults is about double the number of LLL
E10 P4/P5/P6/P7/P8/P9/P10 faults, whereas the SPI is about half. Therefore, for the
COX 138V
monitored period the number of monitored buses affected by
E14 P6/P7/P8/P9/P10/P11 LLG RND-COX 138 kV
sags caused by SLG faults and LLL faults were similar.
E24 P1/P2/P3/P4/P5/P6/P7/P8/P9/P10 LLL NOB-SIN 230 kV E. State of generation
E30 P1/P6/P7/P9/P10/P11 LL RND-COX 138 kV The generation unit dispatch also influences the sag
propagation. In the monitoring period the thermal-generation
was off during the occurrence of five events: E20, E22, E23,
UHE
210MW SNP
138kV
E24, and E25. When the average SPI is estimated considering
P3
RND
230kV COX
E10 NOB
SIN
230kV
Y
∆
Y
the generation dispatch a considerable difference is found, as
P2
E14
P1
shown in Table V.
188 Km
P6 ∆ Y ∆ Y TABLE V
188 Km 104 Km E24 346 Km AVERAGE SPI CALCULATED FOR EACH GENERATION STATE
P9 RND COX Generation state Average SPI
NOB ITA
138kV
Y Y
Y Y
140 Km 215 Km Thermal-generation ON 0.23
Y Y
Y Y Thermal-generation OFF 0.35
P5 ∆ UHE
∆ P4 84 MW
P7
E10
∆ P10
It is interesting to analyze more in detail the event E24
Y
Y ∆ IVM
P11 P8 247 Km 254 Km because it has caused sags at almost all monitored buses. The
77 Km
E14 E30
P12 fault was located on the 230 kV system that supplies the 138
Y ∆
UTE
150 MW 230,0 kV kV network when the thermal-generation is not dispatched.
Therefore, a fault in the 230 kV system during these
UTE 138,0 kV
480 MW 34,5 kV
13,8 kV
generation conditions was expected to cause voltage sags in
Figure 5. Location of the events with large SPI. The influence region for the
events E10 and E14 is represented by the circles. most of the 138 kV buses, as confirmed by the event E24.
F. Vertical and horizontal propagation
Figure 5 shows the region of influence for the events E10
Considering the meshed characteristic of the system, the
and E14. This is a very illustrative way to visualize the
horizontal propagation of sags is expected to be more relevant
propagation of the sags. We can clearly see that the region of
than the vertical one. Table VI shows the average SPI
influence of the event E10 is larger than the region of
considering the voltage level where the faults happen and the
influence of the event E14. The regions of influence that are
voltage level of the measured buses. The results agree with the
shown in Figure 5 are due to a sag threshold of 0.85 per unit.
predictions. The horizontal propagation of the faults at 230 kV
A lower sag threshold would define smaller regions of
reached a SPI of 0.5 whereas the vertical propagation to the
influence.
138 kV and 13.8 kV levels reached a SPI of 0.167. The
D. Fault type dumping for the vertical propagation can be explained by the
It is also relevant to investigate the variation of the SPI for combined effects of the transformers winding connection, the
the different types of faults that happened during the rotational loads, and the distributed generation.
monitoring period. Hence, the SPI is averaged for each type of
fault. Table IV shows the number of faults and the average SPI TABLE VI
SPI CALCULATED FOR VERTICAL AND HORIZONTAL PROPAGATION
for each type of fault.
Average SPI at
TABLE VII
VOLTAGE SAG CHARACTERISTICS FOR THE EVENT E14 TABLE VIII
VOLTAGE PHASORS RECORDED FOR THE EVENT E14 (VOLTAGES IN PU)
PQ-monitor Magnitude (pu) Duration (ms)
P6 – 230 kV – COX P9 – 230 kV – RND
P6 – 230 kV - COX 0.85 72 VA=0.86 VB=0.99 VC=0.85 VA=0.82 VB=1.0 VC=0.83
P7 – 138 kV – COX 0.81 82
P8 – 13.8 kV – COX 0.80 83
P9 – 230 kV – RND 0.82 65
P10 – 138 kV - RND 0.74 79
P11 – 13.8 kV - RND 0.72 86