Sei sulla pagina 1di 24

Clean Compressed Air

The Norgren guide to effective


air preparation
The air leaving a
compressor is hot, dirty, wet
and generally at a higher
pressure than the
downstream equipment
requires. A typical
50 dm3/sec (100 scfm)
compressor will push 4 500
litres of water and 8 litres of
degraded compressor oil
into the system in a year
along with considerable
amounts of dirt particles.
Before this air can be used it
needs to be treated to
remove the contaminants,
have its pressure reduced to
the right level, and in many
cases have oil added to
lubricate downstream
equipment.

Figure 1.
Compressed air installation, showing examples
of air preparation applications. See details on
pages 4 and 5.

2
APPLICATIONS
4~5

REMOVING CONTAMINANTS
6 ~ 10

PRESSURE CONTROL
11 ~ 13

LUBRICATION
14 ~ 15

PROTECTING SYSTEMS,
PERSONNEL AND THE
ENVIRONMENT
16 ~ 17

SAFE SYSTEMS
18

NORGREN AIR PREPARATION


PRODUCT OVERVIEW
19 ~ 21

GLOSSARY
22

REFERENCE TABLES
23

3
Compressed air is often APPLICATIONS General Pneumatic Circuits:
wrongly assumed to be a eg: directional control valves and cylinders, in
cheap or even ‘free’ source The following section shows several typical multi-valve circuits, machine cleaning, air
systems of a generic type and the equipment motors and high speed tools.
of power. In fact it can be
normally used for the application. Remember
10 times as expensive as every system should be treated on its merits A Micro-Fog lubricator is required for
electricity by the time all and broken down into several elements to the several varying flow paths to ensure full
ensure optimum installation, running and lubrication. (Figure 2)
generation, transmission,
maintenance costs are achieved.
treatment and system costs The applications below are typically
are taken into account. branches taken off a large works distribution Figure 2.
Good air preparation must mains and isolating valves are usually placed
in front of all branches to permit isolation
therefore consider the
from the mains to allow for maintenance to
energy consumption of the take place without recourse to complete plant
system and air treatment shut-down.
equipment. For expert advice on the right
equipment for your application contact your
The process of air local Norgren Technical Sales Centre,
Tel: 0345 662266.
preparation has been at the
Shut-off valve, filter/reg, Micro-Fog lubricator,
core of Norgren’s business soft start/dump, relief valve.
for over 70 years. The aim
of this booklet is to offer
guidance on the correct,
economic and safe Multiple Simple Applications:
treatment of compressed air eg: OEM machines.

in industrial applications.
Here we can only provide a It is often a case that with fairly simple
brief summary of the machines, lubricated air is require for valving
and pneumatic circuitry and oil-free air for air
extensive experience
bearings. To keep costs low two separate lines
Norgren has as a world are unnecessary and a typical arrangement from
leader in FRL technology. one air supply only can be arranged as shown.
Other elements such as pressure
For more detailed switches and check valves may be made
available within modular systems. (Figure 3).
advice contact your local
Norgren Technical Sales
Centre, Figure 3.

Tel: 0345 662266.

Shut-off valve, filter/regulator, oil removal


filter, porting block, Micro-Fog lubricator.

4
Breathing Air: Heavy Duty Lubrication: Direct Injection Lubrication:
eg: face masks and hoods, air agitation. eg: large slow moving cylinders. eg: conveyor chains.

The typical application assumes that In such applications large amounts of The application does not allow for
air intakes are of a reasonable quality with no lubricant are required for effective lubrication. ‘fog’ type lubrication because of the
C0 or C02 contamination. It may in some Again a soft start/dump valve is shown but is surrounding environment and absence of a
instances be a consideration to remove water dependent upon the application. (Figure 6). lubrication chamber. (Figure 8).
vapour. (Figure 4)

Figure 4. Figure 6. Figure 8.

Shut-off valve, general purpose filter, Ultraire Shut-off valve, filter/reg, Oil-Fog lubricator, Shut-off valve, filter/reg + direct injection
filter, regulator. soft start/dump valve, relief valve. lubricator.

Oil-Free Applications: Critical Pressure Control (Instrumentation): Continuous Processes:


eg: paint spraying, foodstuffs, film processing, eg: precision regulation, fluidic systems, air eg: paper mills, chemical plants.
powders. gauging, process control.

These applications need to be free A typical arrangement is shown, where Another facet of Norgren’s Olympian Plus is the
from any water deposits in the downstream oil aerosols which can prevent fast response of ability to make duplex systems. This is invalu-
system. For many installations this will require downstream devices, need to be removed. able for systems which cannot be shut-down,
air drying. The drying medium (for desiccant or Dependant upon air quality drying may not be such as continuous process plant. Two identical
deliquescent dryers) will need protecting from required. (Figure 7) air sets are joined together and one may be
oil to allow it to work efficiently and the isolated (and serviced) whilst the other set is in
downstream system will also need protection operation. (Figure 9).
from accidental migration of the material into it.
A typical arrangement would be as figure 5 and
in some instances it might be worth consid-
ering an oil vapour removal filter too.

Figure 5. Figure 7. Figure 9.

Shut-off valve, general purpose filter, oil Shut-off valve, general purpose filter, oil Duplex system: shut-off valve, filter/reg,
removal filter, drier, oil removal filter, regulator, removal filter, drier, oil removal filter, precision lubricator, porting block, oil removal filter and
relief valve. regulator. shut-off valve x 2 with manifold block
connectors.

5
REMOVING CONTAMINANTS take-off lines. See figure 1 for a typical good WATER VAPOUR
distribution main arrangement.
The air produced by a compressor is hot, wet As stated earlier most efficient water A properly designed air line filter of the
and dirty. The first step in good air prepara- removal will take place at high pressure, so correct size, in the correct location will
tion is to filter out these contaminants. This anything which will produce a pressure drop effectively and efficiently remove liquid water,
section considers the removal of liquid water, within the distribution system should be but will not reduce the water vapour content
water vapour, solid particles and finally oil. avoided. This will also be a loss of energy to of the air. Further air cooling may result in
the system and increase the the cost of more water condensing out. If complete
LIQUID WATER compressed air generation. Areas to avoid freedom from water contamination is essen-
here are complex flow paths with undue tial then the water vapour content of the air
In compressed air systems water vapour bends and inadequately sized piping. See must be lowered such that the ‘Dew Point’ of
exists as a contaminant originating at the page 23 Reference Data for friction losses in the air is lower than any temperature that the
compressor outlet in vapour form, but as the pipe and for recommended pipe flows. air can be exposed to in the system.
air cools, it will exist as both liquid and The action of water removal can be Once all liquid water is removed
vapour. achieved by drip leg drains, automatic drain from compressed air, then normally the air
The amount of water vapour that can valves and as discussed later, filters. These will be completely saturated with water
exist in any given volume of compressed air devices should be located in positions where vapour. The particular temperature and
is directly proportional to the air temperature liquid water is present in amounts large pressure at which the compressed air exists
and inversely proportional to the pressure. enough to be removed. (See figure 11). at that moment is known as the ‘Pressure
Most liquid water will be present Because of the possibility of cooling occur- Dew Point’.
when the temperature is lowest and the ring during the passage of the air through
pressure is highest and removal at this point distribution mains and branch lines it is
will achieve the highest efficiency. preferable to install smaller individual filters Figure 10.
In order to achieve this an essential as near to the actual point of air usage as TYPICAL COMPRESSOR INSTALLATION
element of any system following the possible, rather than rely on one large filter
compressor is an efficient after cooler of adjacent to the air receiver. A point to
sufficient capacity to reduce the temperature remember is that since most water will be
of the outgoing air to within 8°C of the present at higher pressures, always locate
temperature of the water entering the after filters upstream of any pressure reducing
cooler. valves.
The outgoing air should then be Filters which have the ability to
piped to a receiver of adequate capacity remove water are designed for efficient water
located in the coolest location available, removal and low pressure drop in accor-
definitely not within the compressor house dance with the recommended pipe flows (see
itself. This will permit further cooling of the page 23) and Norgren filters will have high
air to occur and therefore more condensa- efficiencies up to 200% of this recommended
tion. figure.
Generally the capacity of the receiver
is about 30 times greater than the rated free
air delivery of the compressor when oper- Figure 11.
ating in the 7 bar g region, typical of most DRIP LEG DRAIN
industrial air supplies. See figure 10 for a
typical compressor installation.
Further cooling may occur in the
distribution mains themselves. These should
be laid out with a pitch in the direction of air
flow so that gravity and air flow will carry
water to drain legs located at appropriate
sites. Down loops in distribution mains
should be avoided, if not locate a drain leg at
the down loop. With the exception of drain
legs all air take-off points from the distribu-
tion mains should be taken from the top of
the main to prevent water from entering the

6
Dew Points are normally measured Figure 12. PARTICLE SIZES
at atmospheric pressure and can be related Particle Diameter, Microns
to Pressure Dew Points through appropriate 0,01 0,1 1,0 10,0 100
charts. Aerosols ll l l lll l l l l l l
In order to remove water vapour Spray
from a compressed air system Air Dryers Tobacco Smoke
must be employed. The efficiency of these Human Hair
devices is much increased by ensuring that Viruses
they are not contaminated by liquid water or Bacteria
oil (or combinations - emulsions) and are Silt
supplied with air at the lowest possible Fine Sand
temperature. So they are additions to the Carbon Black
system and not alternatives to filters and after Coal Dust
coolers. Pollens
There are 3 principle types of Air Dryer;
Refrigerant,
Regenerative Adsorbent Desiccant SOLID PARTICLES Figure 13. GENERAL PURPOSE FILTER
and Deliquescent Absorbent Dryers
(The general comparative abilities Like water, solid particles exist in any
and comparative costs are tabled in the compressed air system regardless of the type
Reference Data on page 23) of compressor. These can arise from four
In order to keep the costs of air principle sources:-
drying to a minimum consider the a) Atmospheric dirt inhaled at the
following:- compressor inlet port.
a) Does the particular process require b) Corrosion products due to the action
air drying or will efficient after of water and weak acids, formed by
coolers, receivers and filters suffice? the interaction of water and gases
b) Do not specify extremely low Dew such as sulphur dioxide inhaled by
Points if the process does not the compressor.
warrant them. c) Carbon products formed by the

;;
c) Limit the volume of air being dried action of the heat of compression on

;;
to that actually needed for the the lubricating oil or the normal
particular process with an adequate wear of the carbon piston rings used

;;
margin for future expansion. This in some types of oil free compres-
may indicate only one area of a sors.
process plant need employ a dryer. d) Particles originating from the
d) The major requirement for air dryers mechanical fixing of the metal pipe
in general industrial applications is work and components into the air
where high ambient temperatures distribution system.
exist. The size of dirt particles covers a
very wide range from several hundred to
below one micron (see figure 12) and the Fine filtration in the region 10 –
level of filtration depends upon the degree of 25 µm is normally required for high speed
cleanliness needed for the particular process pneumatic tools or process control instru-
involved. Generally it is inadvisable to mentation. Filtration of 10 µm and below is
provide finer filtration than is absolutely essential for air bearings and miniature
necessary because the finer the filtration, the pneumatic motors. Norgren general purpose
greater the quantity of dirt trapped by the filters are available with different grades of
filter element and the more rapidly it will element to offer these various filtration levels.
become blocked. Some applications may need filtration better
Particles can be broken broadly into than this and indeed for paint spraying,
two groups, coarse (40 microns and above) or breathing air and food related applications
fine. Most normal air line filters will satisfac- particle removal below 1 µm is also essen-
torily remove particles down to 40 microns. tial. Standard air line filters cannot be used

7
and high efficiency filters (oil OIL Figure 14.
removal/coalescing filters) must be ‘PURAIRE’ COALESCING FILTER
employed. Standard air line filters should The principle source of oil contamination
still be employed as pre-filters to these high within a compressed air system is from the
efficiency filters. High efficiency filters will compressor. An oil lubricated compressor of
remove these extremely fine particles and if 50 dm3/s capacity may introduce as much as
exposed also to the coarser particles they 0,16 litres of oil per week into the system.
will simply clog and become congested with Oil is used for lubrication of the
dirt extremely quickly. compressor but when it emerges with the
All elements will become blocked in compressed air prior to distribution the oil is
use. The level to which the blocking is now in a totally unusable state. Having been
acceptable is dependent upon the application subjected to high temperatures during air
and the energy consciousness of the plant compression it becomes oxidized and acidic
operation. Standard filters can be cleaned and can be considered as an aggressive

;;
and reused but in today’s environment with contaminant rather than a lubricant and so
labour costs high and spare parts inexpen- must be removed.

;;
sive it is normally better to replace elements. Normal air line filters will remove

;;
This will also ensure minimum pressure drop sufficient liquid oil (along with water) to
on reinstallation as cleaning at very best will leave the air in a suitable condition to supply
only remove 70% of accumulated particles. most pneumatic tools and cylinders, but
High efficiency filter elements cannot be certain processes demand completely oil-free
cleaned and must be replaced before they air.
become blocked with dirt. One solution is to use oil-free
Under normal usage conditions compressors. These will still produce air
general purpose filter elements are usually contaminated with dirt and water and it is
changed before their pressure drop is greater often more economical to use lubricated
than 0,5 bar, or in routine annual mainte- compressors in conjunction with after
nance. The period can always be adjusted by coolers and standard air line filters, only
monitoring for critical applications using a fitting high efficiency oil removal filters at the Figure 15.
service indicator (figure 15). points in the system which demand oil-free FILTER SERVICE INDICATOR
High efficiency filters should have air. This ensures that the amount of air
their elements replaced when a pressure needing special treatment is kept to a
drop of 0,7 bar is achieved. Again a low cost minimum by allowing a smaller specialised
service indicator is often employed. This filter in the affected area and not a large
device has a scale of two colours, usually specialised filter for the whole plant.
green/red. The elements should be changed Oil in a compressed air system can
when or before all red is achieved. Electrical exist in three forms, oil/water emulsions,
service indicators are also available from aerosols (small particles suspended in the
Norgren, to provide remote signalling. air) and oil vapours.
Maintenance schedules can be produced to Emulsions can be removed by
ensure this ‘last chance’ situation is not standard air line filters but the aerosols are
achieved, indeed some applications cannot our next concern.
tolerate even this much pressure drop,
especially if this is at the generation point of
a large compressed air distribution main as
the cost of extra energy alone would be very
large.

8
OIL AEROSOLS OIL VAPOUR Figure 16.
OIL REMOVAL FILTER WITH GENERAL
These particulate oil droplets exist in the For most processes the removal of oil vapour PURPOSE PRE-FILTER
airstream and the most troublesome are in is unnecessary since unlike water vapour, oil
the size range 0,01 to 1 micron (approx vapour exists only in minute quantities and
90%), the rest may be slightly larger (see is not objectionable except in circumstances
figure 12 particle size chart). where its odour is unacceptable eg. in food
Most standard air line filters achieve processing, pharmaceutical and beverage
water removal by centrifugal action but due industries and breathing air applications.
to their small particle size these aerosols are The most common method of
unaffected and require special coalescing removal is to pass the air through an
filters. adsorbing bed, usually of activated carbon,
In addition to removing the oil although other materials can be used.
droplets these filters will also remove minute Such vapour removal filters will
water droplets, but they must be protected normally reduce the total remaining oil
against gross dirt or water contamination by content when used in conjunction with a pre-
means of standard air line filters mounted filter (general purpose filter) and a coalescing
immediately upstream (figure 16). It is filter to 0,003mg/m3.
normally advisable that these filters are A common misconception of these
capable of removing particles down to 5 filters is that they will remove carbon
microns or less otherwise the coalescing monoxide or carbon dioxide - they will not.
filter may quickly become choked and As with oil removal (coalescing)
blocked with dirt, requiring a filter element filters the vapour removal filters should only
replacement. be employed where their function is needed,
Coalescing filters are normally rated the maximum flow rating is not exceeded and
by the amount of air which they can ‘process’ they are preceded by a general purpose and a
to achieve a given oil removal performance, coalescing filter. This will minimise the size
normally a maximum remaining oil content of the filters required and therefore the cost
in the exit air of 0,01 mg/m3 (or 0,01 ppm). of the installation. Figure 17.
To try to overflow these units will not only Norgren offers an integrated ‘ULTRAIRE’ OIL VAPOUR REMOVAL FILTER
result in a greater pressure drop across the coalescing and vapour removal filter in the
unit and therefore extra energy cost but more Olympian Plus range. (See figure 17). This
importantly the remaining oil content will includes a colour change service indicator as
increase. This may be acceptable for some standard.
applications where oil removal down to the The location of the compressor
order of 0,5 mg/m3 is quite adequate to give intake may also have an effect on the level of
a degree of protection to a system particu- filtration required, if for example the intake is
larly prone to gross oil contamination. situated by a source of hydrocarbon vapours
Figure 19 shows Norgren coalescing etc. Clean air intake will reduce the cost of
filters flow capacities to achieve their given producing clean compressed air.
performance.

9
Figure 18. Figure 21.
FILTER SELECTION
GENERAL PURPOSE FILTER FLOWS RECOMMENDED FILTRATION LEVELS.
Once all of the contaminants have been Pipe Unit Flow (dm3/s)* Typical Quality Classes
Application
Size
considered the degree of cleanliness of air Oil Dirt
for each part of an industrial plant or process 1/8" F07 15
Air agitation 1 3
can be determined. By only employing the 1/4" F72G 30
Air bearings 2 2
correct filters in the right location energy and 1/2" F64G 70
Air gauging 2 2
maintenance costs can be kept to a F74G 83
minimum. The volume of air involved in each Air motors 4 4
1" F15 175
stage must always be considered as under- Brick and glass machines 5 4
sized, inappropriate filters are a prime cause *Flow at 6,3 bar and 0,5 bar pressure drop. Cleaning of machine parts 3 4
of high Construction 4 5
energy costs.
Conveying, granular products 2 4
A very general guide to the typical
levels of cleanliness required for common Conveying, powder products 1 3
processes is given in figure 21. Each appli- Figure 19. HIGH EFFICIENCY FILTER Fluidics, power circuits 2 5
cation should however be considered on its FLOWS Fluidics, sensors 2 3
own merits. Pipe Unit Flow (dm3/s)* Oil Foundry machines 4 5
Recommendations on air drying are Size Removal
Class** Food and beverages 1 1
particularly difficult since this is dependant
1/8" F39 2,8 2 Hand operated air tools 5 5
upon the temperature of the compressed air
main adjacent to the application/machine the 1/4" F72C 4,5 2 Machine tools 5 4
level of pressure reduction and air flow rate. 3/8" F64C 16 2 Mining 5 5
For well laid out generation and Micro-electronics manufacture 1 1
F64B 7 1
distribution systems drying is seldom Packaging and textile machines 5 3
required in countries of typically low to F74C 16 2
1/2" F64H 28 2 Photographic film processing 1 2
moderate relative humidities and ambient
temperatures. F64L 11 1 Pneumatic cylinders 3 5
When choosing a filter to clean F74H 28 2 Pneumatic tools 5 4
compressed air ensure:- Pneumatic tools (high speed) 4 3
1" F53 60 2
● The correct type of filter and element Process control instruments 2 3
F52 60 1
rating is selected for particle
1 1/2" F47 85 2 Paint spraying 1 1
removal.
Sand Blasting 4 5
● The liquid removal efficiency is high F47 120 3
and that re-entrainment is not 2" F47 200 2 Welding macines 5 5
possible. F47 286 3 General Workshop air 5 4
● Ease of maintenance and liquid l
0
l
10
l
100
l
1 000
condensate collection is possible.
*Flow with 6,3 bar inlet to achieve ‘class’
● Easy visibility of condensate and/or
requirements.
element ensures that function is
**See figure 20.
achieved or shows if maintenance is
required.
This may be a pressure drop device,
Figure 20.
liquid level indicator or transparent bowl.
In order to aid determining the type AIR QUALITY CLASSIFICATIONS ISO 8573
of water and particle removal, figure 20 Quality Class Dirt Water Pressure Dew-point Oil
shows ISO 8573 Air Quality Classification. Particle Size in Microns °C (ppm vol.) at 7 bar g (including vapour) mg/m3
1 0,1 -70 (0,3) 0,01
2 1 –40 (16) 0,1
3 5 –20 (128) 1
4 15 +3 (940) 5
5 40 +7 (1 240) 25
6 — +10 (1 500) —

10
PRESSURE CONTROL principle requirements could employ a TYPES OF REGULATOR
standard and therefore low cost reducing
In order to use compressed air most effec- valve. The correct selection and deployment Although Norgren produces a vast array of
tively and efficiently it is necessary to reduce in the relevant part of the air system will regulators they can be broadly broken into 4
the pressure to precisely the level required achieve the lowest cost most energy efficient types:-
for its application. system. General Purpose
All pneumatic equipment has an The penalty for poor regulation Pilot Operated
optimum operating pressure. Using it at a characteristics is that the outlet pressure will Precision
higher pressure causes excessive wear, with vary but in the bulk of compressed air Special Purpose
no significant increase in output, whilst applications, inlet pressures are fairly Most general purpose regulators are
wasting the compressed air itself and the constant so this poses few problems. of the diaphragm type (figure 22). In general
cost expended in generating it. If the The penalty for poor flow character- these are more sensitive than piston type
compressed air is stored at this higher istics is pressure drop which directly reflects regulators which tend to have better flow
pressure and only used at exactly the lower in energy costs. Every regulator suffers from capacity for a given size. In the majority of
level required for the application the storage some amount of pressure drop so for good compressed air systems response, rather
vessel or receiver need only be topped up system design this is the more important than compactness for a given pipe size is the
from some intermediate figure to the full property to examine. major requirement, hence diaphragm type
capacity, which is more efficient. In order to An important cost saving can be regulators are most common.
achieve this optimum usage the compressor achieved by employing a reducing valve in Regulators can be relieving or non-
usually operates between two pressure conjunction with double acting cylinders relieving. The relieving feature allows for the
levels, that is the receiver normally has a where a reduced pressure can often be used system (outlet) pressure to adjust from a
pressure switch set to give compressor cut- advantageously on the non-working return higher level to a lower one without actuating
off at the required storage pressure (usually stroke and cost savings as high as 30% can downstream equipment (this is done by
the highest achievable for filtration efficiency) be achieved. This can be very important on having a vent hole through the diaphragm to
and a lower level usually about 10 - 20% multi-cylinder installations. atmosphere). Generally this relief hole is very
lower. This figure can be adjusted for the A point common to all pressure small in relation to the regulator main ports
optimum when the receiver size, system flow regulators is that in order to work constantly so no more than a bleed flow can be
demand and compressor output rating are and repeatability within their design limits achieved and this should not be considered a
considered. The outcome of this arrangement they will require a supply pressure at least 1 full relief or even safety relief device.
is that the compressor is not continually bar higher than the required outlet pressure. Non-relieving versions do not have
running, using up excess energy, producing They will work with a lower differential but a connection from the downstream system to
more heat which produces more water, which performance can be impaired. atmosphere and so can only be adjusted
must be removed (extra cost) to supply a from a higher desired or achieved outlet
system requirement at too high a pressure pressure to a lower one by cycling down-
which causes excessive wear (extra cost) for stream equipment or using a 3/2 shut-off
no increase in output. valve to expel excess air from the down-
A pressure reducing valve can stream system.
therefore generate cost savings greater than
its purchase price in a short time period. Figure 22. GENERAL PURPOSE REGULATOR
Also it is mandatory in such applications as
blow guns and cooling nozzles where the use
of compressed air at high pressure is
potentially hazardous.
Pressure reducing valves or regula-
tors have two principle characteristics which
must be considered in establishing which to
select, their ability to keep the outlet pressure
constant irrespective of the inlet pressure
(called the regulation characteristic) and
irrespective of the outlet flow (flow character-
istic). Standard designs are manufactured
which achieve certain levels of the ideal
performance on each characteristic. A simple
application with loose demands of the two

11
Pilot operated regulators are those regulator which compares it to the desired Figure 24.
which do not have a direct mechanical outlet signal and ‘compensates’ by increasing NORGREN MICRO-TROL PRECISION
means of adjusting the outlet pressure. This the outlet pressure if the feedback signal is REGULATOR
eliminates leverage problems in achieving too low, or decreases if the signal is too
high (16 bar plus) pressures in large pipe high. This type of control is usually
size units. The outlet pressure is controlled employed where a large steady air flow to a
by means of an air pressure signal (Figure continuous process is required.
23) which is normally produced by a preci- Precision regulators (or controllers)
sion regulator. This allows for example a are normally used for instrumentation
pilot operated regulator to be remotely applications where exact repeatability and
situated in the large distribution mains freedom from outlet pressure setting drift
normally in a building’s roof, but be adjusted over short or long term operation is neces-
to give the desired output pressure from sary. These regulators normally have a small
shop floor level. For the majority of pilot outlet flow range, but exhibit superior flow
operated applications it is best to take the and regulation characteristics. Their ability to
system or outlet pressure reading from the achieve the ideal of these characteristics over
pilot operated (often called a slave or main) flow and pressure ranges is reflected in their overall performance meets the requirements
regulator itself or the distribution system as size and price. of the particular application.
the pilot regulator’s outlet pressure is Generally most precision regulators Another feature of precision regula-
generally not the same. employ a special arrangement to allow a tors is their relief capacity and some have the
Pilot operated regulators also give constant bleed of air to escape to atmos- ability to relieve up to 80/90% of their
better performance by eliminating the control phere. Although this is a cost to system as a recommended regulated flow for specialist
spring and usually have a large diaphragm whole, being a loss of air, it is the price application such as tensioning belts, paper
area compared to valve area which also which must be paid in order to achieve the rolling and balancing. (Figure 24).
improves the accuracy of pressure control in very fast response to the applications Special purpose regulators can
response to small pressure changes. demands needed to keep the system cover a whole range of specific demands
Another level of control accuracy pressure as constant as possible. The best including meeting exact environmental
can be achieved by employing a feedback types of precision regulators also employ an requirements with special materials, having
pilot regulator. This device senses the outlet integral pilot operation, producing effectively high relief flows, plunger operation in place
pressure in the system and a piped connec- two diaphragms and valves, one small and of handwheels etc. They can be derivatives of
tion feeds this signal back to the pilot sensitive the other a slave to ensure that the any of the other types of regulators with
application specific additions.
Figure 23.
A TYPICAL PILOT OPERATED REGULATOR INSTALLATION. REGULATOR SELECTION

Ensure the regulator chosen exactly fits the


performance requirements of the application.
SUPPLY A regulator which controls the pressure to a
AIR distribution main is usually of the general
purpose type or for large volume/flow
applications pilot operated.
Decide if the performance require-
CONVENTIONAL PILOT OUTPUT
PILOT LINE ments need a standard or precision regulator.
REGULATOR Then decide if the flow capacity of the
SUPPLY regulator is suitable for the pipe size needs
AIR
(see figure 38) and check with the regulators
flow characteristics. Figure 25 shows flow
PILOT OPERATED
REGULATOR
ratings of Norgren General Purpose
Regulators . If there is no variation in the
inlet pressure to an application then the
regulation characteristic of the regulator is
unimportant but the flow characteristic will
OUTLET be. If the inlet pressure is exposed to
AIR variations then the regulation characteristics

12
of the chosen regulator must also be consid- FILTER/REGULATORS Figure 27.
ered. GENERAL PURPOSE FILTER/REGULATOR
A variety of spring ranges are offered Filter/regulators both clean the air to the
with most regulators. Ideally the regulators application and control the pressure in one
should be operated inside the middle third of compact unit. For general purpose applica-
their range, since at the lower end of their tions filter/regulators are usually lower cost
range the spring loses some sensitivity and than two separate units.
at the higher end may suffer in linearity. Also Some specialist filter/regulators are
low rate springs can help reduce pressure available for instrument applications with fine
droop, so springs can be selected to best fit particle removal or even oil removal proper-
the systems requirements. ties with precision regulator characteristics,
If a precision regulator is required as are others with special material compati-
decide on the level of sensitivity, flow and bility.
regulation characteristics and if required
relief capacity and temperature sensitivity. Figure 26.
Select only a regulator suitable for its NORGREN FILTER/REGULATOR FLOW
application. Correct selection could see a CAPABILITIES.

;;;
general purpose regulator with ordinary Pipe Unit Flow (dm3/s)*
performance characteristics fulfilling what Size

;;;
may be considered a precision regulators 1/8" B07 6,2

;;;
function without system degradation at a 1/4" B72G 38
lower installed cost and more cost efficiently. 1/2" B64G 110
1/2" B74G 100
Figure 25. 1" B15 230
GENERAL PURPOSE REGULATOR FLOWS *Flow with 10 bar inlet, 6,3 bar outlet and 1 bar
Pipe Unit Flow (dm3/s)* pressure drop.
Size
1/8" R07 6,5
1/4" R72G 33
1/2" R64G 120
R74G 105 Figure 28.
1" R15 180 ALUMINIUM INSTRUMENT
*Flow with 10 bar inlet, 6,3 bar outlet and 1 bar FILTER/REGULATOR
pressure drop.

13
LUBRICATION tions where only very small amounts of Figure 29.
lubricant are required, possibly over large OIL-FOG LUBRICATOR
The next important step in processing areas. By adjustment of the drip rate higher
compressed air is that of introducing into the oil delivery can be achieved to match that of
air a suitable amount of lubricant, usually oil an Oil-Fog lubricator at normal usage rates.
to enable the operating equipment to perform The Micro-Fog principle has made
to its requirements efficiently without exces- possible the application of aerosol lubrica-
sive resistance or wear. Excessive resistance tion to general machine lubrication such as
to motion will result in extra power bearings, gears, chains etc.
consumption and excessive wear will result Both Oil-Fog and Micro-Fog
in shortened equipment life. Both result in lubricators include a non-return valve in the
extra cost. syphon tube to ensure immediate lubrication
There are two basic type of lubri- as soon as the air is turned on. However for
cator in general use, aerosol and injection some rapidly cycling duties or systems with
pump. small stroke cylinders it is sometimes not
The most widely used is the aerosol, possible to lubricate correctly with conven-
which was the first type of dependable tional lubricators. For such applications
automatic air line lubrication device, invented system modifications such as quick exhaust
by Norgren in 1927. valves must be employed or a bi-directional
Aerosol lubricators are available in lubricator suitably located can overcome
two main types, Oil-Fog and Micro-Fog. In such problems.
an Oil-Fog lubricator the fog produced The second type of lubricator, the
generally has relatively large oil particles and injection oil-pump is a positive displacement
so will only remain airborne for relatively device. Because of its nature it cannot
short distances. As a general rule of thumb continuously deliver lubricant but has
the maximum distance an Oil-Fog lubricator particular applications in multi-spindle nut
should be placed from the pneumatic device runners where conventional lubricators will 60 mg/m3 is a good basic starting point.
which it is to service is 9 metres. Large split air flows according to passageway From regular inspection and servicing the
particles are more strongly affected by geometry. The injection pump will deliver the optimum setting may be found by increasing
gravity and so Oil-Fog lubricators should not same amount of lubricant to the application or decreasing the amount delivered.
be used in attempting to lubricate a device at point every time it is cycled. This type of
a higher level than the lubricator. lubricator is often used on conveyor chains FILLING LUBRICATOR BOWLS
The Micro-Fog lubricator uses a where their application will overcome
special fog generator to atomise only a problems of incorrectly located or adjusted With all lubricators eventually the bowl or
fraction of the oil. conventional lubricators. reservoir will need filling. Most Oil-Fog
Because the airborne fog is now Several such injectors can be lubricators have a check valve fitted to allow
made up of only light particles, less than manifolded together to lubricate at several them to be refilled whilst in use. Most Micro-
about 2 microns in size, gravity does not different points, but at the same frequency. Fog lubricators can be fitted with a quick fill
have the same effect upon it and so this fog Whichever type of lubricator is nipple and so be topped up with lubricant,
can travel not only “up-hill” but also for long employed it is important to remember that all supplied at a pressure of approximately 1 bar
distances and through more complex feed lubricators are total loss systems in that the above that within the bowl.
lines without wetting out in the pipe. Micro- dispensed lubricant will reach its ‘bearing’ Remote fill devices also exist which
Fog can also ensure proportionate distribu- surface and be broken down into smaller can do this automatically. Such devices can
tion through multiple lubrication outlets, particles and ‘lost’ as the system is cycled. be used to supply several bowls or reservoirs
ideal for multiple valve control circuits. The amount of oil which should be from one central position.
A comparison of these two types of delivered to a pneumatic system to provide Another way to reduce the scheduled
lubricators can lead to a simple division of sufficient lubrication is difficult to determine task of refilling lubricators or to ensure
them as being high delivery (Oil-Fog) or low as all systems will be different. Pneumatic critical operations never ‘run dry’ is to
delivery types (Micro-Fog). All of the devices in a system may require different employ a liquid level switch. Such devices
droplets of oil shown in the Oil-Fog sight amounts of lubricant and so equipment are normally float operated switches which
dome will be delivered into the system and manufacturers recommendations should can give an electrical signal on low or high
for the Micro-Fog only about 5 to 10% of the always be followed, where they exist. liquid level. Such signals can then be built
droplets witnessed will be delivered. The For a general guide for most into a control system to fill or stop filling or
Micro-Fog can therefore be used in applica- pneumatic systems an oil output density of give warning alarms.

14
Figure 30. application as possible. Always select associated with high flows and so be more
MICRO-FOG LUBRICATOR lubricators and locate them where different energy efficient.
levels of lubrication are required, never For exceptionally high flow rates
attempt to fit one lubricator to supply a whole small amounts of lubricant (especially for
distribution system as differing parts will anti-freeze usage) can be injected by small
then be over lubricated, whilst others are lubricators into large distribution mains of 1
under lubricated. to 2" and above, where a full bore lubricator
Ensure that only special purpose would be expensive in both cost and
Micro-Fog lubricators are used for bearing pressure drop.
lubrication as other types are not suitable.
Check that the lubricator chosen has
sufficient flow capacity without excessive
pressure drop for the pipe line size being
used (see figure 37 and individual lubricator
performance graphs).

Figure 31. LUBRICATOR FLOW RATES


Pipe Unit Flow (dm3/s)*
Size
1/8" L07 5
1/4" L72 24
1/2" L64/L74 72
1" L15 175

*Flow at 6,3 bar and 0,5 bar pressure drop.

Although a high level signal may at Since lubricators require a minimum


first seem strange remember that overfilling pressure drop to operate which is normally
will not only prevent the lubricator from related to a flow, ensure that this minimum
performing its function of producing an flow condition is met or there will be no oil
air/oil mix of fog, but will distribute bulk output. It is important to note that leaks from
lubricant into the pneumatic system, flooding compressed air systems are a source of
it. energy loss and also such leaks are effec-
tively a constant flow through the system. If a
LUBRICATOR SELECTION lubricator with a very low start point is used
then even a small leakage, if in excess of the
Determine which parts of the system require start point will cause it to drip and supply oil
lubrication (some distribution lines will be to to the system. This is often the cause of oil
oil free areas such as paint spraying or flooding during periods of shut-down,
breathing air applications). especially over weekends.
Determine what type of lubrication is Where continual usage exists select
required for each part of the system. Slow a lubricator with sufficient reservoir capacity.
moving heavy cylinders need high delivery For units in 1/2" pipe size and above, several
so chose an Oil-Fog type lubricator. Long reservoir capacities are usually available.
runs of pipe in multi-valve circuits require a Where this is not possible because of space
Micro-Fog (or several Oil-Fog) lubricators to or usage rate utilise remote fill devices or
lubricate effectively. High speed tools are liquid level switches to auxiliary systems.
better served by a Micro-Fog, as are tips of Where very high flows are encoun-
cutting tools. tered use a fixed venturi type lubricator.
All lubricators are a source of Unlike standard types this does not automati-
pressure drop and therefore energy loss, so cally adjust to give a constant air/oil density,
although Micro-Fogs may be positioned so the flow requirement needs to be essen-
almost anywhere in a system select and tially constant. This type of device will then
place them as conveniently close to the not produce excessive pressure drops

15
PROTECTING SYSTEMS, operate when the regulated pressure is TYPES OF RELIEF VALVES
PERSONNEL AND THE exceeded and so need to be set higher than
ENVIRONMENT the regulator. There will be a tolerance on Several types of relief valves exist to achieve
the relief valve setting and on the regulators different levels of performance with respect to
Safety in the workplace is essential and is outlet setting, depending on its flow and the flow capacity and over pressure limita-
emphasised via the Machinery Directive, the regulation characteristics. A common tions. The most common is the ‘pop’ type,
Pressure Systems legislation and the problem is a relief setting too close to the followed by the diaphragm type. For better
Provision and Use of Work Equipment system operating pressure. The conse- performance use pilot operated valves with
Regulations (PUWER). quence of this is to have the relief valve the integral pilot operated type being the
The following section can help operating and venting air during normal most compact and cost effective (figure 32).
machine designers and others using pneu- system operation, which is an expensive An “in-line” type of relief device has
matics by illustrating those air line products waste of air. relief port at 90° to the direction of flow and
which, when correctly applied, can be used Once the relief valve setting pressure in normal operation flow passes through the
to ensure safe pneumatic systems. and acceptable level of over pressure are body of the device, without interfering with
In it we have cross referenced checked the flow capacity of the relief device normal upstream operation. A common use
relevant documents. Norgren strongly and that of the system can be considered. of this type of device is with machine
recommend that all who are involved with The relief device must be able to match or builders, where all the control
machine and system design should become exceed the amount of flow through the part of equipment/protection devices are in one
familiar with these and other relevant safety the system being protected without the discrete position, aiding both installation and
documents. system pressure rising above the acceptable scheduled servicing.
over pressure level. The in-line device differs from the
OVERPRESSURE PROTECTION Several methods can be used to pop or diaphragm type of relief valves which
achieve this:- are connected into the system on a tee-piece.
The components in pneumatic systems will The relief device has a flow capacity Flow through these devices only occurs
often have a pressure rating lower than that in excess of the compressors free air delivery when in operation and air vents to atmos-
generated at the compressor and pressure capacity - in systems where no receiver phere.
regulators are used to reduce this pressure to exists - i.e. flow out of system is greater than In both cases the exhaust flow can
safe efficient levels. In the event of a fault flow in. be piped away to an area where the noise
the components can be exposed to excess The relief device has a capacity in and flow will not cause disruption or harm to
pressures leading to mis-function or in excess of the flow through the smallest flow the environment or the operators. Exhaust
extremes failure of the pressure containing passageway upstream of the equipment silencers may be required to reduce noise
envelope. being protected. Tables of orifice flow exist levels in high flow exhaust applications
To protect against this excessive to determine the flow at different pressures where piping away to less sensitive areas is
over pressure situation several solutions can through differing sizes of orifice. The not possible.
be employed the most common being a relief smallest bore is acting as a restriction to the
valve. Selecting a relief valve is not a simple flow into the downstream system and unless
process, and detailed consideration of the the upstream pressure can be increased the
system or element of the system is required. flow will be choked through this area and
In general all pneumatic components therefore limited. This is important since a
and equipment will have a Safe Working mains distribution system can be of very
Pressure (SWP) and over pressure limit of large volume with pipes of large bore and
10%. The designer of the pneumatic system compressors of high capacity, but the device
can use regulators to run the system at being protected could be fed by 1/8" nominal
pressures below the SWP and use the 10% bore tubing. So a small low cost device only
safety factor to be the limit of over pressure is required and not one large enough to cope
that the system can experience with the relief with the full system capacity.
valve in operation. In areas where no such flow restric-
A relief valve is defined as a device tion exists, one should be created in order to
with its outlet so connected to a pressure reduce the cost of the relief valve to be
system to enable the system pressure to be employed, ensuring of course that the
held at a constant level. This constant level restriction does not cause excessive pressure
would then be at or below the stated SWP + drop in the course of normal operation.
10% over pressure allowance. Legislation Reference:
Relief valves need to be set to only BS EN 983 5.1.2

16
Figure 32. SOFT START/DUMP VALVES EXHAUST AIR
INTERNAL PILOT RELIEF VALVE
The next form of protection is that associated Exhaust air needs to be treated
with the moving parts of the system, where correctly to reduce the effects of noise, oil
the parts themselves can need protection mist and to minimise danger to personnel.
against excessive wear due to loading on Where a dump valve is employed,
start up or there is danger to personnel from large volumes of air can be released at high
sudden movement of the parts. speed which will produce high noise levels.
Here the use of “soft start” (“slow Simple silencers made of porous materials
start”) valves is desirable. The normal are often able to deal with this. In more
operation is to allow air to pass to a pneu- demanding high velocity cycling applications
matic system or device in a gradual manner, a heavy duty silencer may be needed.
where the rate of pressure build-up can be Silencers are normally rated for their
controlled by adjustment of the valve. The noise reduction and associated back
valve design is generally an internal poppet pressure so the choice should be dependent
valve which is spring operated and when the upon the duty required of the device to
gradual pressure build-up produces a force ensure the most cost efficient silencer is
in excess of that holding the poppet closed, utilised.
the poppet moves to the open position The next major pollutant is oil. All
allowing flow to proceed through the normal pneumatic lubrication systems are total loss
flow passageways. The level at which the systems, the lubricant goes into the system,
poppet operates is called the snap point and gets degraded in its function and is carried
for most devices this snap point will be in along with impurities and dirt to the atmos-
the range of 40 to 70% of full line pressure. pheric exhaust.
Because pressure build up in any In well maintained and correctly
system is dependant upon the system lubricated systems of a general engineering
volume it is important to locate these devices nature the amount of exhausting oil is very
close to the piece of equipment they are to small and will disperse without generally
protect. Fitting of a larger valve to a affecting the working environment adversely.
complete distribution system will generally However incorrectly lubricated systems or
mean the system will take many minutes to those which require high levels of lubrication
fully pressurise. for heavy duty applications can expel high
It is extremely common to couple levels of oil into the atmosphere on their
the slow start valve with a dump or exhaust
function valve within one body, for compact- Figure 34.
ness. COALESCING SILENCER
The function of the ‘dump’ valve is to
Figure 33. quickly exhaust the pressure from the
SOFT START/DUMP VALVE downstream system. The valve can have
solenoid or air pilot operators and often a
manual override or emergency dump
function.
Legislation Reference:
BS EN 983 5.1.4

17
exhaust cycle. In such instances use of a PROTECTION DEVICE OTHER PRODUCTS FOR SAFE
coalescing exhaust silencer should be SELECTION SYSTEMS
considered. The action of this device is
exactly as those for oil removal filters which (i) Decide which parts of the system cannot Other air line products that can help create
cause the small oil droplets to merge withstand the maximum pressure which can safe pneumatic systems -
together into large droplets which fall into a be developed in the distribution system (or Preset pressure regulators - where
container for removal. (See figure 34.) In compressor). unauthorised adjustment of the set pressure
the course of this process the porous Determine which type of relief valve can be injurious to personnel.
material employed also reduces the noise is required to control this air pressure most Guidance Document: HS (G) 39
level of the exhaust air. effectively with consideration of failure flow Lockable shut-off valves - ensure
Since these devices are on the through that part of the system. Consider that a ‘safe to work’ procedure can be
exhaust side of the pneumatic system they using a restrictor (orifice) without producing adopted without jeopardy from the unautho-
are exposed to sudden shock loading, which excessive pressure losses in the normal rised re-application of pressure.
means their oil removal capabilities are not operation of that part of the system. Legislation: BS EN 983 5.1.6
as good as those employed in coalescing For very large flows consider a pilot Guidance Document HS (G) 39
filters. A good exhaust coalescing silencer operated regulator as a dump valve. Tamper resistant kits - can be fitted
will however give figures of typically 2 ppm For machines consider an in-line to pressure regulators, filter/regulators, relief
under average usage conditions. device to build-up one complete integral valves and lubricators to ensure that flow,
modular preparation assembly for ease of pressure and other settings are secured
piping, location and servicing. against unauthorised adjustment.
(ii) Decide upon which parts of the Legislation Reference:
system can suffer from problems on initial BS EN 983 5.1.9
start up, or resetting where excessive initial
speeds can lead to wear problems or entrap-
ment, or where an emergency stop/dump
function is required.
Employ one soft start/dump valve for
each section of the system operated in this
way. The larger the system the longer the
dump or emergency stop function will take to
fully empty the system.
Locate soft start/dump valves in the
FRL assembly at the downstream end to
prevent high back flows through the lubri-
cator.
(iii) Where large volumes of air are
to be exhausted consider fitting a silencer if
the air cannot be piped away to a convenient
position.
Where rapid cycling of exhaust is
present fit a heavy duty silencer.
Where the exhaust air can be heavily
laden with lubricant, usually from equipment
requiring high levels of lubrication fit a
coalescing exhaust silencer.

18
NORGREN
AIR PREPARATION
PRODUCT OVERVIEW

UNRIVALLED PRODUCT
RANGE Figure 35.
EXCELON SYSTEM
Norgren, the world leader
in air preparation offers an
unrivalled range of products
to enable you to produce
clean compressed air and
use it economically and
safely.

Whatever your need from


the simplest factory installa-
tion to a complex medical
application, Norgren has
the right air preparation
equipment for you.

Figure 36.
OLYMPIAN PLUS SYSTEM

19
NORGREN
AIR PREPARATION
PRODUCT OVERVIEW
OLYMPIAN PLUS EXCELON
These pages show the main product families,
together with just a few of the more
specialised standard products. In addition we
produce hundreds of products to customers
specifications, utilising the vast experience
Norgren has accumulated over the past 70
years.
All the main ranges include :-
General Purpose Filters
High Efficiency Filters
Vapour Removal Filters
General Purpose Regulators
Filter/Regulators
Oil-Fog and Micro-Fog Lubricators
Soft Start/Dump Valves Olympian Plus is the new generation FRL Excelon is a completely new air preparation
Shut-Off Valves system, which sets new standards for ease of system from Norgren. Although direct ported,
Relief valves use and flexibility. The unique plug in feature thanks to a patented Quikclamp connection
These are supported by a wide allows quick installation or removal of units system, Excelon can be used where both
choice of mounting methods and accessories with a simple quarter turn of the clamp ring. stand alone units or modular assemblies are
Porting Blocks The easily connected yoke systems allows required.
Pressure Switches speedy assembly of combination units. It offers exceptional performance in
Level Controls Packed with features to make field a compact well styled unit. It is ideal for
Service Indicators maintenance easy and convenient Olympian OEM’s offering a flexible modular system
Manifold Blocks Plus is ideal for industrial installations. with useful accessories such as pressure
Equally the wide range of system accessories switches and manifold blocks. The quick
mean it offers the OEM user a highly flexible release bayonet bowl, high visibility liquid
solution. level indicator and easy to operate patented
Olympian Plus is available in basic Quikdrain are just a few of the features
1/2 inch , with optional 1/4, 3/8 and 3/4 designed with ease of maintenance in mind.
porting. There are two sizes in the Excelon
range.
OLYMPIAN 15 SERIES
EXCELON 72 is basic 1/4 (with
The 15 Series is the basic 1" version optional overporting to 3/8). However there
of the Olympian system. Available in 3/4 is nothing basic about its performance,
through 1 1/2 inch ports it offers a flexible which is actually better than many competi-
solution for larger machines and high tors 3/8 products.
volume industrial use. EXCELON 74 is a 1/2 inch range
(optional 3/8 and 3/4).

20
PORTED UNITS PRECISION REGULATORS SPECIALISED PRODUCTS

The ported products have no modular Norgren has several different precision STAINLESS STEEL
connection system, and are generally used as regulators, each offering the designer a
stand alone units. They cover a wide range of particular combination of performance Norgren produces units which meet NACE
basic port sizes from 1/8" (07 Series) characteristics from which to select the best requirements for use offshore and in harsh
through 2" (18 Series). unit for the application. Many specials are process environments. The 38 Series
produced in addition to the catalogued regulator and filter/regulator are 1/4 NPT
07 SERIES
options. units offering high flow with good precision.
The miniature range offers good The 22 Series filter, regulator and lubricator
11-818
performance units for smaller flow require- are basic 1/2" and for lower flow applications
ments. Here regulators are the most common Compact, high precision regulators there is the 1/4" 05 Series.
product and in addition to the catalogued for air gauging, laboratory use and precise
WATER REGULATORS
units Norgren offers a vast array of options. pilot control.
Units are available in a range of body Regulators with plastic or brass
11 400
materials, with internal components chosen bodies suitable for general or potable water
to deliver the specific performance character- For high accuracy pilot control of duty.
istics requested by the customer. large regulators and relief valves.
RELIEF VALVES
11 SERIES R24 MICRO TROL
In addition to the relief valves which
A basic 3/8" size the 11 Series is Exceptionally high flow with excel- are part of the main FRL families Norgren
also offered with 1/4" and in some cases lent relief performance. has several specialised units including Pop
1/2" ports. These are well proven reliable Type and the air piloted 40AC.
R38
units often used as an alternative to a true
ELECTRONIC REGULATORS
1/2" product, where the flow requirements Instrument regulator produced in
are not high. aluminium or stainless steel. Norgren can offer fully program-
mable electronic regulators for use with any
18 SERIES R27
standard industrial PLC. The R26 Pneu-Stat
The 18 Series is a basic 2 inch High precision regulators featuring a electronic regulator gives stable output over
range designed for factory air mains or high wide choice of operators. long periods and is ideal for closed loop
flow OEM applications such as shot blasting pressure control in applications such as
or textile machines. welding machines which require many
different pressure settings.

21
GLOSSARY

After Cooler: Flow Characteristics: Regulation Characteristic:


A heat exchanger mounted on a A characteristic of a pressure A characteristic of a pressure
compressor outlet to extract the heat regulator which shows the variation regulator which shows the variation
of compression. of outlet pressure with varying outlet of outlet pressure with varying inlet
Ambient: flow rates at a constant supply pressure at a constant flow rate.
The conditions, usually temperature, pressure. Relative Humidity:
in the vacinity of the equipment Free Air: The ratio of the actual amount of
under normal working conditions. Air flow measure in dm3/s at STP water vapour present in a given
Back Pressure Regulator: (1 013mbar and 21°C) (ISO R554). volume of air, to the amount of water
A device connected to a system in All air flows are converted to this to vapour necessary to saturate the
such a way that the system pressure make system sizing easier. same volume of air at the same
is held effectively constant by Initial Droop: temperature.
control of the outlet flow to atmos- The amount of pressure drop Soft Start Valve:
phere. incurred by a pressure regulator in A device which on initial pressurisa-
Check Valve: going from a flow (static) condition tion of a system allows the pressure
A device which allows flow in one to a small flow (dynamic) condition. to build up slowly to a pre-deter-
direction only. Micro-Fog: mined intermediate level before
Coalescing: A suspension of light oil fractions in allowing a step-up to full line
The action causing small particles to air, typically less than 2 µm in size pressure to be achieved.
unite to form larger particles. which can travel long distances,
Deliquescent Dryer: through complex passageways.
A dryer using material which Micron (micrometre):
absorbs water vapour to such an A measurement of size on millionth
extent that the material ultimately of a metre (symbol µm).
dissolves into the water it absorbs. Oil-Fog:
Desiccant: A suspension of oil fractions in air,
An adsorbing material used in some heavier and larger than Micro-Fog,
dryers. Many such dryers are suitable for heavy duty lubrication.
regenerative in that they use some of Pilot Operated Regulator:
their energy to dry the material A regulator which has its outlet
making it suitable for reuse. pressure controlled by the outlet
Drip Leg Drain: pressure of another (piloting)
A device at the bottom of a down leg pressure regulator, and not by an
from a distribution main or a system integral adjustable spring load as
low spot to remove condensed water with standard pressure regulators.
from the system. Such devices are Porting Block:
normally fitted with automatic drain A modular device for allowing
valves. several air take-off from a main air
Dump Valve: flow control set.
A valve which is connected to Pressure Drop (Droop):
atmosphere in such a way as to The amount of pressure loss
rapidly exhaust the system pressure. incurred by the flow of air through a
Emulsion: device.
A mixture of oil and water. Pressure Reducing Valve/Pressure
Failure Flow: Regulator:
The maximum flow through a device A device which is used to lower air
at a given pressure with the valve pressure in a pneumatic system to a
open to maximum extent. desired working level.

22
REFERENCE TABLES

Figure 37.
FRICTION LOSS IN PIPE FITTINGS IN TERMS OF EQUIVALENT
METRES OF STRAIGHT PIPE.
8 mm 10 mm 15 mm 20 mm 25 mm 32 mm 40 mm 50 mm
Tee (straight through) 0,15 0,15 0,21 0,34 0,46 0,55 0,67 0,92
Tee (side outlet) 0,76 0,76 1,01 1,28 1,62 2,14 2,47 3,18
90° elbow 0,43 0,43 0,52 0,64 0,79 1,07 1,25 1,59
45° Elbow 0,15 0,15 0,24 0,30 0,38 0,49 0,58 0,73
Ball valve* 0,01 0,03 0,09 0,12 0,15 0,22 — —
* Self exhausting – full open

Figure 38.
MAXIMUM RECOMMENDED FLOW * THROUGH ISO 65 MEDIUM
SERIES STEEL PIPE.
Applied Nominal Standard Pipe Size (Nominal Bore) – mm
Gauge 6 8 10 15 20 25 32 40 50 65 80
Pressure Approximate Pipe Connection – inch
bar 1/8 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3
0,4 0,3 0,6 1,4 2,6 4 7 15 25 45 69 120
1,0 0,5 1,2 2,8 4,9 7 14 28 45 80 130 230
1,6 0,8 1,7 3,8 7,1 11 20 40 60 120 185 330
2,5 1,1 2,5 5,5 10,2 15 28 57 85 170 265 470
4,0 1,7 3,7 8,3 15,4 23 44 89 135 260 410 725
6,3 2,5 5,7 12,6 23,4 35 65 133 200 390 620 14085
8,0 3,1 7,1 15,8 29,3 44 83 168 255 490 780 14375
10,0 3,9 8,8 19,5 36,2 54 102 208 315 605 965 14695
dm3/s
*Air flow rates in free air at standard atmospheric pressure of 1 013 mbar.
General notes
The flow values are based on a pressure drop (DP) as follows:
10% of applied pressure per 30 metres of pipe 6 – 15 mm nominal bore inclusive
5% of applied pressure per 30 metres of pipe 20 – 80 mm nominal bore inclusive

Figure 39.
DRYER COMPARISON
Dryer Type Pressure Atmospheric Drying Media Power Initial Cost Pre Filters After Filters Maintenance
Dew Point Dew Point Replacement Consumption Cost
Refrigerated 2°C –23°C Nil For Medium General purpose None Regular
refrigeration and coalescing maintenance
motor of refrigeration
Regenerative –40°C –57°C Infrequent For drying High General purpose Coalescing Small
Desiccant desicant and coalescing
Deliquescent 10°C –15°C Regularly, Nil Low General purpose Coalescing Recharging
minimum and container
6 monthly coalescing

23
BSI
NATIONAL
ACCREDITATION
OF CERTIFICATION
BODIES

Certificate No. FM 20822

BCAS

Valves
Actuators

Norgren is a leading world manufacturer


and supplier of pneumatic solutions,
offering a comprehensive range of
pneumatic control and automation
components via a global sales and
service network which covers 70
countries worldwide. The company is
a principal member of the diverse and Air Line
internationally successful £1 billion Fittings
IMI Group

● Sales centres

For further details, contact your local Technical Sales Centre on 0345 662266
IMI Norgren Limited
PO Box 22, Eastern Avenue, Lichfield, Staffordshire, WS13 6SB
http://www.norgren.com
‘Olympian’, ‘Excelon’, ‘Quikclamp’, ‘Micro-Fog’, ‘Ultraire’, ‘Puraire’, the Roundel, ‘Norgren’ and ‘IMI’ are registered trade marks.
© IMI Norgren Limited 1997
a subsidiary of IMI plc Due to our policy of continued development, Norgren reserve the right to change specifications without prior notice.

sz0282 5/98

Potrebbero piacerti anche