Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
19-200x
Contribution #: [TF0605-159-1]
CONTRIBUTION
Project: TableFest II, ANSI C12.19
Title: Final modifications and review of Section 9.5, “Decade 4: Security Tables”
Supersedes None
Abstract: This contribution proposes corrections and modifications to Section 9.5, “Decade
4: Security Tables” for review and inclusion in the final draft of the ANSI/MC C1219
and IEEE 1377 working documents.
Objectives addressed
Final review and corrections.
and/or introduced:
Disclaimer:
Page 1 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).
AMERICAN NATIONAL STANDARD C12.19-200x
Contribution List
Final Review
“Subject” Column
Contribution List
May 1, 2006
“Date” Column
Contribution List
Section x.x - Decade x: TLC
“Title” Column
Contribution List
Bin Qiu
“Contributor” Column
Disclaimer:
Page 2 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).
AMERICAN NATIONAL STANDARD C12.19-200x
Transformer losses are the sum of no load losses and load losses [1-4].
The no-load losses are essentially the power required to keep the core energized. When the
winding is energized, the exciting current consists of real component (core loss) and a reactive
component (energy stored momentarily in the winding inductance). The typical distribution
transformer exciting current is less than 0.5% of the rated current.
Transformer load losses are result from the flow of load current in the windings. Load loss can
be divided into two parts: (1) I 2 R loss and (2) eddy loss.
− I 2 R Loss
It is caused by transformer winding electrical resistance when load currents flow.
− Eddy Losses
Eddy losses are caused by currents circulating within the winding conductors. Stray losses are
proportional to current frequency and thus can increase dramatically when loads with harmonic
currents are served.
A deeper discussion would include at least the following, however, they are not covered in this
document:
• Temperature correction
• Stray losses
• Harmonics
Depends on where the transformer is installed, the transformer loss compensation may be added
or subtracted dependant on the following two cases.
Disclaimer:
Page 3 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).
AMERICAN NATIONAL STANDARD C12.19-200x
− Case 1
In case 1, the billing point is on the high voltage side of a transformer, the meter is located on the
low voltage side of the transformer. Transformer losses should be added to the kWh and kVar
measurement.
− Case 2
In case 2, the metering point is on the high voltage side of the transformer, the billing point is on
the low voltage side. Transformer losses should be subtracted from the kWh and kVar
measurement.
In the above calculation, the transformer parameters are treated in aggregate and not as per phase
or element values.
TLC calculation could affect accumulators such as +KWh, -KWh, KVARh as well as registers
and Load Profile data and power factor.
Disclaimer:
Page 4 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).
AMERICAN NATIONAL STANDARD C12.19-200x
KWCU Copper coefficient used in determining watt losses of the transformer due to load (Copper) losses
KVCU Iron coefficient used in determining var losses of the transformer due to no-load (Iron) losses.
KWFE
Iron coefficient used in determining watt losses
of the transformer due to no-load (Iron) losses
KVFE
Iron coefficient used in determining var losses of
the transformer due to no-load (Iron) losses.
Disclaimer:
Page 5 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).
AMERICAN NATIONAL STANDARD C12.19-200x
Transformer Data:
Based on equations 1-1 through 1-15, we can calculate and obtain the following Transformer
Loss Constants:
- Transformer Copper Loss Watt Constant: TLC WCu (%) = 0.537%
- Transformer Copper Loss Var Constant: TLC VCu (%) = 8.95%
- Transformer Iron Loss Watt Constant: TLC WFe (%) = 0.0762%
- Transformer Iron Loss Var Constant: TLC VFe (%) = 0.283%
Disclaimer:
Page 6 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).
AMERICAN NATIONAL STANDARD C12.19-200x
5. References
[1] “Transformers”, The Electric Power Engineering Handbook, Harlow, James H..
[2] “Algorithm for Computing and Programming Transformer Loss Constants in Solid-State
Meters”, Alan, Hannah.
[3] No-load versus load loss, Merritt, S.Y.; Chaitkin, S.D, Industry Applications Magazine,
IEEE, Nov 2003
[4] IEEE Guide for Transformer Loss Measurement, IEEE Std C57.123-2002, 2002
Disclaimer:
Page 7 of 7
This contribution has been prepared to assist TableFest II. This document is offered as a basis for
discussion in accordance with the submission rules of TableFest II (ANSI C12.19-1997, IEEE 1377-1997,
MC-Requirements and TF9804-001).