Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Where t(I) and Ipickup stand for the trip time and the relay IF = IS + IDG (4)
current set point respectively. A, B and P are constants to and
provide selected curve characteristics. The constants in table I ICB2 = IF (5)
define the shape of the standard moderately inverse, very However,
inverse, and extremely inverse trip characteristics if they are ICB2 ≥ IS (6)
applied to Eq. (1). [14]
TABLE I
CONSTANTS FOR STANDARD CHARACTERISTICS
Characteristic A B P
Moderately inverse 0.0515 0.1140 0.02000
Very inverse 19.61 0.491 2.0000
Extremely inverse 28.2 0.1217 2.0000
Considering the fuse interrupting characteristic, they have Fig.2. Typical radial distribution feeder in presence of DG with available
two inverse-times over current characteristic named Minimum three-phase fault current shown
Melting (MM) and Total Clearing (TC). Fuse element melts
when the level of fault current passing through fuse exceeds C. Relay mal operation
interrupting characteristics. After fuse melts, there will always For correct operation of relay it is also important that the
be some period of arcing before the current is interrupted. The relay measures the real fault current. Fig. 3 shows a
melting time is added to this arcing period to obtain the total- distribution feeder with a distributed generator supplying part
clearing time. of the local loads. Assuming a short circuit at point F, the
generator will also contribute to the total fault current and we
III. EFFECTS OF DISTRIBUTED GENERATION ON THE have the following equation.
PROTECTION OF DISTRIBUTION SYSTEM IF = IS + IDG (7)
Previous studies have shown that distributed generation But the relay R1 will only measure the current coming from
causes several problems to the protection of distribution the network. So, the relay detects only a part of the real fault
networks. The most commonly mentioned are as follows: current and may not operate properly.
Fig.5. Relay operating curves for coordinating between two relays Fig.8. Typical radial distribution feeder in presence of DG with available
three-phase fault current shown
D-2) Fuse-Fuse miss Coordination
For coordination between two fuses shown in Fig. 6, for
any fault on feeder2, fuse2 should operate before fuse1 is
melted and damaged. This requires that TC curve of fuse2 is
below the MM characteristics of fuse1. As shown in Fig. 7 the
fuses are coordinated for all fault currents levels below IFmax.
After installing DG, it is possible that the fault current level
exceeds IFmax and the coordination between two fuses is lost
[3].
Fig.9. Minimum melting curve and total clearing curve of fuse and recloser
slow curve and fast curve for coordinating between recloser and fuse
thyristor. Fig. 11 shows the control block diagram of this TABLE III
DISTRIBUTED GENERATOR PARAMETERS
FCL.
Parameter Value
Rated Active power / MW 2.6
Rated Reactive power / MVAR 3.1
Rated Voltage / kV 20
Resistance (Ra) / pu 0.01
Synchronous Reactance ( Xd )/ pu 2.2
Transient Reactance ( X’d )/ pu 0.22
Fig.11. schematic diagram of solid state FCL control Sub transient Reactance ( X’’d )/ pu 0.14
In steady state condition, the GTOs are gated continuously. For studying the impact of DG on protection system DG is
When a fault occurs a fault current must be detected rapidly. modeled in different positions for different fault positions.
This is done by comparing the instantaneous current level The solid state FCL is installed in series with DG for
with a predetermined value. After detecting fault occurred, the minimizing the impact of DG on protection problem. These
turn-off signal is given to the GTO. In this method, it is investigations are carried out as follows;
important to discriminate fault current from an in-rush current.
This problem was solved by choosing a suitable detection A. Study the false tripping
level. The current limiter must continue to limit the current Fig.13 (a) shows the fault current without presence of DG
during fault and returns it to the normal condition when a fault occurs at position 3 (F3). As shown in fig.12 in
automatically after the fault is cleared. Therefore, current the next step a DG is added to system in position 1 (P1). The
magnitude has to be monitored all the time. When detector fault current produced by DG passes through fuse11 (fig. 13
recognizes the current magnitude small for some period, (b)) and fuse11 may operate and cause unreasonable
clearance is assumed and turn-on signals are given to the electricity interruption on this healthy branch feeder. Then the
GTO. Therefore, in steady state operation only switching loss FCL is connected between DG and bus10. Fig. 13(c) shows
appears which is very smaller than other losses in the network. the current flowing through Fuse11. As shown in this Figure
the FCL decreases the fault current level passing through
V. SIMULATION RESULTS fuse11 and the possibility of false tripping is minimized.
Fig. 12 shows a typical radial distribution feeder with
multiple loads. This circuit is a simple model for calculating
the fault current and studying protection problems during the
fault in a simple and clear way. PSCAD/EMTDC software
package is used to simulate the proposed system. DG is
modeled by a synchronous machine. The simulation
parameters are chosen as follow,
Fig.16 (a). Total fault current in presence of DG Fig.18 (b). Fault current passing through recloser in presence of DG
Fig.16 (b). Total fault current in presence of DG and FCL Fig.18 (c). Total fault current in presence of DG and FCL
Fig.18 (d). Fault current passing through recloser in presence of DG and FCL
Fig.17. Minimum melting curve and total clearing curve of fuses for
coordinating between two fuses.
D-2.Fuse-recloser coordination
Recloser R and fuse11 are coordinated based on recloser
fast and slow curve and total clearing and melting curve of
fuse11. After installing DG at position 2 (P2), a fault occurs at
position 5 (F5). As shown in Fig.18 (a), Fig. 18(b) and Fig.19
the fault current passing through fuse11 is higher than
maximum current for coordinating between recloser and
fuse11. Thus, it may cause to every temporary fault change to Fig.19. Minimum melting and total clearing curve of fuse and recloser slow
permanent interruption. Fig.18 (c) and fig. 18(d) show the and fast curve for coordinating between recloser and fuse
fault current level in presence of FCL. As shown in Fig.18 (c), In order to show operation of solid state FCL, we show the
Fig. 18(d) and Fig. 19 the fault current decreases and current of limiting reactor of FCL and GTO thyristor in Fig.
coordination between fuse11 and recloser hasn't any 20(a) and 20(b). As shown in these figures, only during the
problems. fault current limiting reactor enter in the network and limit the
fault current. Therefore, proposed FCL has not any impact on
normal operation of the network.
VII. REFERENCES
[1] M. T. Doyle, "Reviewing the Impacts of Distributed Generation on
Distribution System Protection", Power Engineering Society Summer
Meeting, 2002 وVol.1, pp. 103 - 105.
[2] K. Kauhaniemi, L. Kumpulainen, "Impact of distributed generation on
the protection of distribution networks", Eighth IEE International
Conference on Developments in Power System Protection, Vo 1, 5-8
April 2004 ,pp. 315 – 318.
[3] A. Girgis and S. Brahma, "Effect of Distributed Generation on
Protective Device Coordination in Distribution System", Large
Engineering Systems Conference on Power Engineering, 11-13 July
2001, pp. 115 – 119.
[4] S. M. Brahma and A. A. Girgis, “Development of adaptive protection
scheme for distribution systems with high penetration of distributed
generation,” IEEE Transactions on Power Delivery, Jan. 2004, vol. 19,
no. 1, pp. 56–63.
[5] S. M. Brahma and A. A. Girgis, "Microprocessor - based reclosing to
coordinate fuse and recloser in a system with high penetration of
distributed generation," IEEE Power Engineering Society Winter
Meeting, 2002, Vol. 1, pp. 453–458.
[6] Tang and M. R. Iravani, "Application of a Fault Current Limiter To
Minimize Distributed Generation Impact on Coordinated Relay
Protection," International Conference on Power Systems Transients in
Montreal, Canada on June 19-23, 2005.
[7] L. Ye, L. Z. Lin, K. P. Juengst, "Application Studies of
Superconducting Fault Current Limiters in Electric Power Systems",
IEEE Transactions on Applied Superconductivity, March 2002; Vol. 12;
No. 1; pp. 900-903.
[8] M. Abapour, M. Tarafdar Hagh, “A Non – Control Transformer Inrush
Current Limiter”, IEEE International Conference on Industrial
Technology, ICIT 2006. 15-17 Dec., pp. 2390 – 2395.
[9] M. Tarafdar Hagh, M. Abapour, “DC Reactor Type Transformer Inrush
Current Limiter”, IET Electric Power Application, Vol. 1, Issue 5, Sept.
2007, pp. 808 – 814.
[10] C. S. Chang, P. C. Loh, "Integration of Fault Current Limiters on Power
Systems for Voltage Quality Improvement", Elsevier journal of Electric
Power Systems Research, March 2001; Vol. 57; Issue 2; pp. 83-92.
[11] M. Ahmed, G. Putrus, L. Ran, "Power Quality Improvement Using a
Solid-state Fault Current Limiter", Asia Pacific. IEEE/PES Trans. and
Dist. Conf. and Exhibition; 6-10 Oct., 2002; Vol. 2; pp. 1059 – 1064.
[12] M. Tsuda, Y. Mitani, K. Tsuji, K. Kakihana, “Application of Resistor
Based Superconducting Fault Current Limiter to Enhancement of Power