Sei sulla pagina 1di 7

1

Minimizing the Impact of Distributed


Generation on Distribution Protection System
by Solid State Fault Current Limiter
S. A. A. Shahriari, Student Member, IEEE, M. Abapour, Student Member, IEEE, A. Yazdian, Member,
IEEE, M. R. Haghifam, Senior Member, IEEE.

and expensive. So, these solutions are not practical for


Abstract-- Connection of new distributed generation (DG) to existing distribution systems.
the existing distribution network increases the fault current and A novel idea exists to limit the fault currents produced by
disturbs the existing distribution protection system. In this paper DG and prevent switchgears upgrade is FCLs application [6].
a solid state fault current limiter (SSFCL) application is The implementation of FCLs in electric power systems is not
proposed to minimize the effect of the DG on the distribution restricted to suppress the amplitudes of the short circuits; they
protection system in a radial system during a fault. The
are also applied in variety of performances such as the power
protection problems at distributed generation presence are
studied in detail to determine the effectiveness of the SSFCL for system transient stability enhancement, power quality
the proposed application. The effectiveness of propose SSFCL in improvement, reliability improvement, increasing transfer
protection problems mitigation is determined and examined in capacity of system equipments and inrush current limitation in
the test system. Simulation is accomplished in PSCAD/EMTDC. transformers [7-12].
The proposed method is fully validated on test system Different configurations of fault current limiters are
proposed to mitigate the impact of DG on distribution
Index Terms— Solid state fault current limiter, distributed protection system [6], [13]. In this paper a solid state FCL is
generation, distribution protection system. used to minimize the impact of DG on fault current levels and
distribution protection system. The proposed FCL has simple
I. INTRODUCTION structure and control and its loss is low. More over, the

N Owadays electric utilities try to search new technologies


to improve power quality and reliability of their
customers. Then distributed generations are becoming
operation of this type of FCL is fast. As fault happens, the
FCL will enter the fault line automatically to limit the short
circuit current.
attractive to many utilities. Moreover, these technology In this paper, a DG with appropriate rating is connected to
produce electrical energy with less environmental impacts, the different places of distribution network and recalculates
their installation are easy, and are highly efficient. Previous the fault current in each section after modeling the distribution
studies have shown that distributed generation causes several network in PSCAD/EMTDC. The impact of DG on
challenges to the protection of distribution system [1-3]. The distribution protection system is studied comprehensively.
main disadvantage of DG is producing fault current that are Then the proposed SSFCL is connected in series with DG
more than breaking capacity of circuit breakers and fuses. where the effect of SSFCL on limiting fault current is
Furthermore, the fault current produced by DG are causing investigated through computer simulations. The results
problems in protection coordination, false tripping of feeders indicate the effectiveness of proposed SSFCL by minimizing
and relay mal operation. the problems associated with the existing DG in distribution
Several ideas have been introduced as possible solutions system.
[4], [5]. These papers propose switchgears and protection
coordination upgrade in systems consist of DG. Although II. CHARACTERISTICS OF PROTECTION DEVICES
these solutions may technically operate, they are complicated Before discussing about the problems and the solutions,
some basic characteristics of conventional protection devices
should be addressed [14], [15]. Circuit breakers and reclosers
Sayyed Ali Akbar Shahriari is the Professor with Firoozabad Applied and are normally equipped with inverse-time over current trip
Science University, Iran. devices. Eq. (1) defines pick up time of an inverse-time over
(E-mail: shahriari_sajad@yahoo.com). current curve.
Mehdi Abapour is the Ph.D student with Department of Electrical
Engineering, Tarbiat Modares University, Iran. A
t(I ) = ( P + B) (1)
(E-mail: mehdi.abapour@gmail.com). M −1
Ali Yazdian is the professor with Department of Electrical Engineering,
Tarbiat Modares University, Iran. I input
(E-mail: yazdian@modares.ac.ir).
M = (2)
I pickup
Mahmoud Reaza Haghifam is the professor with Department of Electrical
Engineering, Tarbiat Modares University, Iran.
(E-mail: haghifam@modares.ac.ir).

978-1-4244-6547-7/10/$26.00 © 2010 IEEE


2

Where t(I) and Ipickup stand for the trip time and the relay IF = IS + IDG (4)
current set point respectively. A, B and P are constants to and
provide selected curve characteristics. The constants in table I ICB2 = IF (5)
define the shape of the standard moderately inverse, very However,
inverse, and extremely inverse trip characteristics if they are ICB2 ≥ IS (6)
applied to Eq. (1). [14]
TABLE I
CONSTANTS FOR STANDARD CHARACTERISTICS
Characteristic A B P
Moderately inverse 0.0515 0.1140 0.02000
Very inverse 19.61 0.491 2.0000
Extremely inverse 28.2 0.1217 2.0000
Considering the fuse interrupting characteristic, they have Fig.2. Typical radial distribution feeder in presence of DG with available
two inverse-times over current characteristic named Minimum three-phase fault current shown
Melting (MM) and Total Clearing (TC). Fuse element melts
when the level of fault current passing through fuse exceeds C. Relay mal operation
interrupting characteristics. After fuse melts, there will always For correct operation of relay it is also important that the
be some period of arcing before the current is interrupted. The relay measures the real fault current. Fig. 3 shows a
melting time is added to this arcing period to obtain the total- distribution feeder with a distributed generator supplying part
clearing time. of the local loads. Assuming a short circuit at point F, the
generator will also contribute to the total fault current and we
III. EFFECTS OF DISTRIBUTED GENERATION ON THE have the following equation.
PROTECTION OF DISTRIBUTION SYSTEM IF = IS + IDG (7)
Previous studies have shown that distributed generation But the relay R1 will only measure the current coming from
causes several problems to the protection of distribution the network. So, the relay detects only a part of the real fault
networks. The most commonly mentioned are as follows: current and may not operate properly.

A. False tripping of feeders


When a fault occurs at another feeder, the operating device
located in that faulted feeder should operate. Nevertheless, the
circuit breaker or fuse at the feeder of the DG may operate and
cause unreasonable electricity interruption. The basic principle
of false tripping is shown in Fig. 1. The short-circuit fault Fig.3. Typical radial distribution feeder in presence of DG with available
occurs on feeder1. Fuse1 must operate to remove fault from three-phase fault current shown
network, but also CB2 is tripped because of overcurrent fed
D. Miss coordination of protection devices
by the DG unit [2], [16].
The fault contribution from a DG can significantly alter the
short circuit levels and cause fuse-recloser (relay) or relay-
relay or fuse-fuse miss coordination.
D-1) Relay-relay miss coordination
Fig. 4 shows a main distribution feeder fed through
substation and protected by inverse overcurrent relays R1, R2
and R3. The coordination between R2 and R3 is shown in
Fig.1. Typical radial distribution feeder in presence of DG with available Fig.5. In order to coordinate R2 and R3 for maximum fault
three-phase fault current shown
current in point F, time of operation of relay R2 is larger than
B. Exceeding the interruption capacity of circuit breaker time of operation of R3 at least by a time interval called
The basic principle of exceeding the interruption capacity Coordination Time Interval (CTI). Now DG is connected to
of circuit breaker is shown in Fig. 2. The short-circuit fault the feeder as shown in Fig. 4. When DG is connected, the
occurs in point F. When DG connects to bus 2 the fault fault current increases. Thus, the coordination between two
current through circuit breaker 2 (IF) will be increase. Due to relays is likely to face a problem because the time interval
the increasing fault current levels, the interruption capacity of between two relays operation is less than CTI [3].
switching equipment should be changed for new operation
point. Therefore, the replacement of circuit breakers or fuses
is necessary. What's more, the analysis of the short circuit
level is essential for specifying these circuit breakers or fuses
[1]. The following equations describe this problem.
Without the DG connection (IDG = 0)
IF = IS = ICB2 (3) Fig.4. Typical radial distribution feeder in presence of DG with available
With the DG connection three-phase fault current shown
3

Fig. 9 fuse may operate before recloser and every temporary


fault change to permanent interruption [3], [16].

Fig.5. Relay operating curves for coordinating between two relays Fig.8. Typical radial distribution feeder in presence of DG with available
three-phase fault current shown
D-2) Fuse-Fuse miss Coordination
For coordination between two fuses shown in Fig. 6, for
any fault on feeder2, fuse2 should operate before fuse1 is
melted and damaged. This requires that TC curve of fuse2 is
below the MM characteristics of fuse1. As shown in Fig. 7 the
fuses are coordinated for all fault currents levels below IFmax.
After installing DG, it is possible that the fault current level
exceeds IFmax and the coordination between two fuses is lost
[3].

Fig.9. Minimum melting curve and total clearing curve of fuse and recloser
slow curve and fast curve for coordinating between recloser and fuse

IV. PROPOSED FAULT CURRENT LIMITER AND ITS DESIGN


CONSIDERATION
In this paper, solid state FCL [17] is used and its effect on
fault current is analyzed. The most beneficial property of this
configuration is simplicity of structure and control, low stead-
Fig.6. Typical radial distribution feeder in presence of DG with available
three-phase fault current shown state impedance, fast response and high impedance fault.
Fig.10 shows a general configuration of the solid-state
current limiter. It consists of a fast solid-state switch, current
limiting impedance, voltage limiting element and series
mechanical switch. The GTO thyristors are used as the fast
solid-state switch and the current limiting impedance is
connected in parallel with these. The GTO thyristors are used
to interrupt a current instantly upon receiving a turn-off signal
and the current limiter impedance is used as way for passing
the fault current when the solid state switch interrupt a fault
current. But a sudden interruption of current is likely to cause
an overvoltage in the circuit, so the voltage limiting element is
used to prevent this [17].
Fig.7. Minimum melting curve and total clearing curve of fuses for
coordinating between two fuse

D-2) Fuse-recloser miss coordination


For coordination between reclosers and fuse, the recloser
must protect the fuse from temporary faults and fuse must
operate for permanent faults. This requires that the recloser
fast curve is below than the MM curve of the fuse
As shown in Fig. 8, when DG is located at the end of feeder
and a fault occurs at feeder2, the fault current flowing through
the recloser is different from the fault current passing through Fig.10. basic configuration of solid state FCL
the fuse. Then, the fault current seen by fuse is likely to be The overcurrent detector and control device detect a fault
higher than the fault current seen by recloser. As shown in and produce turn-off and turn-on signals for the GTO
4

thyristor. Fig. 11 shows the control block diagram of this TABLE III
DISTRIBUTED GENERATOR PARAMETERS
FCL.
Parameter Value
Rated Active power / MW 2.6
Rated Reactive power / MVAR 3.1
Rated Voltage / kV 20
Resistance (Ra) / pu 0.01
Synchronous Reactance ( Xd )/ pu 2.2
Transient Reactance ( X’d )/ pu 0.22
Fig.11. schematic diagram of solid state FCL control Sub transient Reactance ( X’’d )/ pu 0.14
In steady state condition, the GTOs are gated continuously. For studying the impact of DG on protection system DG is
When a fault occurs a fault current must be detected rapidly. modeled in different positions for different fault positions.
This is done by comparing the instantaneous current level The solid state FCL is installed in series with DG for
with a predetermined value. After detecting fault occurred, the minimizing the impact of DG on protection problem. These
turn-off signal is given to the GTO. In this method, it is investigations are carried out as follows;
important to discriminate fault current from an in-rush current.
This problem was solved by choosing a suitable detection A. Study the false tripping
level. The current limiter must continue to limit the current Fig.13 (a) shows the fault current without presence of DG
during fault and returns it to the normal condition when a fault occurs at position 3 (F3). As shown in fig.12 in
automatically after the fault is cleared. Therefore, current the next step a DG is added to system in position 1 (P1). The
magnitude has to be monitored all the time. When detector fault current produced by DG passes through fuse11 (fig. 13
recognizes the current magnitude small for some period, (b)) and fuse11 may operate and cause unreasonable
clearance is assumed and turn-on signals are given to the electricity interruption on this healthy branch feeder. Then the
GTO. Therefore, in steady state operation only switching loss FCL is connected between DG and bus10. Fig. 13(c) shows
appears which is very smaller than other losses in the network. the current flowing through Fuse11. As shown in this Figure
the FCL decreases the fault current level passing through
V. SIMULATION RESULTS fuse11 and the possibility of false tripping is minimized.
Fig. 12 shows a typical radial distribution feeder with
multiple loads. This circuit is a simple model for calculating
the fault current and studying protection problems during the
fault in a simple and clear way. PSCAD/EMTDC software
package is used to simulate the proposed system. DG is
modeled by a synchronous machine. The simulation
parameters are chosen as follow,

Fig.13 (a). Fault current without presence of DG

Fig.12. Radial test system with DG and local loads

Fig.13 (b). Fault current in presence of DG


TABLE II
DISTRIBUTION SYSTEM PARAMETERS
From To R(ohm) X(ohm) P(KW) Q(KVAR)
1 2 0.1233 0.4084 1840 460
2 3 0.014 0.5969 980 340
3 4 0.7463 1.1938 1790 446
4 5 0.6984 0.5969 1598 1840
5 6 1.9831 1.4137 1610 600
6 7 0.905 0.7886 780 110
7 8 2.0552 1.1624 1150 60
8 9 2.45 1.5708 980 130
9 10 3.0434 1.885 1640 200 Fig.13 (c). Fault current in presence of DG and FCL
5

B. Study the exceeding the interruption capacity of circuit


breaker
Fig.14 (a) shows the fault current without presence of DG
when a fault occurs at position 2 (F2). Fig.14 (b) shows the
fault current after installing DG at position 4 (P4). As
indicated in this figure the level of fault current is increased
by produced fault current by DG and this fault current is likely
to be higher than exceeding the interruption capacity of circuit
breaker. Then a FCL is installed between DG and bus5. Fig.
Fig.15 (a). Total fault current in presence of DG
14(c) shows the current flowing through circuit breaker. As
shown in this Figure the FCL decreases the fault current
produced by DG and fault current passing through circuit
breaker. Therefore, the possibility of exceeding the
interruption capacity is minimized.

Fig.15 (b). Fault current seen by recloser in presence of DG

Fig.14 (a). Fault current without presence of DG

Fig.15 (c). Total fault current in presence of DG and FCL

Fig.14 (b). Fault current in presence of DG

Fig.15 (d). Fault current seen by recloser in presence of DG and FCL

D. Study the miss coordination of protection devices


The fault contribution from a DG can significantly alter the
short circuit levels. The fuse-fuse and fuse-recloser miss
Fig.14 (c). Fault current in presence of DG and FCL coordination that is very usual in distribution system is
C. Study the relay mal operation simulated in this section.
As shown in Fig.12 when a fault occurs at position 4 (F4), D-1.Fuse-fuse miss coordination
the total fault current flows the recloser. But after installing Fuse10 and fuse11 are coordinated based on total clearing
DG at position 3 (P3), the fault current produced by DG curve and minimum melting curves of these fuses. In this
doesn't pass through recloser. Thus the recloser doesn't see simulation a DG is installed at position 1 (P1) and a fault
total fault current and it may not operate or operate not occurs at position 1 (F1). As shown in Fig.16 (a) and fig.17
properly. Fig.15 (a) and fig.15 (b) shows the total fault current the fault current passing through fuse10 is higher than
and the fault current flowing through recloser consequently. maximum current for coordination between fuse10 and
After installing FCL between DG and bus7 the fault current fuse11. Therefore, the coordination between fuse10 and
produced by DG decreases and the possibility of relay fuse11 is encountered a problem. But Fig.16 (b) and Fig.17
operating error is minimized. Fig.15 (c) and Fig.15 (d) shows show that in presence of FCL the fault current decreases and
the total fault current and the fault current flowing through coordination between fuse10 and fuse11 hasn't any problems.
recloser consequently when FCL is installed.
6

Fig.16 (a). Total fault current in presence of DG Fig.18 (b). Fault current passing through recloser in presence of DG

Fig.16 (b). Total fault current in presence of DG and FCL Fig.18 (c). Total fault current in presence of DG and FCL

Fig.18 (d). Fault current passing through recloser in presence of DG and FCL

Fig.17. Minimum melting curve and total clearing curve of fuses for
coordinating between two fuses.

D-2.Fuse-recloser coordination
Recloser R and fuse11 are coordinated based on recloser
fast and slow curve and total clearing and melting curve of
fuse11. After installing DG at position 2 (P2), a fault occurs at
position 5 (F5). As shown in Fig.18 (a), Fig. 18(b) and Fig.19
the fault current passing through fuse11 is higher than
maximum current for coordinating between recloser and
fuse11. Thus, it may cause to every temporary fault change to Fig.19. Minimum melting and total clearing curve of fuse and recloser slow
permanent interruption. Fig.18 (c) and fig. 18(d) show the and fast curve for coordinating between recloser and fuse
fault current level in presence of FCL. As shown in Fig.18 (c), In order to show operation of solid state FCL, we show the
Fig. 18(d) and Fig. 19 the fault current decreases and current of limiting reactor of FCL and GTO thyristor in Fig.
coordination between fuse11 and recloser hasn't any 20(a) and 20(b). As shown in these figures, only during the
problems. fault current limiting reactor enter in the network and limit the
fault current. Therefore, proposed FCL has not any impact on
normal operation of the network.

Fig.18 (a). Total fault current in presence of DG

Fig.20 (a). Current of limiting rector of FCL


7

System Transient Stability”, IEEE Transactions on Applied


Superconductivity, Vol. 11, Issue 1, Part 2, Mar. 2001, pp. 2122 – 2125.
[13] T. Sato and M. Yamaguchi and T. Terashima and S. Fukui and J.
Ogawa and H. Shimizu, "Study on the Effect of Fault Current Limiter in
Power System With Dispersed Generators", IEEE Transactions on
Applied Superconductivity, June 2007, Vo 17, Issue 2, pp. 2331 – 2334.
[14] IEEE Standard Inverse-Time Characteristic Equations for Overcurrent
Relays, IEEE Standard C37.112-1996, September 1996.
[15] IEEE Guide for the Operation, Classification, Application, and
Coordination of Current-Limiting Fuses with Rated Voltages 1–38 kV.
IEEE Standard C37.48.1, June 2002.
Fig.20 (b). Current of GTOs of FCL [16] S. Chaitusaney and A. Yokoyama, "Impact of Protection Coordination
on Sizes of Several Distributed Generation Sources", The 7th
International Power Engineering Conference, Vol. 2, 29 Nov.-2 Dec
VI. CONCLUSION 2005, page(s): 669- 674.
Presence of DG increases fault current levels and lead to [17] T.Ueda, “Solid-state Current Limiter for Power Distribution System”,
IEEE Transaction on power Delivery, vol.8, no.4, October 1993,
protection problems. In this paper the protection problems in
pp.1796-1801.
presence of DG is reviewed comprehensively. For solving
these problems a solid state FCL is proposed to connect in
series with DG. The main advantages of the proposed FCL are
simplicity in structure and control, fast response. Also this
type of FCL has no effect on utility voltage and current at
normal system operation and has acceptable power loss (only
switching loss). The simulation results demonstrate both the
ability of proposed FCL to limit the fault current level and
minimizing the impact of DG on protection problems.

VII. REFERENCES
[1] M. T. Doyle, "Reviewing the Impacts of Distributed Generation on
Distribution System Protection", Power Engineering Society Summer
Meeting, 2002‫ و‬Vol.1, pp. 103 - 105.
[2] K. Kauhaniemi, L. Kumpulainen, "Impact of distributed generation on
the protection of distribution networks", Eighth IEE International
Conference on Developments in Power System Protection, Vo 1, 5-8
April 2004 ,pp. 315 – 318.
[3] A. Girgis and S. Brahma, "Effect of Distributed Generation on
Protective Device Coordination in Distribution System", Large
Engineering Systems Conference on Power Engineering, 11-13 July
2001, pp. 115 – 119.
[4] S. M. Brahma and A. A. Girgis, “Development of adaptive protection
scheme for distribution systems with high penetration of distributed
generation,” IEEE Transactions on Power Delivery, Jan. 2004, vol. 19,
no. 1, pp. 56–63.
[5] S. M. Brahma and A. A. Girgis, "Microprocessor - based reclosing to
coordinate fuse and recloser in a system with high penetration of
distributed generation," IEEE Power Engineering Society Winter
Meeting, 2002, Vol. 1, pp. 453–458.
[6] Tang and M. R. Iravani, "Application of a Fault Current Limiter To
Minimize Distributed Generation Impact on Coordinated Relay
Protection," International Conference on Power Systems Transients in
Montreal, Canada on June 19-23, 2005.
[7] L. Ye, L. Z. Lin, K. P. Juengst, "Application Studies of
Superconducting Fault Current Limiters in Electric Power Systems",
IEEE Transactions on Applied Superconductivity, March 2002; Vol. 12;
No. 1; pp. 900-903.
[8] M. Abapour, M. Tarafdar Hagh, “A Non – Control Transformer Inrush
Current Limiter”, IEEE International Conference on Industrial
Technology, ICIT 2006. 15-17 Dec., pp. 2390 – 2395.
[9] M. Tarafdar Hagh, M. Abapour, “DC Reactor Type Transformer Inrush
Current Limiter”, IET Electric Power Application, Vol. 1, Issue 5, Sept.
2007, pp. 808 – 814.
[10] C. S. Chang, P. C. Loh, "Integration of Fault Current Limiters on Power
Systems for Voltage Quality Improvement", Elsevier journal of Electric
Power Systems Research, March 2001; Vol. 57; Issue 2; pp. 83-92.
[11] M. Ahmed, G. Putrus, L. Ran, "Power Quality Improvement Using a
Solid-state Fault Current Limiter", Asia Pacific. IEEE/PES Trans. and
Dist. Conf. and Exhibition; 6-10 Oct., 2002; Vol. 2; pp. 1059 – 1064.
[12] M. Tsuda, Y. Mitani, K. Tsuji, K. Kakihana, “Application of Resistor
Based Superconducting Fault Current Limiter to Enhancement of Power

Potrebbero piacerti anche