Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
a r t i c l e i n f o a b s t r a c t
Article history: The use of combined heating and power (CHP) systems is increasing rapidly due to their high potential of
Received 31 August 2009 reducing primary energy consumption (PEC), cost, and carbon dioxide emissions (CDE). These reductions
Received in revised form 18 March 2010 are mainly due to capturing the exhaust heat to satisfy the thermal demand of a building. However, when
Accepted 19 March 2010
the CHP system is operated following the electric load, the recovered exhaust heat may or may not be
sufficient to satisfy the thermal demand of the facility. When the recovered exhaust heat is more than
Keywords:
the heat required, the excess is usually discarded to the atmosphere. An organic rankine cycle (ORC) can
CHP
be used to recover the surplus exhaust heat to generate extra electricity. Therefore, combining the ORC
ORC
CHP–ORC
system with the CHP system (CHP–ORC) reduces the electricity that has to be produced by the CHP sys-
Primary energy reduction tem, thereby reducing the total PEC, cost, and CDE. The objective of this paper is to study the energetic,
Benchmark buildings economical, and environmental performance of a combined CHP–ORC system and compare its perfor-
mance to a standalone CHP system and a reference building for different climate zones. A comparison of
a CHP–ORC system operating 24 h with a system operating during typical office hours is also performed.
© 2010 Elsevier B.V. All rights reserved.
1. Introduction convert about 30% of the fuel’s available energy into electric power.
The majority of the energy content of the fuel is lost at the power
The Annual Energy Outlook [1] reported that about 87% of the plant through the discharge of waste heat. Further energy losses
total energy consumption in the U.S. is due to fossil fuel (coal, nat- occur in the transmission and distribution of electric power to the
ural gas and liquid fuels) combustion. Lately, increasing debates individual user. Inefficiencies and pollution issues associated with
about global climate change, energy security and sustainability are conventional power plants provide the impetus for developments
driving forces that put focus on novel strategies to improve exist- in “on-site and near-site” power generation.
ing energy utilization, conversion and production technologies. The performance of CHP and CCHP systems has been studied by
In addition, increased world-wide demand for energy (especially several authors such as Moran et al. [2], Possidente et al. [3], Cao
electricity), rising energy costs, and heightened environmental con- and Liu [4], Ren and Gao [5], Malico et al. [6], Khan [7,8], Li et al. [9],
cerns are factors that continually press for the improvement and Mago et al. [10], Mago and Chamra [11], Cardona and Piacentino
development of new technologies to promote energy savings and [12,13], Cho et al. [14], and Fumo et al. [15], among others. Moran
emissions reduction. Some of these technologies include combined et al. [2] presented results from micro-CCHP systems simulations
cooling, heating, and power (CCHP) systems, combined heating and following the electric load using natural gas and diesel internal
power (CHP) systems, and organic rankine cycles (ORC). CCHP and combustion engines as prime movers. The system efficiency for
CHP systems deliver electricity on-site through the use of a prime cooling months was found to reach values up to 80% with eco-
mover, such as a spark or compression driven combustion engine nomic feasibility highly dependent on fuel prices. Possidente et al.
or a turbine engine, which delivers useful mechanical power to an [3] analyzed and evaluated the performance of a small-scale cogen-
electrical generator, which in turn creates useable electrical power eration based on energetic, economic and environmental impact
in order to satisfy a given electrical demand. The difference between and compared it to the same parameters of the conventional sys-
these systems and power plant electricity generation is the utiliza- tem for the separate production of heat and electricity. They found
tion of the exhaust heat rejected from the prime mover in order to that the micro-cogeneration using reciprocating internal combus-
satisfy the thermal demand of a facility. Traditional power plants tion engine allows obtaining primary energy savings up to 25% and
a polluter emissions reduction up to 40%. Cao and Liu [4] studied
the performance of a typical building cooling, heating and power
∗ Corresponding author. Tel.: +1 662 325 6602; fax: +1 662 325 7223. generation (BCHP) system using thermodynamic and thermoeco-
E-mail address: mago@me.msstate.edu (P.J. Mago). nomic analyses based on the simulation of off-design operation
0378-7788/$ – see front matter © 2010 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2010.03.019
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
2 P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx 3
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
4 P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx 5
Table 3
Carbon dioxide emissions conversion factors and cost for electricity and natural gas [28].
Representative city ECFCDE a (ton/kW h) FCFCDE a (ton/kW h) costelectricty a ($/kW h) costfuel a ($/kW h)
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
6 P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx
Fig. 3. Variation of the cost, PEC, and CDE for the CHP system and CHP–ORC operating 24 h a day for the selected cities.
was simulated to operate between 7:00 am and 7:00 pm. Outside est reduction was obtained for Duluth (28.5%). Regarding the CDE,
of these hours, building loads were met by the grid and boiler. For with the exception of Los Angeles, operating the CHP–ORC system
this operation, Fig. 4 illustrates the variation of the cost, PEC, and from 7:00 am to 7:00 pm reduces the CDE for all the cities and again
CDE for the CHP–ORC and CHP systems with respect to the refer- yields better results than the CHP system by an average of 20%. In
ence case. Similar to Fig. 3, a negative number implies a reduction Los Angeles the CDE increased by only 3.8%, but when compared to
from the reference case while a positive number implies an increase the CHP system the CDE was reduced by 26%.
from the reference case. In general, by comparing Figs. 3 and 4, it As mentioned before, running the CHP–ORC system during
can be observed that operating during business hours, as opposed office hours improves the performance of the system when com-
continuously, provides greater benefits for both systems. While the pared to the case when the CHP system runs for the whole day.
CHP system reduces the operational cost for the cities of Houston, This can be explained since when the CHP system operates during
Duluth, Fairbanks, and Los Angeles, the CHP–ORC reduces the cost night time, the electric load is generally low and the PGU has to
for all the evaluated cities; and, when compared to the CHP sys- run at low efficiencies therefore consuming more fuel. In addition
tem, the operation cost is reduced by an average 19%. Operating if heating is needed, since the electric load is low, the recovered
both systems for 12 h a day reduces the PEC for all the evaluated heat from the PGU is not enough and natural gas has to be sup-
cities, but the CHP–ORC PEC is always lower than the consumption plied to the boiler to complement the heat required. Therefore, it is
resulting from the CHP system’s operation by an average of 19%. cheaper to just import electricity from the grid and buy natural gas
The highest PEC reduction from the reference case for the CHP–ORC if needed for heating than operating the CHP–ORC system at very
system was obtained for the city of Miami (34.4%) while the low- low efficiencies.
Fig. 4. Variation of the cost, PEC, and CDE for the CHP system and CHP–ORC operating 12 h a day (from 7:00 am to 7:00 pm) for the selected cities.
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx 7
Fig. 5. Comparison of the fuel energy consumption for the operation of CHP and CHP–ORC for the selected cities.
4.2. Fuel energy consumption ence. In addition, the cost of electricity and natural gas along with
the CDE factors vary with location. Also, if a CHP–ORC system pro-
Fig. 5 presents a comparison of the fuel energy consumption for vides some economic benefits from the operational point of view, a
the CHP and CHP–ORC systems operating continuously (24 h a day) more detailed economic analysis that includes capital costs should
and during office hours (12 h a day). This figure illustrates that the be performed to determine the payback period and feasibility of
CHP–ORC operation consumes less fuel than the CHP operation. For the system.
both cases, 24 h and 12 h operation, the maximum reduction was The use of an ORC for waste heat recovery can also be imple-
achieved for Los Angeles, 34.7% and 33.5%, respectively. For 24 h, mented in a combined cooling, heating, and power (CCHP) system,
the minimum reduction was obtained for Fairbanks, 27%, while the where exhaust heat is also used for cooling purposes through, for
minimum reduction for 12 h operation was obtained for Duluth, example, an absorption chiller. Under 24 h a day operation, a CCHP
22.8%. The average fuel consumption reduction for the 24 h and 12 h system will perform better than a CHP system operating under
operation was 29.9% and 28.3%, respectively. These results demon- the same strategy because the CCHP system is able to utilize more
strate the benefits of using an ORC together with a CHP system since waste heat during the summer months for cooling the building. This
it helps to reduce the amount of fuel needed by the PGU of the CHP would leave less surplus heat for an ORC cycle than that would be
system while still satisfying the electric and thermal demand of the available for an ORC cycle combined with a CHP system. Therefore,
building. the use of ORC to recover the unused exhaust heat should be more
beneficial to a CHP system. However, further research is needed to
determine if the addition of an ORC makes the CHP–ORC system
5. Conclusions
more beneficial than the CCHP–ORC system during continuous and
non-continuous operation.
This paper analyzed the performance of a CHP–ORC system
using a vapor compression system to satisfy the cooling demand
of a small commercial office building. Operational cost, PEC, and References
CDE for a CHP–ORC system were determined and compared to a
reference building and a CHP system for different climate zones. [1] Annual energy outlook with projections to 2030, Report No. DOE/EIA-0383.
http://www.eia.doe.gov/oiaf/aeo/index.html, 2006 (retrieved 26.06.06).
A comparison of both systems operating 24 h a day with the sys- [2] A. Moran, P.J. Mago, L.M. Chamra, Thermoeconomic modeling of micro-CHP
tems operating during typical office hours was also performed. The (micro-cooling, heating, and power) for small commercial applications, Inter-
results demonstrate that, in general, the use of CHP–ORC reduces national Journal of Energy Research 32 (July (9)) (2008) 808–823.
[3] R. Possidente, C. Roselli, M. Sasso, S. Sibilio, Experimental analysis of micro-
the cost, PEC, and CDE for all the evaluated cities as compared with cogeneration units based on reciprocating internal combustion engine, Energy
the CHP operation. However, the use of both systems operating 24 h and Buildings 38 (2006) 1417–1422.
is not favorable when compared to the reference benchmark build- [4] J. Cao, F. Liu, Simulation and optimization of the performance in the air-
conditioning season of a BCHP system in China, Energy and Buildings 40 (2008)
ing; and, in general, it is more beneficial to operate the systems 185–192.
during typical office hours. The results highlight that, for all the [5] H. Ren, W. Gao, Economic and environmental evaluation of micro CHP systems
evaluated cities, the use of a CHP–ORC system reduces the cost, PEC, with different operating modes for residential buildings in Japan, Energy and
Buildings (2010), doi:10.1016/j.enbuild.2009.12.007.
and CDE for the same building operating solely with a CHP system.
[6] I. Malico, A.P. Carvalhinho, J. Tenreiro, Design of a trigeneration system using
For the 24 h a day operation, the average cost, PEC, and CDE reduc- a high-temperature fuel cell, International Journal of Energy Research (2008),
tions are 25.9%, 26.1%, and 26.5%, respectively. For the 12 h a day doi:10.1002/er.1430.
[7] J.R Khan, Modeling and experimentation of a novel pressurized CHP system
operation, the average cost, PEC, and CDE reductions are 19%, 19%,
with water extraction, International Journal of Energy Research 32 (11) (2008)
and 20%, respectively, and the fuel energy consumption is reduced 1030–1046.
by an average of 30%. Also, results showed that the CHP–ORC system [8] J.R. Khan, Modeling and optimization of a novel pressurized CHP system with
performance strongly depends on the location where it is installed. water extraction and refrigeration, International Journal of Energy Research 32
(8) (2008) 735–751.
This is due to the variations of the building’s thermal load, which is [9] H Li, L. Fu, K. Geng, Y. Jiang, Energy utilization evaluation of CCHP systems,
a result of the different weather conditions that the cities experi- Energy and Buildings 38 (2006) 253–257.
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019
G Model
ENB-2833; No. of Pages 8 ARTICLE IN PRESS
8 P.J. Mago et al. / Energy and Buildings xxx (2010) xxx–xxx
[10] P.J. Mago, N. Fumo, L.M. Chamra, Performance analysis of CCHP and CHP sys- [20] P.J. Mago, L.M. Chamra, K. Srinivasan, C. Somayaji, An examination of regen-
tems operating following the thermal and electric load, International Journal erative rankine cycles using dry fluids, Applied Thermal Engineering 28 (June
of Energy Research 33 (2009) 852–864. (8–9)) (2008) 998–1007.
[11] P.J Mago, L.M. Chamra, Analysis and optimization of CCHP systems based on [21] STIA-Holzindustrie Ges.m.b.H., Biomass-fired CHP Plant Based on an ORC,
energy, economical, and environmental considerations, Energy and Buildings Project ORC-STIA-Admont, Admont, March 2001.
41 (2009) 1099–1106. [22] I. Obernberger, P. Thonhofer, E. Reisenhofer, Description and evaluation of the
[12] E. Cardona, A. Piacentino, A methodology for sizing a trigeneration plant in new 1,000 kWel organic rankine cycle process integrated in the biomass CHP
Mediterranean areas, Applied Thermal Engineering 23 (2003) 1665–1680. plant in Lienz, Austria, Euroheat & Power 10 (2002).
[13] E. Cardona, A. Piacentino, Matching economical, energetic, and environmental [23] Department of Energy (DOE), Commercial Building Benchmark Models,
benefits: an analysis for hybrid CCHP–heat pump systems, Energy 31 (March Washington, DC, April 2009, 2008, Available from: http://www.eere.energy.
(4)) (2006) 490–515. gov/buildings/highperformance/benchmark.html.
[14] H Cho, R. Luck, S. Eksioglu, L.M. Chamra, Cost-optimized real-time operation of [24] P. Torcellini, et al., DOE commercial building benchmark models, in: ACEEE
CHP systems, Energy and Buildings 41 (2009) 445–451. 2008 Summer Study on Energy Efficiency in Buildings, NREL Confer-
[15] N. Fumo, P.J. Mago, L.M. Chamra, Hybrid-cooling, combined cooling, heat- ence Paper NREL/CP-550-43291, 2008, Available from: http://www.nrel.gov/
ing, and power systems, Journal of Power and Energy 223 (5) (2009) 487– docs/fy08osti/43291.pdf.
495. [25] EnergyPlus, Energy Simulation Software, March 2009. Available from:
[16] R. Chacartegui, D. Sánchez, J.M. Muñoz, T. Sánchez, Alternative ORC bottoming http://www.eere.energy.gov/buildings/energyplus/.
cycles FOR combined cycle power plants, Energy 86 (2009) 2162–2170. [26] American Society of Heating, Refrigerating and Air-Conditioning Engineers
[17] Y. Dai, J. Wang, L. Gao, Parametric optimization and comparative study of (ASHRAE), Energy Standard for Buildings Except Low-Rise Residential Build-
organic rankine cycle (ORC) for low grade waste heat recovery, Energy Con- ings, ANSI/ASHRAE/IESNA Standard 90.1-2007, Atlanta, GA, 2007.
version and Management 50 (2009) 576–582. [27] U.S. Department of Energy, Energy Information Administration, Glossary,
[18] A Schuster, S. Karellas, E. Kakaras, H. Spliethoff, Energetic and economic inves- March 2009. Available from: http://www.eia.doe.gov.
tigation of organic rankine cycle applications, Applied Thermal Engineering 29 [28] U.S. Department of Energy, Environmental Protection Agency, Energy Star Pro-
(2009) 1809–1817. gram, Target Finder, March 2009. Available from: http://energystar.gov/.
[19] P.J. Mago, L.M. Chamra, C. Somayaji, Analysis and optimization of organic rank- [29] Kohler Company, April 2009. Available from: http://www.kohlerpower.com/
ine cycles, IMechE Journal of Power and Energy 221 (3) (May 2007) 255–263. residential.
Please cite this article in press as: P.J. Mago, et al., Analysis and optimization of the use of CHP–ORC systems for small commercial
buildings, Energy Buildings (2010), doi:10.1016/j.enbuild.2010.03.019