“My fan isn’t performing, come fix it.”

“I ordered 3,000 cfm at 1 inch


Balancer said I have 2,500 at 3/4 inch.”

2
MEMBER

3
MEMBER

• Third party verification - Ethical practices

• State-of-the-art testing laboratory


“The AMCA International Certified Ratings Program”

• Information source
– Publications / Test Standards
– Seminars and service
– www.AMCA.org

4
MEMBER

• Look at Manufacturers’ printed catalogs


- is it the most current / recent? - check AMCA web site

• Do you use computer selection software?


- is it licensed / correct formulas? - check AMCA web site

AMCA International’s web site: www.amca.org

5
6
• Test arrangement - shown below cataloged performance data

– “Performance shown is for Type A, Free inlet, Free outlet”

– “Performance shown is for Type B, Free inlet, Ducted outlet”

– “Performance shown is for Type C, Ducted inlet, Free outlet”

– “Performance shown is for Type D, Ducted inlet, Ducted outlet”

• If belt driven - does it include drive losses?

7
MEMBER

Typical Commercial Ventilation

Free inlet, Free outlet (Type A)


8
MEMBER

Typical Commercial Ventilation

Free inlet, Ducted outlet (Type B)


9
MEMBER

Typical Commercial Ventilation

O ffice O ff ic e

Ducted inlet, Free outlet (Type C)


10
MEMBER

Typical Commercial Ventilation

Ducted inlet, Ducted outlet (Type D) 11


12
MEMBER

RPMNew
CFMNew = x CFMBase
RPMBase

2
RPMNew
SPNew = RPMBase x SPBase

3
RPMNew
BHPNew = RPMBase x BHPBase

13
MEMBER

0.7
700 RPM

0.6

0.5

0.4
P ressu re

0.3

0.2

0.1

0
0 2 4 6 8 10 12 14 16 18
CFM x 100

14
MEMBER

0.7

750 RPM
0.6
700 RPM

0.5
650 RPM

0.4
P ressu re

0.3

0.2

0.1

0
0 2 4 6 8 10 12 14 16 18
CFM x 100

15
MEMBER

1.4

1.2

B
1

0.8
P ressu re

0.6

0.4

A
0.2

0
0 5 10 15 20 25 30 35 40 45
CFM x 100

16
MEMBER

1.4

1.2

0.8
P ressu re

In
cr

Curve B
ea
si

0.6
ng
R
es

Curve A
is

0.4
t
an
ce
to

0.2
flo
w

0
0 2 4 6 8 10 12 14 16 18
CFM x 100

17
MEMBER

0.7

0.6
Fan Performance
Curve
0.5

0.4
P ressu re

0.3

Operating Point
0.2

System Resistance
0.1 Curve

0
0 2 4 6 8 10 12 14 16 18
CFM x 100

18
MEMBER

3.5

2.5
1400 RPM
2
P ressu re

1.5
Operating Point
at 1400 RPM
1

700 RPM
0.5 Operating Point
at 700 RPM

0
0 5 10 15 20 25 30 35 40 45
CFM x 100
19
MEMBER

3.5

2.5

Curve B
2
P ressu re

Curve A
1.5
Operating Point
Operating Point
on Curve B
on Curve B
1
Operating Point
Operating Point
on Curve A
0.5 on Curve A

0
0 5 10 15 20 25 30 35 40 45
CFM x 100

20
MEMBER

0.7

0.3
0.6
Fan Performance Curve
0.25
0.5

Brake Horse Power


0.2
0.4
Pressure

0.15
0.3

Brake Horsepower Curve


0.2 0.1

0.1 0.05

0 0
0 2 4 6 8 10 12 14 16 18

CFM x 100
21
MEMBER

0.7
Fan Performance Curve
0.3
0.6
Operating Point
0.25
0.5

Brake Horse Power


0.2
0.4
Pressure

0.15
0.3
Brake Horsepower Curve

0.2 0.1

0.1 0.05
System Resistance Curve

0 0
0 2 4 6 8 10 12 14 16 18

CFM x 100
22
23
MEMBER

24
MEMBER

25
MEMBER

26
MEMBER

OUTLET

VP = 1" VP = 0.85" VP = 0.7"

Note: 1) N’ = New fan speed to achieve design capacity


2) Velocity Pressure = (V/4005)²inch-wg.
V = fpm
3) Fan law
P1 / P2 = (N1/N2)³
P = Power (kW)
N = Fan speed (rpm) 28
MEMBER

INLET

VP = 1" VP = 0.75" VP = 0.6"

Note: 1) N’ = New fan speed to achieve design capacity


2) Velocity Pressure = (V/4005)²inch-wg.
V = fpm
3) Fan law
P1 / P2 = (N1/N2)³
P = Power (kW)
N = Fan speed (rpm) 29
MEMBER

Blast Area
Outlet Discharge
Cut off
Area Duct

25%

Centrifugal Fan 50%

75%

100% Effective Duct Length

Axial Fan

30
MEMBER

 Effective Duct Length = 2.5 Duct Diameters for


2,500 FPM or less

 Add 1 duct diameter for each additional 1,000


FPM

 For rectangular ducts, the equivalent duct


diameter is

4 x width x length
ð
31
MEMBER

FGH IJ K L M N O
5.0
P
4.0
Q

3.0
2.5
R 1
2.0 S

1.5
T

1.0 U
0.9
0.8
3 0.7
0.6 V

0.5
W
0.4

0.3
0.25 X
0.2

0.15

0.1
5 6 7 8 910 15 20 25 30 35 40 45

AIR VELOCITY, FPM IN HUNDREDS


2
3
(Air Density = 0.075 lbm/ft )
32
MEMBER

Axial Fan

100% Effective Duct Length

12% 25% 75% 100%


No Effective Effective Effective Effective
Duct Duct Duct Duct Duct
Tubeaxial Fan -- -- -- -- --
Vaneaxial Fan U V W -- --

33
MEMBER

FGH IJ K L M N O
5.0
P
4.0
Q

3.0 R
2.5
2.0 S

1.5
T

1.0 U
0.9
0.8
0.7
0.6 V

0.5
W
0.4

0.3
0.25 X
0.2

0.15

0.1
5 6 7 8 910 15 20 25 30 35 40 45

AIR VELOCITY, FPM IN HUNDREDS


)
3
(Air Density = 0.075 lbm/ft
34
Blast Area Outlet Discharge
Area Duct
Cutoff

100% Effective Duct Length

No 12% 25% 50% 100%


Duct Effective Effective Effective Effective
Duct Duct Duct Duct

Blast Area
System Effect Curve
Outlet Area
0.4 P R-S U W --
0.5 P R-S U W --
0.6 R-S S-T U-V W-X --
0.7 S U W-X -- --
0 8. T-U V-W X -- --
0 9. W W-X -- -- --
1 0. -- -- -- -- -- 35
MEMBER

Position C

Position D

Position B

Inlet
Position A
36
MEMBER

Outlet No 12% 25% 50% 100%


B las t A rea Elbow O utlet E ffec tive Effective E ffec tive Effective
O utlet A rea P os ition Duc t Duct Duct Duct Duct
A N O P -Q S
0.4 B M -N N O -P R-S
C L-M M N Q
D L-M M N Q
A O -P P-Q R T P o si tio n C
0.5 B N-O O-P Q S-T N
C M -N N O -P R-S O
P o s itio n D
D M -N N O -P R-S
A Q Q-R S U S
0.6 B P Q R T Y
C N-O O Q S S
D N-O O Q S T
P o sit io n B
A R-S S T V E
0.7 B Q -R R-S S -T U-V M
C P Q R-S T
D P Q R-S T E
A S S-T T-U W F
0.8 B R-S S T V F
C Q -R R S U-V E
D Q -R R S U-V C I nle t
P o s iti on A
A T T-U U-V W T
0.9 B S S-T T-U W
C R S S -T V F
D R S S -T V A
A T T-U U-V W C
1 B S-T T U W T
C R-S S T V O
D R-S S T V R 37
MEMBER

Tub eaxial Fan

10 0% Effective D uct Le ng th

V an eax ial Fan

100% Effective Duct Leng th

90o No 1 2% 2 5% 50 % 100 %
Elbow Duc t Effecti ve E ffe ctiv e E ffe ctiv e E ffec tive
D uct D uct D uct Du ct
Tub ea xia l Fan 2 & 4 pc. -- -- -- -- --
Vanea xia l Fa n 2 pc. U U-V V W --
Vanea xia l Fa n 4 p c. W -- -- -- --
38
MEMBER

Example Givens:
Centrifugal Fan
3,000 cfm at 1 inch static pressure
13 by 13 inch fan discharge / duct size
9 by 13 inch blast area
12 inch duct length

3,000 cfm / (13 x 13) / 144 = 2556 FPM


Effective duct length = 2.5 (2,500 FPM or less) + 1 duct for every
additional 1,000 FPM
Effective duct length = 2.5 + 1 = 3.5 ducts = 3.5 x 14.5 inches = 4 ft
Effective duct length is 4 feet
1 ft of duct length = 25% of the effective length
Blast Area / Outlet Area = (9 x 13) / (13 x 13) = 0.7
39
MEMBER

Blast Area Outlet Discharge


Area Duct
Cutoff

100% Effective Duct Length

No 12% 25% 50% 100%


Duct Effective Effective Effective Effective
Duct Duct Duc t Duct

Blast Area
System Effect Curve
Outlet Area
0.4 P R-S U W --
0.5 P R-S U W --
0.6 R-S S-T U-V W-X --
0.7 S U W-X -- --
0.8 T-U VW X -- --
0.9 W-W W-X -- -- --
1.0 -- -- -- -- --
40
MEMBER

FGH IJ K L M N O
5.0
P
4.0
Q

3.0 R
2.5
2.0 S

1.5
T

1.0 U
System Effect Factor 0.9
0.8
(no duct) = 0.65 inches 0.7
0.6 V

0.5
W
0.4
Less system effect with
0.3
25% effective duct 0.25 X
length 0.2

0.15

0.1
5 6 7 8 9 10 15 20 25 30 35 40 45

AIR VELOCITY, FPM IN HUNDREDS


3
(Air Density = 0.075 lbm/ft )
41
MEMBER

Length
of D uct

Inlet with 3-piece Inlet with rectangular Inlet with special


elbow inlet Duct designed inlet box

42
MEMBER

System Effect Curves System Effect Curves

R/D No 2D 5D R/D No 2D 5D
Duct Duct Duct Duct Duct Duct
0.5 O Q S 0.5 P-Q R-S T
System Effect Curves
0.75 Q R-S T-U 0.75 Q-R S U
R/D No 2D 5D
Duct Duct Duct 1.0 R S-T U-V 1.0 R S-T U-V
-- N P R-S 2.0 R-S T U-V 2.0 R-S T U-V
3.0 S T-U V 3.0 S-T U V-W

D D D

Length Length Length


of Duct of Duct of Duct

R R
R

4 or more piece
2 piece mitered 3 piece mitered
mitered round
round section round section
section 43
MEMBER

FGH I J K L M N O
5.0
P
4.0
Q

3.0 R
2.5
2.0 S

1.5
T

1.0
Any velocity greater 0.9
U
0.8
than 1500 fpm would 0.7
0.6 V
develop a system 0.5
effect 0.4 W

0.3
0.25 X
0.2

0.15

0.1
5 6 7 8 9 10 15 20 25 30 35 40 45

AIR VELOCITY, FPM IN HUNDREDS


3
(Air Density = 0.075 lbm/ft )
44
MEMBER

45
MEMBER

S ystem Effect C urve s System E ffect C urves S ystem E ffect C urves

R /D No 2D 5D R /D No 2D 5D R /D No 2D 5D
D u ct D uct D uct D uct Duct D uct D uct D uct D uct
0.5 O Q S 0.5 S T-U V 0.5 S T -U V

0.75 P R S -T 1.0 T U -V W 1.0 T U -V W

1.0 R S-T U -V 2.0 V V-W W -X 2.0 V V -W W -X


2.0 S T-U V

H H H
Square S qua re S quare

Len g th Len gth Le ng th


of D u ct of D uct of D uct

R R R

46
MEMBER

Pre-Rotation Counter-Rotation

47
MEMBER
Inlet Swirl

48
MEMBER

Calculated duct system

Design
Pressure Fan pressure-volume curve

Design Volume
49
MEMBER

Actual duct system


with system effect
Calculated duct system
with no allowance for
system effect

4
System effect at
actual flow volume System effect loss
3 at design volume
1
22 New Fan Curve

Design Pressure Original Fan Curve

Deficient Volume Performance

Design Volume
50
 Minimum 2.5 duct diameters on Outlet
 Minimum 5 to 8 duct diameters on Inlet
 Avoid inlet swirl

 If any of these general rules are broken, make


sure to take system effect into account.

51
MEMBER

C-D duct friction 750 Pa (duct design)


A free inlet 0 Pa (no SEF)
B-C outlet with straight duct attached
for 2 or more dia. 0 Pa (no SEF)
--------------------------------
REQUIRED Fan Ps 750 Pa
52
MEMBER

E-F duct friction at 5000CMH (Q) 750 Pa (duct design)


E contraction loss-plenum to duct 50 Pa (part of duct system)
E Ps energy required to create velocity at E 125 Pa (part of duct system)
D Pv loss (also Pt loss) at D as result of air velocity decrease 0 Pa
Ps does not change from duct to plenum at D
C-D outlet duct on fan as tested 0 Pa
--------------------
REQUIRED Fan Ps 925 Pa 53
MEMBER

D-E duct friction at 5000CMH (Q) 750 Pa (duct design)


D contraction loss-plenum to duct 50 Pa (part of duct system)
D Ps energy required to create velocity at D 125 Pa (part of duct system)
B-C SEF 150 Pa
B-C Pv loss (also Pt loss) at C as result of air velocity decrease 0 Pa
Ps does not change from duct to plenum at C
------------------
REQUIRED Fan Ps 1075 Pa
54
MEMBER

A Entrance loss-sharp edge duct 100 Pa (duct design)


A-B Duct friction at 5000CMH 750 Pa (duct design)
B SEF 1 150 Pa
C SEF 2 50 Pa
E Fan Pv 125 Pa
E SEF 3 150 Pa
------------------
REQUIRED Fan Pt 1325 Pa

Fan Ps = fan Pt – fan Pv


Fan Ps = 1325 Pa – 125 Pa
Fan Ps = 1200 Pa

55
MEMBER

1 2 3 4

Wide product Technical Proper


High range – to support – to system
efficient fan meet different ensure a good
operation match of fan design and
point and system TAB

56