DYNALCO
strategic asset management solutions
Two-Setpoint
Speed Switch
2-Year
Warranty
DYNALCO 3690 N.W. 53rd Street • Fort Lauderdale, FL 33309 USA • Ph: 954.739.4300 • Fax: 954.484.3376 • www.dynalco.com
DYNALCO
strategic asset management solutions
when speed is reduced by at least 2% below setpoint governor. (No shield terminal is provided in the speed
value. switch.)
Power up considerations: No relay flicker on power Test: Jumpering Terminal 5 to Terminal 2 lowers the
up. At stand-still or speeds below setpoints, applying setpoints to 90% ±2% of the actual value to permit
dc power causes no flicker or change in the normally verifying the alarm setpoints without overspeeding
de-energized Auxiliary relay. Power application resets the engine.
the Overspeed relay to the normally energized (no Stability of setpoints:
alarm) condition. a. Signal amplitude effect: ±0.5% full-scale from
Grounding, phase referencing: All circuits are 150 mVrms to 100 Vrms.
isolated from earth ground. The input circuit is b. Power supply voltage effect: ±0.1% of full-scale
referenced to the negative side of the power supply so with 25% supply fluctuation.
that the magnetic pickup can be paralleled with c. Temperature effect: ±2.5% of full-scale
electrical governors and other similarly constructed maximum with change in enviromental temperature
devices. from –40oC to +85oC (–40oF to +185oF).
Signal cable shield: can be grounded directly or Hysteresis: 2% of full-scale frequency, nominal.
taken to any designated electrical terminal on the
3.12 3.75
(7.9) (9.5)
2.00
(5.1)
.25
(.64)
DYNALCO 3690 N.W. 53rd Street • Fort Lauderdale, FL 33309 USA • Ph: 954.739.4300 • Fax: 954.484.3376 • www.dynalco.com