MM200A
Contact Resistance Test System
Model : MM 200A
www.agm-power.com
0 MM 200A_UM_ v 1.1
CONTENTS
1. Safety Regulations 2
2. Introduction 3
2.1 Application & Design
3. Description 4
4. Display Settings 6
5. Operation 8
Model : MM 200A
6. Application Example 9
6.1 Testing a Circuit Breaker
6.2 Testing Bus-bar Joints
7. Troubleshooting 10
8. Specifications 11
www.agm-power.com
1 MM 200A_UM_ v 1.1
1. SAFETY REGULATIONS
This equipment should only be used by a well trained personnel
instructed in the safe operation of the equipment under test.
Model : MM 200A
panel. Always connect the separate earth (ground) binding post
located on the front panel to earth (ground).
IMPORTANT!
WARNING!
UNPLUG the MM200A from the supply before cleaning. Only use
a damp cloth. Do not use any liquid cleaners aerosol cleaners.
DO NOT attempt to service the unit. Opening the front cover will
expose the user to dangerous voltage and other hazards.
www.agm-power.com
2 MM 200A_UM_ v 1.1
2. INTRODUCTION
2.1 Application & Design
Model : MM 200A
The MM200A is equipped with a built-in Ammeter. The Resistance is
calculated via voltage drop measurement and shown on the display.
NOTE!
www.agm-power.com
3 MM 200A_UM_ v 1.1
3. DESCRIPTION
Current
Sensing
5
4
Ω
Model : MM 200A
2
O
I
1. LCD Display
2. Control Module
‘SEL’ – Test Current Range (100A / 200A / Factory
Preset ‘10A’ )
‘TEST’ – Calculate Resistance Value at Selected Test
Current Range
‘RST’ – Timer Reset
‘I/O’ – ON/OFF Current Output
3. Variable Current Injection Knob
4. DC Current Source (Output)
5. Voltage Sensing Channel (Input)
www.agm-power.com
4 MM 200A_UM_ v 1.1
Output DC current and measured resistance are displayed on a
backlit LCD
IMPORTANT!
Model : MM 200A
For safety purpose, should the MM200A is accidently left
unattended during current injection, the MM200A is designed to
automatically turn OFF if the injection period is longer than 2
minutes. To resume current injection, select ‘I/O’.
Note: The manufacturer and distributor shall not be liable for any
accidents or injuries caused by inappropriate or incorrect use of
this test equipment.
www.agm-power.com
5 MM 200A_UM_ v 1.1
4. DISPLAY SETTINGS
Model : MM 200A
Display shown during power up.
SEL – Press ‘▲/▼’ button to select the test current (100A / 200A /
Factory Preset ‘10A’ )
www.agm-power.com
6 MM 200A_UM_ v 1.1
Selection of 200Adc
Model : MM 200A
SEL – Press ‘▲/▼’ button to select the test current (100A / 200A /
Factory Preset ‘10A’ )
Selection of 10Adc
SEL – Press ‘▲/▼’ button to select the test current (100A / 200A /
Factory Preset ‘10A’ )
www.agm-power.com
7 MM 200A_UM_ v 1.1
5. OPERATION
This equipment should only be used by a well trained personnel
instructed in the safe operation of the equipment under test.
Model : MM 200A
3. Set the current adjustor knob to zero position.
4. I/O – Select ‘I/O’ to begin current injection.
5. Rotate variac until current value on display shows selected test
current.
6. TEST – Select ‘TEST’ to view resistance value.
7. Rotate the current adjustor knob back to zero position.
8. RST – Reset values.
CAUTION!
IMPORTANT!
www.agm-power.com
8 MM 200A_UM_ v 1.1
6. APPLICATION EXAMPLE
6.1 Testing a circuit breaker
Model : MM 200A
test current setting. (100A / 200A / Factory Preset ‘10A’)
6. Select ‘TEST’ to retrieve the resistance value.
www.agm-power.com
9 MM 200A_UM_ v 1.1
7. TROUBLESHOOTING
Model : MM 200A
above 0 %
Current cables open Check circuit and
circuit ensure closed loop
between test set and
equipment under test
Internal circuit Select ‘I/O’ to OFF.
overheat above 85°C Allow unit to cool
down.
*Caution – output
source will
automatically resume
when unit
temperature
decreases below
85°C
Fuse F1 or F2 trip Reset fuse F1 of F2
by pushing down on
F1 or F2 fuse.
www.agm-power.com
10 MM 200A_UM_ v 1.1
8. SPECIFICATIONS
Operation Duty Cycle ( ON circuit / OFF circuit ) Open Circuit Voltage
100 A dc 5 min / 15 min 9V
200 A dc 5 sec / 15 min 9V
Measurement
DC Current Range Resistance Range Accuracy :
(1A Resolution) ±1% of metering
10A 0 – 300 mΩ (0.01 mΩ Resolution)
100A 0 – 50 mΩ (1 μΩ Resolution)
200A 0 – 25 mΩ (1 μΩ Resolution)
Communication
RJ 45 network port
Model : MM 200A
General
Mains Voltage 220 – 260 VAC , 50 / 60 Hz
Operating Temperature 0 – 55 °C , 5 - 95% R.H., non-condensing
Dimensions 32 cm x 23 cm x 29 cm
Weight 15 kg
The test set has been designed to incorporate EN 61010-1 specifications to
Safety
Safety Class 1 & Installation Category 2
Calibration Certificate of calibration with data provided, traceable to NML standards
Accessories
Mains Cable 1 x 4m Ground Cable
2 x 3.5m Sensing Cable c/w Crocodile Clips 2 x 3.5m Current Cable c/w Crocodile Clips
www.agm-power.com
11 MM 200A_UM_ v 1.1