Sei sulla pagina 1di 12

THERMAL OVERLOAD RELAYS

MN1 to MN5 Page MN12 to MN12 L Page

General Information 7/1 General Information 7/2

Accessories 7/3 Accessories 7/3

Technical Data 7/5 Technical Data 7/5

Characteristic Curves 7/7 Characteristic Curves 7/7

7 Overall Dimensions 7/9 Overall Dimensions 7/9

ML0 to ML3 Page

General Information 7/4

Accessories 7/4

Technical Data 7/6

Characteristic Curves 7/8

Overall Dimensions 7/10,7/11


THERMAL OVERLOAD RELAYS - TYPE MN
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1

✦ Relays with single phase protection.


✦ Built-in ‘Start’ and ‘Off/Reset push buttons eliminates the requirement of additional actuators.
✦ An auto-manual slide facilitates conversion from auto-reset mode to manual reset and vice-versa.
✦ Relays are compensated for variation in ambient temperatures from -50C to +550C.

For Contactor Setting Wt Qty Catalogue No.


type Range approx. per per
relay Packing
A [[Kg]] [No.]

For mounting onto contactors

MN9 0.67-1.0 0.18 10 ST26746OOKO


MN12 1.0-1.5 ST26746OOMO
MN16 1.4-2.1 ST26746OONO
1.8-2.7 ST26746OOPO
2.4-3.6 ST26746OOFO
3.5-5.0 ST26746OOGO
4.0-6.0 ST26746OOTO
5.5-8.5 ST26746OOUO
MN1 8.5-12.5 ST26747OOAO 7
12.5-18.0 ST26747OOCO

MN9 0.2-0.3 0.2 10 SS94141OOEO


MN12 0.3-0.5 SS94141OOGO
MN16 0.45-0.75 SS94141OOJO
MN25 0.6-1.0 SS94141OOKO
MN32 0.9-1.5 SS94141OOMO
ML01) 1.4-2.3 SS9414OOPO
ML11) 2.0-3.3 SS94141OOQO
ML1.5 1)
3.0-5.0 SS94141OOSO
4.5-7.5 SS94141OOUO
6.0-10 SS94142OOVO
MN2 9.0-15 SS94142OOBO
14-23 SS94144OODO
20-33 SS94145OOEO

MN45 20-33 0.5 10 SS94136OOEO


MN65 30-50 SS94136OOGO
MN802) 45-75 SS94137OOJO
MN952) 66-110 SS94137OOKO
MN1402)
ML23)
ML33)
ML43)
ML63)
MN5

1) Kit SS94701OOOO available for mounting.


2) Kit SS94638OOOO available for mounting.
3) Kit SS94151OOOO available for mounting.

7/1
THERMAL OVERLOAD RELAYS - TYPE MN
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1

✦ Relays with single phase protection.


✦ An auto-manual slide facilitates conversion from auto-reset mode to manual reset and vice-versa.
✦ Relays are compensated for variation in ambient temperatures from -50C to +550C.
✦ Single CT assembly.
✦ Provision of versatile location of links.
✦ Provision for using system cable as primary.
✦ Suitable for applications on loads with high inertia or large gyrating mass.
✦ Trip class 30 for motors with long starting time for MN12L relay.

For Contactor Setting Wt Qty Catalogue No.


type Range approx. per
Packing
A [Kg] [No.]

For mounting onto contactors

MN185 42-69 2.9 1 SS94138OOHO


MN225 60-100 SS94138OOKO
MN265 90-150 SS94138OOMO
MN325 135-225 SS94138OOPO

7 MN400
ML10
180-300
270-450
SS94139OOQO
SS94139OORO
ML12

MN12

MN185 42-69 2.9 1 SS94127OOHO


MN225 60-100 SS94127OOKO
MN265 90-150 SS94127OOMO
MN325 135-225 SS94127OOPO
MN400 180-300 SS94127OOQO
ML10
ML12
MN12L

7/2
ACCESSORIES
Accessories For Relay type Qty Wt Catalogue No.
Type per approx. per
Packing accessory
[No.] [Kg]

Push- button unit MN2 20 0.01 SS94001OOOO


MN5
MN12
MN12L

Mounting kit

MN21) 50 0.04 SS94701OOOO

Mounting kit

MN22) 50 0.05 SS94700OOOO

DIN Rail mounting kit MN2 50 0.06 SS91887OOOO

Mounting kit 7

MN53) 50 — SS94638OOOO

Mounting kit

MN54) 50 0.025 SS94151OOOO

Mounting kit

MN55) 50 0.1 SS94152OOOO

1) For mounting MN2 relay on ML0,ML1,ML1.5 Contactor.


2) For mounting MN2 relay separately (Direct mounting type).
3) For mounting MN5 relay on MN80,MN95,MN110,MN140 Contactor.
4) For mounting MN5 relay on ML2,ML3 Contactor.
5) For mounting MN5 relay on ML4, ML6 Contactor.
7/3
THERMAL OVERLOAD RELAYS - TYPE ML
✦ Built-in ‘Start’ and ‘Off/Reset push buttons eliminates the requirement of additional actuators.
✦ Relays are compensated for variation in ambient temperatures from -50C to +550C.

For Contactor Setting Wt Qty Catalogue No.


type Range approx. per per
relay Packing
A [Kg] [No.]

For mounting onto contactors

ML0 0.15-0.25 0.22 10 SS91858OODO


ML1 0.25-0.40 SS91858OOFO
ML1.5 0.4-0.65 SS91858OOHO
0.6-1.0 SS91858OOKO
1.0-1.6 SS91858OOMO
1.5-2.5 SS91858OOPO
2.5-4.0 SS91858OORO
ML0/ML1/ML1.5 4.0-6.5 SS91858OOTO
6.0-10. SS91858OOVO
10.0-16.0 SS91858OOBO

ML2 9.0-14.0 0.33 2 SS91859OOAO


ML3 13.0-21.0 SS91859OOCO

7 20.0-32.0
28.0-42.0
SS91859OOEO
SS91859OOFO

ML2/ML3

ACCESSORIES
Accessories For Relay type Qty Wt Catalogue No.
Type per approx. per
Packing accessory
[No.] [Kg]

Push- button unit ML0 20 0.01 SS90004OOOO


ML1
ML1.5
ML2
ML3

7/4
TECHNICAL DATA FOR THERMAL OVERLOAD RELAYS
MN1/2/5/12/12L

MN1 MN2 MN5 MN12 MN12L

Rated insulation voltage, 7i 690V 690V 690V 690V 690V

Rated impluse strenght, 7imp 6KV 6KV 6KV 6KV 6KV

Service temperature o
C -5 to +55 -5 to +55 -5 to +55 -5 to +55 -5 to +55

Rated thermal current Ith


at 415V,50Hz A 6 6 6 6 6

Rated operational current for AC-15


utilization category at 50Hz 24V 6A 6A 6A 6A 6A
110V 5A 5A 5A 5A 5A
220V 3A 3A 3A 3A 3A
380/415V 2A 2A 2A 2A 2A
500V 2A 2A 2A 2A 2A

Built in contacts 1 Start/Reset 1 Start 1 Start 1 Start 1 Start


1 Off 1 Off/ Reset 1 Off/ Reset 1 Off/ Reset 1 Off/ Reset
1 NO+ 1NC 1 Alarm(NO) 1 Alarm(NO) 1 Alarm(NO) 1 Alarm(NO)
7
Tripping class A 10 10 10 10 30

Max. frequency of operation


op.cycles/hr 30 30 30 30 30

Main terminal capacity Lug(mm2) 10 10 50 240 240

Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 2x2.5 2x2.5

7/5
TECHNICAL DATA FOR THERMAL OVERLOAD RELAYS
ML0/1/1.5/2/3

ML0/1/1.5 ML2/3

Rated insulation voltage 7i 500V 500V

Rated impluse strenght 7imp 6KV 6KV

Service temperature o
C -5 to +55 -5 to +55

Rated thermal current Ith


at 415V,50Hz A 6 6

Rated operational current for AC-15


utilization category at 50Hz 24V 6A 6A
110V 5A 5A
220V 3A 3A
380/415V 2A 2A
500V 2A 2A

Built in contacts 1 Start 1 Start


1 Off/ Reset 1 Off/ Reset
7 1 Alarm(NO) 1 Alarm(NO)

Tripping class 10A 10A

Max. frequency of operation


op.cycles/hr 30 30

Main terminal capacity Lug(mm2) 16 50

Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5

7/6
I-T CHARACTERISTICS
3 POLE BALANCED LOADING CONDITION

MN1 RELAY MN2/5/12 RELAY

MN12L RELAY

7/7
I-T CHARACTERISTICS
3 POLE BALANCED LOADING CONDITION

Multiples of set current Multiples of set current

ML1 (upto 6-10 Amps) ML1 (upto 10-16 Amps)

Multiples of set current

ML2 / 3

7/8
OVERALL DIMENSIONS

MN1 RELAY MN2 RELAY

MN5 RELAY MN 12/12L RELAY

Note: All dimensions are in mm.


7/9
OVERALL DIMENSIONS

ML1 RELAY

Note: All dimensions are in mm.


7/10
OVERALL DIMENSIONS

ML2/3 RELAY

Note: All dimensions are in mm.


7/11