Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Abstract—Significant changes have occurred in the protection of A. Improved sensitivity and security—in protection areas
generators in the past ten years as discussed in IEEE guide C-37.102. where older relaying does not provide the level of
[1]. This paper discusses these changes as well as the risks of not detection required. Examples of protection in this area are
addressing them. It specifically addresses the risks in two functional the following:
areas where 20+-year-old generator protection is inadequate. These
1. 100% Stator Ground Fault Protection
areas include: sensitive stator ground fault protection using schemes to
provide 100% winding ground detection, field ground fault protection, 2. Field Ground Fault Protection
and inadvertent (accidental) generator off-line energizing protection. 3. Enhancing Generator System Backup Security
Most of these upgrade schemes were made possible through the use of B. New or additional protection—areas that twenty years
digital protection. ago were not perceived to be a problem, but operating
experiences have since proved otherwise. One key area is
inadvertent generator energizing.
I. INTRODUCTION
Contrary to popular belief, generators do experience short III. IMPROVED SENSITIVITY AND SECURITY
circuits and abnormal electrical conditions. In many cases,
equipment damage due to these events can be reduced or A. 100% Stator Ground Fault Protection
prevented by proper generator protection. As generators Three basic methods of 100% stator ground fault protection
become older, the likelihood for failure increases as insulation are widely used to provide ground fault protection over the
begins to deteriorate. Generators, unlike some other power entire stator winding. Two methods use the 3rd harmonic
system components, need to be protected not only from short detection while a third method uses an injection of a sub-
circuits, but also from abnormal operating conditions. harmonic signal at the stator neutral. This is an important
Examples of such abnormal conditions are overexcitation, upgrade area because older generators do not have stator
loss-of-field, unbalanced currents, and abnormal frequency. ground fault protection for fault over the entire stator winding.
When subjected to these conditions, damage or complete
failure can occur within seconds, thus requiring automatic 1. 100% Stator Ground Fault Protection Using
detection and tripping. 3rd Harmonic Neutral Undervoltage Methods
In the late 1980's, the IEEE Power System Relay The most widely used conventional stator ground fault
Committee first issued its ANSI/IEEE C37.102 [Ref. 1] guide protection scheme in high impedance-grounded systems is a
for the protection of synchronous generators. This guide time-delayed overvoltage relay (59N) connected across the
outlines current recommended practices for the protection of grounding resistor to sense zero-sequence voltage as shown in
generators and documents the substantial changes that have Fig 1. The relay used for this function is designed to be
occurred in generator protection over the last twenty years. sensitive to fundamental frequency voltage and insensitive to
These changes fall into two broad categories: improved third harmonic and other zero sequence harmonic voltages that
sensitivity and security as well as new protection areas. These are present at the generator neutral. Typically, this overvoltage
are the key functional areas that need to be addressed when relay has a minimum pickup setting of approximately 5 V.
developing an upgrade program to bring the generator With this setting and typical grounding transformer ratios, this
protection up to current industry standards. relay is not capable of detecting faults over the entire stator
winding as shown in Fig. 1 with typical 90-95% winding
coverage.
II. AREAS OF PROTECTION UPGRADE It is important to protect major generators with an
ON OLDER GENERATORS additional ground fault protection system so that fault
coverage for 100% of the winding is obtained. Generators that
The areas of upgrade on generator protection that are are twenty years old or older typically have only 90-95% of
twenty years old or more fall into two broad categories: the stator winding protected for ground faults. One of the 3rd
harmonic methods uses a 3rd harmonic undervoltage relay
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on July 20, 2009 at 01:44 from IEEE Xplore. Restrictions apply.
connected as illustrated in Fig.2. Third-harmonic voltages are
present at the neutral of most generators to varying degrees—
it varies due to differences in stator winding pitch, machine
load and power factor. If present in a sufficient amount, this
voltage can be used to detect stator ground faults near the
generator neutral. For faults near the neutral, the level of 3rd
harmonic voltage measured at the neutral decreases.
467
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on July 20, 2009 at 01:44 from IEEE Xplore. Restrictions apply.
subharmonic injection scheme that is widely used in Europe recent price reductions in the cost of the injection equipment
but not used much in North America. The scheme shown in have made this an attractive choice for many users.
Fig. 5 provides full coverage of the entire stator winding. It
also provides off-line detection of stator ground faults. The
Natural Capacitance
V
*
5 9ground
other N C ovoltage
n v e nelements
tio n a l P ro te c tio n
Notes:
Subharmonic injection typically at 15-20 Hz
Coupling filter low pass or notch tuned for subharmonic frequency
Measurement inputs tuned to respond to subharmonic frequency
468
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on July 20, 2009 at 01:44 from IEEE Xplore. Restrictions apply.
B. Field Ground Fault Detection (64F) recently, it was not available in a multifunction relay. As
The field circuit of a generator is an ungrounded (typically illustrated in Fig. 7, a 15-volt square wave signal is injected
600- 800 V) dc system, as shown in Fig. 6. into the field through a coupling network. The return signal
waveform is modified due to field winding capacitance. The
injection frequency setting is adjusted (0.1 to 1.0 Hz) to
compensate for field winding capacitance. From the input and
return voltage signals, the relay calculates the field insulation
resistance. The relay setpoints are in ohms, typically with a 20
K ohm and a 5 K ohm critical alarm or trip.
The injection scheme provides a major improvement over
traditional voltage schemes in terms of both sensitivity as well
as security. In addition, digital relays can provide real-time
monitoring of field insulation resistance so deterioration with
time can be monitored. The scheme can also detect grounds on
an off-line generator, allowing the operator to determine if the
field circuitry is free of a ground before start-up. An added
benefit of the injection scheme described above is that it
operates at a low voltage (15 V) compared to the scheme it
Fig. 6 A Basic Generator Field Circuit
typically replaces (120 V), thus improving operator safety
when changing brushes with the unit on-line.
A single field ground fault generally will not affect the
operation of a generator, nor will it produce any immediate
damaging effects. However, the probability of a second
ground fault occurring is greater after the first ground fault has
established a ground reference. When a second ground fault
occurs, a portion of the field winding will be short-circuited,
thereby producing unbalanced air gap fluxes in the machine.
These unbalanced fluxes produce unbalanced magnetic forces,
which result in machine vibration. A field ground fault also
produces rotor iron heating from the unbalanced short circuit
currents. The tripping practices within the industry for field
ground relaying are not well established. Some users trip
while others prefer to alarm, thereby risking a second ground
fault and major damage before the first ground is cleared.
The existing practice within the industry has been to use
voltage detection systems. These voltage schemes have been
prone to false operation—especially during start-up. Unit
operators routinely reset the alarm and continue with start-up
procedures. If a persistent alarm occurred, operators attempted
to locate the problem. If the ground could not be found within
a reasonable time, the unit was supposed to be tripped
manually. However, the many nuisance alarms and the very
few legitimate ones caused some unit operators to lose
confidence in the field ground voltage scheme. Therefore, the
alarm lost credibility. Operators continued to keep the units
on-line, hoping that a second ground would not occur.
Catastrophic rotor failures have occurred due to a second
ground in the field developing very quickly after the first Fig. 7 Field Ground Protection Using an Injection Voltage Signal
ground. In these instances, the operators were not able to
isolate the cause of the first alarm, nor were they able to bring C. Enhancing Generator System Backup Security (21-2)
the units off-line in an orderly fashion before the second A mho distance relay characteristic is commonly used to
ground occurred. detect system phase faults and to trip the generator after a set
Clearly, a more secure field ground relay is desirable if time delay. These relays, however, have frequently operated
automatic tripping is being considered. Such a relay is shown improperly during major system disturbances—unnecessarily
in Fig. 7 and uses an injection principle. This principle has tripping generators and thereby exacerbating the disturbance.
been widely used in Europe with great success, but until This was the case during the 1996 West Coast blackout.
469
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on July 20, 2009 at 01:44 from IEEE Xplore. Restrictions apply.
Investigation revealed that these relays were improperly set 3. 80 to 90% of generator load impedance at the
for the system conditions they encountered and were expected maximum torque angle of the 21-2 impedance relay
to “ride through.” They operated due to stable power swings setting (typically 85°).
or load encroachment during low system voltage conditions. The capability curve for the generator and settings are
The IEEE Power System Relay Committee, through the plotted on the R-X diagram as shown in Fig. 8. The time delay
latest revision of C-37.102 [1], provides guidance on setting for the 21-2 relay should be set longer than the transmission
this relay. The relay’s impedance reach and delay settings lines’ backup and breaker failure protection with an
must be coordinated with transmission backup protection and appropriate margin for proper coordination.
breaker failure to allow selectivity. Typically, the phase To enhance security and safe load margins while still
distance relay’s reach begins at the generator terminals and providing the necessary 21-2 relay reach, it is possible to use
ideally extends to the length of the longest line out of the both load encroachment and out-of-step blocking techniques.
power plant transmission substation. Some factors impacting Out-of-step blocking uses a 21-3 impedance element that
the settings are as follows: completely surrounds the 21-2 trip element to provide
1. In-feeds: Apparent impedance due to multiple in- blocking logic.
feeds will require larger reaches to cover long lines and will
overreach adjacent shorter lines. The apparent impedance
effect occurs because the generator is only one of several
sources of fault current for a line fault. This causes the ohmic JX
value of the faulted line to appear further away and require a Z2 Reach 120% of Longest Line but
Must be Less then 80 to 90%
larger ohmic setting to cover faults at the remote end of the Z2
of Capability Curve
line.
2. Transmission System Protection: If the transmission Generator
Capability
lines exiting the power plant have proper primary and backup Curve
protection, as well as local breaker failure, the need to set the Max.
21-2 generator relay to respond to faults at the end of the Torque
Angle
longest lines is mitigated since local backup has been provided Z1
470
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on July 20, 2009 at 01:44 from IEEE Xplore. Restrictions apply.
Z 3 out of step blocking
widely used to detect inadvertent energizing is the voltage-
JX
Z3 supervised overcurrent scheme shown in Fig. 10. An
Z2 Reach 120% of Longest Line but undervoltage element with adjustable pickup and dropout time
Must be Less then 80 to 90%
Z2
of Capability Curve
delays supervises an instantaneous overcurrent relay. The
undervoltage detectors automatically arm the overcurrent
Generator tripping when the generator is taken off-line. The undervoltage
Capability
Curve detector will disable or disarm the overcurrent relay when the
Max. machine is returned to service. Great care should be taken
Torque
Angle Z2 Reach at 50 to 67% of when implementing this protection, so that the dc tripping
Generator Capability Curve
Z1 power and relay input quantities to the scheme are not
Load Encroachment
Blocking
removed when the generator is off-line.
RPFA
471
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on July 20, 2009 at 01:44 from IEEE Xplore. Restrictions apply.