YCIV0600SE-YCIV1500SE & YCIV0590HE-YCIV1380HE

ENGINEERING GUIDE Revision 3 Form 201.26 EG 03 (GB 0508)

AIR-COOLED SCREW LIQUID CHILLERS


STYLE A
(541-1405 KW)
SE - STANDARD EFFICIENCY & HE - HIGH EFFICIENCY

Symphony

R134a
Form No. 201.26 EG 03 (GB 05/08)
CONTENTS Operating Limitations . . . . . . . . . . . . . . .23

Features. . . . . . . . . . . . . . . . . . . . . . . 3 Standard Efficiency (SE/SERS) - Capacities . . .24

Variable Speed Drive Chiller History . . . . . . . 4 Standard Efficiency (SELS) - Capacities . . . . .26

Nominal Data . . . . . . . . . . . . . . . . . . . . 5 Standard Efficiency (SELS) - Capacities . . . . .28

Specification . . . . . . . . . . . . . . . . . . . . 6 High Efficiency (HE/HERS) - Capacities . . . . .30

End of Line Test and Quality Plan . . . . . . . . . 9 High Efficiency (HELS) - Capacities . . . . . . .32

Accessories and Options . . . . . . . . . . . . . 9 High Efficiency (HELS) - Capacities . . . . . . .34

Refrigerant Flow Diagram . . . . . . . . . . . . .11 Sound Data SE/SERS & HE/HERS . . . . . . . .36

Component Locations . . . . . . . . . . . . . . .12 Sound Data SELS & HELS . . . . . . . . . . . . .37

Chiller Control Logic . . . . . . . . . . . . . . . .13 Standard Efficiency Chillers - Physical Data . . .38

Application Data . . . . . . . . . . . . . . . . . .14 High Efficiency Chillers - Physical Data . . . . .39

Outdoor Installations Standard Efficiency Chillers - Electrical Data . .40

Indoor Installations High Efficiency Chillers - Electrical Data . . . .40

Operating in Low Ambient Conditions 2 System Electrical Data (Standard Efficiency) .41

Ductwork Connection 3 System Electrical Data (Standard Efficiency) .42

Location Clearances 2 System Electrical Data (High Efficiency) . . . .43

Location Clearances . . . . . . . . . . . . . . . .16 3 System Electrical Data (High Efficiency) . . . .44

Vibration Isolators YCIV0590HE, 0600SE, 0650SE - Dimensions . . .45

Chilled Liquid Piping YCIV0630HE, 0720SE, 0770SE - Dimensions . . .46

Pipework Arrangement YCIV0700HE, 0760HE, 0840SE - Dimensions . . .47

Cooler Connections YCIV0800HE, 0920SE - Dimensions . . . . . . . .48

Option Flanges YCIV0830HE, 0930HE, 1000SE - Dimensions . . .49

WaterTreatment YCIV1050HE - Dimensions. . . . . . . . . . . . .50

Refrigerant Relief Valve Piping YCIV1070SE - Dimensions . . . . . . . . . . . . .51

Electrical Connection . . . . . . . . . . . . . . .19 YCIV1120HE - Dimensions. . . . . . . . . . . . .52

Power Wiring YCIV1180SE - Dimensions . . . . . . . . . . . . .53

115 Vac Control Supply Transformer YCIV1220HE, 1340SE - Dimensions . . . . . . . .54

Control Panel Wiring YCIV1380HE, 1500SE - Dimensions . . . . . . . .55

Chiller Selection Data . . . . . . . . . . . . . . .21 Electrical Cable Entry . . . . . . . . . . . . . . .56

Selection Guide Chilled Water Chillers Desuperheater Option Water Pressure Drop . . .57

Fouling and Altitude Factors Desuperheater Option Water Connections . . . .58

Water Temperature Range Correction Factors Consultants Guide Specification . . . . . . . . .59

Pressure Drop Graph . . . . . . . . . . . . . . .22

All data in this document is subject to change without prior notice.

2
Form No. 201.26 EG 03 (GB 05/08)
FEATURES Increased Reliability and Minimal Maintenance
Costs
YCIV is a fully packaged air cooled liquid chiller with
inverter driven screw compressors designed to be The heart of the YCIV chiller is the YORK MTS semi-
located outside on the roof of a building or at ground hermetic screw compressor. The following design
level. features provide increased reliability and minimal
maintenance costs:
There are four levels of operating efficiency:
• Each compressor motor has a dedicated inverter,
1. Standard YCIV with standard capacity control to match motor speed to cooling demand, there is
2. Standard YCIV with optimised capacity control no slide valve, return spring or control solenoid.
Therefore this simple dual screw rotor compressor
3. High Efficiency YCIV with standard capacity control has 50% less moving parts than conventional
4. High Efficiency YCIV with optimised capacity control screw compressors.
• YCIV controls monitor compressor runtime and
The optimised capacity control increases the operating start-ups and automatically switch the lead and lag
efficiency of the chiller. compressors to balance operating hours.
Each efficiency level has a selection of three acoustic • The soft start characteristics of variable speed
options: drive, the starting current never exceeds full load
amps, eliminates any compressor starting stress.
1. Standard Sound Level (SE or HE models) -
Generally applicable for daytime operation in city Another advantage, of low starting current, is that
centres etc. standby generators are smaller than those required for
conventional chillers.
2. Reduced Sound Level (RS) - For daytime operation
where background noise is lower. Smooth and Step-less Capacity Control
3. Low Sound Level (LS) - For night and day operation Capacity control is smooth and step-less providing a
near residential areas. minimum capacity control of 10% on two compressor
Economical Operating Costs Year Round chillers and 7.5% on three compressor models.

The incorporation of variable compressor speed Chiller Will Continue To Operate


technology, flash tank economisers, electronic Load limiting controls have been included to ensure
expansion valves and Optimised capacity control that if maximum-operating conditions, such as: motor
results in exceptionally high full load (Efficiency class A) current, suction or discharge pressure or excess inverter
and part load Energy Efficiency Ratios and economical temperatures, are exceeded the chiller will continue to
operating costs year round. Further reductions in operate to maintain performance within safety limits.
operating cost may be realised from the high 0.95
power factor that is maintained throughout the chillers’ Plain Language 80 Character Display
entire operating range.
The control centre has a plain language 80 character
Fuzzy Logic Control is utilised to make decisions to display of system temperatures, pressures, motor
increase or reduce compressor speeds according to the currents, compressor operating hours and number of
error or deviation from Setpoint and the rate of change starts, variable speed frequency, start/stop times and
of chilled liquid temperature. This further improves holidays etc. Full information to facilitate data logging,
energy efficiency by ensuring that compressors do not maintenance schedules and energy management is
needlessly operate to over cool the system. provided.
Specifically Designed For Low Sound Operation Optional Communications Interfaces
Most major cities today have rigorous noise control Bacnet, Lonmark and Modbus
legislation and many applications such as medical,
educational, hotels and theatres are extremely noise Single Point Electrical Connection
sensitive. In such situations a chiller must not only meet
Symphony is supplied, as standard, with a single
sound level requirements during the day, when background
point lockable circuit breaker for safety and installation
noise levels often mask chiller sound levels, but also
convenience.
during evenings and at night when legislated levels are
more stringent and back ground levels are diminished. Wide Range of Ambient Conditions
The YCIV LS chiller has been specifically designed for Symphony has been designed to operate in ambient
low sound operation, to satisfy the needs of various temperatures from –18°C to +52°C.
locations, by positioning noise emitting components
together in one location and enclosing them in an Wide Range of Leaving Liquid Temperatures
acoustically treated chamber. Two speed fans are
incorporated, that automatically operate at a quiet low Symphony has been designed to provide leaving liquid
speed as ambient temperatures reduce during the temperatures from –9°C to +15°C.
evening and at night.

3
Form No. 201.26 EG 03 (GB 05/08)
VARIABLE SPEED DRIVE CHILLER HISTORY
1979: YORK introduces water cooled VSD for process
cooling applications. Up to 400 hp.

1985: First floor mounted, air cooled, VSD in the


industry for centrifugal chillers for air-conditioning
applications. Up to 500 hp.

1995: First unit mounted VSD in the industry on


centrifugal chillers for air conditioning applications.
Up to 500 hp.

2000: Reduced size unit mounted VSD on centrifugal


chillers for air-conditioning applications. Up to
1000 hp.

2004: YORK introduces the Worlds first variable speed


drive air-cooled screw chiller.

2005: YORK awarded Climate Protection Award for VSD


technology by the United States Environmental
Protection Agency.

2006: YORK introduces the Worlds first low sound


variable speed drive air-cooled screw chiller.

4
Form No. 201.26 EG 03 (GB 05/08)
NOMINAL DATA
Acoustic YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV
Standard Efficiency (SE) Models
Option 0600 0650 0720 0770 0840 0920 1000 1070 1180 1340 1500
Cooling Capacity kW* 562 620 678 727 793 870 948 994 1104 1250 1405
Energy Efficiency Ratio SE (EER)* Standard Sound 2.90 2.91 2.95 2.92 2.99 2.99 3.00 2.94 2.95 2.96 2.97
Energy Efficiency Ratio SERS (EER)* Models (SE) & 2.93 2.94 2.98 2.94 3.02 3.02 3.03 2.97 2.98 2.99 3.00
Efficiency Class Reduced Sound B B B B B B B B B B B
Normal Control ESEER** Models (SE RS) 3.56 3.52 3.63 3.46 3.73 3.81 3.75 3.78 3.93 3.90 4.01
Optimised Control ESEER** 4.03 4.01 4.05 4.01 4.05 4.09 4.14 4.08 4.09 4.12 4.19
SE 68.5 69.4 70.4 69.4 72.4 71.3 71.3 73.1 74.1 75.0 75.9
Sound Pressure at 10 Metres dB(A)
SE RS 64.5 65.4 66.4 65.4 68.4 67.3 67.3 69.1 70.1 71.0 71.9
Cooling Capacity kW* 562 620 678 727 793 870 948 994 1104 1250 1405
Energy Efficiency Ratio SELS (EER)* Models with 2.93 2.94 2.99 2.95 3.03 3.03 3.04 2.98 2.99 3.00 3.01
Efficiency Class 2 Speed Fans B B B B B B B B B B B
Normal Control ESEER** (SE LS) 3.62 3.58 3.69 3.51 3.80 3.88 3.81 3.85 4.01 3.97 4.08
Optimised Control ESEER** 4.11 4.09 4.13 4.08 4.12 4.17 4.22 4.16 4.17 4.20 4.27
Normal Fans Speed 60.5 60.4 61.4 60.4 62.4 62.3 62.3 63.1 64.1 66.0 65.9
Sound Pressure at 10 Metres dB(A)
Low Fan Speed 57.5 57.4 58.4 57.4 59.4 60.3 60.3 60.1 61.1 64.0 63.9
Cooling Capacity kW* 547 604 660 708 772 847 929 968 1075 1217 1368
Energy Efficiency Ratio (EER)* 2.72 2.72 2.76 2.72 2.80 2.80 2.81 2.75 2.76 2.77 2.78
SE LS Models with
Efficiency Class C C C C C C C C C C C
High Fan Speed
Normal Control ESEER** 3.59 3.55 3.66 3.48 3.77 3.85 3.78 3.81 3.97 3.94 4.05
Inhibited
Optimised Control ESEER** 4.07 4.05 4.10 4.05 4.09 4.14 4.18 4.12 4.13 4.16 4.24
Sound Pressure at 10 Metres dB(A) 57.5 57.4 59.4 58.4 60.4 60.3 60.3 60.1 61.1 64.0 63.9
Acoustic YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV
High Efficiency (HE) Models
Option 0590 0630 0700 0760 0800 0830 0930 1050 1120 1220 1380
Cooling Capacity kW* 555 595 661 714 760 791 876 983 1047 1139 1289
Energy Efficiency Ratio HE (EER)* Standard Sound 3.13 3.13 3.12 3.09 3.14 3.17 3.09 3.1 3.1 3.11 3.1
Energy Efficiency Ratio HERS (EER)* Models (HE) & 3.16 3.17 3.16 3.13 3.18 3.21 3.13 3.14 3.14 3.14 3.14
Efficiency Class Reduced Sound A A A A A A A A A A A
Normal Control ESEER** Models (HE RS) 3.65 3.78 3.66 3.59 3.92 3.87 3.83 3.85 3.93 3.96 3.98
Optimised Control ESEER** 4.07 4.1 4.09 4.07 4.07 4.09 4.11 4.14 4.14 4.14 4.19
HE 66.5 68.4 69.4 70.4 70.3 72.3 70.3 71.1 72.0 73.0 73.9
Sound Pressure at 10 Metres dB(A)
HE RS 62.5 64.4 64.4 66.4 66.3 68.3 67.3 67.1 68.0 69.0 69.9
Cooling Capacity kW* 555 595 661 714 760 791 876 983 1047 1139 1289
Energy Efficiency Ratio HELS (EER)* Models with 3.17 3.18 3.16 3.14 3.19 3.22 3.13 3.15 3.15 3.15 3.14
Efficiency Class 2 Speed Fans A A A A A A A A A A A
Normal Control ESEER** (HE LS) 3.72 3.84 3.72 3.65 3.99 3.94 3.89 3.92 4 4.03 4.05
Optimised Control ESEER** 4.15 4.17 4.17 4.15 4.15 4.17 4.19 4.21 4.22 4.22 4.27
Normal Fans Speed 60.5 60.4 61.4 61.4 61.3 62.3 62.3 63.1 64.0 64.0 64.9
Sound Pressure at 10 Metres dB(A)
Low Fan Speed 56.5 57.4 58.4 58.4 58.3 59.3 59.3 59.1 60.0 61.0 60.9
Cooling Capacity kW* 541 579 643 695 740 770 853 957 1019 1109 1255
Energy Efficiency Ratio HELS (EER)* 2.94 2.95 2.94 2.91 2.96 2.99 2.9 2.92 2.92 2.92 2.91
HELS Models with
Efficiency Class B B B B B B B B B B B
High Fan Speed
Normal Control ESEER** 3.68 3.81 3.68 3.61 3.95 3.9 3.86 3.88 3.97 4 4.02
Inhibited
Optimised Control ESEER** 4.11 4.14 4.13 4.11 4.11 4.13 4.16 4.18 4.18 4.19 4.24
Sound Pressure at 10 Metres dB(A) 56.5 58.4 57.4 58.4 58.3 60.3 60.3 59.1 60.0 61.0 60.9

* At 7oC leaving chilled water and 35oC ambient.


** ESEER is European Energy Efficiency Ratio. ESEER = 0.03A + 0.33B + 0.41C + 0.23D
A = EER is 100% capacity at 35oC ambient. B = EER is 75% capacity at 30oC ambient.
o
C = EER is 50% capacity at 25 C ambient. D = EER is 25% capacity at 20oC ambient.

5
Form No. 201.26 EG 03 (GB 05/08)
SPECIFICATION • The fluorinated greenhouse gases in this equip-
ment may not be vented to the atmosphere.
YCIV air-cooled chillers are completely assembled with
all interconnecting refrigerant piping and internal wiring, • This equipment should only be serviced by quali-
ready for field installation. The unit is pressure tested, fied technicians.
evacuated, and fully factory charged with refrigerant
R134a and oil in each of the independent refrigerant Semi-Hermetic York Twin-Screw Compressors
circuits. After assembly, an operational test is performed
Continuous function, microprocessor controlled,
with water flowing through the evaporator to ensure that
Variable Speed Drive (VSD) shall provide valve-less,
each refrigerant circuit operates correctly.
smooth capacity control from 100% down to 10% of
The unit structure is manufactured from heavy gauge, chiller capacity for two compressor chillers and 100%
galvanised steel and coated with baked-on powder down to 7.5% for three compressor chillers. In addition,
paint (colour Champagne ((RAL 7006), (Munsel No. elimination of the slide valve and associated unloading
9.8YR4.36/1.2)) which when subject to ASTMB117, components has resulted in a 50% reduction in
1,000 hour, 5% salt spray test, yields minimum ASTM compressor moving parts.
1654 rating of “6”.
• Compressors are direct drive, semi-hermetic, rotary
YCIV chillers are designed within EN ISO 9001 and twin-screw type, including: muffler, temperature
built within an EN ISO 9002 accredited manufacturing actuated ‘off-cycle’ heater, IP55 terminal box,
organisation. discharge shut-off service valve, and precision
machined cast iron housing.
Chillers conform with the following European
• Reliable suction gas cooled, high efficiency,
Directives:
accessible hermetic compressor motor, full suction
• Machinery Directive (98/37/EC) gas flow through mesh screen filter, with inherent
internal thermal overload protection and external
• Low Voltage Directive (73/23/EEC, EN 60204) current overload on all three phases.
• EMC Directive (89/336/EEC) • Suction gas screen and serviceable, 0.5 micron full
• Pressure Equipment Directive (97/23/EC) flow oil filter within the compressor housing.
• Safety Code for Mechanical Refrigeration (EN378) • Cast iron compressor housing precisely machined
for optimal clearances and superb efficiency. Entire
Or conversely comply with the applicable sections of compressor, from suction to discharge has a Design
the following Standards and Codes: Working Pressure (DWP) of 24 bar.
• ANSI/ASHRAE Standard 15, Safety Code for Power and Electrical
Mechanical Refrigeration.
YORK has over 25 years of experience designing
• ANSI/NFPA Standard 70, National Electrical Code variable -speed drives specifically for chiller applications.
(N.E.C.). The result is an extremely reliable air-cooled chiller
system that offers industry leading efficiency at real
• ASME Boiler and Pressure Vessel Code, Section
world operating conditions, valve-less compressor
VIII Division 1.
loading/unloading, excellent capacity control, high
• ARI Standard 550/590-98, Water Chilling Packages power factor and soft start.
Using the Vapor Compression Cycle.
• All controls and motor starting equipment necessary
• ASHRAE 90.1 Energy Standard for Building Except for unit operation shall be factory wired and function
Low-Rise Residential Buildings. tested.
• VSD Power/Control Panel includes main power
• ARI 370 Sound Rating of Large Outdoor
connection(s), VSD and fan motor contactors,
Refrigeration and Air Conditioning Equipment.
current overloads, and factory wiring. Standard
In addition, the chillers conform to Underwriters design includes IP55 rating, powder painted steel
Labratories (U.L.) for construction of chillers and cabinet with hinged, latched, and gasket sealed
provide U.L./cU.L. Listing Label. outer doors equipped with wind struts for safer
servicing.
Fluorinated Greenhouse Gases
• VSD section of power panel includes a dedicated
• This equipment contains fluorinated greenhouse inverter output for each compressor.
gases covered by the Kyoto Protocol. • The variable speed drive (VSD) Inverters are
cooled by a propylene glycol cooling loop. A glycol
• The global warming potential of the refrigerant pump circulates glycol through the VSD heat sink
(R134a) used in this unit is 1300. to cool the power components. The glycol is then
• The refrigerant quantity is stated in the Physical circulated through several of the bottom rows of the
condenser coil to reject the heat.
Data table in this document.

6
Form No. 201.26 EG 03 (GB 05/08)
• The panel includes a control display access door so • Insulated external oil separators with no moving
that display and control features can be accessed parts, 24 bar design working pressure.
without opening main cabinet doors.
• Refrigerant system differential pressure provides
• Two and three compressor models have as standard oil flow through service replaceable, 0.5 micron, full
a single point power connection. In addition, all flow, cartridge type oil filter internal to compressor.
models are supplied with a factory mounted and
wired control transformer that will supply all unit • Suction lines, oil separators and flash tanks are
control voltage from the main unit power supply. covered with closed-cell insulation.
The transformer utilises scheduled line voltage on Evaporator
the primary side and provides 115 V/ 1 phase on
secondary. The unit uses a Shell and Tube type high-efficiency
Direct Expansion Evaporator. Each of the refrigerant
• The power panel is equipped with a factory mounted circuits consists of 2 passes with the chilled liquid
circuit breaker, at point of incoming single point flowing through the baffled shell.
connection, that provides the means to disconnect
power and short circuit protection. A lockable The design working pressure of the evaporator on the
operating handle extends through the power panel shell side is 10.3 bar, and 16 bar for the tube (refrigerant
door so that power may be disconnected without side).
opening any panel doors.
• Constructed and marked in accordance with the
• Compressor motors are powered by a variable- Pressure Equipment Directive and pressure tested
speed drive. Therefore, motor current never exceeds to Refrigerant Safety Standard EN 378 or ASME
the rated full load amps, providing soft starts with no Pressure Vessel Code, Section VII, Division (1).
electrical inrush. This eliminates the motor heating Waterside exempt per paragraph U-1, c, (6).
and stress always found with conventional motor
starters. In addition, by eliminating the heat buildup • The water baffles are fabricated from galvanized
during starting, the required off-time between starts steel to resist corrosion.
is reduced to a maximum of two minutes.
• Removable heads are provided for access to
• Many utility companies charge an additional fee internally enhanced, seamless, copper tubes.
if power factor is below 0.95. These power factor
• Water vent and drain connections are included.
adjustments/penalties can affect both regular
tariff rates, as well as demand charges. All YCIV • The evaporator is equipped with a thermostatically
models have a full load power factor of 95% and controlled heater for protection to -29°C ambient
maintain this level throughout the operating range. and is insulated with 19 mm flexible closed-cell
Specifications should always require the installing foam.
contractor to be responsible for additional cost to
supply and install power factor correction capacitors • Water nozzles have victaulic grooves as standard
if they are not factory mounted and wired. and are available with optional flanges.

• All exposed power wiring is routed through Condenser


conduit.
Standard (SN) and reduced (RS) sound level models
Refrigerant Circuits have condensers fitted with single speed fans. Low
sound (LS) models have two speed fans fitted.
An independent refrigerant circuit is provided per
compressor. Each circuit uses copper refrigerant pipe • The fans are dynamically and statically balanced,
formed on computer controlled bending machines direct drive with corrosion resistant glass fibre
to reduce the number of brazed joints resulting in a reinforced composite blades moulded into full airfoil
reliable and leak resistant system. cross section, providing vertical air discharge from
extended orifices for efficiency and low sound.
• Liquid line components include: manual shut-off
valve with charging port, high absorption removable • Guards of heavy gauge, PVC (polyvinyl chloride)
core filter-drier, sight glass with moisture indicator, coated steel wire are provided.
and electronic expansion valve.
• The fan motors are the high efficiency, direct drive,
• Discharge lines are provided with a manual 6 pole on SN models and 8 pole on RS and LS
compressor shutoff service valve (See Options and models, 3 phase, Class-“F”, current overload
Accessories for suction line valve). protected, totally enclosed (TEAC) type with double
sealed, permanently lubricated, ball bearings.
• A Flash tank is located in each refrigerant circuit to
increase the system efficiency. The design working
pressure is 31 bar.

7
Form No. 201.26 EG 03 (GB 05/08)
The fin and tube condenser coils are manufactured Programmable Setpoints:
from seamless, internally enhanced, high condensing
coefficient, corrosion resistant copper tubes arranged • display language;
in staggered rows and mechanically expanded into • leaving chilled liquid temperature:
corrosion resistant aluminium alloy fins with full height • setpoint, control range;
fin collars. • local or remote control;
• Oil cooling is provided by routing oil, from the oil • units of measure;
separator, through several of the top rows of the • compressor lead/lag;
condenser coil and returned to the compressor. • maximum chilled water setpoint reset temperature
• The design working pressure is 24 bar. range.
Display Data:
Microprocessor Controls
• chiller liquid return and leaving temperatures;
The microprocessor control system provides automatic
control of chiller operation including compressor start/ • ambient temperature;
stop and load/unload, anti-recycle timers, condenser • lead compressor identification;
fans, evaporator pump, evaporator heater, unit alarm • clock and schedule;
contacts and run signal contacts. • variable out of range;
• Chiller automatically resets to normal chiller • remote input indication;
operation after power failure. • chilled liquid reset setpoint;
• Unit operating software is stored in non-volatile • history data for last ten shutdown faults;
memory. Field programmed set points are retained • compressor suction, discharge, and oil pressures
in a lithium battery backed real time clock (RTC) and temperatures;
memory for minimum five years. • suction and discharge superheats;
• Alarm contacts are provided to remote alert • percent of full-load;
contacts for any unit or system safety fault.Display • operating hours, starts, and anti-recycle timer
and Keypad: status;
80 character liquid crystal display that is both viewable • Status Messages for manual override, unit switch
in direct sunlight and has LED backlighting for night- off, compressor run, run permissive, remote
time viewing. One keypad and display panel is provided controlled shut down, no cooling load, daily/holiday
with every chiller. shut down, anti-recycle timer.

During extreme or unusual conditions (i.e. blocked


condenser coils, ambient above scheduled maximum,
etc.) the chiller control system will avoid safety shutdown
by varying the chiller controls and cooling load output
to stay on-line and avoid safety limits being reached.
This allows maximum possible cooling capacity until
the unusual condition is cleared and avoids costly
shutdowns.

The system monitors the following parameters and


maintains the maximum cooling output possible without
shutdown of the equipment:

• motor current;
• suction pressure;
• discharge pressure.

System Safeties are provided for individual compressor


systems to perform auto-reset shut down (manual reset
required after the third trip in 90 minutes). Safeties
Display and keypad is accessible through display include:
access door without opening main control/electrical
• high discharge pressure or temperature;
cabinet doors.
• low suction pressure;
Display provides unit setpoints, status, electrical data, • high / low motor current;
temperature data, pressures, safety lockouts and
• high motor temperature;
diagnostics without the use of a coded display.
• high pressure switch;
Sealed keypad shall include unit On/Off switch. • high / low differential oil pressure;
• high oil temperature;
• low suction superheat;
8
Form No. 201.26 EG 03 (GB 05/08)
• critical sensor malfunction; • The low sound option (LS) has 2 speed fans and
• low or high current; an acoustically lined compressor enclosure.
• phase loss/single phase power; At high ambient conditions the fans operate at normal
• overload of motor windings; speed and as the ambient temperature falls the fans
• low voltage. automatically reduce to slow speed. If very low sound
is required at all ambient conditions normal fan speed
Unit Safeties are provided for the chiller to perform can be inhibited.
auto-reset shut down for the following conditions:
This option is typically for locations near residential
• high or low ambient; areas, hotels or hospitals etc where fans operate at
• low leaving chilled liquid temperature; normal speed during the day, when background noise
levels are noticeable, and at low speed in the evening
• under voltage;
and at night when background levels are lower.
• flow switch operation.
Energy Efficiency Option
END OF LINE TEST AND QUALITY PLAN
Optimised capacity control option increases the Energy
Leak Test Efficiency Ratio at all operating conditions.
After unit assembly refrigerant circuits are separately Condenser Coil Protection
leak tested using nitrogen.
Standard condenser coil construction materials include
Strength Test aluminium fins, copper tubes, and galvanized tube
supports for generally good corrosion resistance.
The system is evacuated and charged with a helium
mixture. The high and low-pressure sides, of the However, these materials are not adequate for all
refrigerant circuits, are tested separately at their design environments. The system designer can take steps to
working pressures to ensure that pressure is held. An inhibit coil corrosion in harsh applications and enhance
electronic leak detector is used to check all joints in the equipment life by choosing from these factory fitted
refrigerant circuits for signs of leakage. options based on project design parameters and related
environmental factors:
Operating Function Test
• PRE-COATED FIN CONDENSER COILS – The air-
The chiller is connected to a water loop and electrical
cooled condenser coils are constructed of epoxy-
power source and each refrigerant system is operated
coated aluminium fins. This can provide corrosion
for a minimum of 10 minutes to check that all functions
resistance comparable to copper-fin coils in typical
are operating satisfactorily. If a safety shut down occurs
seashore locations.
the problem is solved and the system is retested.
Either these or the post-coated coils (below), are
At the completion of the test the evaporator is drained
recommended for units being installed at the seashore
and a final leak check (using a leak detector) is
or where salt spray may hit the unit.
performed. The unit is then inspected and prepared for
shipment. • POST-COATED EPOXY DIPPED CONDENSER
COILS – The unit is built with dipped-cured epoxy
ACCESSORIES AND OPTIONS condenser coils.
Acoustic Options
This is another choice for seashore and other corrosive
There are three acoustic options to suit the various applications (with the exception of strong alkalies,
locations where air-cooled chillers are applied: oxidisers and wet bromine, chlorine and fluorine in
concentrations greater than 100 ppm).
• The standard sound option (SE and HE) has fans
that operate at normal speed and no compressor • COPPER FIN CONDENSER COILS – The unit
enclosure. constructed with copper tube condenser coils,
which have copper fins.
This option is typically used in non-sensitive sound
areas such as industrial areas or locations with loud This is not recommended for units in areas where they
traffic noise etc. may be exposed to acid rain.

• The reduced sound option (RS) has fans that Heat Recovery Option
operate at normal speed and an unlined compressor
Factory fitted desuperheaters on system 1 and 2
enclosure.
compressor discharge lines to provide hot water during
This option is typically used for daytime operation where cooling operation.
background noise is lower than normal city traffic etc.

9
Form No. 201.26 EG 03 (GB 05/08)
Unit Protective Panels • Vibration Isolation

• Wire Panels (full unit) – UV stabilized black polyvinyl • Neoprene isolation to provides very good
chloride coated, heavy gauge, welded wire mesh performance in most applications for the least cost
guards mounted on the exterior of the unit (factory (field mounted).
mounted).
• 1” level adjustable spring Isolators. Spring and
Protects condenser coil faces and prevents unauthorized cage type isolators for mounting under the unit
access to refrigerant components (compressors, pipes, base rails. 1” nominal deflection may vary slightly
cooler, etc.), yet provides free air-flow. This can cut by application (field mounted).
installation cost by eliminating the need for separate,
expensive fencing. Roof installations should incorporate the use of spring-
type isolators.
Evaporator Options
• 2” Seismic Spring Isolators. Restrained Spring-
• For ease of installation evaporator water Flex Mountings incorporate a rugged welded steel
connections are left or right handed when viewed housing with vertical and horizontal limit stops.
from the control panel end. Left handed water Housings designed to withstand a minimum 1.0
connections are standard. g accelerated force in all directions to 51 mm.
• 38 mm Insulation – Double thickness insulation Level adjustable, deflection may vary slightly by
provided (factory mounted). application (field mounted).
• Victaulic PN10 flange joint kit (10 bar) supplied Dual Pressure Relief Valves
loose for field installation. Includes flange and
companion flange and all necessary nuts, bolts Each relief valve is mounted on a sealable ball valve to
and gaskets aid maintenance.
• Flow Switch - Vapour proof 10.3 bar DWP, -28.9°C Two safety valves in parallel of which one is operational
to 121.1°C with 1” BSP connection for upright to assist in valve replacement during maintenance.
mounting in horizontal pipe. This flow switch or
equivalent must be supplied with each unit (field Low Temperature Brine
mounted).
Control amendments for leaving liquid operation
• Field fitted differential pressure switch to protect to -9°C.
evaporator from loss of liquid flow..

Building Automation System (BAS) Interface

The BAS input is :

• Leaving Chilled Liquid Temperature

Each BAS input can accept a reset via a 0 to 10 Vdc, or


2 to 10 Vdc, or 0 to 20 mAdc, or 4 to 20 mAdc signal.

10
Form No. 201.26 EG 03 (GB 05/08)
REFRIGERANT FLOW DIAGRAM

Oil
Low Pressure Liquid
Low Pressure Superheated Vapour Oil Cooler Coil
High Pressure Superheated Vapour
High Pressure Sub-cooled Liquid Condenser Coil
Medium Pressure Vapour

Economiser Solenoid

Feed
SMV

Drain
SMV
Flash
Tank

Compressor Oil Separator

Liquid Evaporator Chilled


In Liquid Out

Low-pressure liquid refrigerant enters the evaporator tubes and is evaporated and superheated by the heat energy
absorbed from the chilled water passing through the evaporator shell. Low-pressure vapour enters the compressor
where pressure and superheat are increased. High-pressure vapour is passed through the oil separator where oil
is removed, from the refrigerant, and recirculated to the compressor via the oil cooler. High-pressure oil-free vapour
is fed to the air-cooled condenser coil where heat is rejected to the air that is forced across the coil surface by fans.
The fully condensed liquid refrigerant enters the feed stepper motor valve that controls the liquid flow to maintain a
constant liquid level in the Flash Tank. The drain stepper motor valve functions as an Electronic Expansion Valve and
controls the refrigerant flow to the evaporator based on the compressor suction superheat. The Economiser Solenoid
Valve controls a medium pressure vapour feed to the compressor economiser port. When the valve is open refrigerant
vapour flashes off, in the flash tank, to provide additional subcooling to the liquid in the tank. The subcooled liquid
is then fed to the evaporator. Increasing both the subcooling and the superheat therefore enhancing the cooling
capacity.

11
Form No. 201.26 EG 03 (GB 05/08)
COMPONENT LOCATIONS

Condenser Coil

Standard Unit

Discharge Service
Valve

Flash Economiser
Oil Separator Cooler
Compressor

Condenser Fan

Low Sound Unit


Relief
Economiser SV
Valve

Drain SMV

Feed SMV
Liquid Line SV

Filter Drier

12
Form No. 201.26 EG 03 (GB 05/08)
CHILLER CONTROL LOGIC
Optimised European Seasonal Energy Efficiency
(ESEER) Control

Smart Anticipatory Control determines how many


compressors need to start to satisfy the current cooling
load. The “smart” logic is capable of reducing short
cycling and reducing loading time on a hot water start
and starting all compressors at the same time.

It is desirable to run as many compressors as possible


for increased efficiency. Smart anticipatory control logic
will keep as many compressors on line and reduce
the speed in an effort to optimise the use of the entire
evaporator tube surface.

Set number of
compressors to start
= number
compressors in unit

No No Rate of change of chilled


Last run time less Off time less than 5 liquid temperature.
than 5 minutes minutes Temperature deviation
from setpoint high limit

Yes Yes Yes

Reduce number of Reduce number of Reduce number of


compressors to start compressors to start compressors to start

Continue

Minimum Variable Speed Start Frequency

The minimum VSD start frequency is based on ambient 100


temperature and determines the frequency that the 95
compressors are ramped to at start. At higher ambients 90
Minimum VSD Frequency Hz

higher motor speeds are needed to provide adequate 85


motor cooling and at low ambients higher motor speeds 80
are needed to develop oil pressure differential at start. 75

Minimum Variable Speed Run Frequency 70


65
The minimum VSD compressor run frequency is based 60
on ambient temperature and determines the minimum 55
frequency that the compressors are permitted to run as
50
the system unloads. At higher ambients higher motor
45
speeds are needed to cool the compressor motor.
40
40 42 44 46 48 50 52
The graph illustrates the scaled frequency for both Ambient Temperature °C
Minimum VSD Start and Run frequencies.

13
Form No. 201.26 EG 03 (GB 05/08)
Smart Anticipatory Control Loading/Unloading and APPLICATION DATA
Starting Additional Compressors
Location Requirements
Setpoint High
Limit +CR To achieve optimum performance and trouble-free
Control Range

service it is essential that the proposed installation


site meets the location and space requirements for
Setpoint the model being installed. It is important to ensure that
the minimum service access space is maintained for
cleaning and maintenance purposes.
Setpoint Low Outdoor Installations
Limit -CR
The units can be installed at ground level on a suitable
During the first 30 seconds after a compressor reaches at level foundation easily capable of supporting the
the start frequency loading/unloading is inhibited. After weight of the unit, or on a suitable rooftop location. In
30 seconds the control logic looks at the actual leaving both cases an adequate supply of air is required. Avoid
liquid temperature, compares it with the Setpoint locations where the sound output and air discharge
+CR and makes a decision to load or unload. As from the unit may be objectionable.
additional cooling is required the chiller control board
microprocessor increases the speed of the compressor The location should be selected for minimum sun
at the rate of 1 Hz each 2 seconds until the load is exposure and away from boiler flues and other sources
satisfied. Loading will continue for as long as the leaving of airborne chemicals that could attack the condenser
liquid temperature is above Setpoint +CR. coils and steel parts of the unit.

If the chilled liquid temperature is not satisfied, and If located in an area accessible to unauthorized persons,
is above Setpoint + CR, the microprocessor will start steps must be taken to prevent access to the unit by
an additional compressor and all compressors are means of a protective fence. This will help to prevent
accelerated to start frequency. the possibility of vandalism, accidental damage, or
possible harm caused by unauthorized removal of
If the cooling capacity exceeds the demand the control protective guards or opening panels to expose rotating
board microprocessor will decrease the compressor or high voltage components.
speed at the rate of 0.1 – 1 Hz each 2 seconds until
the leaving liquid temperature rises to within the control For ground level locations, the unit must be installed
range. on a suitable flat and level concrete base that extends
to fully support the two side channels of the unit
Fuzzy Logic Control base frame. A one-piece concrete slab, with footings
extending below the frost line is recommended. To
The fuzzy logic control makes decisions to load or avoid noise and vibration transmission, the unit should
unload according to the error or deviation from Setpoint not be secured to the building foundation.
and the rate of change of chilled liquid temperature.
On rooftop locations, choose a place with adequate
In most situations, when the chilled liquid temperature structural strength to safely support the entire operating
is above the Setpoint + CR, the control board weight of the unit and service personnel. The unit can
microprocessor will continue to increase the speed of be mounted on a concrete slab, similar to ground floor
the compressors to load the chiller until the temperature locations, or on steel channels of suitable strength. The
drops within the range of the Setpoint High Limit. As channels should be spaced with the same centres as
the temperature drops and approaches the Setpoint the unit side and front base rails.
High Limit (Setpoint + CR) the microprocessor’s fuzzy
logic will begin considering the rate of change before This will allow vibration isolators to be fitted if required.
continuing to load. If the rate of change is dropping Isolators are recommended for rooftop locations. Any
too fast and there is potential for overshoot, the chiller ductwork or attenuators fitted to the unit must not have
control board microprocessor may decide not to a total static pressure resistance, at full unit air-flow,
continue to increase speed. The table below illustrates exceeding the capability of the fans installed in the
Fuzzy Logic Loading/Unloading verses Error. unit.

Deviation from Setpoint


Rate of Change
Negative Zero Positive
of Liquid Temperature
Error Error* Error
Rate of change
UNLOAD UNLOAD HOLD
of falling temperature
Zero Rate UNLOAD HOLD HOLD
Rate of change
HOLD LOAD LOAD
of rising temperature
*Zero Error is when the liquid temperature is at Setpoint.

14
Form No. 201.26 EG 03 (GB 05/08)
Indoor Installations Top Flange Guard

The unit can be installed in an enclosed plant room,


provided the floor is level and of suitable strength
to support the full operating weight of the unit. It is 150 mm
essential that there is adequate clearance for air flow to
the unit. The discharge air from the top of the unit must
be ducted away to prevent re-circulation of air within
the plant room. If common ducts are used for fans, non- 8 Holes , 9 mm
for M8 bolts
return dampers must be fitted to the outlet from each on 970 mm.
fan.

The discharge ducting must be properly sized with a


total static pressure loss, together with any intake static
pressure loss, less than the available static pressure
45
capability for the type of fan fitted.

m
m
45

0
90
The discharge air duct usually rejects outside the
building through a louvre. The outlet must be positioned
to prevent the air being drawn directly back into the air
intake for the condenser coils, as such re-circulation

m
m
will affect unit performance.

50
Operating in Low Ambient Conditions The unit is not designed to take structural loading. No
significant amount of weight should be allowed to rest
If low cooling capacities are required, at lower ambient on the fan outlet flange, deck assemblies or condenser
conditions (-4°C and below), the refrigerant pressure coil module. No more than 1 meter of light construction
will fall. To prevent operational problems the two speed ductwork should be supported by the unit.
fan option should be used.
Where cross-winds may occur, any ductwork must be
At ambient conditions of -10°C and below the Condenser supported to prevent side loading on the unit. If the
Coil Louvred Panels option must be used, if the ducts from two or more fans are to be combined into
customer has not provided adequate wind protection. a common duct, back-flow dampers should be fitted in
Ductwork Connection the individual fan ducts. This will prevent re-circulation
of air when only one of the fans is running.
The following ductwork recommendations are intended
to ensure satisfactory operation of the unit. Failure to Units are supplied with outlet guards for safety and
follow these recommendations could cause damage to prevent damage to the fan blades. If these guards
to the unit, or loss of performance, and may invalidate are removed to fit ductwork, adequate alternative
the warranty. When ducting is to be fitted to the fan precautions must be taken to ensure persons cannot
discharge it is recommended that the duct should be be harmed or put at risk from rotating fan blades.
the same cross sectional area as the fan outlet and
straight for at least 1 meter to obtain static regain from
the fan.

Ductwork should be suspended with flexible hangers


to prevent noise and vibration being transmitted to the
structure. A flexible joint is also recommended between
the duct attached to the fan and the next section for
the same reason. Flexible connectors should not be
allowed to concertina.

15
Form No. 201.26 EG 03 (GB 05/08)
Location Clearances When units are installed in an enclosure, the enclosure
height should not exceed the height of the unit on
Adequate clearances around the unit(s) are required more than one side. If the enclosure is of louvered
for the unrestricted air-flow for the air-cooled condenser construction, the same requirement of static pressure
coils and to prevent re-circulation of warm discharge loss applies as for ducts and attenuators stated above.
air back onto the coils. If clearances given are not Where accumulation of snow is likely, additional height
maintained, air-flow restriction or re-circulation will must be provided under the unit to ensure normal air-
cause a loss of unit performance, an increase in power flow to the unit.
consumption, and may cause the unit to malfunction.
Consideration should also be given to the possibility of
down drafts, caused by adjacent buildings, which may
cause re-circulation or uneven unit air-flow.

For locations where significant cross winds are


expected, such as exposed roof tops, an enclosure of
solid or louvre type is recommended to prevent wind
turbulence interfering with the unit air-flow.

LOCATION CLEARANCES
WALL A WALL A
A B A A A

1200 1200

WALL D
WALL B

WALL D WALL B

1000 1200

WALL C

1000

WALL C

SOLID WALLS
SE 0600-0920 1000-1500
Models
HE 0590-0800 0830-1380
Dimension A mm 1500 1700
Dimension B mm 2700 3000
LOUVRES ON WALLS B & D
Dimension A mm 800 800
Dimension B mm 2700 3000

Notes
Walls must not exceed height of chiller on more than one side.
Louvres must be minimum 50% free area
Dimensions A may have to be increased to allow for pipework and service access around pipework.

16
Form No. 201.26 EG 03 (GB 05/08)
Vibration Isolators Liquid system lines at risk of freezing, due to low ambient
temperatures should be protected using insulation and
Optional sets of vibration isolators can be supplied heater tape and/or a suitable glycol solution. The liquid
loose with each unit. pump(s) may also be used to ensure liquid is circulated
when the ambient temperature approaches freezing
Chilled Liquid Piping
point.
The following piping recommendations are intended to
Insulation should also be installed around the cooler
ensure satisfactory operation of the unit(s). Failure to
nozzles. Heater tape of 21 watts per meter under the
follow these recommendations could cause damage to
insulation is recommended, supplied independently
the unit, or loss of performance, and may invalidate the
and controlled by an ambient temperature thermostat
warranty.
set to switch on at approximately 2.2°C, above the
A flow switch must be installed in the customer pipework freezing temperature of the chilled liquid.
at the outlet of the cooler and wired back to the control
The cooler is protected by heater mats placed under
panel using shielded cable to prevent damage to the
the insulation, which are powered from the unit control
cooler caused by the unit operating without adequate
system power supply. During cold weather when there
liquid flow. There should be a straight run of piping of at
is a risk of freezing, chiller power should be left switched
least 5 pipe diameters on either side of the switch. The
on to provide the freeze protection function unless the
flow switch used must have gold plated contacts for low
liquid systems have been drained.
voltage/current operation.
Pipework Arrangement
Alternatively, a differential pressure switch fitted across
an orifice plate may be used, preferably of the high/low The following is a suggested piping arrangement for
limit type single unit installations. For multiple unit installations,
each unit should be piped as shown in the diagram
The chilled liquid pump(s) installed in the piping
below.
system(s) should discharge directly into the unit cooler
section of the system. The pump(s) may be controlled
by the chiller controls or external to the unit. Pipework
and fittings must be separately supported to prevent
any loading on the cooler.

Flexible connections are recommended which will also


minimise transmission of vibrations to the building.
Flexible connections must be used if the unit is mounted
on anti-vibration mounts, as some movement of the unit
can be expected in normal operation.

Piping and fittings immediately next to the cooler


-Isolating Valve - Normally Open -Pressure Tapping
should be readily de-mountable to enable cleaning
-Isolating Valve - Normally Closed -Flow Switch
before operation, and to facilitate visual inspection of
-Flow Regulating Valve -Flanged Connection
the exchanger nozzles.
-Flow Measurement Device -Pipework
The cooler must be protected by a strainer, preferably -Strainer
of 40 mesh, fitted as close as possible to the liquid
inlet connection, and provided with a means of local Cooler Connections
isolation. The cooler must not be exposed to flushing
Standard chilled liquid connections on all coolers are of
velocities or debris released during . flushing.
the Victaulic Groove type.
It is recommended that a suitably sized bypass and valve
arrangement is installed to allow flushing of the piping
system. The bypass can be used during maintenance
to isolate the heat exchanger without disrupting flow to
other units.

Thermometer and pressure gauge connections should


be provided on the inlet and outlet connections of each
cooler. Gauges and thermometers are not provided
with the unit.

Drain and air vent connections should be provided at all


low and high points in the piping to permit drainage of
the system and to vent any air in the pipes.

17
Form No. 201.26 EG 03 (GB 05/08)
Option Flanges Refrigerant Relief Valve Piping

One of two types of flanges may be fitted depending The evaporator is protected against internal refrigerant
on the customer or local Pressure Vessel Code overpressure by refrigerant relief valves. A pressure
requirements. These are Victaulic Adapter flanges, relief valve is mounted on each of the main refrigerant
normally supplied loose, or weld flanges, which may lines connecting the cooler to the compressors.
be supplied loose or ready-fitted. Victaulic Adapter and
weld flange dimensions are to ISO 7005 - NP10. A piece of pipe is fitted to each valve and directed so
that when the valve is activated the release of high
pressure gas and liquid cannot be a danger or cause
injury. For indoor installations, pressure relief valves
should be piped to the exterior of the building.

The size of any piping attached to a relief valve must be


of sufficient diameter so as not to cause resistance to
the operation of the valve. Unless otherwise specified
by local regulations. Internal diameter depends on the
length of pipe required and is given by the following
VICTAULIC ADAPTER formula:

D5 = 1.447 x L
Water Treatment
Where:
The unit performance provided in the Design Guide is
based on a fouling factor of 0.018 m²/hr °C/kW. Dirt, D = minimum pipe internal diameter in cm
scale, grease and certain types of water treatment L = length of pipe in meters
will adversely affect the heat exchanger surfaces and
therefore the unit performance. Foreign matter in the If relief piping is common to more than one valve, its
water system(s) can increase the heat exchanger cross-sectional area must be at least the total required
pressure drop, reducing the flow rate and causing by each valve. Valve types should not be mixed on a
potential damage to the heat exchanger tubes. common pipe. Precautions should be taken to ensure
the outlets of relief valves or relief valve vent pipes
Aerated, brackish or salt water is not recommended remain clear of obstructions at all times.
for use in the water system(s). YORK recommends
that a water treatment specialist should be consulted
to determine whether the proposed water composition
will adversely affect the evaporator materials of carbon
steel and copper. The pH value of the water flowing
through the evaporator must be kept in a range between
7 and 8.5.

18
Form No. 201.26 EG 03 (GB 05/08)
ELECTRICAL CONNECTION 115 Vac Control Supply Transformer

No additional controls (relays, etc.) should be mounted A 3 wire high voltage to 115 Vac supply transformer is
in the control panel. Power and control wiring not standard in the chiller. This transformer is mounted in
connected to the control panel should not be run the cabinet and steps down the high voltage supply to
through the control panel. If these precautions are 115 Vac to be used by the Controls, VSD, Feed &Drain
not followed it could lead to a risk of electrocution. In Valve Controller, valves, solenoids, heaters, etc.
addition, electrical noise could cause malfunctions or
damage the unit and its controls. The high voltage for the transformer primary is taken
from the chiller input. Fusing is provided for the
After power wiring connection, do not switch on mains transformer.
power to the unit. Some internal components are live
when the mains are switched on and this must only be Removing high voltage power to the chiller will remove
done by “Authorized ” persons familiar with starting, the 115 Vac supply voltage to the control panel circuitry
operating, and troubleshooting this type of equipment. and the evaporator heater. In cold weather, this could
cause serious damage to the chiller due to evaporator
freeze-up. Do not remove power unless alternate means
are taken to ensure operation of the evaporator heater

VSD CONTROL PANEL


STANDARD UNIT CONTROLS
CONTROL
VSD VSD VSD TRANSFORMER EVAPORATOR HEATER
1 2 3

FAN
CONTACTORS
LINE
REACTOR

CIRCUIT
BREAKER
PE

FIELD PROVIDED
UNIT POWER
SUPPLY

Power Wiring Control Panel Wiring

All electrical wiring should be carried out in accordance All control wiring utilizing contact closures to the control
with local regulations. Route properly sized cables to panel terminal block is nominal 115 Vac and must be
cable entries on the unit. In accordance with CE or U.L. run in shielded cable, with the shield grounded at the
Standard it is the responsibility of the user to install panel end only. Run shielded cable separately from
over current protection devices between the supply mains cable to avoid electrical noise pick-up. Use the
conductors and the power supply terminals on the control panel cable entry to avoid the power cables.
unit.
Voltage free contacts connected to the panel must
To ensure that no eddy currents are set up in the power be suitable for 115 Vac, 10 ma (gold contacts
panel, the cables forming the 3 phase power supply recommended). If the voltage free contacts form part
must enter via the same cable entry. All sources of of a relay or contactor, the coil of the device must be
supply to the unit must be taken via a common point of suppressed using a standard R/C suppressor. The
isolation (not supplied by YORK). above precautions must be taken to avoid electrical
noise, which could cause a malfunction or damage to
Units require only one 3 phase supply, plus earth the unit and its controls.
ground. Connect the 3 phase supplies to the terminal
block or optional circuit breaker located in the panel
using lug sizes detailed in the Technical Data Section.

Connect a ground wire from the chiller panel ground


lug to the incoming line supply ground.

19
Form No. 201.26 EG 03 (GB 05/08)
VOLTS FREE CONTACTS Remote Run /Stop

Chilled Liquid Pump Starter A Remote Run/Stop input is available for each pair of
systems (1/3 & 2/4). These inputs require a dry contact
Terminals 23 and 24 on 1TB close to start the chilled to start and stop the system. System 1/3 remote dry
liquid pump.This contact can be used as a master start/ contacts are connected between Terminals 2 and 15
stop for the pump in conjunction with the daily start/ of 1TB and System 2/4 dry contacts are connected
stop schedule. between Terminals 2 and 16 of 1TB. If remote start/
Run Contact stop is not utilized, a jumper must be paced across the
terminals to allow the system to run.
Terminals 21 and 22 on 1TB close to indicate that a
system is running. The remote run/stop circuitry is a 115 Vac circuit.
Contacts must be rated for low current (10 ma). Gold
Alarm Contacts contacts should be used.

The Systems 1/3 & 2/4 each have a single voltage-free Remote Print
contact, which will operate to signal an alarm condition
whenever any system locks out, or there is a power Closure of suitable contacts connected to Terminals
failure. To obtain system alarm signal, connect the 2 and 14 of 1TB will cause a hard copy printout of
alarm circuit to volt free Terminals 25 & 26 (System Operating Data/Fault History to be made if an optional
1/3), Terminals 27 and 28 (System 2/4) of 1TB. printer is connected to the RS-232 port.

SYSTEM INPUTS The remote print circuitry is a 115 Vac circuit. Contacts
must be rated for low current (10 ma). Gold contacts
Flow Switch should be used.

A chilled liquid flow switch of suitable type MUST be Optional Remote Setpoint Offset –Temperature
connected between Terminals 2 and 13 of 1TB to
provide protection against loss of liquid flow, which will A current or voltage signal connected to Terminals
cause evaporator freeze-up if the chiller is permitted to 17 and 18 will provide a remote offset function of the
run. chilled liquid setpoint, if required.

The flow switch circuitry is a 115 Vac circuit. Contacts Optional Remote Setpoint Offset – Current
must be rated for low current (10 ma). Gold contacts A current or voltage signal connected to Terminals 19
should be used. and 20 will provide remote setting of the current limit
setpoint, if required.

Optional Remote Setpoint Offset – Sound Limiting

A current or voltage signal connected to Terminals


40 and 41 will provide remote setting of sound limit
setpoint, if required.

CONTROL RELAY
BOARD BOARD
No. 1

SYS. 1/3
FLOW SWITCH ALARM
CONTACTS
PRINT

SYS. 1/3 RUN/STOP

SYS. 2/4 RUN/STOP

RELAY
BOARD
No. 2

EVAP. PUMP
START
SIGNAL
LEGEND

SYS. 2 TERMINAL BLOCK FOR CUSTOMER


ALARM CONNECTIONS (1TB)
CONTACTS
TERMINAL BLOCK FOR YORK
CONNECTIONS (1TB)

CHILLER WIRING AND COMPONENTS BY YORK


RUN
OPTIONAL EQUIPMENT
WIRING AND/OR COMPONENTS BY OTHERS

20
Form No. 201.26 EG 03 (GB 05/08)
CHILLER SELECTION DATA YCIV SAMPLE SELECTION - COOLING

Selection Guide Chilled Water Chillers A standard chiller is required to cool water from 12°C
to 7°C having a cooling capacity of 865 kW at a design
DATA REQUIRED flow rate of 41 l/s. Other design conditions applying
are:
To select a YORK YCIV chiller the following information
is required: Ambient air entering condenser: 35°C
1. Required cooling capacity. Fouling factor: 0.044 m² °C./kW
2. Design chilled water entering and leaving Altitude:Sea level
temperatures.
From a cursory examination of the SE Capacity Table,
3. Design water flow rate if one of the temperatures in a model YCIV0920 gives approximately the required
item 3 are unknown. capacity:
4. Design condenser entering air temperature. This Capacity = 870.4 kW
will normally be the design summer ambient air
temperature unless location or other factors have Compressor power = 271.3 kW
an influence.
No correction factors apply therefore, after calculating
5. Altitude above sea level. the flow rate, the conditions will be as follows:

6. Design evaporator fouling factor. Cooling capacity: 870.4 kW

7. Static pressure resistance against condenser Water temperature: 12°C to 7°C (Range = 5°C)
entering and leaving air flow (where ducts, louvres,
attenuators, etc., are used) at full unit air volume. Water flow rate: 41.6 I/s

Note: Items 1, 2 and 3 must be linked by the following Compressor power: 271.3 kW
formulae: All values are within the Operating Limitations. From
Cooling Capacity (kW) = Range (°C) x Flow (litres/sec) Pressure Drop Graph, YCIV0920 evaporator water
x 4.18 pressure drop = 65 kPa at the calculated flow of 41.6 l/s.

Where: Fouling and Altitude Factors


EVAPORATOR
Range = Entering liquid temperature - Leaving liquid Fouling Factor m² °C/kW Capacity Factor Comp. Input Factor
temperature. 0.044 1.000 1.000
0.088 0.987 0.995
0.176 0.964 0.985
CHILLER SELECTION METHOD 0.352 0.915 0.962

1. Determine the correct size of chiller by selecting Altitude (m) Capacity Factor Comp. Input Factor
the model which most closely matches the required 0 1.000 1.000
600 0.987 1.010
capacity at the design conditions of leaving water 1200 0.973 1.020
temperature and entering air temperature (Cooling 1800 0.958 1.029
2400 0.943 1.038
Capacity Tables).
Water Temperature Range Correction Factors
2. Apply correction factors for fouling factor and
Temperature Correction Factors
altitude to the capacity and power values from the Range °C Cooling Capacity Compressor kW Input
capacity tables. Ensure the corrected capacity is 3 0.98 0.99
still sufficient for requirements. 4 0.99 1.00
5 1.00 1.00
6 1.01 1.00
3. Using the corrected capacity of the selected chiller 7 1.02 1.00
adjust the design temperature range, or flow rate, 8 1.02 1.01
9 1.03 1.01
to balance the formulae shown in “Data Required”. 10 1.04 1.01

4. Physical and electrical data can now be determined


from the relevant tables.

Always re-check that selections fall within the design


limitations specified in the Operating Limitations.

21
Form No. 201.26 EG 03 (GB 05/08)
PRESSURE DROP GRAPH
160
B
140 A C
Mean Water Temperature: 9.4 °C
120
F
100
D
90 E
80

70

60

50

40
Pressure Drop (kPa)

30

20

15

10

5
5 10 20 30 40 50 60 70 80
Water Flow Rate (l/s)

Line Pressure Drop Calculation


A Pressure Drop [kPa] = 0.1724 x (Flow Rate [l/s]^1.7925)
B Pressure Drop [kPa] = 0.1898 x (Flow Rate [l/s]^1.7475)
C Pressure Drop [kPa] = 0.1781 x (Flow Rate [l/s]^1.7468)
D Pressure Drop [kPa] = 0.1100 x (Flow Rate [l/s]^1.7183)
E Pressure Drop [kPa] = 0.0602 x (Flow Rate [l/s]^1.6792)
F Pressure Drop [kPa] = 0.0923 x (Flow Rate [l/s]^1.6265)
Line Model
A YCIV0600SE
B YCIV0590HE, YCIV0630HE, YCIV0650SE. YCIV0700HE, YCIV0720SE
C YCIV0760HE, YCIV0800HE, YCIV0830HE,
D YCIV0770SE, YCIV0840SE, YCIV0920SE, YCIV0930HE, YCIV1000SE
E YCIV1050HE, YCIV1070SE, YCIV1120HE
F YCIV1180SE, YCIV1220HE, YCIV1340SE, YCIV1380HE,YCIV1500SE

22
Form No. 201.26 EG 03 (GB 05/08)
OPERATING LIMITATIONS
YCIV0600 YCIV0650 YCIV0720 YCIV0770 YCIV0840 YCIV0920
Standard Efficiency (SE) Models
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
o
Water Outlet C 4.4 to 15.6
Liquid Outlet o
Glycol Outlet C -9 to 15.6
Temperature
o
Chilled Liquid Temp. Range C 3 to 10
Evaporator Flow Rate l/s 8.8 42.6 10.1 47.3 10.1 47.3 11.4 50.5 11.4 50.5 11.4 50.5
Evaporator Pressure Drop kPa 8.5 143.6 10.8 160.4 10.8 160.4 7.2 92.9 7.2 92.9 7.2 92.9
Maximum Water Side Pressure bar 10
o
Air Entering Temperature C -18 to 52
Fan Standard Fans Pa 10
Ambient Air
Available Static 2 Speed Fans Pa 10
Pressure High Static Fans Pa 100
Maximum Refrigerant Side Pressure bar 16
Power Supply Voltage 400V, 3 ~, 50 Hz (nominal) V 360 to 440
Recommended Minimum System Water Volume litres 560 620 680 730 800 870

YCIV1000 YCIV1070 YCIV1180 YCIV1340 YCIV1500


Standard Efficiency (SE) Models
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
o
Water Outlet C 4.4 to 15.6
Liquid Outlet o
Glycol Outlet C -9 to 15.6
Temperature
o
Chilled Liquid Temp. Range C 3 to 10
Evaporator Flow Rate l/s 11.4 50.5 15.8 75.7 18.9 75.7 18.9 75.7 18.9 75.7
Evaporator Pressure Drop kPa 7.2 92.9 6.2 86.1 11.0 105.1 11.0 105.1 11.0 105.1
Maximum Water Side Pressure bar 10
o
Air Entering Temperature C -18 to 52
Fan Standard Fans Pa 10
Ambient Air
Available Static 2 Speed Fans Pa 10
Pressure High Static Fans Pa 100
Maximum Refrigerant Side Pressure bar 16
Power Supply Voltage 400V, 3 ~, 50 Hz (nominal) V 360 to 440
Recommended Minimum System Water Volume litres 950 1000 1100 1250 1400

YCIV0590 YCIV0630 YCIV0700 YCIV0760 YCIV0800 YCIV0830


High Efficiency (HE) Models
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
o
Water Outlet C 4.4 to 15.6
Liquid Outlet o
Glycol Outlet C -9 to 15.6
Temperature
o
Chilled Liquid Temp. Range C 3 to 10
Evaporator Flow Rate l/s 10.1 47.3 10.1 47.3 10.1 47.3 11.4 47.3 11.4 47.3 11.4 47.3
Evaporator Pressure Drop kPa 10.8 160.4 10.8 160.4 10.8 160.4 12.5 150.1 12.5 150.1 12.5 150.1
Maximum Water Side Pressure bar 10
o
Air Entering Temperature C -18 to 52
Fan Standard Fans Pa 10
Ambient Air
Available Static 2 Speed Fans Pa 10
Pressure High Static Fans Pa 100
Maximum Refrigerant Side Pressure bar 16
Power Supply Voltage 400V, 3 ~, 50 Hz (nominal) V 360 to 440
Recommended Minimum System Water Volume litres 550 600 700 760 800 880

YCIV0930 YCIV1050 YCIV1120 YCIV1220 YCIV1380


High Efficiency (HE) Models
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
o
Water Outlet C 4.4 to 15.6
Liquid Outlet o
Glycol Outlet C -9 to 15.6
Temperature
o
Chilled Liquid Temp. Range C 3 to 10
Evaporator Flow Rate l/s 11.4 50.5 15.8 75.7 15.8 75.7 18.9 75.7 18.9 75.7
Evaporator Pressure Drop kPa 7.2 92.9 6.2 86.1 6.2 86.1 11.0 105.1 11.0 105.1
Maximum Water Side Pressure bar 10
o
Air Entering Temperature C -18 to 52
Fan Standard Fans Pa 10
Ambient Air
Available Static 2 Speed Fans Pa 10
Pressure High Static Fans Pa 100
Maximum Refrigerant Side Pressure bar 16
Power Supply Voltage 400V, 3 ~, 50 Hz (nominal) V 360 to 440
Recommended Minimum System Water Volume litres 880 980 1050 1140 1300
(1) Units operating at ambient temperatures below -4°C must have the Two Speed Fans.

23
Form No. 201.26 EG 03 (GB 05/08)
STANDARD EFFICIENCY (SE AND SE RS) MODELS WITH STANDARD FANS - COOLING CAPACITIES
Condenser Coil Entering Air Temperature oC
LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 561.6 145.7 3.56 541.3 159.3 3.16 525.5 173.3 2.84 502.7 189.0 2.50 484.2 233.9 1.97
5 566.0 146.2 3.58 545.5 159.9 3.17 529.4 174.1 2.85 507.0 189.8 2.51 487.3 234.1 1.98
6 583.9 148.4 3.64 562.6 162.3 3.23 545.2 177.0 2.89 524.0 192.7 2.56 499.5 234.8 2.02
7 601.5 150.5 3.70 579.7 164.6 3.28 562.0 180.0 2.93 541.1 195.9 2.60 512.0 235.9 2.07
YCIV
0600 8 619.3 152.5 3.77 596.7 166.8 3.34 578.2 182.1 2.98 557.7 199.1 2.64 525.5 237.6 2.11
10 655.3 155.7 3.91 632.1 172.0 3.44 614.1 188.0 3.07 592.0 206.4 2.71 562.5 245.9 2.18
12 691.1 158.3 4.06 667.6 176.5 3.54 651.9 193.8 3.17 626.2 214.1 2.77 592.3 256.3 2.21
15 748.1 166.6 4.19 727.1 184.1 3.71 713.5 202.2 3.33 668.5 220.3 2.88 611.1 252.1 2.31
15.5 757.6 168.6 4.19 737.1 186.0 3.72 723.7 203.6 3.36 674.5 221.5 2.89 613.9 250.9 2.33
4.5 623.7 160.3 3.62 599.1 175.8 3.19 578.4 191.5 2.84 541.8 201.4 2.54 468.5 205.9 2.15
5 628.7 160.9 3.64 604.0 176.5 3.20 582.9 192.3 2.85 546.7 202.2 2.55 469.7 204.7 2.17
6 649.0 163.4 3.70 623.5 179.3 3.26 601.1 195.6 2.90 566.3 205.3 2.61 474.2 199.9 2.24
YCIV 7 669.1 165.9 3.76 642.8 181.9 3.32 620.3 199.2 2.94 585.2 208.3 2.66 479.5 195.9 2.31
0650 8 689.2 168.1 3.83 662.3 184.3 3.37 638.3 201.2 2.99 603.8 211.5 2.70 485.6 192.4 2.38
10 729.9 171.6 3.97 702.8 190.2 3.48 677.0 206.5 3.10 642.1 218.7 2.78 504.6 189.2 2.51
12 769.7 174.8 4.12 742.7 195.3 3.58 717.4 211.5 3.21 680.4 226.0 2.86 515.7 187.0 2.59
15 833.2 184.0 4.25 809.0 203.7 3.75 785.1 220.6 3.37 726.4 232.6 2.97 532.1 183.8 2.72
15.5 843.8 186.3 4.26 820.0 205.8 3.76 796.4 222.1 3.40 732.9 233.9 2.98 534.5 183.0 2.74
4.5 678.9 172.9 3.64 653.3 189.0 3.23 633.1 205.7 2.89 601.0 221.7 2.55 578.4 267.7 2.06
5 684.4 173.6 3.66 658.5 189.8 3.24 638.0 206.6 2.90 606.0 222.5 2.57 582.0 267.8 2.07
6 706.4 176.4 3.72 679.6 192.8 3.29 657.4 210.2 2.94 626.2 225.8 2.62 596.4 268.4 2.12
YCIV 7 728.1 179.1 3.78 700.5 195.6 3.35 678.1 213.8 2.98 646.7 228.9 2.67 611.5 269.3 2.16
0720 8 750.0 181.7 3.84 721.4 198.4 3.40 698.0 216.5 3.03 666.9 232.4 2.71 628.0 270.7 2.21
10 794.6 186.0 3.98 765.2 204.9 3.50 741.9 223.9 3.13 708.4 240.3 2.79 671.9 279.3 2.29
12 838.9 189.6 4.13 808.7 210.7 3.61 788.5 231.1 3.22 749.5 248.4 2.86 708.1 290.2 2.33
15 908.1 199.6 4.26 880.9 219.8 3.78 862.9 241.0 3.39 800.2 255.7 2.97 730.5 285.4 2.44
15.5 919.6 202.1 4.27 892.9 222.0 3.79 875.3 242.7 3.42 807.4 257.1 2.98 733.9 284.1 2.47
4.5 733.1 186.7 3.66 704.0 206.1 3.21 680.8 226.8 2.83 636.9 239.2 2.52 591.1 270.2 2.08
5 739.1 187.4 3.68 709.7 206.8 3.22 685.9 227.6 2.84 642.2 240.0 2.53 593.0 268.9 2.10
6 763.0 190.2 3.75 732.3 209.7 3.28 706.3 230.8 2.89 663.5 242.9 2.59 600.6 263.5 2.17
7 786.8 193.1 3.81 755.1 212.5 3.34 727.3 233.6 2.94 685.1 245.7 2.64 608.4 258.5 2.24
YCIV
0770 8 810.9 196.0 3.87 777.8 215.2 3.40 747.6 235.3 3.00 706.4 248.6 2.69 616.9 253.7 2.31
10 859.7 201.3 4.00 825.5 222.0 3.50 792.5 241.1 3.11 750.2 255.5 2.79 643.2 249.7 2.44
12 908.8 206.2 4.14 873.3 228.5 3.61 839.8 246.5 3.23 793.9 262.5 2.88 659.1 247.9 2.52
15 983.7 217.0 4.27 951.3 238.3 3.78 919.1 257.2 3.40 847.6 270.2 2.99 680.1 243.7 2.64
15.5 996.2 219.7 4.27 964.2 240.7 3.79 932.3 258.9 3.42 855.2 271.7 3.00 683.2 242.7 2.67
4.5 795.6 199.7 3.71 764.7 218.2 3.28 740.1 237.6 2.93 698.6 253.6 2.60 671.7 300.6 2.13
5 802.1 200.5 3.72 770.9 219.1 3.29 745.8 238.7 2.94 704.5 254.4 2.62 675.9 300.6 2.14
6 828.1 203.9 3.78 795.7 222.6 3.35 768.7 242.8 2.98 728.0 257.7 2.67 692.9 300.9 2.19
YCIV 7 854.1 207.1 3.85 820.4 226.0 3.40 792.8 247.2 3.02 751.7 261.1 2.72 710.3 301.5 2.24
0840 8 880.0 210.3 3.91 845.3 229.2 3.46 816.4 250.3 3.08 775.2 264.7 2.77 729.3 302.6 2.30
10 933.3 215.7 4.04 897.1 237.1 3.56 868.5 258.9 3.17 823.3 273.0 2.86 780.4 311.5 2.39
12 986.2 220.4 4.19 949.3 244.1 3.66 923.7 267.5 3.27 871.6 281.4 2.94 819.7 321.1 2.44
15 1067.5 232.0 4.32 1034.0 254.6 3.83 1010.9 279.0 3.44 930.5 289.7 3.05 845.7 315.8 2.56
15.5 1081.0 234.9 4.33 1048.1 257.3 3.85 1025.4 280.9 3.47 938.8 291.3 3.07 849.6 314.4 2.58
4.5 872.6 220.1 3.69 839.5 239.8 3.28 813.0 260.4 2.94 771.3 279.2 2.61 751.3 337.1 2.13
5 879.7 221.0 3.70 846.3 240.8 3.29 819.3 261.5 2.95 777.9 280.3 2.62 756.2 337.3 2.14
6 908.1 224.7 3.77 873.2 244.8 3.34 844.1 266.3 2.98 804.5 284.5 2.67 775.5 338.1 2.19
7 936.3 228.4 3.82 900.1 248.6 3.40 870.4 271.3 3.02 831.1 288.7 2.72 795.5 339.1 2.24
YCIV
0920 8 964.4 231.9 3.88 927.0 252.4 3.45 896.2 274.8 3.08 857.6 293.1 2.77 817.3 341.1 2.29
10 1022.2 237.7 4.02 983.5 261.1 3.54 952.9 284.6 3.17 911.7 303.4 2.85 870.9 349.2 2.38
12 1079.5 242.8 4.16 1040.0 269.0 3.64 1012.9 294.2 3.26 966.2 314.0 2.92 893.2 345.0 2.47
15 1168.5 255.6 4.29 1132.8 280.5 3.81 1108.5 306.8 3.43 1031.5 323.2 3.04 921.6 339.2 2.59
15.5 1183.4 258.8 4.30 1148.3 283.4 3.83 1124.4 308.9 3.46 1040.7 324.9 3.05 925.8 337.7 2.61

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.

24
Form No. 201.26 EG 03 (GB 05/08)
Standard Efficiency (SE and SE RS) Models with Standard Fans - Cooling Capacities continued

Condenser Coil Entering Air Temperature oC

LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 950.0 240.2 3.68 914.5 261.1 3.28 886.2 282.9 2.95 844.3 304.7 2.62 831.2 373.2 2.12
5 957.7 241.3 3.69 921.8 262.2 3.29 893.0 284.2 2.95 851.7 306.0 2.63 836.7 373.5 2.14
6 988.3 245.3 3.75 951.0 266.7 3.34 919.9 289.6 2.99 881.2 310.9 2.68 858.5 374.7 2.19
7 1018.8 249.4 3.81 980.1 271.0 3.39 948.5 295.0 3.03 910.8 315.9 2.73 881.0 376.4 2.23
YCIV
1000 8 1049.1 253.2 3.87 1009.2 275.2 3.44 976.3 299.0 3.08 940.1 321.2 2.77 905.5 379.1 2.28
10 1111.4 259.5 4.01 1070.1 284.8 3.53 1037.5 310.0 3.16 1000.5 333.6 2.85 965.7 388.9 2.37
12 1173.1 265.0 4.14 1131.0 293.6 3.63 1102.4 320.5 3.26 1061.0 346.2 2.91 990.1 383.7 2.47
15 1269.8 279.0 4.28 1231.9 306.2 3.80 1206.4 334.3 3.42 1132.7 356.3 3.03 1021.5 377.3 2.58
15.5 1286.0 282.5 4.28 1248.7 309.3 3.81 1223.8 336.6 3.45 1142.9 358.3 3.04 1026.3 375.6 2.61
4.5 999.6 252.8 3.67 960.3 277.9 3.23 928.1 304.1 2.87 875.2 324.2 2.55 823.0 376.3 2.08
5 1007.7 253.7 3.69 968.1 279.0 3.24 935.3 305.3 2.88 882.7 325.3 2.56 825.2 374.4 2.09
6 1040.4 257.6 3.76 999.2 283.1 3.30 964.2 310.4 2.92 913.0 329.8 2.61 834.3 367.0 2.16
7 1072.9 261.4 3.82 1030.4 287.1 3.36 994.3 315.1 2.97 943.2 334.2 2.67 845.0 360.5 2.22
YCIV
1070 8 1105.5 264.9 3.89 1061.6 290.7 3.42 1022.8 317.9 3.03 972.9 338.8 2.72 858.2 355.1 2.29
10 1171.8 271.2 4.03 1127.0 299.8 3.53 1086.1 326.6 3.14 1034.5 349.5 2.80 896.8 350.8 2.42
12 1237.8 276.9 4.18 1192.3 308.0 3.64 1152.6 334.9 3.25 1095.6 360.3 2.88 920.5 348.9 2.50
15 1339.9 291.4 4.31 1298.7 321.3 3.81 1261.4 349.3 3.42 1169.7 370.9 3.00 949.8 343.0 2.62
15.5 1356.9 295.0 4.31 1316.4 324.6 3.83 1279.5 351.7 3.45 1180.2 372.9 3.01 954.1 341.5 2.64
4.5 1110.7 278.7 3.71 1067.2 307.7 3.25 1032.9 338.5 2.87 972.6 360.9 2.55 902.9 407.3 2.11
5 1119.8 279.7 3.72 1075.8 308.8 3.26 1040.6 339.8 2.88 980.7 362.0 2.56 905.3 405.1 2.12
6 1156.0 284.1 3.79 1110.2 313.1 3.32 1071.6 344.6 2.93 1013.2 366.4 2.62 915.1 396.4 2.19
7 1192.2 288.4 3.85 1144.7 317.3 3.38 1104.0 349.1 2.98 1046.1 370.6 2.67 926.9 388.8 2.26
YCIV
1180 8 1228.6 292.6 3.92 1179.2 321.2 3.45 1135.4 351.9 3.04 1078.7 375.1 2.72 939.8 381.6 2.33
10 1303.0 300.3 4.06 1251.7 331.2 3.55 1205.2 361.2 3.15 1145.8 385.5 2.82 980.4 375.8 2.47
12 1377.4 307.4 4.19 1324.5 340.7 3.66 1278.9 370.0 3.27 1212.8 396.0 2.91 1005.3 373.2 2.55
15 1491.0 323.6 4.33 1442.7 355.4 3.83 1399.6 386.0 3.44 1294.8 407.6 3.02 1037.2 367.0 2.67
15.5 1509.9 327.6 4.33 1462.4 359.0 3.85 1419.7 388.6 3.47 1306.4 409.8 3.03 1042.0 365.4 2.70
4.5 1253.7 319.0 3.66 1205.7 347.9 3.24 1167.5 378.3 2.90 1107.3 405.6 2.58 1074.7 486.8 2.10
5 1263.9 320.3 3.67 1215.4 349.4 3.26 1176.5 380.0 2.91 1116.7 407.1 2.59 1081.5 487.0 2.12
6 1304.9 325.5 3.73 1254.4 355.0 3.31 1212.4 386.7 2.95 1154.4 412.9 2.64 1108.8 488.0 2.17
7 1345.5 330.7 3.79 1293.2 360.6 3.36 1250.5 393.7 2.99 1192.5 418.8 2.69 1137.0 489.5 2.21
YCIV
1340 8 1386.4 335.7 3.85 1332.2 365.9 3.42 1287.5 398.8 3.05 1230.1 425.0 2.74 1167.8 492.0 2.26
10 1470.0 344.2 3.99 1413.9 378.3 3.51 1369.4 412.9 3.13 1307.7 439.6 2.82 1250.3 507.8 2.35
12 1552.9 351.4 4.14 1495.8 389.6 3.62 1456.4 426.5 3.23 1385.6 454.3 2.90 1284.6 503.6 2.43
15 1680.9 369.9 4.27 1629.2 406.4 3.79 1593.8 444.9 3.40 1479.2 467.6 3.01 1325.3 495.2 2.55
15.5 1702.2 374.5 4.27 1651.5 410.5 3.80 1616.7 448.0 3.43 1492.5 470.1 3.02 1331.4 493.0 2.58
4.5 1406.7 359.2 3.64 1354.1 390.6 3.24 1311.9 423.3 2.91 1251.3 456.2 2.59 1232.3 558.7 2.10
5 1418.2 360.7 3.66 1364.9 392.3 3.26 1322.0 425.3 2.92 1262.2 458.1 2.60 1240.3 559.3 2.12
6 1463.9 366.8 3.72 1408.4 398.9 3.31 1362.3 433.2 2.96 1305.5 465.6 2.65 1272.4 561.3 2.16
7 1509.3 372.8 3.78 1451.8 405.3 3.36 1404.8 441.3 3.00 1349.5 473.2 2.70 1305.6 563.9 2.21
YCIV
1500 8 1555.0 378.4 3.84 1495.4 411.6 3.41 1446.2 447.2 3.05 1393.3 481.2 2.74 1341.8 567.8 2.26
10 1648.2 387.9 3.97 1586.7 426.0 3.50 1537.8 463.8 3.13 1483.1 499.6 2.82 1438.4 588.3 2.34
12 1739.6 395.9 4.11 1677.9 438.9 3.60 1635.1 479.4 3.23 1573.7 518.5 2.88 1476.3 581.6 2.43
15 1883.0 416.7 4.24 1827.6 457.8 3.77 1789.4 500.1 3.39 1680.1 533.7 3.00 1523.2 571.9 2.54
15.5 1906.9 421.9 4.25 1852.6 462.5 3.76 1815.1 503.5 3.42 1695.1 536.6 3.01 1530.2 569.4 2.57

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.

25
Form No. 201.26 EG 03 (GB 05/08)
STANDARD EFFICIENCY (SE LS) MODELS WITH TWO SPEED FANS - COOLING CAPACITIES
Condenser Coil Entering Air Temperature oC

LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 551.7 155.9 3.36 541.3 159.3 3.17 525.5 173.3 2.84 502.7 189.0 2.51 484.2 233.9 1.97
5 555.5 156.4 3.37 545.5 159.9 3.18 529.4 174.1 2.85 507.0 189.8 2.52 487.3 234.1 1.98
6 570.6 158.7 3.42 562.6 162.3 3.23 545.2 177.0 2.89 524.0 192.7 2.56 499.5 234.8 2.03
7 585.5 160.9 3.46 579.7 164.6 3.29 562.0 180.0 2.93 541.1 195.9 2.61 512.0 235.9 2.07
YCIV
0600 8 600.5 163.0 3.50 596.7 166.8 3.34 578.2 182.1 2.99 557.7 199.1 2.65 525.5 237.6 2.11
10 636.5 167.4 3.62 632.1 172.0 3.44 614.1 186.9 3.09 592.0 206.4 2.72 562.5 245.9 2.18
12 672.3 170.9 3.75 667.6 176.5 3.55 651.9 193.8 3.17 626.2 214.1 2.77 592.3 256.3 2.21
15 737.3 179.3 3.93 727.1 184.1 3.72 713.5 202.2 3.34 668.5 219.5 2.89 611.1 252.1 2.32
15.5 748.1 180.7 3.96 737.1 186.0 3.73 723.7 203.6 3.36 674.5 220.2 2.91 613.9 250.9 2.34
4.5 612.8 171.5 3.41 599.1 175.8 3.20 578.4 191.5 2.85 541.8 201.4 2.54 468.5 205.9 2.15
5 617.1 172.2 3.42 604.0 176.5 3.21 582.9 192.3 2.86 546.7 202.2 2.56 469.7 204.7 2.17
6 634.2 174.8 3.46 623.5 179.3 3.27 601.1 195.6 2.90 566.3 205.3 2.61 474.2 199.9 2.24
7 651.3 177.4 3.51 642.8 181.9 3.32 620.3 199.2 2.94 585.2 208.3 2.66 479.5 195.9 2.31
YCIV
0650 8 668.3 179.7 3.55 662.3 184.3 3.38 638.3 201.2 3.00 603.8 211.5 2.71 485.6 192.4 2.38
10 708.9 184.5 3.68 702.8 190.2 3.48 677.0 205.2 3.12 642.1 218.7 2.79 504.6 189.2 2.51
12 748.7 188.8 3.80 742.7 195.3 3.59 717.4 211.5 3.22 680.4 226.0 2.86 515.7 187.0 2.60
15 821.1 198.1 3.98 809.0 203.7 3.76 785.1 220.6 3.38 726.4 231.7 2.99 532.1 183.8 2.72
15.5 833.2 199.6 4.00 820.0 205.8 3.77 796.4 222.1 3.41 732.9 232.5 3.00 534.5 183.0 2.75
4.5 667.0 185.0 3.43 653.3 189.0 3.23 633.1 205.7 2.89 601.0 221.7 2.56 578.4 267.7 2.06
5 671.7 185.8 3.44 658.5 189.8 3.25 638.0 206.6 2.90 606.0 222.5 2.57 582.0 267.8 2.07
6 690.3 188.7 3.48 679.6 192.8 3.30 657.4 210.2 2.94 626.2 225.8 2.62 596.4 268.4 2.12
7 708.7 191.5 3.53 700.5 195.6 3.36 678.1 213.8 2.99 646.7 228.9 2.67 611.5 269.3 2.17
YCIV
0720 8 727.3 194.2 3.57 721.4 198.4 3.41 698.0 216.5 3.04 666.9 232.4 2.72 628.0 270.7 2.21
10 771.8 199.9 3.69 765.2 204.9 3.51 741.9 222.5 3.15 708.4 240.3 2.80 671.9 279.3 2.30
12 816.0 204.8 3.81 808.7 210.7 3.61 788.5 231.1 3.23 749.5 248.4 2.87 708.1 290.2 2.33
15 894.9 214.9 3.99 880.9 219.8 3.78 862.9 241.0 3.40 800.2 254.7 2.99 730.5 285.4 2.45
15.5 908.1 216.5 4.02 892.9 222.0 3.80 875.3 242.7 3.42 807.4 255.6 3.01 733.9 284.1 2.47
4.5 720.3 199.8 3.44 704.0 206.1 3.21 680.8 226.8 2.84 636.9 239.2 2.52 591.1 270.4 2.09
5 725.4 200.5 3.46 709.7 206.8 3.23 685.9 227.6 2.85 642.2 240.0 2.54 593.0 269.0 2.10
6 745.7 203.4 3.50 732.3 209.7 3.29 706.3 230.8 2.90 663.5 242.9 2.59 600.6 263.5 2.17
7 765.9 206.5 3.55 755.1 212.5 3.35 727.3 233.6 2.95 685.1 245.7 2.65 608.4 258.5 2.24
YCIV
0770 8 786.3 209.5 3.59 777.8 215.2 3.41 747.6 235.3 3.01 706.4 248.6 2.70 616.9 253.7 2.31
10 835.0 216.3 3.70 825.5 222.0 3.51 792.5 239.6 3.14 750.2 255.5 2.79 643.2 249.7 2.45
12 884.0 222.7 3.81 873.3 228.5 3.62 839.8 246.5 3.24 793.9 262.5 2.88 659.1 247.9 2.53
15 969.4 233.6 3.99 951.3 238.3 3.78 919.1 257.2 3.40 847.6 269.1 3.00 680.1 243.7 2.65
15.5 983.6 235.5 4.02 964.2 240.7 3.80 932.3 258.9 3.43 855.2 270.1 3.02 683.2 242.7 2.67
4.5 781.7 213.6 3.49 764.7 218.2 3.29 740.1 237.6 2.94 698.6 253.6 2.61 671.7 300.6 2.13
5 787.2 214.5 3.50 770.9 219.1 3.30 745.8 238.7 2.95 704.5 254.4 2.62 675.9 300.6 2.14
6 809.3 218.1 3.54 795.7 222.6 3.36 768.7 242.8 2.99 728.0 257.7 2.67 692.9 300.9 2.20
7 831.3 221.5 3.58 820.4 226.0 3.41 792.8 247.2 3.03 751.7 261.1 2.73 710.3 301.5 2.25
YCIV
0840 8 853.3 224.8 3.63 845.3 229.2 3.47 816.4 250.3 3.08 775.2 264.7 2.78 729.3 302.6 2.30
10 906.5 231.9 3.74 897.1 237.1 3.57 868.5 257.3 3.20 823.3 273.0 2.86 780.4 311.5 2.39
12 959.3 238.1 3.86 949.3 244.1 3.67 923.7 267.5 3.28 871.6 281.4 2.95 819.7 321.1 2.44
15 1052.0 249.8 4.04 1034.0 254.6 3.84 1010.9 279.0 3.44 930.5 288.6 3.07 845.7 315.8 2.56
15.5 1067.4 251.7 4.07 1048.1 257.3 3.86 1025.4 280.9 3.47 938.8 289.6 3.09 849.6 314.4 2.58
4.5 857.4 235.5 3.47 839.5 239.8 3.28 813.0 260.4 2.94 771.3 279.2 2.61 751.3 337.1 2.13
5 863.4 236.5 3.48 846.3 240.8 3.30 819.3 261.5 2.95 777.9 280.3 2.63 756.2 337.3 2.14
6 887.5 240.3 3.52 873.2 244.8 3.35 844.1 266.3 2.99 804.5 284.5 2.68 775.5 338.1 2.19
7 911.3 244.2 3.56 900.1 248.6 3.40 870.4 271.3 3.03 831.1 288.7 2.73 795.5 339.1 2.24
YCIV
0920 8 935.2 247.9 3.60 927.0 252.4 3.46 896.2 274.8 3.08 857.6 293.1 2.77 817.3 341.1 2.29
10 992.9 255.5 3.72 983.5 261.1 3.55 952.9 282.8 3.19 911.7 303.4 2.85 870.9 349.2 2.39
12 1050.1 262.3 3.83 1040.0 269.0 3.65 1012.9 294.2 3.27 966.2 314.0 2.93 893.2 345.0 2.47
15 1151.6 275.2 4.02 1132.8 280.5 3.82 1108.5 306.8 3.43 1031.5 321.9 3.05 921.6 339.2 2.59
15.5 1168.5 277.3 4.04 1148.3 283.4 3.84 1124.4 308.9 3.46 1040.7 323.0 3.07 925.8 337.7 2.62

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.
°
Fans operate at low speed at 28 C ambient and below.

26
Form No. 201.26 EG 03 (GB 05/08)
Standard Efficiency (SE LS) Models with Two Speed Fans - Cooling Capacities continued

Condenser Coil Entering Air Temperature oC

LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 933.4 257.1 3.46 914.5 261.1 3.28 886.2 282.9 2.95 844.3 304.7 2.62 831.2 373.2 2.13
5 939.9 258.1 3.47 921.8 262.2 3.30 893.0 284.2 2.96 851.7 306.0 2.63 836.7 373.5 2.14
6 965.9 262.4 3.51 951.0 266.7 3.35 919.9 289.6 3.00 881.2 310.9 2.68 858.5 374.7 2.19
7 991.6 266.7 3.55 980.1 271.0 3.40 948.5 295.0 3.04 910.8 315.9 2.73 881.0 376.4 2.24
YCIV
1000 8 1017.3 270.6 3.59 1009.2 275.2 3.45 976.3 299.0 3.09 940.1 321.2 2.78 905.5 379.1 2.28
10 1079.5 278.9 3.70 1070.1 284.8 3.54 1037.5 308.1 3.19 1000.5 333.6 2.85 965.7 388.9 2.38
12 1141.1 286.3 3.82 1131.0 293.6 3.64 1102.4 320.5 3.26 1061.0 346.2 2.92 990.1 383.7 2.47
15 1251.4 300.4 4.00 1231.9 306.2 3.81 1206.4 334.3 3.43 1132.7 355.0 3.04 1021.5 377.3 2.59
15.5 1269.8 302.7 4.03 1248.7 309.3 3.82 1223.8 336.6 3.46 1142.9 356.2 3.06 1026.3 375.6 2.61
4.5 982.1 270.5 3.46 960.3 277.9 3.24 928.1 304.1 2.87 875.2 324.2 2.55 823.0 376.3 2.08
5 989.1 271.5 3.47 968.1 279.0 3.25 935.3 305.3 2.89 882.7 325.3 2.57 825.2 374.4 2.10
6 1016.8 275.5 3.52 999.2 283.1 3.31 964.2 310.4 2.93 913.0 329.8 2.62 834.3 367.0 2.16
YCIV 7 1044.3 279.5 3.56 1030.4 287.1 3.37 994.3 315.1 2.98 943.2 334.2 2.67 845.0 360.5 2.23
1070 8 1071.9 283.2 3.61 1061.6 290.7 3.43 1022.8 317.9 3.04 972.9 338.8 2.72 858.2 355.1 2.29
10 1138.2 291.5 3.73 1127.0 299.8 3.54 1086.1 324.6 3.16 1034.5 349.5 2.81 896.8 350.8 2.43
12 1204.1 299.0 3.85 1192.3 308.0 3.65 1152.6 334.9 3.26 1095.6 360.3 2.89 920.5 348.9 2.50
15 1320.5 313.7 4.03 1298.7 321.3 3.82 1261.4 349.3 3.43 1169.7 369.4 3.01 949.8 343.0 2.62
15.5 1339.9 316.2 4.06 1316.4 324.6 3.83 1279.5 351.7 3.45 1180.2 370.7 3.03 954.1 341.5 2.65
4.5 1091.3 298.1 3.49 1067.2 307.7 3.25 1032.9 338.5 2.88 972.6 360.9 2.55 902.9 407.3 2.11
5 1099.0 299.3 3.50 1075.8 308.8 3.27 1040.6 339.8 2.89 980.7 362.0 2.57 905.3 405.1 2.13
6 1129.7 303.9 3.55 1110.2 313.1 3.33 1071.6 344.6 2.94 1013.2 366.4 2.62 915.1 396.4 2.20
7 1160.5 308.4 3.59 1144.7 317.3 3.39 1104.0 349.1 2.99 1046.1 370.6 2.68 926.9 388.8 2.27
YCIV
1180 8 1191.4 312.8 3.64 1179.2 321.2 3.45 1135.4 351.9 3.05 1078.7 375.1 2.73 939.8 381.6 2.34
10 1257.7 322.7 3.73 1244.3 331.2 3.54 1194.8 359.0 3.15 1129.9 385.5 2.78 959.4 375.8 2.42
12 1339.8 332.1 3.86 1324.5 340.7 3.67 1278.9 370.0 3.28 1212.8 396.0 2.91 1005.3 373.2 2.55
15 1469.4 348.4 4.05 1442.7 355.4 3.84 1399.6 386.0 3.45 1294.8 406.0 3.04 1037.2 367.0 2.68
15.5 1490.9 351.1 4.08 1462.4 359.0 3.86 1419.7 388.6 3.47 1306.4 407.4 3.05 1042.0 365.4 2.70
4.5 1231.8 341.3 3.44 1205.7 347.9 3.25 1167.5 378.3 2.91 1107.3 405.6 2.58 1074.7 486.8 2.11
5 1240.5 342.7 3.45 1215.4 349.4 3.26 1176.5 380.0 2.92 1116.7 407.1 2.60 1081.5 487.0 2.12
6 1275.2 348.2 3.49 1254.4 355.0 3.32 1212.4 386.7 2.96 1154.4 412.9 2.65 1108.8 488.0 2.17
YCIV 7 1309.7 353.6 3.54 1293.2 360.6 3.37 1250.5 393.7 3.00 1192.5 418.8 2.70 1137.0 489.5 2.22
1340 8 1344.3 358.9 3.58 1332.2 365.9 3.42 1287.5 398.8 3.05 1230.1 425.0 2.74 1167.8 492.0 2.27
10 1427.8 369.9 3.69 1413.9 378.3 3.52 1369.4 410.3 3.16 1307.7 439.6 2.83 1250.3 507.8 2.35
12 1510.5 379.6 3.81 1495.8 389.6 3.62 1456.4 426.5 3.24 1385.6 454.3 2.90 1284.6 503.6 2.44
15 1656.5 398.2 3.99 1629.2 406.4 3.79 1593.8 444.9 3.40 1479.2 465.8 3.03 1325.3 495.2 2.56
15.5 1680.8 401.3 4.02 1651.5 410.5 3.81 1616.7 448.0 3.43 1492.5 467.4 3.04 1331.4 493.0 2.58
4.5 1382.2 384.3 3.43 1354.1 390.6 3.25 1311.9 423.3 2.92 1251.3 456.2 2.59 1232.3 558.7 2.11
5 1391.9 385.9 3.44 1364.9 392.3 3.26 1322.0 425.3 2.93 1262.2 458.1 2.61 1240.3 559.3 2.12
6 1430.6 392.3 3.48 1408.4 398.9 3.31 1362.3 433.2 2.97 1305.5 465.6 2.65 1272.4 561.3 2.17
YCIV 7 1469.1 398.6 3.52 1451.8 405.3 3.37 1404.8 441.3 3.01 1349.5 473.2 2.70 1305.6 563.9 2.21
1500 8 1507.8 404.5 3.56 1495.4 411.6 3.42 1446.2 447.2 3.06 1393.3 481.2 2.75 1341.8 567.8 2.26
10 1600.8 416.9 3.67 1586.7 426.0 3.51 1537.8 460.9 3.16 1483.1 499.6 2.82 1438.4 588.3 2.34
12 1692.1 427.6 3.79 1677.9 438.9 3.61 1635.1 479.4 3.23 1573.7 518.5 2.89 1476.3 581.6 2.43
15 1855.7 448.7 3.97 1827.6 457.8 3.78 1789.4 500.1 3.40 1680.1 531.6 3.01 1523.2 571.9 2.55
15.5 1882.9 452.1 4.00 1852.6 462.5 3.79 1815.1 503.5 3.43 1695.1 533.5 3.03 1530.2 569.4 2.57

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.
°
Fans operate at low speed at 28 C ambient and below.

27
Form No. 201.26 EG 03 (GB 05/08)
STANDARD EFFICIENCY (SE LS) MODELS WITH TWO SPEED FANS (HIGH SPEED INHIBITED) -
COOLING CAPACITIES

LWT °C Condenser Coil Entering Air Temperature oC


Model 25 30 35 40
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 551.7 155.9 3.36 529.9 170.0 2.97 510.3 185.7 2.63 485.6 202.4 2.30
5 555.5 156.4 3.37 533.9 170.8 2.98 514.6 186.5 2.64 488.2 202.4 2.32
6 570.6 158.7 3.42 549.9 174.0 3.01 532.2 189.7 2.69 498.8 202.2 2.37
7 585.5 160.9 3.46 565.9 177.1 3.05 547.2 193.1 2.72 509.4 202.1 2.42
YCIV
0600 8 600.5 163.0 3.50 581.8 180.0 3.09 562.0 196.4 2.74 519.7 202.0 2.47
10 636.5 167.4 3.62 616.3 186.5 3.16 596.5 203.6 2.81 536.9 201.7 2.56
12 672.3 170.9 3.75 650.7 192.1 3.25 631.4 210.4 2.89 544.8 201.3 2.60
15 737.3 179.3 3.93 708.2 201.8 3.37 657.8 201.8 3.13 557.6 197.7 2.71
15.5 748.1 181.4 3.94 717.8 204.3 3.38 662.2 199.6 3.18 560.4 197.1 2.73
4.5 612.8 171.5 3.41 586.5 187.6 2.99 561.6 205.1 2.63 523.3 215.7 2.34
5 617.1 172.2 3.42 591.1 188.5 3.00 566.6 206.0 2.64 526.5 215.6 2.35
6 634.2 174.8 3.46 609.4 192.2 3.04 586.8 209.7 2.69 539.0 215.3 2.41
YCIV 7 651.3 177.4 3.51 627.6 195.7 3.08 603.9 213.7 2.72 551.0 214.9 2.47
0650 8 668.3 179.7 3.55 645.9 199.0 3.11 620.4 217.0 2.75 562.7 214.6 2.52
10 708.9 184.5 3.68 685.2 206.2 3.19 657.6 223.6 2.83 582.2 213.7 2.62
12 748.7 188.8 3.80 724.0 212.6 3.28 694.8 229.5 2.92 592.0 212.6 2.68
15 821.1 198.1 3.98 787.9 223.4 3.40 723.9 220.2 3.17 605.9 208.7 2.79
15.5 833.2 200.4 3.99 798.5 226.1 3.41 728.7 217.8 3.22 608.9 208.1 2.81
4.5 667.0 185.0 3.43 639.5 201.7 3.03 614.7 220.4 2.67 580.4 237.5 2.35
5 671.7 185.8 3.44 644.5 202.7 3.04 620.1 221.3 2.69 583.6 237.3 2.36
6 690.3 188.7 3.48 664.3 206.7 3.07 641.7 225.3 2.73 596.1 236.8 2.42
7 708.7 191.5 3.53 683.9 210.5 3.11 660.2 229.4 2.76 608.9 236.2 2.48
YCIV
0720 8 727.3 194.2 3.57 703.5 214.1 3.15 678.4 233.5 2.79 621.5 235.8 2.53
10 771.8 199.9 3.69 746.0 222.1 3.22 720.7 242.4 2.86 642.4 234.7 2.63
12 816.0 204.8 3.81 788.4 229.3 3.30 763.6 250.8 2.93 652.2 233.6 2.68
15 894.9 214.9 3.99 858.0 240.9 3.43 795.6 240.5 3.18 667.5 229.4 2.79
15.5 908.1 217.4 4.00 869.6 243.8 3.43 800.9 238.0 3.24 670.7 228.7 2.82
4.5 720.3 199.8 3.44 689.2 219.9 3.00 661.0 243.0 2.62 615.1 256.2 2.32
5 725.4 200.5 3.46 694.5 220.9 3.01 666.7 243.9 2.63 618.4 255.9 2.33
6 745.7 203.4 3.50 715.8 224.8 3.06 689.5 247.3 2.69 631.6 254.8 2.39
7 765.9 206.5 3.55 737.2 228.6 3.10 708.1 250.6 2.72 645.0 253.5 2.45
YCIV
0770 8 786.3 209.5 3.59 758.5 232.3 3.14 726.6 253.8 2.76 658.3 252.3 2.51
10 835.0 216.3 3.70 804.8 240.7 3.22 769.8 261.1 2.85 680.3 249.6 2.63
12 884.0 222.7 3.81 851.3 248.6 3.30 813.4 267.6 2.94 690.8 246.9 2.69
15 969.4 233.6 3.99 926.5 261.2 3.42 847.4 256.6 3.19 707.0 242.5 2.81
15.5 983.6 236.4 4.00 939.0 264.4 3.43 853.1 253.9 3.24 710.5 241.7 2.83
4.5 781.7 213.6 3.49 748.7 232.8 3.08 718.6 254.5 2.71 674.7 271.5 2.39
5 787.2 214.5 3.50 754.5 234.0 3.09 724.9 255.7 2.72 678.4 271.3 2.41
6 809.3 218.1 3.54 777.8 238.6 3.12 750.3 260.3 2.77 693.0 270.3 2.47
7 831.3 221.5 3.58 801.0 243.2 3.16 771.9 265.3 2.80 707.8 269.3 2.53
YCIV
0840 8 853.3 224.8 3.63 824.3 247.4 3.20 793.5 269.9 2.83 722.4 268.6 2.59
10 906.5 231.9 3.74 874.7 257.0 3.27 843.6 280.3 2.90 746.5 266.7 2.69
12 959.3 238.1 3.86 925.3 265.7 3.35 894.6 290.3 2.97 758.4 264.7 2.76
15 1052.0 249.8 4.04 1007.1 279.2 3.48 932.1 278.4 3.23 776.2 260.0 2.87
15.5 1067.4 252.7 4.06 1020.7 282.5 3.48 938.3 275.5 3.28 780.0 259.2 2.89
4.5 857.4 235.5 3.47 821.9 255.9 3.07 789.5 278.9 2.72 744.9 299.0 2.40
5 863.4 236.5 3.48 828.2 257.2 3.08 796.4 280.2 2.73 749.1 298.9 2.41
6 887.5 240.3 3.52 853.5 262.4 3.12 824.0 285.4 2.77 765.8 298.4 2.47
7 911.3 244.2 3.56 878.8 267.4 3.15 847.5 291.1 2.80 782.6 297.8 2.53
YCIV
0920 8 935.2 247.9 3.60 904.0 272.4 3.18 871.0 296.3 2.83 799.1 297.5 2.59
10 992.9 255.5 3.72 958.9 283.0 3.26 925.5 308.1 2.90 826.7 296.4 2.68
12 1050.1 262.3 3.83 1013.8 292.7 3.33 981.0 319.2 2.97 840.7 295.3 2.74
15 1151.6 275.2 4.02 1103.3 307.5 3.46 1022.1 306.2 3.22 860.4 290.0 2.85
15.5 1168.5 278.4 4.03 1118.3 311.3 3.76 1028.9 302.9 3.27 864.6 289.1 2.88

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors.
EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.

28
Form No. 201.26 EG 03 (GB 05/08)
Standard Efficiency (SE LS) Models with Two Speed Fans (High Speed Inhibited) - Cooling Capacities
continued

LWT °C
Condenser Coil Entering Air Temperature oC
Model 25 30 35 40
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 933.4 257.1 3.46 895.3 278.6 3.07 860.5 303.0 2.73 815.4 326.3 2.41
5 939.9 258.1 3.47 902.2 280.1 3.08 868.0 304.5 2.74 820.1 326.3 2.42
6 965.9 262.4 3.51 929.5 285.9 3.11 897.9 310.4 2.78 838.8 326.1 2.48
7 991.6 266.7 3.55 956.8 291.6 3.15 923.4 316.5 2.81 857.6 325.9 2.53
YCIV
1000 8 1017.3 270.6 3.59 984.2 297.0 3.18 948.9 322.4 2.83 876.1 326.0 2.59
10 1079.5 278.9 3.70 1043.4 308.8 3.25 1007.7 335.6 2.89 907.2 325.9 2.68
12 1141.1 286.3 3.82 1102.5 319.5 3.32 1067.7 347.8 2.96 923.2 325.6 2.73
15 1251.4 300.4 4.00 1199.8 335.7 3.44 1112.4 333.6 3.21 944.9 319.8 2.84
15.5 1269.8 303.9 4.01 1216.1 339.7 3.45 1119.8 330.0 3.27 949.5 318.8 2.86
4.5 982.1 270.5 3.46 940.1 296.6 3.03 901.2 325.7 2.66 845.3 347.1 2.34
5 989.1 271.5 3.47 947.4 298.0 3.04 909.2 327.1 2.67 850.0 346.9 2.36
6 1016.8 275.5 3.52 976.7 303.5 3.08 941.2 332.7 2.72 869.1 345.9 2.42
7 1044.3 279.5 3.56 1006.0 308.8 3.12 968.0 338.1 2.75 888.0 344.8 2.48
YCIV
1070 8 1071.9 283.2 3.61 1035.3 313.8 3.16 994.2 342.8 2.79 906.6 343.9 2.54
10 1138.2 291.5 3.73 1098.8 325.0 3.24 1054.9 353.6 2.87 938.0 341.5 2.64
12 1204.1 299.0 3.85 1162.2 335.3 3.33 1116.3 363.4 2.96 953.3 338.9 2.70
15 1320.5 313.7 4.03 1264.9 352.2 3.46 1163.0 348.6 3.21 975.7 332.8 2.82
15.5 1339.9 317.4 4.05 1281.9 356.5 3.46 1170.8 344.9 3.27 980.5 331.8 2.84
4.5 1091.3 298.1 3.49 1044.8 328.4 3.05 1002.9 362.6 2.66 939.3 386.4 2.34
5 1099.0 299.3 3.50 1052.9 329.8 3.06 1011.6 364.0 2.67 944.4 386.0 2.36
6 1129.7 303.9 3.55 1085.2 335.7 3.10 1046.0 369.4 2.72 964.5 384.3 2.42
7 1160.5 308.4 3.59 1117.5 341.3 3.14 1074.9 374.6 2.76 985.0 382.4 2.48
YCIV
1180 8 1191.4 312.8 3.64 1149.9 346.7 3.18 1103.6 379.6 2.80 1005.2 380.6 2.54
10 1257.7 322.7 3.73 1220.4 359.1 3.27 1170.6 391.1 2.88 1039.0 376.6 2.66
12 1339.8 332.1 3.86 1291.1 370.8 3.35 1238.6 401.6 2.98 1055.3 372.5 2.73
15 1469.4 348.4 4.05 1405.1 389.6 3.48 1290.5 385.1 3.23 1080.0 365.8 2.84
15.5 1490.9 352.5 4.06 1424.1 394.3 3.48 1299.1 381.0 3.28 1085.3 364.7 2.86
4.5 1231.8 341.3 3.44 1180.3 371.3 3.04 1133.6 405.3 2.69 1069.4 434.4 2.37
5 1240.5 342.7 3.45 1189.5 373.2 3.05 1143.6 407.1 2.70 1075.3 434.1 2.38
6 1275.2 348.2 3.49 1226.1 380.6 3.09 1183.5 414.4 2.74 1098.9 433.1 2.44
YCIV 7 1309.7 353.6 3.54 1262.5 387.9 3.12 1217.4 422.4 2.77 1122.8 432.1 2.50
1340 8 1344.3 358.9 3.58 1299.1 395.0 3.15 1251.4 430.1 2.80 1146.3 431.3 2.56
10 1427.8 369.9 3.69 1378.5 410.1 3.23 1330.1 447.0 2.87 1185.8 429.5 2.66
12 1510.5 379.6 3.81 1458.0 424.1 3.31 1410.5 462.9 2.94 1205.6 427.3 2.71
15 1656.5 398.2 3.99 1586.8 445.5 3.43 1469.5 444.0 3.19 1233.9 419.6 2.83
15.5 1680.8 402.9 4.01 1608.3 450.9 3.44 1479.3 439.2 3.24 1239.9 418.3 2.85
4.5 1382.2 384.3 3.43 1325.6 416.8 3.04 1273.9 453.4 2.70 1208.5 488.5 2.38
5 1391.9 385.9 3.44 1335.8 419.0 3.05 1285.1 455.6 2.71 1215.4 488.5 2.40
6 1430.6 392.3 3.48 1376.6 427.6 3.08 1329.8 464.3 2.75 1242.7 488.4 2.45
YCIV 7 1469.1 398.6 3.52 1417.4 436.0 3.12 1367.7 473.5 2.78 1270.7 488.1 2.51
1500 8 1507.8 404.5 3.56 1458.3 444.3 3.15 1405.7 482.3 2.80 1298.3 488.3 2.56
10 1600.8 416.9 3.67 1547.0 461.8 3.22 1493.7 502.1 2.87 1344.9 488.1 2.65
12 1692.1 427.6 3.79 1635.6 477.7 3.29 1583.6 520.3 2.94 1369.3 487.7 2.70
15 1855.7 448.7 3.97 1780.1 501.9 3.42 1649.9 499.0 3.19 1401.4 478.9 2.81
15.5 1882.9 453.9 3.98 1804.1 508.0 3.44 1660.9 493.7 3.24 1408.3 477.5 2.84

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors.
EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.

29
Form No. 201.26 EG 03 (GB 05/08)
HIGH EFFICIENCY (HE AND HE RS) MODELS WITH STANDARD FANS - COOLING CAPACITIES
Condenser Coil Entering Air Temperature oC
LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 557.5 134.6 3.80 535.9 145.4 3.40 516.8 156.6 3.06 493.3 170.0 2.71 467.2 207.3 2.13
5 562.1 135.1 4.16 540.3 146.1 3.42 521.0 157.4 3.08 497.8 170.8 2.72 469.4 206.7 2.15
6 580.4 137.4 4.22 558.0 148.8 3.47 537.8 160.5 3.12 515.6 173.8 2.77 478.4 204.5 2.21
7 598.3 139.6 4.29 575.7 151.3 3.53 555.5 163.6 3.16 533.4 176.9 2.82 487.0 202.3 2.27
YCIV
8 616.2 141.6 4.35 593.3 153.7 3.58 572.6 165.9 3.22 551.1 180.2 2.87 493.5 199.0 2.34
0590
10 652.5 144.7 4.51 630.0 159.0 3.68 610.2 172.2 3.31 587.2 187.7 2.94 515.1 197.1 2.46
12 688.3 147.0 4.68 666.4 163.6 3.80 649.8 178.2 3.42 623.0 195.3 3.00 526.9 196.0 2.53
15 745.1 154.7 4.82 725.9 170.6 3.98 711.1 185.9 3.59 665.1 201.1 3.12 543.6 192.7 2.66
15.5 754.5 156.0 4.84 735.8 171.8 4.00 721.4 187.1 3.62 671.1 202.2 3.13 546.1 191.9 2.68
4.5 593.3 141.2 3.83 571.9 153.9 3.42 554.8 167.4 3.07 530.7 182.8 2.70 515.9 228.3 2.13
5 598.2 141.8 3.85 576.5 154.6 3.43 559.1 168.1 3.08 535.4 183.6 2.72 519.1 228.5 2.15
6 617.7 144.1 3.92 595.2 157.0 3.49 576.4 171.0 3.12 554.4 186.6 2.77 532.3 229.2 2.19
7 637.0 146.3 3.99 613.7 159.4 3.55 594.7 173.9 3.17 573.5 189.5 2.82 546.1 230.0 2.24
YCIV
8 656.3 148.5 4.05 632.3 161.5 3.61 612.5 176.0 3.23 592.5 192.8 2.87 561.0 231.5 2.29
0630
10 695.8 152.1 4.20 671.2 166.8 3.72 651.8 181.9 3.34 631.7 200.3 2.96 601.1 239.4 2.38
12 735.3 155.2 4.36 710.2 171.6 3.84 693.5 187.6 3.45 671.2 208.0 3.03 634.0 249.5 2.41
15 795.9 163.3 4.50 773.6 179.0 4.02 758.9 195.7 3.63 716.6 214.1 3.15 654.1 245.3 2.53
15.5 806.0 164.7 4.52 784.2 180.2 4.05 769.8 197.0 3.66 723.0 215.3 3.16 657.2 244.2 2.55
4.5 659.4 156.8 3.84 635.5 171.7 3.40 616.0 187.5 3.04 589.1 204.1 2.69 573.2 248.5 2.18
5 664.8 157.4 3.86 640.7 172.4 3.42 620.9 188.3 3.05 594.4 204.8 2.70 577.0 248.6 2.19
6 686.3 159.8 3.92 661.4 174.9 3.48 640.3 191.2 3.10 615.5 207.7 2.76 592.2 249.0 2.24
7 707.6 162.3 3.99 682.0 177.3 3.55 660.7 194.3 3.16 636.9 210.6 2.82 607.7 249.6 2.30
YCIV
8 728.7 164.4 4.06 702.6 179.7 3.61 680.6 196.5 3.22 658.1 213.7 2.88 624.5 250.7 2.35
0700
10 771.9 168.3 4.21 745.3 185.2 3.72 724.1 202.8 3.32 702.0 221.1 2.97 660.1 252.2 2.47
12 814.6 171.5 4.37 788.0 190.3 3.84 770.0 208.9 3.44 745.7 228.5 3.06 682.3 252.5 2.55
15 881.8 180.5 4.51 858.3 198.5 4.02 842.7 217.9 3.62 796.1 235.2 3.18 703.9 248.2 2.67
15.5 893.0 182.0 4.53 870.0 199.9 4.05 854.8 219.4 3.65 803.2 236.5 3.19 707.2 247.1 2.70
4.5 714.6 169.6 3.87 687.7 187.3 3.40 666.3 206.8 3.00 638.6 228.2 2.63 558.1 235.0 2.23
5 720.4 170.3 3.89 693.3 187.9 3.42 671.5 207.5 3.02 644.0 228.8 2.64 561.5 234.7 2.25
6 743.8 173.0 3.96 715.6 190.3 3.49 692.2 210.3 3.07 665.9 231.3 2.70 575.0 233.7 2.31
7 767.1 175.6 4.02 737.8 192.7 3.55 714.0 213.2 3.13 687.8 233.9 2.76 588.5 232.7 2.38
YCIV
8 790.4 178.3 4.09 760.1 195.1 3.62 735.3 215.2 3.19 709.6 236.4 2.82 602.0 231.7 2.44
0760
10 838.1 183.4 4.23 806.9 201.1 3.73 782.3 221.4 3.31 754.5 242.7 2.93 628.9 229.7 2.57
12 885.8 188.4 4.35 853.7 207.0 3.85 832.3 227.6 3.43 799.5 249.0 3.03 642.6 227.5 2.65
15 958.8 198.3 4.50 929.9 215.9 4.03 910.9 237.4 3.61 853.5 256.3 3.15 663.0 223.7 2.78
15.5 971.0 199.9 4.52 942.6 217.4 4.06 924.0 239.0 3.64 861.2 257.7 3.16 666.1 222.7 2.80
4.5 759.6 178.5 3.90 731.6 196.2 3.44 709.7 215.5 3.06 679.7 236.1 2.69 649.6 256.8 2.38
5 765.9 179.2 3.91 737.5 196.9 3.46 715.2 216.3 3.07 685.7 237.0 2.71 656.2 257.6 2.39
6 790.8 182.1 3.98 761.2 199.5 3.52 737.1 219.5 3.12 709.8 240.2 2.77 682.4 260.8 2.46
7 815.5 184.9 4.05 784.9 202.2 3.59 760.4 222.7 3.18 734.1 243.3 2.83 707.7 263.9 2.52
YCIV
8 840.4 187.8 4.11 808.7 204.8 3.65 783.1 225.0 3.24 758.2 246.6 2.88 733.4 268.3 2.57
0800
10 891.2 192.9 4.26 858.5 211.3 3.77 833.1 231.7 3.36 808.3 254.5 2.98 783.4 277.3 2.67
12 941.4 197.8 4.39 908.2 217.5 3.88 886.2 238.5 3.48 857.0 262.1 3.08 827.8 285.7 2.74
15 1019.0 208.2 4.54 989.3 226.8 4.07 969.9 248.8 3.66 915.0 269.8 3.20 860.1 290.8 2.80
15.5 1031.9 209.9 4.56 1002.8 228.4 4.10 983.8 250.5 3.68 923.2 271.2 3.21 862.6 292.0 2.80
4.5 789.1 184.9 3.89 760.7 201.7 3.46 738.2 220.0 3.10 710.5 241.6 2.74 693.3 293.2 2.23
5 795.6 185.7 3.91 766.9 202.5 3.48 743.9 220.9 3.11 717.1 242.6 2.75 697.9 293.1 2.24
6 821.5 188.6 3.98 791.5 205.7 3.54 766.9 224.5 3.16 743.4 246.7 2.81 716.0 293.1 2.30
7 847.2 191.7 4.04 816.2 208.6 3.60 791.2 228.1 3.21 770.0 250.9 2.86 734.3 293.6 2.36
YCIV
8 873.0 194.5 4.11 841.0 211.5 3.67 814.9 230.7 3.28 796.7 255.2 2.92 754.4 294.6 2.41
0830
10 925.4 199.4 4.26 892.8 218.4 3.78 867.2 238.2 3.38 849.2 264.0 3.01 808.3 302.9 2.52
12 976.8 203.8 4.41 943.6 224.5 3.89 921.9 245.6 3.50 899.7 272.1 3.10 852.5 313.9 2.57
15 1057.4 214.5 4.55 1027.9 234.2 4.08 1008.9 256.2 3.68 960.6 280.1 3.22 879.5 308.7 2.69
15.5 1070.8 216.2 4.57 1041.9 235.8 4.11 1023.4 257.9 3.71 969.2 281.6 3.23 883.6 307.3 2.72

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.

30
Form No. 201.26 EG 03 (GB 05/08)
High Efficiency (HE and HE RS) Models with Standard Fans - Cooling Capacities continued

Condenser Coil Entering Air Temperature oC

LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 876.1 213.1 3.79 843.6 231.8 3.38 817.7 252.0 3.03 782.2 273.5 2.68 765.9 333.4 2.18
5 883.3 214.0 3.81 850.4 232.8 3.39 824.0 253.1 3.04 789.3 274.7 2.70 770.9 333.5 2.19
6 911.8 217.5 3.87 877.6 236.7 3.45 849.2 257.5 3.08 817.5 279.2 2.75 790.9 334.2 2.25
7 940.1 221.2 3.93 904.8 240.3 3.50 875.9 262.1 3.13 845.9 283.8 2.80 811.4 335.3 2.30
YCIV
8 968.6 224.6 3.99 932.1 243.9 3.56 902.0 265.4 3.18 874.2 288.7 2.85 834.0 337.1 2.35
0930
10 1026.9 230.4 4.13 989.1 252.4 3.66 959.4 274.8 3.28 930.5 299.1 2.93 889.2 344.8 2.45
12 1084.6 235.6 4.28 1046.2 260.0 3.76 1020.3 283.9 3.38 986.6 309.4 3.01 912.0 340.0 2.55
15 1174.1 247.9 4.41 1139.6 271.2 3.94 1116.6 296.1 3.55 1053.3 318.4 3.13 941.0 334.4 2.67
15.5 1189.0 250.0 4.44 1155.1 273.1 3.97 1132.7 298.2 3.58 1062.7 320.2 3.14 945.3 332.9 2.69
4.5 985.2 234.4 3.86 947.4 257.6 3.40 916.1 282.4 3.02 877.0 310.4 2.65 842.2 373.8 2.13
5 993.3 235.3 3.87 955.1 258.5 3.42 923.4 283.4 3.03 884.9 311.4 2.66 847.8 373.9 2.15
6 1025.7 239.0 3.94 986.3 262.1 3.48 952.3 287.8 3.08 916.2 315.6 2.72 870.1 374.3 2.20
7 1057.9 242.7 4.01 1017.3 265.7 3.55 983.1 292.2 3.14 947.5 319.7 2.78 892.9 375.0 2.25
YCIV
8 1090.2 246.1 4.08 1048.5 269.1 3.61 1012.9 295.1 3.20 977.8 324.0 2.83 917.7 376.6 2.31
1050
10 1156.0 252.4 4.23 1113.6 277.5 3.73 1078.8 304.4 3.32 1040.8 333.9 2.93 983.9 387.7 2.41
12 1221.5 258.3 4.37 1178.8 285.4 3.85 1148.7 313.3 3.44 1103.9 344.0 3.02 1038.9 401.9 2.46
15 1322.2 271.9 4.51 1284.0 297.7 4.03 1257.1 326.8 3.61 1178.5 354.1 3.14 1071.8 395.2 2.58
15.5 1339.0 274.1 4.54 1301.5 299.7 4.06 1275.1 329.1 3.64 1189.1 356.0 3.15 1076.8 393.4 2.60
4.5 1048.4 246.4 3.88 1008.5 271.9 3.41 976.2 299.6 3.02 937.1 332.2 2.63 902.2 397.2 2.14
5 1057.1 247.4 3.90 1016.7 272.8 3.43 983.9 300.7 3.03 945.5 333.2 2.65 908.0 397.2 2.16
6 1091.6 251.2 3.97 1049.8 276.4 3.50 1014.6 305.0 3.08 979.1 337.6 2.71 931.6 397.1 2.21
7 1126.0 255.1 4.03 1082.8 279.8 3.56 1047.0 309.3 3.14 1011.8 341.3 2.77 955.7 397.5 2.27
YCIV
8 1160.5 258.9 4.10 1115.9 283.3 3.63 1078.6 312.1 3.21 1044.0 345.2 2.83 982.0 398.5 2.32
1120
10 1231.0 266.0 4.24 1185.3 291.8 3.75 1148.5 321.2 3.33 1111.1 354.4 2.94 1052.5 408.8 2.43
12 1301.4 273.3 4.38 1254.8 300.3 3.87 1222.8 330.1 3.45 1178.1 363.9 3.04 1110.9 422.2 2.49
15 1408.7 287.7 4.52 1366.8 313.2 4.05 1338.2 344.3 3.63 1257.8 374.5 3.16 1146.2 415.2 2.61
15.5 1426.6 290.1 4.54 1385.5 315.4 4.08 1357.4 346.7 3.66 1269.0 376.6 3.17 1151.4 413.4 2.63
4.5 1139.6 271.3 3.86 1096.7 298.1 3.40 1062.7 327.5 3.02 1014.7 357.7 2.66 981.7 429.6 2.16
5 1149.0 272.3 3.88 1105.6 299.1 3.42 1071.0 328.7 3.04 1023.6 358.8 2.67 987.9 429.6 2.18
6 1186.6 276.6 3.95 1141.3 303.3 3.49 1103.9 333.6 3.09 1058.9 363.5 2.73 1012.9 429.6 2.23
7 1224.1 281.0 4.01 1177.0 307.4 3.55 1139.0 338.4 3.14 1094.8 368.0 2.79 1038.7 430.0 2.29
YCIV
8 1261.6 285.3 4.08 1212.9 311.3 3.62 1172.9 342.0 3.21 1130.4 372.9 2.85 1066.9 431.2 2.34
1220
10 1338.5 293.1 4.22 1288.1 321.3 3.73 1248.5 352.4 3.32 1204.1 384.4 2.95 1142.5 442.7 2.45
12 1415.6 300.7 4.36 1363.5 330.8 3.84 1328.6 362.9 3.43 1276.2 395.4 3.04 1204.8 457.7 2.50
15 1532.4 316.5 4.50 1485.2 345.0 4.02 1454.0 378.6 3.61 1362.5 407.0 3.16 1243.0 450.1 2.62
15.5 1551.8 319.1 4.52 1505.5 347.4 4.05 1474.9 381.2 3.64 1374.7 409.2 3.17 1248.8 448.1 2.65
4.5 1292.5 313.9 3.79 1242.5 340.6 3.38 1201.5 368.9 3.04 1148.2 400.8 2.68 1125.4 491.0 2.17
5 1303.1 315.3 3.81 1252.7 342.0 3.39 1211.0 370.5 3.05 1158.6 402.4 2.70 1133.0 491.3 2.19
6 1345.6 320.9 3.87 1293.5 347.9 3.45 1249.0 377.2 3.09 1200.4 409.1 2.75 1163.5 492.4 2.24
7 1387.7 326.3 3.93 1334.2 353.5 3.51 1289.2 384.1 3.14 1242.8 415.8 2.81 1194.7 494.3 2.29
YCIV
8 1430.1 331.4 3.99 1375.0 359.0 3.56 1328.2 389.3 3.19 1284.9 423.0 2.86 1228.9 497.2 2.34
1380
10 1516.4 340.4 4.13 1460.3 371.9 3.66 1414.5 403.5 3.29 1371.8 439.6 2.94 1319.8 514.1 2.44
12 1602.2 348.2 4.27 1545.6 383.6 3.76 1505.8 417.4 3.39 1457.8 456.2 3.02 1395.1 535.6 2.48
15 1734.3 366.5 4.41 1683.5 400.1 3.94 1647.9 435.4 3.56 1556.3 469.5 3.13 1439.4 526.6 2.60
15.5 1756.4 369.5 4.43 1706.5 402.9 3.97 1671.6 438.4 3.59 1570.3 472.1 3.15 1446.1 524.3 2.62

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.

31
Form No. 201.26 EG 03 (GB 05/08)
HIGH EFFICIENCY (HE LS) MODELS WITH TWO SPEED FANS - COOLING CAPACITIES
Condenser Coil Entering Air Temperature oC

LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 547.8 144.0 3.59 535.9 145.4 3.41 516.8 156.6 3.07 493.3 170.0 2.72 467.2 207.3 2.13
5 551.6 144.6 3.61 540.3 146.1 3.43 521.0 157.4 3.08 497.8 170.8 2.73 469.4 206.7 2.15
6 567.2 147.0 3.65 558.0 148.8 3.48 537.8 160.5 3.13 515.6 173.8 2.78 478.4 204.5 2.21
7 582.4 149.2 3.69 575.7 151.3 3.53 555.5 163.6 3.17 533.4 176.9 2.83 487.0 202.3 2.28
YCIV
8 597.6 151.4 3.74 593.3 153.7 3.59 572.6 165.9 3.23 551.1 180.2 2.87 493.5 199.0 2.34
0590
10 633.8 155.5 3.87 630.0 159.0 3.69 610.2 171.2 3.34 587.2 187.7 2.95 515.1 197.1 2.47
12 669.5 158.8 4.01 666.4 163.6 3.80 649.8 178.2 3.42 623.0 195.3 3.01 526.9 196.0 2.54
15 734.3 166.6 4.20 725.9 170.6 3.98 711.1 185.9 3.60 665.1 200.3 3.14 543.6 192.7 2.66
15.5 745.1 167.9 4.23 735.8 172.3 4.00 721.4 187.1 3.63 671.1 201.0 3.16 546.1 191.9 2.68
4.5 583.0 151.1 3.63 571.9 153.9 3.42 554.8 167.4 3.07 530.7 182.8 2.71 515.9 228.3 2.14
5 587.1 151.7 3.64 576.5 154.6 3.44 559.1 168.1 3.09 535.4 183.6 2.72 519.1 228.5 2.15
6 603.7 154.1 3.69 595.2 157.0 3.50 576.4 171.0 3.13 554.4 186.6 2.78 532.3 229.2 2.20
7 620.0 156.5 3.74 613.7 159.4 3.56 594.7 173.9 3.18 573.5 189.5 2.83 546.1 230.0 2.25
YCIV
8 636.4 158.8 3.78 632.3 161.5 3.62 612.5 176.0 3.24 592.5 192.8 2.88 561.0 231.5 2.29
0630
10 675.8 163.4 3.91 671.2 166.8 3.73 651.8 180.8 3.36 631.7 200.3 2.96 601.1 239.4 2.38
12 715.2 167.6 4.04 710.2 171.6 3.85 693.5 187.6 3.46 671.2 208.0 3.04 634.0 249.5 2.42
15 784.3 175.8 4.23 773.6 179.0 4.03 758.9 195.7 3.64 716.6 213.3 3.17 654.1 245.3 2.53
15.5 794.9 177.2 4.26 784.2 180.8 4.04 769.8 197.0 3.66 723.0 214.0 3.18 657.2 244.2 2.55
4.5 647.9 167.8 3.63 635.5 171.7 3.41 616.0 187.5 3.05 589.1 204.1 2.69 573.2 248.5 2.18
5 652.4 168.4 3.65 640.7 172.4 3.43 620.9 188.3 3.06 594.4 204.8 2.71 577.0 248.6 2.19
6 670.7 171.0 3.70 661.4 174.9 3.49 640.3 191.2 3.11 615.5 207.7 2.77 592.2 249.0 2.25
7 688.7 173.5 3.74 682.0 177.3 3.56 660.7 194.3 3.16 636.9 210.6 2.83 607.7 249.6 2.30
YCIV
8 706.6 175.8 3.79 702.6 179.7 3.62 680.6 196.5 3.23 658.1 213.7 2.88 624.5 250.7 2.35
0700
10 749.7 180.9 3.92 745.3 185.2 3.73 724.1 201.5 3.35 702.0 221.1 2.98 660.1 252.2 2.48
12 792.4 185.2 4.05 788.0 190.3 3.85 770.0 208.9 3.45 745.7 228.5 3.07 682.3 252.5 2.56
15 869.0 194.4 4.24 858.3 198.5 4.03 842.7 217.9 3.63 796.1 234.3 3.20 703.9 248.2 2.68
15.5 881.8 195.9 4.27 870.0 200.6 4.05 854.8 219.4 3.66 803.2 235.1 3.22 707.2 247.1 2.70
4.5 702.1 181.5 3.66 687.7 187.3 3.41 666.3 206.8 3.01 638.6 228.2 2.63 558.1 235.0 2.24
5 707.1 182.2 3.67 693.3 187.9 3.43 671.5 207.5 3.02 644.0 228.8 2.65 561.5 234.7 2.25
6 726.9 185.0 3.72 715.6 190.3 3.49 692.2 210.3 3.08 665.9 231.3 2.71 575.0 233.7 2.32
7 746.6 187.8 3.77 737.8 192.7 3.56 714.0 213.2 3.14 687.8 233.9 2.77 588.5 232.7 2.38
YCIV
8 766.4 190.6 3.81 760.1 195.1 3.63 735.3 215.2 3.20 709.6 236.4 2.83 602.0 231.7 2.44
0760
10 814.0 197.1 3.92 806.9 201.1 3.74 782.3 220.0 3.34 754.5 242.7 2.93 628.9 229.7 2.58
12 861.6 203.5 4.03 853.7 207.0 3.85 832.3 227.6 3.44 799.5 249.0 3.03 642.6 227.5 2.66
15 944.9 213.5 4.22 929.9 215.9 4.04 910.9 237.4 3.62 853.5 255.3 3.16 663.0 223.7 2.78
15.5 958.8 215.2 4.25 942.6 218.1 4.05 924.0 239.0 3.64 861.2 256.2 3.18 666.1 222.7 2.81
4.5 746.4 191.0 3.68 731.6 196.2 3.45 709.7 215.5 3.07 679.7 236.1 2.70 649.6 243.9 2.50
5 751.6 191.7 3.70 737.5 196.9 3.47 715.2 216.3 3.08 685.7 237.0 2.71 656.2 259.5 2.38
6 772.8 194.7 3.75 761.2 199.5 3.53 737.1 219.5 3.13 709.8 240.2 2.77 682.4 321.7 2.02
7 793.8 197.7 3.79 784.9 202.2 3.60 760.4 222.7 3.19 734.1 243.3 2.83 707.7 323.8 2.08
YCIV
8 814.9 200.7 3.84 808.7 204.8 3.66 783.1 225.0 3.25 758.2 246.6 2.89 733.4 326.5 2.14
0800
10 865.6 207.3 3.96 858.5 211.3 3.78 833.1 230.2 3.38 808.3 254.5 2.99 783.4 281.6 2.63
12 915.7 213.6 4.07 908.2 217.5 3.89 886.2 238.5 3.48 857.0 262.1 3.08 827.8 298.9 2.63
15 1004.2 224.1 4.26 989.3 226.8 4.08 969.9 248.8 3.66 915.0 268.7 3.21 860.1 293.9 2.78
15.5 1019.0 225.9 4.29 1002.8 229.1 4.09 983.8 250.5 3.69 923.2 269.7 3.23 862.6 292.6 2.80
4.5 775.4 197.9 3.68 760.7 201.7 3.47 738.2 220.0 3.11 710.5 241.6 2.74 693.3 293.2 2.23
5 780.8 198.6 3.70 766.9 202.5 3.49 743.9 220.9 3.12 717.1 242.6 2.76 697.9 293.1 2.25
6 802.8 201.7 3.75 791.5 205.7 3.55 766.9 224.5 3.17 743.4 246.7 2.81 716.0 293.1 2.31
7 824.6 205.0 3.79 816.2 208.6 3.61 791.2 228.1 3.22 770.0 250.9 2.87 734.3 293.6 2.36
YCIV
8 846.5 207.9 3.84 841.0 211.5 3.67 814.9 230.7 3.28 796.7 255.2 2.92 754.4 294.6 2.42
0830
10 898.8 214.3 3.96 892.8 218.4 3.79 867.2 236.7 3.41 849.2 264.0 3.02 808.3 302.9 2.52
12 950.2 220.1 4.08 943.6 224.5 3.90 921.9 245.6 3.51 899.7 272.1 3.11 852.5 313.9 2.57
15 1042.1 230.9 4.28 1027.9 234.2 4.09 1008.9 256.2 3.69 960.6 279.0 3.24 879.5 308.7 2.70
15.5 1057.4 232.7 4.31 1041.9 236.6 4.10 1023.4 257.9 3.72 969.2 280.0 3.26 883.6 307.3 2.72

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
Data based on 5°C chilled liquid temperature difference.
Fans operate at low speed at 28°C ambient and below.

32
Form No. 201.26 EG 03 (GB 05/08)
High Efficiency (HE LS) Models with Two Speed Fans - Cooling Capacities continued

Condenser Coil Entering Air Temperature oC

LWT °C
Model 25 30 35 40 45
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 860.8 228.0 3.6 843.6 231.8 3.4 817.7 252.0 3.0 782.2 273.5 2.7 765.9 333.4 2.2
5 866.9 228.9 3.6 850.4 232.8 3.4 824.0 253.1 3.0 789.3 274.7 2.7 770.9 333.5 2.2
6 891.0 232.7 3.6 877.6 236.7 3.5 849.2 257.5 3.1 817.5 279.2 2.8 790.9 334.2 2.2
7 915.1 236.5 3.7 904.8 240.3 3.5 875.9 262.1 3.1 845.9 283.8 2.8 811.4 335.3 2.3
YCIV
8 939.3 240.1 3.7 932.1 243.9 3.6 902.0 265.4 3.2 874.2 288.7 2.9 834.0 337.1 2.4
0930
10 997.4 247.6 3.8 989.1 252.4 3.7 959.4 273.1 3.3 930.5 299.1 2.9 889.2 344.8 2.5
12 1055.0 254.4 4.0 1046.2 260.0 3.8 1020.3 283.9 3.4 986.6 309.4 3.0 912.0 340.0 2.6
15 1157.0 266.9 4.1 1139.6 271.2 3.9 1116.6 296.1 3.6 1053.3 317.2 3.1 941.0 334.4 2.7
15.5 1174.0 269.0 4.2 1155.1 274.0 4.0 1132.7 298.2 3.6 1062.7 318.3 3.2 945.3 332.9 2.7
4.5 968.0 250.8 3.6 947.4 257.6 3.4 916.1 282.4 3.0 877.0 310.4 2.7 842.2 373.8 2.1
5 974.9 251.8 3.7 955.1 258.5 3.4 923.4 283.4 3.0 884.9 311.4 2.7 847.8 373.9 2.2
6 1002.4 255.6 3.7 986.3 262.1 3.5 952.3 287.8 3.1 916.2 315.6 2.7 870.1 374.3 2.2
7 1029.7 259.6 3.8 1017.3 265.7 3.6 983.1 292.2 3.1 947.5 319.7 2.8 892.9 375.0 2.3
YCIV
8 1057.1 263.1 3.8 1048.5 269.1 3.6 1012.9 295.1 3.2 977.8 324.0 2.8 917.7 376.6 2.3
1050
10 1122.8 271.3 3.9 1113.6 277.5 3.7 1078.8 302.5 3.3 1040.8 333.9 2.9 983.9 387.7 2.4
12 1188.2 279.0 4.0 1178.8 285.4 3.9 1148.7 313.3 3.4 1103.9 344.0 3.0 1038.9 401.9 2.5
15 1303.1 292.7 4.2 1284.0 297.7 4.0 1257.1 326.8 3.6 1178.5 352.7 3.2 1071.8 395.2 2.6
15.5 1322.2 295.0 4.3 1301.5 300.7 4.1 1275.1 329.1 3.6 1189.1 353.9 3.2 1076.8 393.4 2.6
4.5 1030.1 263.7 3.7 1008.5 271.9 3.4 976.2 299.6 3.0 937.1 332.2 2.6 902.2 397.2 2.1
5 1037.5 264.7 3.7 1016.7 272.8 3.4 983.9 300.7 3.0 945.5 333.2 2.7 908.0 397.2 2.2
6 1066.8 268.6 3.7 1049.8 276.4 3.5 1014.6 305.0 3.1 979.1 337.6 2.7 931.6 397.1 2.2
7 1096.0 272.8 3.8 1082.8 279.8 3.6 1047.0 309.3 3.1 1011.8 341.3 2.8 955.7 397.5 2.3
YCIV
8 1125.3 276.7 3.8 1115.9 283.3 3.6 1078.6 312.1 3.2 1044.0 345.2 2.8 982.0 398.5 2.3
1120
10 1195.6 285.9 3.9 1185.3 291.8 3.8 1148.5 319.2 3.4 1111.1 354.4 2.9 1052.5 408.8 2.4
12 1265.9 295.2 4.1 1254.8 300.3 3.9 1222.8 330.1 3.5 1178.1 363.9 3.0 1110.9 422.2 2.5
15 1388.3 309.7 4.3 1366.8 313.2 4.1 1338.2 344.3 3.6 1257.8 373.1 3.2 1146.2 415.2 2.6
15.5 1408.7 312.1 4.7 1385.5 316.5 4.1 1357.4 346.7 3.7 1269.0 374.4 3.2 1151.4 413.4 2.6
4.5 1119.7 290.2 3.6 1096.7 298.1 3.4 1062.7 327.5 3.0 1014.7 357.7 2.7 981.7 429.6 2.2
5 1127.7 291.4 3.7 1105.6 299.1 3.4 1071.0 328.7 3.0 1023.6 358.8 2.7 987.9 429.6 2.2
6 1159.7 295.9 3.7 1141.3 303.3 3.5 1103.9 333.6 3.1 1058.9 363.5 2.7 1012.9 429.6 2.2
7 1191.4 300.5 3.8 1177.0 307.4 3.6 1139.0 338.4 3.1 1094.8 368.0 2.8 1038.7 430.0 2.3
YCIV
8 1223.3 304.9 3.8 1212.9 311.3 3.6 1172.9 342.0 3.2 1130.4 372.9 2.9 1066.9 431.2 2.3
1220
10 1300.1 315.0 3.9 1288.1 321.3 3.7 1248.5 350.2 3.3 1204.1 384.4 3.0 1142.5 442.7 2.5
12 1377.0 324.8 4.0 1363.5 330.8 3.9 1328.6 362.9 3.4 1276.2 395.4 3.0 1204.8 457.7 2.5
15 1510.1 340.8 4.2 1485.2 345.0 4.0 1454.0 378.6 3.6 1362.5 405.4 3.2 1243.0 450.1 2.6
15.5 1532.2 343.4 6.3 1505.5 348.6 4.0 1474.9 381.2 3.6 1374.7 406.8 3.2 1248.8 448.1 2.6
4.5 1269.9 335.9 3.6 1242.5 340.6 3.4 1201.5 368.9 3.0 1148.2 400.8 2.7 1125.4 491.0 2.2
5 1278.9 337.4 3.6 1252.7 342.0 3.4 1211.0 370.5 3.1 1158.6 402.4 2.7 1133.0 491.3 2.2
6 1315.0 343.2 3.6 1293.5 347.9 3.5 1249.0 377.2 3.1 1200.4 409.1 2.8 1163.5 492.4 2.2
7 1350.8 349.0 3.7 1334.2 353.5 3.5 1289.2 384.1 3.1 1242.8 415.8 2.8 1194.7 494.3 2.3
YCIV
8 1386.7 354.3 3.7 1375.0 359.0 3.6 1328.2 389.3 3.2 1284.9 423.0 2.9 1228.9 497.2 2.3
1380
10 1472.8 365.8 3.8 1460.3 371.9 3.7 1414.5 401.0 3.3 1371.8 439.6 2.9 1319.8 514.1 2.4
12 1558.5 376.1 3.9 1545.6 383.6 3.8 1505.8 417.4 3.4 1457.8 456.2 3.0 1395.1 535.6 2.5
15 1709.2 394.6 4.1 1683.5 400.1 3.9 1647.9 435.4 3.6 1556.3 467.7 3.2 1439.4 526.6 2.6
15.5 1734.3 397.7 4.2 1706.5 404.2 4.0 1671.6 438.4 3.6 1570.3 469.3 3.2 1446.1 524.3 2.6

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors. EER = Energy Efficiency Ratio (includes compressors and fans).
°
Data based on 5 C chilled liquid temperature difference.
°
Fans operate at low speed at 28 C ambient and below.

33
Form No. 201.26 EG 03 (GB 05/08)
HIGH EFFICIENCY (HE LS) MODELS WITH TWO SPEED FANS (HIGH SPEED INHIBITED) - COOLING
CAPACITIES

LWT °C Condenser Coil Entering Air Temperature oC


Model 25 30 35 40
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 547.8 144.0 3.59 524.6 155.2 3.21 501.8 167.8 2.85 476.4 182.1 2.50
5 551.6 144.6 3.61 528.8 156.1 3.22 506.4 168.6 2.86 479.3 182.1 2.52
6 567.2 147.0 3.65 545.4 159.5 3.25 525.0 172.0 2.91 490.8 182.3 2.57
7 582.4 149.2 3.69 562.0 162.7 3.28 540.8 175.5 2.94 502.2 182.5 2.63
YCIV
8 597.6 151.4 3.74 578.6 165.9 3.32 556.6 178.9 2.97 513.6 182.8 2.69
0590
10 633.8 155.5 3.87 614.2 172.4 3.40 592.7 186.5 3.04 532.5 183.3 2.78
12 669.5 158.8 4.01 649.6 178.0 3.48 629.4 193.4 3.12 542.1 183.7 2.82
15 734.3 166.6 4.20 707.0 187.0 3.62 655.7 185.5 3.38 554.8 180.4 2.94
15.5 745.1 168.5 6.23 716.5 189.3 3.62 660.1 183.5 3.44 557.5 179.9 2.96
4.5 583.0 151.1 3.63 559.8 164.3 3.22 538.7 179.4 2.85 512.6 195.8 2.50
5 587.1 151.7 3.64 564.2 165.1 3.23 543.5 180.1 2.87 515.6 195.8 2.51
6 603.7 154.1 3.69 581.8 168.3 3.27 562.6 183.3 2.92 527.7 195.7 2.57
7 620.0 156.5 3.74 599.1 171.4 3.31 579.0 186.6 2.95 540.0 195.5 2.63
YCIV
8 636.4 158.8 3.78 616.6 174.3 3.35 595.3 189.8 2.99 552.1 195.6 2.69
0630
10 675.8 163.4 3.91 654.4 180.9 3.44 633.1 197.0 3.07 572.9 195.6 2.79
12 715.2 167.6 4.04 692.3 186.8 3.53 671.6 203.6 3.15 584.1 195.6 2.85
15 784.3 175.8 4.23 753.5 196.2 3.66 699.7 195.3 3.42 597.8 192.1 2.97
15.5 794.9 177.9 4.24 763.7 198.6 3.67 704.4 193.2 3.48 600.7 191.5 2.99
4.5 647.9 167.8 3.63 622.2 183.3 3.21 598.1 200.9 2.83 568.9 218.6 2.48
5 652.4 168.4 3.65 627.0 184.1 3.22 603.5 201.7 2.84 572.3 218.4 2.50
6 670.7 171.0 3.70 646.5 187.5 3.26 625.0 205.0 2.90 585.9 217.9 2.57
7 688.7 173.5 3.74 665.8 190.7 3.31 643.2 208.5 2.94 599.7 217.3 2.63
YCIV
8 706.6 175.8 3.79 685.1 194.0 3.35 661.5 211.9 2.97 613.2 216.9 2.70
0700
10 749.7 180.9 3.92 726.7 200.8 3.44 703.3 219.6 3.06 636.5 216.0 2.81
12 792.4 185.2 4.05 768.1 207.2 3.53 745.8 226.7 3.14 648.8 214.9 2.88
15 869.0 194.4 4.24 836.0 217.6 3.66 777.0 217.4 3.41 664.0 211.1 3.00
15.5 881.8 196.6 6.29 847.3 220.3 3.67 782.2 215.1 3.47 667.3 210.4 3.02
4.5 702.1 181.5 3.66 673.3 199.9 3.20 647.0 221.5 2.79 616.7 244.3 2.42
5 707.1 182.2 3.67 678.5 200.7 3.21 652.7 222.3 2.80 620.2 244.0 2.44
6 726.9 185.0 3.72 699.4 204.0 3.26 675.6 225.4 2.86 633.9 242.6 2.50
7 746.6 187.8 3.77 720.3 207.3 3.31 695.2 228.8 2.91 647.6 241.3 2.57
YCIV
8 766.4 190.6 3.81 741.2 210.6 3.35 714.7 232.1 2.95 661.3 239.9 2.64
0760
10 814.0 197.1 3.92 786.7 218.0 3.44 759.9 239.7 3.04 684.2 237.1 2.76
12 861.6 203.5 4.03 832.2 225.3 3.53 806.1 247.0 3.13 695.6 234.2 2.84
15 944.9 213.5 4.22 905.7 236.7 3.66 839.8 236.9 3.39 712.0 230.0 2.96
15.5 958.8 216.0 6.26 918.0 239.6 3.67 845.4 234.4 3.45 715.4 229.3 2.98
4.5 746.4 191.0 3.68 716.2 209.3 3.24 689.1 230.8 2.84 656.4 252.9 2.48
5 751.6 191.7 3.70 721.8 210.3 3.25 695.2 231.7 2.86 660.3 252.7 2.50
6 772.8 194.7 3.75 744.1 213.9 3.30 719.5 235.2 2.92 675.6 251.9 2.56
7 793.8 197.7 3.79 766.3 217.6 3.34 740.3 238.9 2.96 691.2 251.0 2.63
YCIV
8 814.9 200.7 3.84 788.6 221.1 3.39 761.1 242.6 2.99 706.6 250.3 2.70
0800
10 865.6 207.3 3.96 837.1 229.0 3.48 809.2 250.8 3.08 733.0 248.6 2.82
12 915.7 213.6 4.07 885.3 236.7 3.57 858.3 258.8 3.17 745.7 246.5 2.89
15 1004.2 224.1 4.26 963.5 248.7 3.70 894.2 248.2 3.44 763.2 242.1 3.01
15.5 1019.0 226.8 6.32 976.5 251.6 3.71 900.2 245.6 3.50 767.0 241.3 3.03
4.5 775.4 197.9 3.68 744.7 215.3 3.27 716.8 235.7 2.89 686.2 258.8 2.53
5 780.8 198.6 3.70 750.5 216.3 3.28 723.1 236.7 2.90 690.5 258.8 2.54
6 802.8 201.7 3.75 773.7 220.5 3.32 748.6 240.6 2.96 707.6 258.7 2.61
7 824.6 205.0 3.79 796.9 224.4 3.36 770.4 244.8 2.99 725.0 258.8 2.67
YCIV
8 846.5 207.9 3.84 820.2 228.3 3.40 792.1 248.9 3.03 742.4 259.0 2.73
0830
10 898.8 214.3 3.96 870.4 236.7 3.49 842.4 257.9 3.11 770.0 257.9 2.85
12 950.2 220.1 4.08 919.8 244.4 3.58 892.9 266.5 3.20 782.9 255.9 2.92
15 1042.1 230.9 4.28 1001.1 256.7 3.72 930.2 255.6 3.47 801.3 251.4 3.04
15.5 1057.4 233.6 6.35 1014.6 259.8 3.76 936.5 252.9 3.53 805.2 250.6 3.06

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors.
EER = Energy Efficiency Ratio (includes compressors and fans).
Data based on 5°C chilled liquid temperature difference.

34
Form No. 201.26 EG 03 (GB 05/08)
High Efficiency (HE LS) Models with Two Speed Fans (High Speed Inhibited) - Cooling Capacities continued

LWT °C
Condenser Coil Entering Air Temperature oC
Model 25 30 35 40
kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER
4.5 860.8 228.0 3.58 825.9 247.4 3.18 794.0 269.9 2.81 755.5 292.9 2.47
5 866.9 228.9 3.59 832.3 248.6 3.19 801.0 271.1 2.82 760.0 292.9 2.49
6 891.0 232.7 3.63 857.8 253.7 3.22 828.9 276.0 2.87 778.2 292.9 2.55
7 915.1 236.5 3.67 883.4 258.5 3.26 852.8 281.2 2.90 796.5 292.8 2.61
YCIV
8 939.3 240.1 3.72 908.9 263.3 3.29 876.7 286.3 2.93 814.7 293.0 2.67
0930
10 997.4 247.6 3.83 964.4 273.6 3.37 931.9 297.5 3.00 843.7 292.2 2.77
12 1055.0 254.4 3.95 1019.8 283.0 3.45 988.2 308.1 3.08 858.4 291.0 2.83
15 1157.0 266.9 4.14 1109.9 297.3 3.58 1029.5 295.5 3.34 878.6 285.8 2.94
15.5 1174.0 270.1 6.14 1124.9 300.9 3.59 1036.4 292.3 3.40 882.9 284.9 2.97
4.5 968.0 250.8 3.65 927.5 274.9 3.20 889.6 302.5 2.80 847.1 332.4 2.44
5 974.9 251.8 3.66 934.8 276.1 3.21 897.6 303.7 2.82 852.1 332.1 2.46
6 1002.4 255.6 3.71 964.0 281.0 3.26 929.6 308.4 2.88 872.1 331.0 2.52
7 1029.7 259.6 3.75 993.2 285.8 3.31 957.1 313.5 2.92 892.1 329.8 2.59
YCIV
8 1057.1 263.1 3.81 1022.4 290.5 3.35 984.6 318.3 2.96 911.2 328.8 2.65
1050
10 1122.8 271.3 3.93 1085.7 300.9 3.44 1047.9 329.6 3.04 943.8 326.2 2.77
12 1188.2 279.0 4.05 1149.1 310.6 3.53 1112.5 340.0 3.14 960.5 323.6 2.84
15 1303.1 292.7 4.2 1250.6 326.3 3.7 1159.0 326.1 3.40 983.1 317.7 3.0
15.5 1322.2 296.1 6.3 1267.5 330.3 3.7 1166.8 322.6 3.46 987.9 316.8 3.0
4.5 1030.1 263.7 3.67 987.3 290.2 3.22 947.9 321.0 2.81 905.1 355.7 2.43
5 1037.5 264.7 3.69 995.0 291.4 3.23 956.4 322.1 2.82 910.5 355.4 2.45
6 1066.8 268.6 3.74 1026.1 296.3 3.28 990.3 326.9 2.88 932.0 354.1 2.51
7 1096.0 272.8 3.79 1057.1 301.0 3.33 1019.3 331.9 2.92 952.7 352.1 2.58
YCIV
8 1125.3 276.7 3.83 1088.2 305.8 3.37 1048.3 336.6 2.97 972.9 350.4 2.65
1120
10 1195.6 285.9 3.95 1155.6 316.4 3.47 1115.6 347.8 3.06 1007.5 346.2 2.78
12 1265.9 295.2 4.06 1223.2 326.9 3.56 1184.3 358.3 3.16 1025.1 342.2 2.86
15 1388.3 309.7 4.25 1331.2 343.4 3.70 1233.8 343.6 3.42 1049.2 336.1 2.97
15.5 1408.7 313.4 6.31 1349.2 347.5 3.70 1242.1 340.0 3.48 1054.3 335.1 3.00
4.5 1119.7 290.2 3.65 1073.6 318.1 3.21 1031.9 350.8 2.81 980.0 383.0 2.45
5 1127.7 291.4 3.66 1082.0 319.5 3.22 1041.0 352.2 2.82 985.6 382.7 2.47
6 1159.7 295.9 3.71 1115.5 325.1 3.26 1077.6 357.5 2.88 1007.9 381.3 2.53
7 1191.4 300.5 3.76 1149.0 330.7 3.31 1108.9 363.1 2.92 1030.8 379.6 2.60
YCIV
8 1223.3 304.9 3.80 1182.8 336.0 3.35 1140.1 368.8 2.96 1053.4 378.4 2.67
1220
10 1300.1 315.0 3.9 1255.8 348.3 3.4 1212.7 381.5 3.04 1091.8 375.5 2.8
12 1377.0 324.8 4.03 1329.2 360.1 3.53 1286.8 393.9 3.13 1110.5 371.9 2.86
15 1510.1 340.8 4.22 1446.6 378.3 3.66 1340.6 377.8 3.40 1136.5 365.2 2.98
15.5 1532.2 344.8 6.26 1466.1 382.8 3.67 1349.6 373.7 3.46 1142.1 364.1 3.00
4.5 1269.9 335.9 3.58 1216.4 363.5 3.18 1166.6 395.1 2.82 1109.0 429.2 2.47
5 1278.9 337.4 3.59 1226.0 365.3 3.19 1177.1 396.9 2.83 1115.7 429.2 2.49
6 1315.0 343.2 3.63 1264.3 372.9 3.23 1219.2 404.3 2.88 1142.6 429.1 2.55
7 1350.8 349.0 3.67 1302.6 380.3 3.26 1255.2 412.1 2.91 1170.1 429.0 2.61
YCIV
8 1386.7 354.3 3.72 1340.8 387.6 3.30 1291.0 419.9 2.94 1197.3 429.2 2.67
1380
10 1472.8 365.8 3.83 1423.8 403.1 3.37 1373.9 436.9 3.01 1243.9 429.5 2.77
12 1558.5 376.1 3.95 1506.6 417.5 3.45 1458.4 453.0 3.09 1268.4 429.0 2.83
15 1709.2 394.6 4.13 1639.7 438.7 3.58 1519.4 434.5 3.35 1298.2 421.3 2.95
15.5 1734.3 399.2 6.13 1661.8 443.9 3.59 1529.5 429.9 3.41 1304.6 420.1 2.97

Notes:
kWo = Full load cooling capacity. kWci = kW input of all compressors.
EER = Energy Efficiency Ratio (includes compressors and fans).
Data based on 5°C chilled liquid temperature difference.

35
Form No. 201.26 EG 03 (GB 05/08)
STANDARD/HIGH EFFICIENCY (SE & SERS/HE &HERS) MODELS - SOUND DATA
Sound Power dB Standard Efficiency Chillers (SE) SPL Sound Power dB Standard Efficiency Chillers (SE RS) SPL
Model Mean Band Levels - Frequency Hz at Model Mean Band Levels - Frequency Hz at
YCIV SWL 63 125 250 500 1000 2000 4000 8000 10 m YCIV SWL 63 125 250 500 1000 2000 4000 8000 10 m
LWA 101 75 82 93 95 96 95 85 77 LWA 97 71 78 89 91 92 91 81 73
0600 68.5 0600 64.5
LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 94.2 92 92.2 82 74.1
LWA 102 76 83 94 96 97 96 86 78 LWA 98 72 79 90 92 93 92 82 74
0650 69.4 0650 65.4
LW 108 102 99.1 103 99.2 97 97.2 87 79.1 LW 104 98.2 95.1 98.6 95.2 93 93.2 83 75.1
LWA 103 77 84 95 97 99 97 87 79 LWA 99 73 80 91 93 95 93 83 75
0720 70.4 0720 66.4
LW 109 103 100 104 100 99 98.2 88 80.1 LW 105 99.2 96.1 99.6 96.2 95 94.2 84 76.1
LWA 102 76 83 94 96 97 96 86 78 LWA 98 72 79 90 92 93 92 82 74
0770 69.4 0770 65.4
LW 108 102 99.1 103 99.2 97 97.2 87 79.1 LW 104 98.2 95.1 98.6 95.2 93 93.2 83 75.1
LWA 105 79 86 97 99 100 99 89 81 LWA 101 75 82 93 95 96 95 85 77
0840 72.4 0840 68.4
LW 111 105 102 106 102 100 100 90 82.1 LW 107 101 98.1 102 98.2 96 96.2 86 78.1
LWA 104 77 85 96 98 99 98 88 80 LWA 100 73 81 92 94 95 94 84 76
0920 71.3 0920 67.3
LW 110 103 101 105 101 99 99.2 89 81.1 LW 106 99.2 97.1 101 97.2 95 95.2 85 77.1
LWA 104 78 85 96 98 99 98 88 80 LWA 100 74 81 92 94 95 94 84 76
1000 71.3 1000 67.3
LW 110 104 101 105 101 99 99.2 89 81.1 LW 106 100 97.1 101 97.2 95 95.2 85 77.1
LWA 106 59.6 73.7 82.2 101 98.5 102 93 86.4 LWA 102 56 70 78 97 94 98 89 82
1070 73.1 1070 69.1
LW 108 85.8 89.8 90.8 104 98.5 103 94 87.5 LW 104 82 86 87 100 94 99 90 84
LWA 107 60.6 74.7 83.2 103 99.8 104 94.8 86.7 LWA 103 57 71 79 99 96 100 91 83
1180 74.1 1180 70.1
LW 109 86.8 90.8 91.8 106 99.8 105 95.8 87.8 LW 105 83 87 88 102 96 101 92 84
LWA 108 58.9 75.7 78.2 106 100 102 95.1 88.5 LWA 104 55 72 74 102 96 98 91 85
1340 75 1340 71.0
LW 111 85.1 91.8 86.8 109 100 104 96.1 89.6 LW 107 81 88 83 105 96 100 92 86
LWA 109 59.6 76.7 79.2 107 102 101 95.8 90.7 LWA 105 56 73 75 103 98 97 92 87
1500 75.9 1500 71.9
LW 111 85.8 92.8 87.8 110 102 102 96.8 91.8 LW 107 82 89 84 106 98 98 93 88
X models have normal speed fans and no compressor enclosure. RS models have normal speed fans and an unlined compressor enclosure.
All data tested at 7°C leaving chilled water and 35°C ambient. All data tested at 7°C leaving chilled water and 35°C ambient.

Sound Power dB High Efficiency Chillers (HE) SPL Sound Power dB High Efficiency Chillers (HE RS) SPL
Model Mean Band Levels - Frequency Hz at Model Mean Band Levels - Frequency Hz at
YCIV SWL 63 125 250 500 1000 2000 4000 8000 10 m YCIV SWL 63 125 250 500 1000 2000 4000 8000 10 m
LWA 99 73 80 91 93 94 93 83 75 LWA 95 69 76 87 89 90 89 79 71
0590 66.5 0590 62.5
LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1 LW 101 95.2 92.1 95.6 92.2 90 90.2 80 72.1
LWA 101 75 82 93 95 96 95 85 77 LWA 97 71 78 89 91 92 91 81 73
0630 68.4 0630 64.4
LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 94.2 92 92.2 82 74.1
LWA 102 75 82 93 95 96 95 85 77 LWA 98 71 78 89 92 93 91 81 73
0700 69.4 0700 64.4
LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 95.2 93 92.2 82 74.1
LWA 103 77 84 95 97 98 97 87 79 LWA 99 73 80 91 93 94 93 83 75
0760 70.4 0760 66.4
LW 109 103 100 104 100 98 98.2 88 80.1 LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1
LWA 103 77 84 95 97 98 97 87 79 LWA 99 73 80 91 93 94 93 83 75
0800 70.3 0800 66.3
LW 107 101 98 102 98.6 95.8 96.2 85.8 78.1 LW 103 97 95 98 95 93 93 83 75
LWA 105 79 86 97 98 100 99 89 81 LWA 101 75 82 93 94 96 95 85 77
0830 72.3 0830 68.3
LW 111 105 102 106 101 100 100 90 82.1 LW 107 101 98.1 102 97.2 96 96.2 86 78.1
LWA 103 78 85 96 97 99 98 88 80 LWA 99 74 81 92 92 94 94 84 76
0930 70.3 0930 67.3
LW 110 104 101 105 100 99 99.2 89 81.1 LW 106 100 97.1 101 95.2 94 95.2 85 77.1
LWA 104 59.6 71.7 86.2 98.8 99.5 99.6 92 86.4 LWA 100 56 68 82 95 95 96 88 82
1050 71.1 1050 67.1
LW 106 85.8 87.8 94.8 102 99.5 98.4 91 87.5 LW 102 82 84 91 98 95 97 89 84
LWA 105 59.6 71.7 86.2 99.6 99.8 101 92.8 85.7 LWA 101 56 68 82 96 96 97 89 82
1120 72.0 1120 68.0
LW 106 85.8 87.8 94.8 103 99.8 99.8 91.8 86.8 LW 102 82 84 91 98 95 97 90 83
LWA 106 59.6 73.7 82.2 102 98.8 103 93.8 85.7 LWA 102 56 70 78 98 95 99 90 82
1220 73.0 1220 69.0
LW 108 85.8 89.8 90.8 105 98.8 102 92.8 86.8 LW 104 82 86 87 101 95 100 91 83
LWA 107 59.9 74.7 83.2 103 102 101 94.1 90.5 LWA 103 56 71 79 99 98 97 90 87
1380 73.9 1380 69.9
LW 108 86.1 90.8 91.8 106 102 100 93.1 91.6 LW 104 82 87 88 101 98 98 90 88
X models have normal speed fans and no compressor enclosure. RS models have normal speed fans and an unlined compressor enclosure.
All data tested at 7°C leaving chilled water and 35°C ambient. All data tested at 7°C leaving chilled water and 35°C ambient.

36
Form No. 201.26 EG 03 (GB 05/08)
STANDARD/HIGH EFFICIENCY (SELS/HELS) MODELS - SOUND DATA
Sound Power dB Standard Efficiency Chillers (SE LS) SPL Sound Power dB High Efficiency Chillers (HE LS) SPL
Model Fan Mean Band Levels - Frequency Hz at Model Fan Mean Band Levels - Frequency Hz at
YCIV Speed SWL 63 125 250 500 1000 2000 4000 8000 10 m YCIV Speed SWL 63 125 250 500 1000 2000 4000 8000 10 m
LWA 93 73 77 85 89 87 85.3 78.7 70.8 LWA 93 76 79.1 85 89 88 84 78.7 70.8
Std. 60.5 Std. 60.5
LW 102 99.2 93.1 93.6 92.2 87 86.5 79.7 71.9 LW 104 102 95.2 93.6 92.2 88 82.8 77.7 71.9
0600 0590
LWA 90 68.8 76 79.4 86 86 81 76.9 70.8 LWA 89 70 75 78.4 85 84 80.5 75.9 69.8
Low 57.5 Low 56.5
LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 97 96.2 91.1 87 88.2 84 79.3 74.9 70.9
LWA 93 75.3 79.1 85.6 89 87 85.3 78.7 70.8 LWA 93 75.3 79.1 85.6 89 87 85.3 78.7 70.8
Std. 60.4 Std. 60.4
LW 104 102 95.2 94.2 92.2 87 86.5 79.7 71.9 LW 104 102 95.2 94.2 92.2 87 84.1 77.7 71.9
0650 0630
LWA 90 68.8 76 79.4 86 86 81 76.9 70.8 LWA 90 71 76 79.4 85 86 81.5 76.9 70.8
Low 57.4 Low 57.4
LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 98 96 91 87 88.2 86 80.3 75.9 71.9
LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8
Std. 61.4 Std. 61.4
LW 105 103 96.2 95.2 93.2 88 87.5 80.7 72.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9
0720 0700
LWA 91 69.8 77 80.4 87 87 82 77.9 71.8 LWA 91 69.8 77 80.4 87 86 82.5 77.9 71.8
Low 58.4 Low 58.4
LW 99 96 93.1 89 90.2 87 83.2 78.9 72.9 LW 99 96 93.1 89 90.2 86 81.3 76.9 72.9
LWA 93 75.3 79.1 85.6 89 87 85.3 78.7 70.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8
Std. 60.4 Std. 61.4
LW 104 102 95.2 94.2 92.2 87 86.5 79.7 71.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9
0770 0760
LWA 90 68.8 76 79.4 86 86 81 76.9 70.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8
Low 57.4 Low 58.4
LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 100 97.2 93.1 89 90.2 87 80.8 76.9 72.9
LWA 95 77.3 81.1 87.6 91 89 87.3 80.7 72.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8
Std. 62.4 Std. 61.3
LW 106 104 97.2 96.2 94.2 89 88.5 81.7 73.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9
0840 0800
LWA 92 70.8 78 81.4 88 88 83 78.9 72.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8
Low 59.4 Low 58.3
LW 100 97 94.1 90 91.2 88 84.2 79.9 73.9 LW 100 97.2 93.1 89 90.2 87 80.8 76.9 72.9
LWA 95 77.3 81.1 87.6 91 89 87.3 80.7 72.8 LWA 95 77.3 81.1 87.6 91 89 87.3 80.7 72.8
Std. 62.3 Std. 62.3
LW 106 104 97.2 96.2 94.2 89 88.5 81.7 73.9 LW 106 104 97.2 96.2 94.2 89 86.1 79.7 73.9
0920 0830
Low LWA 93 71.8 79 82.4 89 89 84 79.9 73.8 Low LWA 92 72 78 81.4 88 88 83 78.9 72.8
60.3 59.3
LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 101 98.2 94.1 90 91.2 88 81.8 77.9 73.9
Std. LWA 95 77.3 81.1 87 90 90.8 86 80.7 72.8 Std. LWA 95 77.3 81.1 87.6 91 89 85 80.7 72.8
62.3 62.3
LW 105 104 97.2 95.6 93.2 90.8 87.2 81.7 73.9 LW 106 104 97.2 96.2 94.2 89 83.8 79.7 73.9
1000 0930
LWA 93 71.8 79 82.4 89 89 84 79.9 73.8 LWA 92 72 78 81.4 88 88 83 78.9 72.8
Low 60.3 Low 59.3
LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 101 98.2 94.1 90 91.2 88 81.8 77.9 73.9
LWA 96 78 82 88 93 90 86 80 75 LWA 96 78 82 88 92 90 86 80 75
Std. 63.1 Std. 63.1
LW 106 104 98 97 96 90 85 79 76 LW 106 104 98 97 95 90 85 79 76
1070 1050
LWA 93 72 79 81 91 85 81 74 69 LWA 92 72 79 82 89 86 80 74 69
Low 60.1 Low 59.1
LW 101 98 95 90 94 85 80 73 70 LW 101 98 95 90 93 86 79 73 70
LWA 97 78 82 88 94 90 86 80 75 LWA 97 78 82 89 93 90 86 80 76
Std. 64.1 Std. 64.0
LW 106 104 98 97 97 90 85 79 76 LW 107 104 99 97 96 90 85 79 77
1180 1120
LWA 94 72 79 82 92 86 82 74 69 LWA 93 72 79 82 90 86 81 74 69
Low 61.1 Low 60.0
LW 102 98 95 90 95 86 80 73 70 LW 102 99 95 90 93 86 80 73 70
LWA 99 79 83 89 97 91 87 81 76 LWA 97 79 83 89 94 91 87 80 76
Std. 66.0 Std. 64.0
LW 107 105 99 97 100 91 85 80 77 LW 107 105 99 97 97 91 85 79 77
1340 1220
LWA 97 73 80 82 96 87 82 75 70 LWA 94 73 79 82 92 86 82 74 70
Low 64.0 Low 61.0
LW 103 99 96 91 99 87 81 74 71 LW 102 99 95 91 95 86 81 73 71
LWA 99 79 83 89 97 91 87 81 76 LWA 98 79 83 89 94 91 87 81 76
Std. 65.9 Std. 64.9
LW 108 105 99 98 100 91 86 80 77 LW 107 105 99 98 97 91 86 80 77
1500 1380
LWA 97 73 80 83 96 87 81 75 70 LWA 94 73 80 83 92 87 81 75 70
Low 63.9 Low 60.9
LW 103 99 96 91 99 87 80 74 71 LW 103 99 96 91 95 87 80 74 71
LS models have two speed fans and an acoustically lined compressor enclosure. LS models have two speed fans and an acoustically lined compressor enclosure.
Normal (Std.) fan speed data tested at 7°C leaving chilled water and 35°C ambient. Normal (Std.) fan speed data tested at 7°C leaving chilled water and 35°C ambient.
Low fan speed data tested at 7°C leaving chilled water and 25°C ambient. Low fan speed data tested at 7°C leaving chilled water and 25°C ambient.

Standard Efficiency Chillers (SE LS) High Efficiency Chillers (HE LS)
Sound Power dB SPL Sound Power dB SPL
Normal Fan Speed Inhibited Normal Fan Speed Inhibited
at at
Model Mean Band Levels - Frequency Hz Model Mean Band Levels - Frequency Hz
10 m 10 m
YCIV SWL 63 125 250 500 1000 2000 4000 8000 YCIV SWL 63 125 250 500 1000 2000 4000 8000
LWA 90 69.8 77 80.4 85 86 81 77.9 71.8 LWA 89 68.8 76 78 85 85 80 75 70.8
0600 57.5 0590 56.5
LW 99 96 93.1 89 88.2 86 82.2 78.9 72.9 LW 98 95 92.1 86.6 88.2 85 81.2 76 71.9
LWA 90 69.8 76 79 85 86 81 77.9 71.8 LWA 91 70.8 78 80 87 87 82 77 72.8
0650 57.4 0630 58.4
LW 99 96 92.1 87.6 88.2 86 82.2 78.9 72.9 LW 100 97 94.1 88.6 90.2 87 83.2 78 73.9
LWA 92 71.8 78 81 87 88 83 79.9 73.8 LWA 90 69.8 77 78 85 86 81 77.9 71.8
0720 59.4 0700 57.4
LW 101 98 94.1 89.6 90.2 88 84.2 80.9 74.9 LW 99 96 93.1 86.6 88.2 86 82.2 78.9 72.9
LWA 91 70.8 78 80 86 87 83 78.9 72.8 LWA 91 69.8 77 80.4 87 87 82 77.9 71.8
0770 58.4 0760 58.4
LW 100 97 94.1 88.6 89.2 87 84.2 79.9 73.9 LW 99 96 93.1 89 90.2 87 83.2 78.9 72.9
LWA 93 71 79 82.4 89 89 84 79.9 73.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8
0840 60.4 0800 58.3
LW 101 97.2 95.1 91 92.2 89 85.2 80.9 74.9 LW 100 97.2 93.1 89 90.2 87 83.2 78.9 72.9
LWA 93 71.8 79 82.4 89 89 84 79.9 73.8 LWA 93 73 79 82.4 89 89 84 79.9 73.8
0920 60.3 0830 60.3
LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9
LWA 93 73 79 82.4 89 89 84 79.9 73.8 LWA 93 73 79 82.4 89 89 84 79.9 73.8
1000 60.3 0930 60.3
LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9 LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9
LWA 93 72 79 81 91 85 81 74 69 LWA 92 72 79 82 89 86 80 74 69
1070 60.1 1050 59.1
LW 101 98 95 90 94 85 80 73 70 LW 101 98 95 90 93 86 79 73 70
LWA 94 72 79 82 92 86 82 74 69 LWA 93 72 79 82 90 86 81 74 69
1180 61.1 1120 60.0
LW 102 98 95 90 95 86 80 73 70 LW 102 99 95 90 93 86 80 73 70
LWA 97 73 80 82 96 87 82 75 70 LWA 94 73 79 82 92 86 82 74 70
1340 64.0 1220 61.0
LW 103 99 96 91 99 87 81 74 71 LW 102 99 95 91 95 86 81 73 71
LWA 97 73 80 83 96 87 81 75 70 LWA 94 73 80 83 92 87 81 75 70
1500 63.9 1380 60.9
LW 103 99 96 91 99 87 80 74 71 LW 103 99 96 92 95 87 80 74 71
LS models have two speed fans and an acoustically lined compressor enclosure. LS models have two speed fans and an acoustically lined compressor enclosure.
All data tested at 7°C leaving chilled water and 35°C ambient. All data tested at 7°C leaving chilled water and 35°C ambient.

37
Form No. 201.26 EG 03 (GB 05/08)
STANDARD EFFICIENCY (SE) MODELS - PHYSICAL DATA

Standard Efficiency Chillers


Refrigerant R134a YCIV YCIV YCIV YCIV YCIV YCIV
0600 0650 0720 0770 0840 0920
Quantity Refrigerant Circuits 2 2 2 2 2 2
Refrigerant Charge Circuit 1/Circuit 2 kg 74/74 77/77 84/77 87/80 87/87 105/89
Oil Charge Circuit 1/Circuit 2 kg 19/19 19/19 19/19 19/19 19/19 19/19
Compressor Quantity 2 2 2 2 2 2
Water Volume litre 253.6 359.6 359.6 529.9 529.9 529.9
Evaporator
Water Connections (nominal bore) inch 8 10 10 10 10 10
Air Total Coil Face Area m² 21.8 21.8 24.5 24.5 27.2 30
Cooled Number of Tube Rows 3 3 3 3 3 3
Condenser Number Fins per metre 669 669 669 669 669 669
Number Fans (Circuit 1/Ct 2) 4/4 4/4 5/4 5/4 5/5 6/5
Normal Fans SE & SE RS Models: Total Air Flow m³/s 48.8 48.8 54.9 54.9 61.0 67.1
Dual LS Models: Norm. Speed Total Air Flow m³/s 48.8 48.8 54.9 54.9 61.0 67.1
Speed Fans LS Models: Low Speed Total Air Flow m³/s 36.6 36.6 41.2 41.2 45.8 50.3
Length mm 5848 5848 6966 6966 6966 8083
Dimensions Width mm 2241 2241 2241 2241 2241 2241
Height mm 2384 2384 2384 2384 2384 2384
SE Models Shipping Weight kg 5216 5619 5818 6295 6524 6692
SE Models: Operating Weight kg 5470 5979 6178 6825 6940 7222
Weight RS Models Extra Weight kg 260 260 260 260 260 260
LS Models Extra Weight kg 325 325 325 325 325 325
Copper Fins Extra Weight kg 725 725 910 910 910 1085

Standard Efficiency Chillers


Refrigerant R134a YCIV YCIV YCIV YCIV YCIV
1000 1070 1180 1340 1500
Quantity Refrigerant Circuits 2 3 3 3 3
Circuit 1/Circuit 2 84/77/ 84/84/ 84/84/ 105/105
Refrigerant Charge kg 105/105
Circuit 3 77 77 105 /105
Circuit 1/Circuit 2 19/15/ 19/19/ 19/19/ 19/19/
Oil Charge kg 19/19
Circuit 3 15 15 19 19
Compressor Quantity 2 3 3 3 3
Water Volume litre 529.9 764.6 893.3 893.3 893.3
Evaporator
Water Connections (nominal bore) inch 10 10 10 10 10
Air Total Coil Face Area m² 32.7 35 38 44 49
Cooled Number of Tube Rows 3 3 3 3 3
Condenser Number Fins per metre 669 669 669 669 669
Number Fans (Circuit 1/Ct 2/Ct 3) 6/6 5/4/4 5/5/4 5/5/6 6/6/6
Normal Fans SE & SE RS Models: Total Air Flow m³/s 73.2 79.3 85.4 97.6 109.8
Dual LS Models: Norm. Speed Total Air Flow m³/s 73.2 79.3 85.4 97.6 109.8
Speed Fans LS Models: Low Speed Total Air Flow m³/s 54.9 59.5 64.1 73.2 82.4
Length mm 8083 9581 9581 10699 11816
Dimensions Width mm 2241 2241 2241 2241 2241
Height mm 2384 2384 2384 2384 2384
SE Models Shipping Weight kg 6768 9633 10137 10638 11075
SE Models: Operating Weight kg 7298 10437 11077 11577 12014
Weight RS Models Extra Weight kg 260 520 520 520 520
LS Models Extra Weight kg 325 640 640 640 640
Copper Fins Extra Weight kg 1085 1179 1270 1451 1632

38
Form No. 201.26 EG 03 (GB 05/08)
HIGH EFFICIENCY (HE) MODELS - PHYSICAL DATA
High Efficiency Chillers
Refrigerant R134a YCIV YCIV YCIV YCIV YCIV YCIV
0590 0630 0700 0760 0800 0830
Quantity Refrigerant Circuits 2 2 2 2 2 2
Refrigerant Charge Circuit 1/Circuit 2 kg 77/77 84/77 84/84 87/87 102/87 102/102
Oil Charge Circuit 1/Circuit 2 kg 19/19 19/19 19/19 19/19 19/19 19/19
Compressor Quantity 2 2 2 2 2 2
Water Volume litre 359.6 359.6 359.6 416.4 416.4 416.4
Evaporator
Water Connections (nominal bore) inch 10 10 10 10 10 10
Air Total Coil Face Area m² 21.8 24.5 27.2 27.2 30 32.7
Cooled Number of Tube Rows 3 3 3 3 3 3
Condenser Number Fins per metre 669 669 669 669 669 669
Number Fans (Circuit 1/Ct 2) 4/4 5/4 5/5 5/5 6/5 6/6
Normal Fans HE & HE RS Models: Total Air Flow m³/s 48.8 54.9 61.0 61.0 67.1 73.2
Dual LS Models: Norm. Speed Total Air Flow m³/s 48.8 54.9 61.0 61.0 67.1 73.2
Speed Fans LS Models: Low Speed Total Air Flow m³/s 36.6 41.2 45.8 45.8 50.3 54.9
Length mm 5848 6966 6966 6966 8083 8083
Dimensions Width mm 2241 2241 2241 2241 2241 2241
Height mm 2384 2384 2384 2384 2384 2384
HE Models Shipping Weight kg 5708 5801 5993 6080 6342 6410
HE Models: Operating Weight kg 5962 6161 6353 7404 6758 6826
Weight RS Models Extra Weight kg 260 260 260 260 260 260
LS Models Extra Weight kg 325 325 325 325 325 325
Copper Fins Extra Weight kg 725 910 910 910 1085 1085

High Efficiency Chillers


Refrigerant R134a YCIV YCIV YCIV YCIV YCIV
0930 1050 1120 1220 1380
Quantity Refrigerant Circuits 2 3 3 3 3
Circuit 1/Circuit 2 84/84/ 84/84/ 84/84/ 105/105
Refrigerant Charge kg 105/105
Circuit 3 77 105 105 /105
Circuit 1/Circuit 2 19/19/ 19/19/ 19/19/ 19/19/
Oil Charge kg 19/19
Circuit 3 15 19 19 19 `
Compressor Quantity 2 3 3 3 3
Water Volume litre 529.9 764.6 764.6 893.3 893.3
Evaporator
Water Connections (nominal bore) inch 10 10 10 10 10
Air Total Coil Face Area m² 32.7 38 44 44 49
Cooled Number of Tube Rows 3 3 3 3 3
Condenser Number Fins per metre 669 669 669 669 669
Number Fans (Circuit 1/Ct 2/Ct 3) 6/6 5/5/4 5/5/6 5/5/6 6/6/6
Normal Fans HE & HE RS Models: Total Air Flow m³/s 73.2 85.4 97.6 97.6 109.8
Dual LS Models: Norm. Speed Total Air Flow m³/s 73.2 85.4 97.6 97.6 109.8
Speed Fans LS Models: Low Speed Total Air Flow m³/s 54.9 64.1 73.2 73.2 82.4
Length mm 8083 9581 10699 10699 11816
Dimensions Width mm 2241 2241 2241 2241 2241
Height mm 2384 2384 2384 2384 2384
HE Models Shipping Weight kg 6760 9755 10112 10623 11059
HE Models: Operating Weight kg 7290 10559 10916 11562 11999
Weight RS Models Extra Weight kg 260 520 520 520 520
LS Models Extra Weight kg 325 640 640 640 640
Copper Fins Extra Weight kg 1085 1270 1360 1451 1632

39
Form No. 201.26 EG 03 (GB 05/08)
STANDARD EFFICIENCY (SE) MODELS - ELECTRICAL DATA

(1) Maximum
YCIV Nominal Amps Maximum Instantaneous Amps (2)
Amps
Model Std Fans 2 Spd Fans High Static Fans Std Fans 2 Spd Fans High Static Fans All Fans
0600 313 334 362 173 184 198 393
0650 343 360 392 220 230 245 387
0720 367 394 423 228 216 259 438
0770 400 411 462 228 231 259 446
0840 419 450 481 227 242 258 485
0920 461 496 536 268 286 305 540
1000 491 524 553 266 283 303 598
1070 543 576 630 416 439 472 615
1180 595 632 682 420 442 476 672
1340 669 718 774 475 508 543 781
1500 724 775 799 512 549 587 897
o o
(1) N om inal input am ps at 35 C am bient and 7 C leavin g c hilled w ater 400V A C .
(2) M axim um A m ps is the m axim um input current draw before the com pressor
unloads and is the condition that should be used for pow er cable sizing.
S yste m in ru sh cu rre n t is le ss th a n R L A d u e to th e u se o f Y o rk V a ria b le S p e e d D rive te ch n o lo g y.
T yp ica l C o m p re sso r S ta rtin g C u rre n t ( first fo u r se co n d s o f sta rtu p ):
R a te d V o lta g e T yp ica l S ta rtin g C u rre n t p e r C o m p re sso r
3 8 0 -4 0 0 /5 0 /3 17A

HIGH EFFICIENCY (HE) MODELS - ELECTRICAL DATA

(1) Maximum
YCIV Nominal Amps Maximum Instantaneous Amps (2)
Amps
Model Std Fans 2 Spd Fans High Static Fans Std Fans 2 Spd Fans High Static Fans All Fans
0590 289 306 338 161 170 186 363
0630 311 323 373 179 186 210 385
0700 342 361 404 218 232 249 415
0760 371 398 433 203 216 234 449
0800 390 411 465 219 231 256 468
0830 397 424 472 216 229 253 491
0930 445 471 513 269 286 306 537
1050 509 545 596 388 411 450 624
1120 539 572 632 376 401 438 659
1220 588 631 693 414 443 476 702
1380 640 679 715 490 521 565 803
o o
(1) N om inal input am ps at 35 C am bient and 7 C leavin g c hilled w ater 400V A C .
(2) M axim um A m ps is the m axim um input current draw before the com pressor
unloads and is the condition that should be used for pow er cable sizing.
S yste m in ru sh cu rre n t is le ss th a n R L A d u e to th e u se o f Y o rk V a ria b le S p e e d D rive te ch n o lo g y.
T yp ica l C o m p re sso r S ta rtin g C u rre n t ( first fo u r se co n d s o f sta rtu p ):
R a te d V o lta g e T yp ica l S ta rtin g C u rre n t p e r C o m p re sso r
3 8 0 -4 0 0 /5 0 /3 17A

40
Form No. 201.26 EG 03 (GB 05/08)
2 SYSTEM ELECTRICAL DATA (STANDARD EFFICIENCY)
System 1

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. (3) Qty.
(EA) (EA) (EA) (EA)
0600 400 50 144 4 3.1 18.0 152 4 1.9/3.8 4.5/10.3
0650 400 50 191 4 3.1 18.0 198 4 1.9/3.8 4.5/10.3
0720 400 50 195 5 3.1 18.0 180 5 1.9/3.8 4.5/10.3
0770 400 50 174 5 3.1 18.0 178 5 1.9/3.8 4.5/10.3
0840 400 50 194 5 3.1 18.0 206 5 1.9/3.8 4.5/10.3
0920 400 50 232 6 3.1 18.0 246 6 1.9/3.8 4.5/10.3
1000 400 50 230 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

System 2

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
Fans)
(7) (7)
(6) Nominal Amps LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. FLA (EA) (3) Qty.
(EA) (EA) (EA)
0600 400 50 144 4 3.1 18.0 152 4 1.9/3.8 4.5/10.3
0650 400 50 127 4 3.1 18.0 132 4 1.9/3.8 4.5/10.3
0720 400 50 144 4 3.1 18.0 180 4 1.9/3.8 4.5/10.3
0770 400 50 195 4 3.1 18.0 195 4 1.9/3.8 4.5/10.3
0840 400 50 194 5 3.1 18.0 206 5 1.9/3.8 4.5/10.3
0920 400 50 192 5 3.1 18.0 204 5 1.9/3.8 4.5/10.3
1000 400 50 230 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Unit Short
Model Control Circuit Field Wiring & Protection
Withstand (KA)

Maxmum Full Load


Lugs/
YCIV KVA
(4)
At 400VAC Current Std, UQ or 2- (1)
Lug Wire Range
(2) Phase
Spd. Fans
0600 2.4 65K A 393 2 70 - 240 mm²
0650 2.4 65K A 387 2 70 - 240 mm²
0720 2.4 65K A 438 2 70 - 240 mm²
0770 2.4 65K A 446 2 70 - 240 mm²
0840 2.4 65K A 485 2 70 - 240 mm²
0920 2.4 65K A 540 3 95 - 195 mm²
1000 2.4 65K A 598 3 95 - 195 mm²

1. A s standard, all units have single point pow er connection.


2. M axim um S ystem Full Load C urrent is the m axim um input current draw before the
com pressor unloads and is the condition that should be used for pow er cable sizing.

C onditions 7 D eg. C leaving ch illed w ater, condenser air on increasing, S tandard low sound, U ltra-Q uiet or 2-S pd. fans, 400V A C .
M ultiply current by 1.02 for operation at 360V A C . S ize per E N 60204.

3. N om inal A m ps at 35 D eg. C am bient and 7 D e g. C leavin g c hilled w ater, 400V A C .


4. C ontrol K V A inc ludes o perational controls and eva porator heaters.
5. S ystem inrush current is less than R LA due to the use of Y ork V ariable S peed D riv e
technology. T ypical C om pressor S tarting C urrent ( firs t four seconds of startup):

R ated V oltage T ypical S tarting C urrent per C om pressor


380-400/50/3 17A
6. V oltage U tilization R ange:

R ated V oltage U tilization R ange


380-415/50/3 360-440

7. V alues stated are for S low (s tar) and Fast (delta) respectively.

41
Form No. 201.26 EG 03 (GB 05/08)
3 SYSTEM ELECTRICAL DATA (STANDARD EFFICIENCY)

System 1

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. (3) Qty.
(EA) (EA) (EA) (EA)
1070 400 50 175 5 3.1 18.0 186 5 1.9/3.8 4.5/10.3
1180 400 50 177 5 3.1 18.0 188 5 1.9/3.8 4.5/10.3
1340 400 50 192 5 3.1 18.0 204 5 1.9/3.8 4.5/10.3
1500 400 50 229 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

System 2

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
Fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. (3) Qty.
(EA) (EA) (EA) (EA)
1070 400 50 196 4 3.1 18.0 202 4 1.9/3.8 4.5/10.3
1180 400 50 177 5 3.1 18.0 188 5 1.9/3.8 4.5/10.3
1340 400 50 192 5 3.1 18.0 204 5 1.9/3.8 4.5/10.3
1500 400 50 229 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3
System 3

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
Fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq Qty. Qty.
(3) (EA) (EA) (3) (EA) (EA)
1070 400 50 129 4 3.1 18.0 135 4 1.9/3.8 4.5/10.3
1180 400 50 198 4 3.1 18.0 203 4 1.9/3.8 4.5/10.3
1340 400 50 232 6 3.1 18.0 245 6 1.9/3.8 4.5/10.3
1500 400 50 229 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Unit Short
Model Control Circuit Field Wiring & Protection
Withstand (KA)

Maxmum Full Load


Lugs/
YCIV KVA
(4)
At 400VAC Current Std, UQ or 2- (1)
Lug Wire Range
(2) Phase
Spd. Fans
1070 2.4 65K A 615 4 120 - 240 mm²
1180 2.4 65K A 672 4 120 - 240 mm²
1340 2.4 65K A 781 4 120 - 240 mm²
1500 2.4 65K A 897 4 120 - 240 mm²

1. A s standard, all units have single point pow er connection.


2. M axim um S ystem Full Load C urrent is the m axim um input current draw before the
com pressor unloads and is the condition that should be used for pow er cable sizing.

C onditions 7 D eg. C leaving ch illed w ater, condenser air on increasing, S tandard low sound, U ltra-Q uiet or 2-S pd. fans, 400V A C .
M ultiply current by 1.02 for operation at 360V A C . S ize per E N 60204.

3. N om inal A m ps at 35 D eg. C am bient and 7 D e g. C leavin g c hilled w ater, 400V A C .


4. C ontrol K V A inc ludes operational controls and eva porator heaters.
5. S ystem inrush current is less than R LA due to the use of Y ork V ariable S peed D riv e
technology. T ypical C om pressor S tarting C urrent ( firs t four seconds of startup):

R ated V oltage T ypical S tarting C urrent per C om pressor


380-400/50/3 17A
6. V oltage U tilization R ange:
R ated V oltage U tilization R ange
380-415/50/3 360-440

7. V alues stated are for S low (s tar) and Fast (delta) respectively.

42
Form No. 201.26 EG 03 (GB 05/08)
2 SYSTEM ELECTRICAL DATA (HIGH EFFICIENCY)

System 1

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. (3) Qty.
(EA) (EA) (EA) (EA)
0590 400 50 132 4 3.1 18.0 138 4 1.9/3.8 4.5/10.3
0630 400 50 134 5 3.1 18.0 139 5 1.9/3.8 4.5/10.3
0700 400 50 185 5 3.1 18.0 196 5 1.9/3.8 4.5/10.3
0760 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.3
0800 400 50 170 6 3.1 18.0 178 6 1.9/3.8 4.5/10.3
0830 400 50 180 6 3.1 18.0 189 6 1.9/3.8 4.5/10.3
0930 400 50 233 6 3.1 18.0 246 6 1.9/3.8 4.5/10.3

System 2

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
Fans)
(7) (7)
(6) Nominal Amps LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. FLA (EA) (3) Qty.
(EA) (EA) (EA)
0590 400 50 132 4 3.1 18.0 138 4 1.9/3.8 4.5/10.3
0630 400 50 146 4 3.1 18.0 154 4 1.9/3.8 4.5/10.3
0700 400 50 126 5 3.1 18.0 131 5 1.9/3.8 4.5/10.3
0760 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.3
0800 400 50 183 5 3.1 18.0 195 5 1.9/3.8 4.5/10.3
0830 400 50 180 6 3.1 18.0 189 6 1.9/3.8 4.5/10.3
0930 400 50 178 6 3.1 18.0 187 6 1.9/3.8 4.5/10.3

Unit Short
Model Control Circuit Field Wiring & Protection
Withstand (KA)

Maxmum Full Load


(4) Lugs/
YCIV KVA At 400VAC Current Std, UQ or 2- (1)
Lug Wire Range
(2) Phase
Spd. Fans
0590 2.4 65K A 363 2 70 - 240 mm²
0630 2.4 65K A 385 2 70 - 240 mm²
0700 2.4 65K A 415 2 70 - 240 mm²
0760 2.4 65K A 449 2 70 - 240 mm²
0800 2.4 65K A 468 2 70 - 240 mm²
0830 2.4 65K A 491 2 70 - 240 mm²
0930 2.4 65K A 537 3 95 - 195 mm²

1. A s standard, all units have single point pow er connection.


2. M axim um S ystem Full Load C urrent is the m axim um input current draw before the
com pressor unloads and is the condition that should be used for pow er cable sizing.

C onditions 7 D eg. C leaving ch illed w ater, condenser air on increasing, S tandard low sound, U ltra-Q uiet or 2-S pd. fans, 400V A C .
M ultiply current by 1.02 for operation at 360V A C . S ize per E N 60204.

3. N om inal A m ps at 35 D eg. C am bient and 7 D e g. C leavin g c hilled w ater, 400V A C .


4. C ontrol K V A inc ludes o perational controls and eva porator heaters.
5. S ystem inrush current is less than R LA due to the use of Y ork V ariable S peed D riv e
technology. T ypical C om pressor S tarting C urrent ( firs t four seconds of startup):

R ated V oltage T ypical S tarting C urrent per C om pressor


380-400/50/3 17A
6. V oltage U tilization R ange:

R ated V oltage U tilization R ange


380-415/50/3 360-440
7. V alues stated are for S low (s tar) and Fast (delta) respectively.

43
Form No. 201.26 EG 03 (GB 05/08)
3 SYSTEM ELECTRICAL DATA (HIGH EFFICIENCY)
System 1

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. (3) Qty.
(EA) (EA) (EA) (EA)
1050 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.3
1120 400 50 164 5 3.1 18.0 173 5 1.9/3.8 4.5/10.3
1220 400 50 183 5 3.1 18.0 194 5 1.9/3.8 4.5/10.3
1380 400 50 218 6 3.1 18.0 229 6 1.9/3.8 4.5/10.3

System 2

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
Fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq (3) Qty. (3) Qty.
(EA) (EA) (EA) (EA)
1050 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.3
1120 400 50 164 5 3.1 18.0 173 5 1.9/3.8 4.5/10.3
1220 400 50 183 5 3.1 18.0 194 5 1.9/3.8 4.5/10.3
1380 400 50 218 6 3.1 18.0 229 6 1.9/3.8 4.5/10.3
System 3

Model No./Nameplate Compressor


Compressor (2-
(Std. & UQ Std. & UQ Cond. Fans 2-Spd. Cond. Fans
Spd fans)
Fans)
(7) (7)
(6) Nominal Amps FLA LRA Nominal Amps FLA LRA
YCIV Volts Freq Qty. Qty.
(3) (EA) (EA) (3) (EA) (EA)
1050 400 50 126 4 3.1 18.0 132 4 1.9/3.8 4.5/10.3
1120 400 50 164 5 3.1 18.0 173 5 1.9/3.8 4.5/10.3
1220 400 50 169 6 3.1 18.0 178 6 1.9/3.8 4.5/10.3
1380 400 50 167 6 3.1 18.0 175 6 1.9/3.8 4.5/10.3

Unit Short
Model Control Circuit Field Wiring & Protection
Withstand (KA)

Maxmum Full Load


Lugs/
YCIV KVA
(4)
At 400VAC Current Std, UQ or 2- (1) Lug Wire Range
(2) Phase
Spd. Fans
1050 2.4 65K A 624 4 120 - 240 mm²
1120 2.4 65K A 659 4 120 - 240 mm²
1220 2.4 65K A 702 4 120 - 240 mm²
1380 2.4 65K A 803 4 120 - 240 mm²
1. A s standard, all units have single point pow er connection.
2. M axim um S ystem Full Load C urrent is the m axim um input current draw before the
com pressor unloads and is the condition that should be used for pow er cable sizing.

C onditions 7 D eg. C leaving ch illed w ater, condenser air on increasing, S tandard low sound, U ltra-Q uiet or 2-S pd. fans, 400V A C .
M ultiply current by 1.02 for operation at 360V A C . S ize per E N 60204.

3. N om inal A m ps at 35 D eg. C am bient and 7 D e g. C leavin g c hilled w ater, 400V A C .


4. C ontrol K V A inc ludes o perational controls and eva porator heaters.
5. S ystem inrush current is less than R LA due to the use of Y ork V ariable S peed D riv e
technology. T ypical C om pressor S tarting C urrent ( firs t four seconds of startup):

R ated V oltage T ypical S tarting C urrent per C om pressor


380-400/50/3 17A
6. V oltage U tilization R ange:

R ated V oltage U tilization R ange


380-415/50/3 360-440
7. V alues stated are for S low (s tar) and Fast (delta) respectively.

44
Drawing shows lefthanded cooler
For ease of installation evaporator
water connections are left or right
handed when viewed from the control
panel end. Left handed water
connections are standard.
YCIV0590HE, 0600SE AND 0650SE - DIMENSIONS

Model A B C D
YCIV0590HE 2865.9 (112.8) 2146.3 (84.5) 484.5 (19.1) 714.0 (28.1")
YCIV0600SE 2796.9 (110.1) 2286 (90.0) 441.6 (17.4) 739.4 (29.1"),
YCIV0650SE 2865.9 (112.8) 2146.3 (84.5) 484.5 (19.1) 714.0 (28.1")
Form No. 201.26 EG 03 (GB 05/08)

45
46
Drawing shows lefthanded cooler
For ease of installation evaporator
water connections are left or right
handed when viewed from the control
Form No. 201.26 EG 03 (GB 05/08)

panel end. Left handed water


connections are standard.
YCIV0630HE, 0720SE AND 0770SE - DIMENSIONS

Dimension
Model A B C D
YCIV0630HE 2865.9 (112.8) 2146.3 (84.5) 484.5 (19.1) 714.0 (28.1")
YCIV0720SE 2865.9 (112.8) 2146.3 (84.5) 484.5 (19.1) 714.0 (28.1")
YCIV0770SE 2878.6 (113.3) 2009.9 (79.1) 535.3 (21.1) 660.6 (26.0")
Drawing shows lefthanded cooler
For ease of installation evaporator
water connections are left or right
handed when viewed from the control
panel end. Left handed water
connections are standard.
YCIV0700HE, 0760HE AND 0840SE - DIMENSIONS

Dimension
Model A B C D
YCIV0700HE 2865.9 (112.8) 2146.3 (84.5) 484.5 (19.1) 714.0 (28.1")
YCIV0760HE 2853.3 (112.3) 2174.8 (85.6) 519.4 (20.4) 714.0 (28.1")
YCIV0840SE 2878.6 (113.3) 2009.9 (79.1) 535.3 (21.1) 660.6 (26.0")
Form No. 201.26 EG 03 (GB 05/08)

47
48
Drawing shows lefthanded cooler
For ease of installation evaporator
water connections are left or right
handed when viewed from the control
panel end. Left handed water
connections are standard.
Form No. 201.26 EG 03 (GB 05/08)
YCIV0800HE AND 0920SE - DIMENSIONS

Dimension
Model A B C D
YCIV0800HE 2853.3 (112.3) 2174.8 ([85.6) 519.4 (20.4) 714.0 (28.1")
YCIV0920SE 2878.6 (113.3) 2009.9 (79.1) 535.3 (21.1) 660.6 (26.0")
Drawing shows lefthanded cooler
For ease of installation evaporator
water connections are left or right
handed when viewed from the control
panel end. Left handed water
connections are standard.
YCIV0830HE, 0930HE AND 1000SE - DIMENSIONS

Dimension
Model A B C D
YCIV0830HE 2853.3 (112.3) 2174.8 (85.6) 519.4 (20.4) 714.0 (28.1")
YCIV0930HE 2878.6 (113.3) 2009.9 ([79.1) 535.3 (21.1) 660.6 (26.0")
YCIV1000SE 2878.6 (113.3) 2009.9 ([79.1) 535.3 (21.1) 660.6 (26.0")
Form No. 201.26 EG 03 (GB 05/08)

49
50
Form No. 201.26 EG 03 (GB 05/08)
YCIV1050HE - DIMENSIONS

Drawing shows lefthanded cooler.For ease of installation evaporator water connections are left or right
handed when viewed from the control panel end. Left handed water connections are standard.
YCIV1070SE - DIMENSIONS

Drawing shows lefthanded cooler.For ease of installation evaporator water connections are left or right
handed when viewed from the control panel end. Left handed water connections are standard.
Form No. 201.26 EG 03 (GB 05/08)

51
52
Form No. 201.26 EG 03 (GB 05/08)
YCIV1120HE - DIMENSIONS

Drawing shows lefthanded cooler.For ease of installation evaporator water connections are left or right
handed when viewed from the control panel end. Left handed water connections are standard.
YCIV1180SE - DIMENSIONS

Drawing shows lefthanded cooler.For ease of installation evaporator water connections are left or right
handed when viewed from the control panel end. Left handed water connections are standard.
Form No. 201.26 EG 03 (GB 05/08)

53
54
Form No. 201.26 EG 03 (GB 05/08)
YCIV1220HE AND 1340SE- DIMENSIONS

Drawing shows lefthanded cooler.For ease of installation evaporator water connections are left or right
handed when viewed from the control panel end. Left handed water connections are standard.
YCIV1380HE AND 1500SE- DIMENSIONS

Drawing shows lefthanded cooler.For ease of installation evaporator water connections are left or right
handed when viewed from the control panel end. Left handed water connections are standard.
Form No. 201.26 EG 03 (GB 05/08)

55
Form No. 201.26 EG 03 (GB 05/08)
ELECTRICAL CABLE ENTRY

244
442
484

148

DEPTH OF OPENING 150mm

56
Form No. 201.26 EG 03 (GB 05/08)
DESUPERHEATER OPTION WATER PRESSURE DROP

160
140 C
120
100 B

80
70 A
Pressure Drop kPa

60
50
40

30
25
20

15

10
1 1.25 1.5 1.75 2 2.5 3 3.5 4 4.5 5 5.5 6
Flow Rate l/s
Line Pressure Drop Calculation
A Pressure Drop [kPa] = 11.5132 x (Flow Rate [l/s]^1.9187)
B Pressure Drop [kPa] = 6.8514 x (Flow Rate [l/s]^1.9400)
C Pressure Drop [kPa] = 5.6073 x (Flow Rate [l/s]^1.9209)

Line YCIV Model


A 0590HE, 0600SE, 0630HE 0650SE
0700HE, 0720SE, 0760HE, 0770SE, 0800HE,
B 0830HE, 0840SE,1050HE, 1070SE, 1120HE,
1180SE, 1220HE, 1340SE
C 0920SE, 0930HE, 1000SE, 1380HE, 1500SE
Note: Desuperheaters are not fitted on System 3 on Models 1050HE,
1070SE, 1120HE, 1180SE, 1220HE, 1340SE, 1380HE, 1500SE

57
Form No. 201.26 EG 03 (GB 05/08)
DESUPERHEATER OPTION WATER CONNECTIONS

CONTROL
PANEL

WATER IN

WATER OUT

850

2230

251

2" BSP MALE


COUPLING

219

58
Form No. 201.26 EG 03 (GB 05/08)
CONSULTANTS GUIDE SPECIFICATION 4. Unit shall be stored and handled per Manufacturer’s
instructions.
PART 1 — GENERAL
PART 2 — PRODUCTS
1.01 SCOPE
2.01 GENERAL
1. The requirements of the General Conditions,
Supplementary Conditions and Drawings apply to 1. Manufacturers: The design shown on the drawings
all work herein. is based on York International. Alternate equipment
will be acceptable if their equipment meets the
2. Provide Microprocessor controlled, twin-screw scheduled performance and complies with these
compressor, air-cooled, liquid chillers of the specifications. If equipment manufactured by a
scheduled capacities as shown and indicated on manufacturer other than that scheduled is utilised,
the Drawings, including but not limited to: then the Mechanical Contractor shall be responsible
for coordinating with the General Contractor and all
• Chiller package
affected Subcontractors to insure proper provisions
• Charge of refrigerant (Except remote evaporator for installation of the unit supplied. This coordination
applications) and oil shall include, but not be limited to, the following:

• Electrical power and control connections • Structural supports for units.

• Chilled water connections • Piping size and connection/header locations.

• Start-up by manufacturers personnel. • Electrical power requirements and wire/conduit


and over-current protection sizes.
1.02 QUALITY ASSURANCE
• Chiller physical size impact on plant layout.
1. Products shall be Designed, Tested, Rated and
Certified in accordance with, and installed in • Site noise considerations.
compliance with applicable sections of the following
1. The Mechanical Contractor shall be responsible
Standards and Codes:
for all costs incurred by the General Contractor,
2. Chillers will be designed within an EN ISO 9002 Subcontractors, and Consultants to modify the
and built within an EN ISO 9001 accredited building provisions to accept the units supplied.
manufacturing organisation and in conformity with
2. Description: Install and commission, as shown on the
the following European Directives:
schedules and plans, factory assembled, charged,
• Machinery Directive (89/392/EEC) and operational tested air-cooled screw compressor
chiller(s) as specified herein. Chiller shall include,
• Low Voltage Directive (73/23/EEC, EN 60204)
but is not limited to: a complete system with not
• EMC Directive (89/336/EEC) less than two independent refrigerant circuits,
• Pressure Equipment Directive (97/23/EC) semi-hermetic twin screw compressors, shell and
• Safety Code for Mechanical Refrigeration (EN378) tube type evaporator, air-cooled condenser, R134a
refrigerant, lubrication system, interconnecting
1. Factory Test: Chiller shall be pressure-tested, wiring, safety and operating controls including
evacuated and fully charged with refrigerant and capacity controller, control centre, motor starting
oil, and shall be factory operational run tested with components, and special features as specified
water flowing through the vessel. herein or required for safe, automatic
operation.
2. Chiller manufacturer shall have a factory trained
and supported service organization. C. Operating Characteristics:
3. Warranty: Manufacturer shall Warranty all 1. Provide low ambient control and high ambient
equipment and material of its manufacture against options as required to ensure unit is capable of
defects in workmanship and material for a period of operation from -18°C to 52°C ambient.
eighteen (18) months from date of availability.
2. Provide capacity control system capable of
1.03 DELIVERY AND HANDLING reducing unit capacity to (10% for 2 compressor
units and 7.5% for 3 compressor units) of full load.
1. Unit shall be delivered to job site fully assembled and
Compressor shall start in unloaded condition.
charged with refrigerant (except remote evaporator
applications) and oil by the Manufacturer.

2. A protective covering, over vulnerable components,


shall be provided during shipment. Fit nozzles and
open ends with plastic enclosures.

3. The chiller shall be protected, and its accessories,


from the weather and dirt exposure during
shipment.

59
Form No. 201.26 EG 03 (GB 05/08)
3. Cabinet: Unit panels, structural elements and 2.04 HEAT EXCHANGERS
heavy gauge structural base shall be constructed
of galvanised steel. Unit panels, control boxes Evaporator:
and structural base are finished with a baked on 1. Direct expansion type or flooded type shell and
powder paint. All painted surfaces shall be coated tube evaporator with high efficiency copper tubes.
with baked on powder paint which, when subject to Independent refrigerant circuits shall be provided
ASTMB117, 1,000 hour, 5% salt spray test, yields per compressor.
minimum ASTM 1654 rating of “6”.
2. The design working pressure of the cooler on the
4. Unit shall ship in one piece and shall require shell side shall be 10.3 bar, and 16 bar for the
installer to provide evaporator inlet and outlet pipe tube (refrigerant side). The evaporator shall be
connections. If providing chiller model that ships constructed and marked in accordance with the
in multiple pieces, Contractor shall include all the Pressure Equipment Directive and pressure tested
material and field labour costs for factory authorised to Refrigerant Safety Standard EN 378.
personnel to install a trim kit to connect the pieces
as well as all interconnecting piping and wiring. 3. The shell shall be covered with 19 mm, flexible,
closed-cell insulation. The water nozzles shall have
2.02 COMPRESSORS AND MOTORS grooves for mechanical couplings, and be insulated
1. Compressors: Shall be direct drive, semi- by the Contractor after pipe installation.
hermetic, rotary twin-screw type, including: muffler, 4. Vent and drain fittings, and thermostatically
temperature actuated ‘off-cycle’ heater, rain-tight controlled heaters to protect to -29°C ambient in
terminal box, discharge shut-off service valve, the off-cycle, shall be provided.
and precision machined cast iron housing. Design
working pressure of entire compressor, suction to Air Cooled Condenser:
discharge, shall be 24 bar.
1. Coils: Internally enhanced, seamless copper
2. Motors: Refrigerant suction gas cooled accessible tubes, mechanically expanded into aluminium alloy
hermetic compressor motor, full suction gas flow fins with full height collars. A subcooling coil shall
through mesh screen, with inherent internal thermal be provided as an integral part of the condenser.
overload protection and external current overload Design working pressure shall be 24 bar.
on all three phases.
2. Fans: Shall be dynamically and statically balanced,
3. Lubrication: External oil separators with no moving direct-drive, corrosion-resistant glass-fibre-
parts, 24 bar design working pressure. Refrigerant reinforced composite blades moulded into low
system differential pressure shall provide oil flow noise, full airfoil cross section, providing vertical air
through service replaceable, 0.5 micron, full flow, discharge from extended orifices. Guards of heavy
cartridge type oil filter internal to compressor. Filter gauge, PVC (polyvinyl chloride) coated steel wire.
bypass, less restrictive media, or oil pump not
acceptable. 3. Fan Motors: High efficiency, direct drive, 3 phase,
insulation class “F”, current protected, Totally
4. Capacity Control: Compressors shall start at Enclosed Air Over (TEAO), with double sealed,
minimum load. Provide Microprocessor control permanently lubricated ball bearings.
to command compressor capacity to balance
compressor capacity with cooling load. 2.05 POWER AND ELECTRICAL REQUIREMENTS

2.03 REFRIGERANT CIRCUIT COMPONENTS Power/Control Panel:

1. Each independent refrigerant circuit shall include: 1. IP55 powder painted steel cabinets with hinged,
liquid line shutoff valve with charging port, low side latched, and gasket sealed outer doors equipped
pressure relief device, removable core filter-drier, with wind struts for safer servicing. Provide main
sight glass with moisture indicator, and electronic power connection, compressor starters and fan
expansion valve. motor contactors, current overloads, and factory
wiring.
2. Chiller manufacturer shall provide independent
circuit for each compressor to provide maximum 2. Panel shall include control display access door.
redundancy. If equipment does not have
Single Point Power
independent circuits per compressor, manufacturer
(As standard for 2 and 3 compressor chillers)
shall provide owner one spare compressor of each
unique size. 1. Provide a single point power connection to chiller,
shall be 3 phase of scheduled voltage.
3. Discharge lines shall be provided with manual
compressor shutoff service valves. Suction line 2. Circuit breaker shall be provided at point of incoming
shall be covered with closed cell foam insulation. single point connection to provide means of disconnecting
and short circuit protection. Circuit breaker shall be
equipped with lockable operating handle that shall
extend through power panel door so that power may be
disconnected without opening any panel doors.
60
Form No. 201.26 EG 03 (GB 05/08)
3. Control Transformer: Power panel shall be Setpoints, Data and Safeties
supplied with a factory mounted and wired control
transformer that will supply all unit control voltage 1. Programmable Setpoints: display language;
from the main unit power supply. Transformer shall leaving chilled liquid temperature: setpoint, control
utilize scheduled line voltage on the primary side range; local or remote control; units of measure;
and provide 115 V/1 phase on secondary. compressor lead/lag; and maximum chilled water
setpoint reset temperature range.
4. Starting current shall not exceed compressor full
load amps. 2. Display Data: Chiller liquid return and leaving
temperatures, ambient, lead compressor
5. Exposed compressor and fan motor power wiring identification, clock and schedule, (variable)
shall be routed through conduit. out of range, remote input indication, chilled
liquid reset setpoint, and history data for last ten
6. Power Factor: shutdown faults. Compressor suction, discharge,
and oil pressures and temperatures, suction
• Provide equipment with power factor correction
and discharge superheats, percent of full-load,
capacitors as required to maintain a power factor
operating hours, starts, and anti-recycle timer
of 95% at all load conditions.
status. Status Messages for manual override, unit
• The installing contractor shall be responsible for switch off, compressor run, run permissive, remote
additional cost to supply and install power factor controlled shut down, no cooling load, daily/holiday
correction capacitors if they are not factory mounted shut down, anti-recycle timer.
and wired.
3. Predictive Control Points: Unit controls shall avoid
2.06 CONTROLS safety shutdown when operating outside design
conditions by optimising the chiller controls and
General: cooling load output to stay on-line and avoid safety
limits being reached. The system shall monitor the
1. Provide automatic control of chiller operation
following parameters and maintain the maximum
including compressor start/stop and load/unload,
cooling output possible without shutdown of the
anti-recycle timers, condenser fans, evaporator
equipment: motor current, suction pressure and
pump, evaporator heater, unit alarm contacts and
discharge pressure.
run signal contacts.
4. System Safeties: Shall cause individual compressor
2. Chiller shall automatically reset to normal chiller
systems to perform auto-reset shut down; manual
operation after power failure.
reset required after the third trip in 90 minutes.
3. Unit operating software shall be stored in non- Includes: high discharge pressure or temperature,
volatile memory. Field programmed set points shall low suction pressure, high / low motor current, high
be retained in lithium non-rechargeable battery motor temperature, high pressure switch, high /
backed real time clock (RTC) memory for minimum low differential oil pressure, high oil temperature,
5 years. low suction superheat, critical sensor malfunction,
low or high current, phase loss/single phase power,
4. Alarm contacts shall be provided for remote alert of overload of motor windings, and low voltage.
any unit or system safety fault.
5. Unit Safeties: Shall be automatic reset and cause
Display and Keypad: compressors to shut down if: high or low ambient,
low leaving chilled liquid temperature, under voltage,
1. Provide minimum 80 character liquid crystal and flow switch operation. Contractor shall provide
display that can be viewed in both direct sunlight flow switch and wiring per chiller manufacturer
and has LED backlighting for night-time viewing. requirements.
A unit mounted keypad and display panel shall be
provided. Manufacturer shall provide any controls not listed above,
necessary for automatic chiller operation. Mechanical
2. Display and keypad shall be accessible through Contractor shall provide field control wiring necessary
display access door without opening main control/ to interface sensors to the chiller control system.
electrical cabinet doors.
2.07 ACCESSORIES AND OPTIONS
3. Display shall provide a minimum of unit setpoints,
status, electrical data, temperature data, pressures, Some accessories and options supersede standard
safety lockouts and diagnostics without the use of a product features. Your YORK representative will be
coded display. pleased to provide assistance.

4. Numeric data in Metric (or English) units.

5. Sealed keypad shall include unit On/Off switch.

61
Form No. 201.26 EG 03 (GB 05/08)
Sound Reduction 4. 10.3 bar companion weld flanges.

Provide the following options as required to meet 5. 20.7 bar welded flanges.
scheduled sound performance data at all load points. 6. 20.7 bar companion weld flanges.
• Normal speed fans and unlined compressor 7. 10.3 bar Victaulic™ Flanges (field kit, matching
enclosure (Factory Mounted) pipe flange by contractor).

• Two speed fans and acoustically lined compressor Flow Switch (Field Mounted):
enclosure (Factory Mounted)
Vapour proof 10.3 bar or 20.7 bar, -28.9°C to 121.1°C.
Sound Power Levels
Building Automation System Interface:
Sound power octave band data, dB in accordance with
ISO 3744, at 35°C ambient and 7°C leaving chilled 1. Chiller to accept 4 to 20 mA or 0 to 10 Vdc input
water. to reset the leaving chilled liquid temperature, or
percent full load amps (current limit). (Factory
Provide optional control input to limit sound output of Mounted)
the chiller based on time of day. Shall be programmable
at the chiller panel or controlled remotely via signal (4- 2. Provide chiller with microgateway for an interface
20 mA or 0-10 Vdc) from BAS system. Chillers without to other systems that can share data via BACNet™
this feature shall be provided with the necessary sound (Factory Mounted)
attenuation to meet the scheduled sound performance Vibration Isolation (Field Mounted):
data at all load points.
1. Neoprene Isolators - 1 Inch Deflection Spring
Condenser Coil Environmental Protection: Isolators: Level adjustable, spring and cage type
1. PRE-COATED FIN CONDENSER COILS – The air- isolators for mounting under the unit base rails.
cooled condenser coils are constructed of epoxy- 2. 2 Inch Deflection Seismic Isolators - Level
coated aluminium fins. adjustable, restrained mounts in rugged welded
2. COPPER FIN – Provide condenser coils with steel housing with vertical and horizontal limit
copper fins in lieu of aluminium fins. stops. Housings shall be designed to withstand a
minimum 1.0 g accelerated force in all directions
3. POST-COATED EPOXY DIPPED CONDENSER to 50 mm.
COILS – The unit is built with dipped-cured
condenser coils. Service Shut-off Valve

Protective Chiller Panels (Factory Mounted): Provide suction service shut-off valve for each
compressor. (Factory Mounted)
1. Louvered Panels (condenser coils only): Painted
steel to match unit panels, over external condenser PART 3 — EXECUTION
coil faces. 3.01 INSTALLATION
2. Wire Panels (full unit): Heavy gauge, welded 1. General: Rig and Install in full accordance with
wire mesh, coated to resist corrosion, to protect Manufacturer’s requirements, Project drawings,
condenser coils from incidental damage and restrict and Contract documents.
unauthorized access to internal components.
2. Location: Locate chiller as indicated on drawings,
3. Louvered Panels (full unit): Painted steel to including cleaning and service maintenance
match unit panels, to protect condenser coils clearance per Manufacturer instructions. Adjust
from incidental damage, visually screen internal and level chiller on support structure.
components, and prevent unauthorized access to
internal components. 3. Components: Installing Contractor shall provide
and install all auxiliary devices and accessories for
4. Louvered/Wire Panels: Louvered steel panels on fully operational chiller.
external condenser coil faces, painted to match unit
panels. Heavy gauge, welded wire-mesh, coated to 4. Electrical: Coordinate electrical requirements and
resist corrosion, around base of machine to restrict connections for all power feeds with Electrical
unauthorized access. Contractor.
Evaporator options: 5. Controls: Coordinate all control requirements and
connections with Controls Contractor.
1. Provide 38 mm cooler insulation in lieu of standard
19 mm. 6. Finish: Installing Contractor shall paint damaged
2. Provide raised Face Flange Accessory for cooler and abraded factory finish with touch-up paint
nozzles: matching factory finish.

3. 10.3 bar welded flanges.

62
Form No. 201.26 EG 03 (GB 05/08)

63
www.johnsoncontrols.com

FORM 201.26 EG 03 (GB 0508) Subject to change without notice.


Revision 3 ALL RIGHTS RESERVED