Sei sulla pagina 1di 6

1168 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO.

2, APRIL 2005

Analysis of Zig-Zag Transformer Applying in the


Three-Phase Four-Wire Distribution Power System
Hurng-Liahng Jou, Member, IEEE, Jinn-Chang Wu, Kuen-Der Wu, Wen-Jung Chiang, and Yi-Hsun Chen

Abstract—The load unbalance and the nonlinear loads result the neutral conductor of the three-phase four-wire distribution
in a significant neutral current in the three-phase four-wire power system is three times of the zero-sequence components
distribution power system. The Zig-Zag transformer has been of each phase current. Furthermore, the single-phase loads may
proposed to attenuate the neutral current of the three-phase
four-wire distribution power system. In this paper, an analysis
result in serious load unbalance. The unbalanced load currents
is carried out and computer simulation is used to evaluate the contain zero-sequence components and also flow in the neutral
performance of the Zig-Zag transformer under ideal and nonideal conductor. Survey results across computer sites in U.S. show
power conditions. The simulation results show that (a) the Zig-Zag that 22.6% of the sites have neutral currents exceeding the
transformer can effectively attenuate the neutral current and full-load phase currents [2], which may result in an overload
zero-sequence harmonic currents on the utility side under the accident of the neutral conductor. Additionally, a large neutral
balanced utility voltage, (b) the utility side neutral current becomes
larger under the unbalanced utility voltage or the distorted utility current may also result in the saturation problem in the dis-
voltage with zero sequence harmonic components after applying tribution power transformer. Thus, the three-phase four-wire
the Zig-Zag transformer, (c) the insertion of an inductor in the distribution power systems have the problems of harmonic
utility side of the neutral conductor can alleviate overloading pollution, load unbalance and over-load of neutral conductor
of the neutral current caused by the unbalanced utility voltages [3]–[6].
and the distorted utility voltages with zero sequence harmonic
The Zig-Zag transformer has been used to attenuate the neu-
components.
tral current and zero-sequence harmonic currents on the utility
Index Terms—Neutral current, three-phase four-wire, Zig-Zag. sites [7]–[9] in recent years due to the advantages of low cost,
high reliability and simplified circuit connection. The Zig-Zag
I. INTRODUCTION transformer has also another application for avoiding DC mag-
netization and iron losses caused by the three-phase single-way

T HREE-PHASE four-wire distribution power system has


been widely used for supplying low-level voltage to office
buildings, commercial complexes, manufacturing facilities,
rectifier [10]. In order to understand the performance of the
Zig-Zag transformer, the analysis and computer simulation are
made under ideal and nonideal power conditions in this paper.
etc [1]. The loads connected to the three-phase four-wire The simulation results can be used as the reference in the appli-
distribution power system may be either the single-phase cation of the Zig-Zag transformer.
or the three-phase loads. The typical loads connected to the
three-phase four-wire distribution power systems may be com- II. BASIC THEORY
puter related equipment, automatic office machines, adjustable
speed drives, lighting ballasts and other power electronic re- Zig-Zag transformer is a special connection of three
lated equipment. Most of these loads have the nonlinear input single-phase transformer’s windings or a three-phase trans-
characteristic, which creates a problem of high input current former’s windings [8], [9]. The circuit connection is as shown
harmonics. The harmonic current will pollute the power system in Fig. 1(a). In the three-phase four-wire distribution power
and result in the problems such as transformer overheats, rotary system, the three-phase zero-sequence currents ( ,
and ) have the same amplitude and the same phase, and
machine vibration, degrading voltage quality, damaging electric
they can be represented as
power components, medical facilities malfunction, etc. The
third harmonic is most serious for the single-phase nonlinear (1)
loads. The current of the integer multiples 3rd are regarded as
the zero-sequence current. The zero-sequence current flowing in The neutral current is the sum of three-phase zero-se-
quence currents, and it is represented as

Manuscript received December 9, 2003; revsied July 12, 2004. Paper no.
(2)
TPWRD-00621-2003.
H.-L. Jou is with the Department of Electrical Engineering, National Kaoh- Because the turn ratio of the transformer’s windings is 1:1 in
siung University of Applied Sciences, Kaohsiung 807, Taiwan, R.O.C. (e-mail: Fig. 1, the input current flowing into the dot point of the primary
hljou@mail.e.kuas.edu.tw). winding is equal to the output current flowing out from the dot
J.-C. Wu is with the Department of Electrical Engineering, Kun
Shan University of Technology, Tainan 710, Taiwan, R.O.C. (e-mail: point of the secondary winding. Then, we can obtain
jinnwu@mail.ksut.edu.tw)
K.-D. Wu, W.-J. Chiang, and Y.-H. Chen are with the Department of Electrical (3)
Engineering, National Kaohsiung University of Applied Sciences, Kaohsiung (4)
807, Taiwan, R.O.C.
Digital Object Identifier 10.1109/TPWRD.2005.844281 (5)
0885-8977/$20.00 © 2005 IEEE

Authorized licensed use limited to: Mohamed Ahmed. Downloaded on February 3, 2010 at 06:00 from IEEE Xplore. Restrictions apply.
JOU et al.: ANALYSIS OF ZIG-ZAG TRANSFORMER APPLYING IN THE THREE-PHASE FOUR-WIRE DISTRIBUTION POWER SYSTEM 1169

Fig. 2. The system configuration of three-phase four-wire distribution power


system with the Zig-Zag transformer.

Fig. 1. Zig-Zag transformer: (a) circuit connection and (b) phasor diagram.
Fig. 3. The zero-sequence equivalent circuit.
Equations (3)–(5) indicate that three-phase currents flowing
into three transformers must be equal. This means that the From (6), the zero-sequence voltage can be expressed as
Zig-Zag transformer can supply the path for the zero-sequence
current. Fig. 1(b) shows the phasor diagram [10] of Fig. 1(a). (7)
From Fig. 1(b), it can be found that the voltage across the
transformer’s winding is of the phase voltage of the is the zero-sequence current source, and it contains the
three-phase four-wire distribution power system. unbalanced fundamental load currents and zero-sequence of
harmonic load currents , and it can be derived as
III. ANALYSIS OF ZIG-ZAG TRANSFORMER IN THE
THREE-PHASE FOUR-WIRE SYSTEM (8)
Fig. 2 shows the system configuration of the Zig-Zag trans-
former applied in the three-phase four-wire distribution power In Fig. 3, is the zero-sequence impedance of the Zig-Zag
systems. In Fig. 2, is the impedance of the neutral con- transformer. The effects of the and to the neutral
ductor between the load and the Zig-Zag transformer, and is current of the utility side after using the Zig-Zag transformer can
the impedance between the utility and the Zig-Zag transformer. be analyzed by using the superposition theory. For considering
consists of and , where is the impedance of the effect of the , the should be assumed to be a
the neutral conductor and is the impedance of the inserted short circuit in Fig. 3. Then, the utility side neutral current
inductor. caused by can be expressed as
The current flowing through the Zig-Zag transformer is only
the zero-sequence component, and the zero-sequence equivalent (9)
circuit of Fig. 2 is shown in Fig. 3. This consists of two zero-se-
quence sources, and . In the practical three-phase Equation (9) indicates that the magnitude of the utility side neu-
four-wire industry distribution power system, the unbalanced tral current caused by will be reduced after applying the
utility voltages may occur frequently due to the unequal load Zig-Zag transformer. If is reduced or is increased,
distribution of the upstream in each phase or the abnormal phase in the utility side can be further attenuated.
change even when the loads are balanced. The is a zero For considering the effect of , should be assumed
sequence voltage source caused by the unbalanced utility volt- to be an open circuit in Fig. 3. From Fig. 3, it can be found that
ages. Assuming the thee-phase voltages ( , , ) the Zig-Zag transformer supplies a low impedance path for the
are unbalanced, the zero-sequence, the positive-sequence and zero-sequence voltage . This implies that the utility neu-
the negative-sequence components ( , , ) can tral current becomes larger under the unbalanced utility voltage
be represented as after applying the Zig-Zag transformer. The neutral current of
the utility side caused by can be expressed as
(6)
(10)

Authorized licensed use limited to: Mohamed Ahmed. Downloaded on February 3, 2010 at 06:00 from IEEE Xplore. Restrictions apply.
1170 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

Equation (10) shows that the Zig-Zag transformer supplies TABLE I


a path for the zero-sequence current flowing between the MAJOR PARAMETERS USED IN THE SIMULATION
utility and the Zig-Zag transformer. However, the impedance
of the utility system, the Zig-Zag transformer and the neutral
conductor are very small in most of the three-phase four-wire
distribution power systems. This implies that a significant
neutral current will be generated after applying the Zig-Zag
transformer under the condition of unbalanced utility voltages,
and this significant neutral current is an undesired performance
of the Zig-Zag transformer. This significant neutral current may
result in the burn-down of the Zig-Zag transformer, the neutral
conductor and the distribution power transformer. This means
that the undesired performance of the Zig-Zag transformer
occurs under the condition of unbalanced utility voltages.
Additionally, the distorted utility voltages may also contain the
zero-sequence voltages. To avoid this problem, the Zig-Zag
transformer is not suggested to be applied in the unbalanced or
the distorted voltages of the three-phase four-wire distribution
power system except an inductor ( ) is inserted in the
neutral conductor of the utility side.
Then, the practical utility side current can be obtained
by adding (9) and (10), and this can be expressed as

Fig. 4. Simulation result of phase A under the balanced nonlinear loads,


(11) (a) utility current, (b) load current, (c) Zig-Zag transformer current, (d) utility
side neutral current, and (e) load side neutral current.
From (11), it can be found that the Zig-Zag transformer can
be used to bypass the zero-sequence current of the load, but it
A. Balanced Utility Conditions
will also induce a significant zero-sequence current when the
utility voltages contain zero sequence components. Equation The simulation result of the three-phase four-wire distribution
(11) shows that the larger the is, the smaller the will power system with the Zig-Zag transformer under the balanced
be. This means that the installation of Zig-Zag transformer must nonlinear loads is shown in Fig. 4. The loads are three same
be as near to the load as possible to increase . For reducing single-phase rectifier loads, and the load currents are 12.1 A
the utility side neutral current furthermore, an inductor ( ), (RMS). The dominant harmonic current of single-phase rectifier
shown in Fig. 2, can be inserted in the neutral conductor of is the 3rd harmonic current. The 3rd harmonic current is a zero
the utility side in some applications. However, this application sequence component, and it will flow into the neutral line. As
may result in the neutral voltage variation or raising the neutral seen in Fig. 4(e), the neutral conductor of the load side contains
voltage of the load side. Because many electrical facilities use a significant zero-sequence current (20.89 A RMS). Fig. 4(d)
the neutral line as the referred ground, the neutral voltage vari- shows that the neutral current on the utility side is only 0.96
ation or raising the neutral voltage of the load side may cause A (RMS). This indicates that the neutral current on the utility
shut down or abnormal operation of the electric facilities in the side is only 4.59% of that on the load side. This result shows
load side. that the Zig-Zag transformer has the expected performance for
attenuating the neutral current effectively. Moreover, the THD
(total harmonic distortion) of the utility current is reduced from
IV. COMPUTER SIMULATIONS 140% to 129% because the 3rd harmonic current is attenuated
by the Zig-Zag transformer.
Computer simulations under different utility and load condi- Load unbalance occurs frequently in the practical three-phase
tions are made to verify the performance of the Zig-Zag trans- four-wire industry distribution power systems due to the unequal
former in the application for attenuating the neutral current of load currents in each phase. To represent this, the load currents
the three-phase four-wire distribution power system. The pa- of each phase are 0.6:0.8:1 in a, b and c phases respectively in
rameters used in the computer simulation are shown in Table I. the following simulation; and Fig. 5 shows the simulation results
The load in the following computer simulation is the single- of this condition. The unbalanced load generates a fundamental
phase rectifier with a load of capacitor and resistor connected in component current in the neutral conductor. Hence, the neutral
parallel. In general, the input power stage of computer related current on the load side, shown in Fig. 5(e), contains not only the
equipment could be regarded as this kind of load. The current of 3rd harmonic component but also the fundamental component,
single-phase rectifier contains rich harmonics, such as 3rd, 5th, and it is 27.023 A (RMS). As seen in Fig. 5(d), the neutral
7th, etc. orders. Because only the steady state is considered in current on the utility side is very small. The neutral current
this paper, the start time of computer simulation is 450 ms in the on the utility side is only about 4.5% of that on the load
following simulation. side. The utility currents are 0.77:0.83:1 in a, b and c phases,

Authorized licensed use limited to: Mohamed Ahmed. Downloaded on February 3, 2010 at 06:00 from IEEE Xplore. Restrictions apply.
JOU et al.: ANALYSIS OF ZIG-ZAG TRANSFORMER APPLYING IN THE THREE-PHASE FOUR-WIRE DISTRIBUTION POWER SYSTEM 1171

Fig. 5. Simulation result of phase A under the unbalanced nonlinear loads,


(a) utility current, (b) load current, (c) Zig-Zag transformer current, (d) utility
side neutral current, and (e) load side neutral current.
Fig. 7. Simulation result of phase A under the utility voltage with phase
unbalance, (a) three-phase utility voltage, (b) utility current, (c) load current,
(d) Zig-Zag transformer current, (e) utility side neutral current, and (f) load
side neutral current.

B. Unbalanced Utility Voltages


In the practical three-phase four-wire industry distribution
power system, the unbalanced utility voltages caused by the
unequal load distribution in each phase or the abnormal phase
change may occur frequently. The unbalanced utility voltages
can be divided into amplitude unbalance and phase unbalance.
Considering the phase unbalance, the phases of three-phase
voltages are 0 , and 110 respectively. Fig. 7 shows
the simulation results of this condition. Since the unbalanced
three-phase voltages contain a zero-sequence voltage, and this
will generate a significant fundamental component flows be-
tween the utility, the neutral conductor on the utility side and
the Zig-Zag transformer. As seen in Fig. 7, the neutral cur-
Fig. 6. Simulation result of phase A under the single-phase nonlinear loads,
rent on the utility side contains a large fundamental component.
(a) utility current, (b) load current, (c) Zig-Zag transformer current, (d) utility This coincides with the above analysis that the use of Zig-Zag
side neutral current, and (e) load side neutral current. transformer in an unbalanced three-phase four-wire distribution
power system will induce a significant unexpected neutral cur-
respectively. This indicates that the Zig-Zag transformer is rent. The neutral current on the utility side is 97.72 A (RMS),
capable of balancing the three- phase currents due to canceling and that is 20.95 A (RMS) on the load side. The neutral cur-
the zero-sequence current. rent of the utility side becomes larger, and that is more than four
In the practical three-phase four-wire industry distribution times of that on the load side.
power system, the condition of the single-phase load also may Considering the amplitude unbalance, the amplitudes of
occur. This can be regarded as the most serious load unbalance. three-phase voltages are 180 V, 180 V and 160 V respectively.
Fig. 6 shows the simulation results of this condition indicating Fig. 8 shows the simulation results of this condition. Since
that the neutral current is attenuated from 12.323 A (RMS) to the unbalanced three-phase voltages contain a zero-sequence
less than 0.539 A (RMS). This means that the neutral current voltage, and this will generate a significant fundamental com-
of the utility side is only 4.37% of that on the load side. The ponent flows through the utility, the neutral conductor on the
utility currents are 1:0.5:0.5 in a, b and c phases, respectively. utility side and the Zig-Zag transformer. The neutral current on
This indicates that the Zig-Zag transformer has the performance the utility side is 62.17 A (RMS), and that is 20.17 A (RMS)
of balancing the three-phase currents. on the load side. The neutral current on the utility side is about
From the above simulation, it can be found that the Zig-Zag three times of that on the load side.
is capable of attenuating the neutral current under the condi- The above results show that the neutral current and phase
tion of balanced utility voltages. This result is very consistent current of three-phase four-wire distribution power system
to (9). Moreover, the Zig-Zag transformer can reduce the total under the unbalanced utility voltages becomes larger after
harmonic distortion and balance the three- phase currents of the applying the Zig-Zag transformer. At the same time, the current
utility side. flowing through the Zig-Zag transformer is also very high.

Authorized licensed use limited to: Mohamed Ahmed. Downloaded on February 3, 2010 at 06:00 from IEEE Xplore. Restrictions apply.
1172 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

Fig. 8. Simulation result of phase A under the utility voltage with amplitude Fig. 9. Simulation result of phase A under the distorted utility voltage,
unbalance, (a) three-phase utility voltage, (b) utility current, (c) load current, (a) three-phase utility voltage, (b) utility current, (c) load current, (d) Zig-Zag
(d) Zig-Zag transformer current, (e) utility side neutral current, and (f) load side transformer current, (e) utility side neutral current, and (f) load side neutral
neutral current. current.

These results are very consistent to (10). Although the Zig-Zag


transformer can balance the utility currents to reduce the zero
sequence components of the utility voltages, but the utility
voltages still may contain zero-sequence components due to the
zero-sequence current generated by the upstream loads. This
indicates that the unbalance analysis of the three-phase four-wire
utility voltages is very important before applying the Zig-Zag
transformer. Otherwise, the use of the Zig-Zag transformer in
the three-phase four-wire distribution power system may result
in the burn-down of the Zig-Zag transformer or the neutral
conductor. The unbalanced utility voltages, which may cause Fig. 10. The relationship between utility side neutral current and the insertion
the neutral current after applying the Zig-Zag transformer to inductor.

become larger than that before applying the Zig-Zag transformer,


is depended on the impedances of , and . If the D. The Effect of Insertion Inductor
voltage unbalance is larger than 3%, the neutral current becomes From the analysis in Section III, it can be found that an
larger after applying Zig-Zag transformer under the system inductor can be inserted into the neutral conductor on the utility
parameters using in this paper. Fortunately, the use of an side to increase the impedance of the neutral conductor on the
insertion inductor ( ) can alleviate this problem. utility side to reduce the neutral current on the utility side in
the three-phase four-wire distribution power system with the
C. Distorted Utility Voltage Zig-Zag transformer. Hence, an inductor is suggested to be
Waveforms of the utility voltages are frequently distorted due inserted in the neutral conductor of the utility side in some
to the wide use of the nonlinear loads in the distribution power applications to intensify the effect of the Zig-Zag transformer for
system. Fig. 9 shows the simulation result under the condition attenuating the neutral current. Fig. 10 shows the relationship
of the utility voltages containing 19 V 3rd harmonic and 17 V of the neutral current on the utility side and the insertion
5th harmonic. Because the 3rd harmonic voltage is a zero-se- inductor. As seen in Fig. 10, the larger the insertion inductance
quence voltage, it will induce a significant neutral current is, the better the attenuating effect of the neutral current on
flowing through the utility and the Zig-Zag transformer. Fig. 9 the utility side will be. Besides, the insertion of an inductor in
shows that the utility current, the utility side neutral current the utility side neutral conductor can improve overloading of
and the Zig-Zag transformer current all contain a significant the neutral current caused by the unbalanced utility voltages
3rd harmonic component due to the 3rd harmonic voltage. The and the distorted utility voltages with zero-sequence harmonic
neutral current on the utility side is 113.46 A (RMS) and that components.
is 20.754 A (RMS) on the load side. The neutral current on the
utility side is more than five times of that on the load side. These V. CONCLUSIONS
results show that the neutral current in three-phase four-wire The over-load of the neutral conductor is a very serious
system after applying the Zig-Zag becomes larger when the problem in today’s three-phase four-wire distribution power
utility voltages contain zero-sequence harmonic components. systems. Although this problem can be solved effectively by
This result is very consistent (10). using the three-phase four-wire active power filter, the use of

Authorized licensed use limited to: Mohamed Ahmed. Downloaded on February 3, 2010 at 06:00 from IEEE Xplore. Restrictions apply.
JOU et al.: ANALYSIS OF ZIG-ZAG TRANSFORMER APPLYING IN THE THREE-PHASE FOUR-WIRE DISTRIBUTION POWER SYSTEM 1173

three-phase four-wire active power filter is limited due to its [7] Z. J. Wang, “A Study of the Harmonics for the Taiwan Electrified
high cost. The Zig-Zag transformer is still a popular solution Railway,” M.S., Feng Chia University, 2002.
[8] P. P. Khera, “Application of Zig-Zag transformers for reducing har-
for this problem due to its low cost, easy installation and free monics in the neutral conductor of low voltage distribution system,” in
maintenance. The analysis and simulation results in this paper Proc. IEEE IAS, vol. 2, 1990, pp. 1092–1096.
show that: [9] P. A. Dahono, R. E. Widjaya, Syafrudin, and Qamaruzzaman, “A
practical approach to minimize the zero-sequence current harmonics in
(1) the Zig-Zag transformer can effectively attenuate the power distribution systems,” in IEEE Proc. Power Conversion Conf.,
neutral current and zero-sequence harmonic currents vol. 2, Aug. 1997, pp. 683–686.
on the utility side under the balanced utility voltages; [10] B. K. Bird and K. G. King, An Introduction to Power Electronics. Wilt-
shire, U.K.: Westinghouse Brake and Signal Co., Ltd., 1983.
(2) the utility side neutral current becomes larger under the
unbalanced utility voltages after applying the Zig-Zag
transformer;
(3) the utility side neutral current becomes larger under the Hurng-Liahng Jou (M’98) was born in Taiwan, R.O.C., in 1959. He received
distorted utility voltages with zero sequence harmonic the B.S.E.E. degree from Chung Yuan University, Jonglih, Taiwan, in 1982,
and the M.S.E.E and Ph.D.E.E. degrees from National Cheng Kung University,
components after applying the Zig-Zag transformer; Tainan, Taiwan, in 1984 and 1991, respectively.
(4) the insertion of an inductor in the utility side can in- Currently, he is a Professor in the Department of Electrical Engineering of
crease the attenuated rate of the utility side neutral cur- National Kaohsiung University of Applied Sciences, Kaohsiung, Taiwan. His
research interests include power electronics applications and power quality im-
rent, however, it may cause abnormal operation of the provement technique.
electric facilities in the load side and even electrical
accidents;
(5) the insertion of an inductor in the utility side neu-
tral conductor can improve the undesired increasing Jinn-Chang Wu was born in Tainan, Taiwan, in 1968. He received the M.S.E.E.
and Ph.D.E.E. degrees from National Cheng Kung University, Tainan, Taiwan,
of the neutral current and the zero-sequence harmonic in 1992 and 2000.
currents of the utility side after applying the Zig-Zag Currently he is an Associate Professor at the Department of Electrical Engi-
transformer under the unbalanced utility voltages and neering, Kun Shan University of Technology. His research interests are power
the distorted utility voltages with zero-sequence har- quality and power electronic applications.
monic components;
(6) the performance of the Zig-Zag will be better if the
Zig-Zag transformer is installed near to the load. Kuen-Der Wu was born in Tainan, Taiwan, R.O.C., in 1954. He received the
B.S.E.E. degree from Tamkang University, Taipei, Taiwan, in 1977, and the
M.S.E.E. degree from National Cheng Kung University, Tainan, Taiwan, in
REFERENCES 1980.
[1] J. P. Nelson, “The grounding of power systems above 600 volts: A prac- He is currently an Associate Professor in the Department of Electrical En-
tical view point,” in Proc. IEEE IAS, 2003, pp. 13–22. gineering of National Kaohsiung University of Applied Sciences, Kaohsiung,
[2] P. T. Cheng, Y. F. Huang, and C. C. Hou, “A new harmonic suppression Taiwan. His research interests are power electronics applications and power
scheme for three-phase four-wire distribution systems,” in Proc. IEEE quality improvement technique.
APEC, vol. 2, 2001, pp. 1287–1293.
[3] P. N. Enjeti, W. Shireen, P. Packebush, and I. J. Pitel, “Analysis and
design of a new active power filter to cancel neutral current harmonics
in three-phase four-wire electric distribution systems,” IEEE Trans. Ind. Wen-Jung Chiang was born in Changhua, Taiwan, R.O.C., in 1980. He re-
Applicat., vol. 30, pp. 1565–1572, 1994. ceived the B.S.E.E. degree from National Kaohsiung University of Technology,
[4] C. A. Quinn, N. Mohan, and H. Mehta, “A four-wire, current-controlled Taiwan, in 2003. He is currently pursuing the M.S. degree in the Electrical En-
converter provides harmonic neutralization in three-phase, four-wire gineering Department of National Kaohsiung University of Applied Sciences,
systems,” in Proc. IEEE APEC, 1993, pp. 841–846. Kaohsiung Taiwan.
[5] T. Fukami, T. Onchi, N. Naoe, and R. Hanaoka, “Compensation for His research interests are power electronics applications and DSP control.
neutral current harmonics in a three-phase four-wire system by a syn-
chronous machine,” IEEE Trans. Ind. Applicat., vol. 38, pp. 1232–1236,
2002.
[6] K. Wada and T. Shimizu, “Mitigation method of 3rd-harmonic voltage
for a three-phase four-wire distribution system based on a series active Yi-Hsun Chen was born in Kaohsiung, Taiwan, R.O.C., on April 16, 1984. He is
filter for the neutral conductor,” in Proc. IEEE IAS, vol. 1, 2002, pp. currently pursuing the B.S. degree in electrical engineering, National Kaohsiung
64–69. University of Applied Sciences, Kaohsiung Taiwan.

Authorized licensed use limited to: Mohamed Ahmed. Downloaded on February 3, 2010 at 06:00 from IEEE Xplore. Restrictions apply.

Potrebbero piacerti anche