Switchgear & Cables for D G Set

Sr. No. KVA Phases Current Switchgear suitable for Select Switchgear PVC Al. Ar. PVC Cu. Ar.
rating rated Current or suitable for fault 1100V AYFY 1100v
or DG higher than rated level of kA at 415 V cable YFY cable
current
1 15 Single 65 32 Amp TP / TPN More than 1kA 2c X 25 2c X 10
2 20 Single 87 32 Amp TP / TPN More than 1kA 2c X 35 2c X 16
3 25 Single 109 45 Amp TP / TPN More than 1kA 2c X 50 2c X 25
4 15 Three 23 25 Amp TP / TPN More than 1kA 4c X 6 4c X 2.5
5 20 Three 31 32 Amp TP / TPN More than 1kA 4c X 10 4c X 4
6 25 Three 39 45 Amp TP / TPN More than 1kA 4c X 16 4c X 6
7 30 Three 46 63 Amp TP / TPN More than 1kA 4c X 16 4c X 10
8 35 Three 54 63 Amp TP / TPN More than 1kA 3.5c X 25 4c X 10
9 40 Three 62 63 Amp TP / TPN More than 1kA 3.5c X 35 4c X 16
10 50 Three 77 80 Amp TP / TPN More than 1kA 3.5c X 50 3.5c X 25
11 63 Three 97 110 Amp TP / TPN More than 1kA 3.5c X 70 3.5c X 25
12 70 Three 108 110 Amp TP / TPN More than 1kA 3.5c X 70 3.5c X 35
13 82.5 Three 127 140 Amp TP / TPN More than 1kA 3.5c X 95 3.5c X 50
14 85 Three 131 140 Amp TP / TPN More than 1kA 3.5c X 95 3.5c X 50
15 100 Three 154 185 Amp TP / TPN More than 1kA 3.5c X 120 3.5c X 70
16 115 Three 177 185 Amp TP / TPN More than 1kA 3.5c X 150 3.5c X 70
17 125 Three 193 200 Amp TP / TPN More than 1kA 3.5c X 185 3.5c X 95
18 140 Three 216 225 Amp TP / TPN More than 2kA 3.5c X 240 3.5c X 95
19 160 Three 246 300 Amp TP / TPN More than 2kA 3.5c X 300 3.5c X 120
20 180 Three 277 300 Amp TP / TPN More than 2kA 2 X 3.5c X 95 3.5c X 150
21 200 Three 308 325 Amp TP / TPN More than 2kA 2 X 3.5c X 120 3.5c X 185
22 225 Three 347 350 Amp TP / TPN More than 2kA 2 X 3.5c X 150 3.5c X 240
23 250 Three 385 400 Amp TP / TPN More than 2kA 2 X 3.5c X 185 2 X 3.5c X 95
24 275 Three 424 450 Amp TP / TPN More than 2kA 2 X 3.5c X 240 2 X 3.5c X 95
25 300 Three 462 500 Amp TP / TPN More than 3kA 2 X 3.5c X 240 2 X 3.5c X 120
26 320 Three 493 500 Amp TP / TPN More than 3kA 2 X 3.5c X 300 2 X 3.5c X 120
27 380 Three 585 630 Amp TP / TPN More than 3kA 3 X 3.5c X 185 2 X 3.5c X 150
28 400 Three 616 630 Amp TP / TPN More than 3kA 3 X 3.5c X 240 2 X 3.5c X 185
29 500 Three 770 800 Amp TP / TPN More than 5kA 3 X 3.5c X 300 2 X 3.5c X 185
30 625 Three 963 1000 Amp TP / TPN More than 5kA 4 X 3.5c X 300 3 X 3.5c X 185
31 750 Three 1155 1250 Amp TP / TPN More than 10kA 5 X 3.5c X 300 4 X 3.5c X 150
32 1000 Three 1540 1600 Amp TP / TPN More than 10kA 6 X 3.5c X 300 4 X 3.5c X 240

Notes:

1 The term Switchgear refers either of contactors, MCBs, MCCBs, Fuse disconnectors and ACBs.
2 When used for single phase application TP switchgear to be shorted and used.
3 Contactors used to be suitabe foe AC 1 duty.
4 For switching on DG in manual panels user can use MCBs upto 30 KVA Dgsets.
5 For all ratings Contactor can be used, but should hace back up HRC fuses or switchgear.
6 Cable sizes are indicative. One may use any other combination for specified rated current.