DESIGN PHILOSOPHY FOR FIRE ALARM DETECTION & FIRE FIGHTING SERVICES
The Fire Alarm and Detection System for the Substation Building and Guard Room shall
comprise the following:
Fire alarm devices at the Guard Room and Pump Room are linked directly to the main fire
alarm control panel located at C & R room and no separate panel shall be provided being
very small rooms. Guard room shall be linked to the main fire alarm control panel through
fire alarm junction box and fire alarm repeater panel shall be located in Guard room.
The fire alarm control panel shall be located at Control and Relay room with alarm
and fault indication. An analogue addressable system fire alarm control panel shall
be used complete with battery / charger units.
All the control wiring system shall be fire resistant cables in GI conduits.
2. Fire Detectors
• Smoke Fire Alarm Detectors shall be provided in all station rooms covering an
area of approximately 80 m 2 .
• Explosion proof heat detectors and explosion proof manual call points shall be
provided inside the Battery room.
• For areas under flat ceiling, the maximum horizontal distance between any
point and nearest smoke detector is not more than 7.5 meters and 5.3 meters
for the heat detectors.
• Areas that are low fire risk such as toilet and emergency escape staircase,
smoke detectors shall not be provided where it might be subject to false alarm.
Sheet. 3
Q.E.A. Page 3 EZD-04-1 0-76-POO 1
Contract No.EZ-GCC-04/2010 Doc No.EZD-04-10-76-P001
Feeding EZDAN and International Housing Group Project in Wukhair Area Fire Alarm Detection &
COMMON SUBSTATIONS Fire Fighting Design Philosophy
• Combined fixed temperature and rate of rise detectors shall be provided in the
substation rooms with 11°C. above the maximum expected ambient
temperature at the ceiling and rate of rise of temperature shall be 8° C.lminute.
• 11 kV Switchgear room
• Pantry
• Fire pump room
• Battery room
• Store room
• Guard room
• Cable basement
• Manual Pull Stations shall be provided throughout the building and can be sited
within 1.5 m of the exit points and along the escape routes.
• Manual Pull Stations shall be located throughout the protection area so that
they are unobstructed and accessible.
• Fire Alarm Bells sounder shall be provided throughout the Substation building
to provide a minimum of 65 dBA at any location.
• Sound audibility calculation shall be provided in design stage to comply with the
project technical specifications.
• 2 No. flashers shall be provided for 66 kV substations and 4 No. flashers shall
be provided for 220 kV substations.
• Fire alarm cabling shall be carried out using fire resistant cables in GI
conduits.
Sheet. 4
Q.E.A. Page 4 EZD-04-10-76-P001
Contract No.EZ-GCC-04/2010 Doc No.EZD-04-10-76-P001
Feeding EZDAN and International Housing Group Project in Wukhair Area Fire Alarm Detection &
COMMON SUBSTATIONS Fire Fighting Design Philosophy
• Fire Suppression System (with clean agent) shall be provided in Control and
Relay room, Telecom room and LV AC/DC room only (by others). The system
shall be integrated and programmed through interface units connected to fire
alarm system.
• Deluge Water Spray System shall be provided (by others) for the transformers
in the open area. The system shall be integrated and programmed through
interface units connected to the fire alarm system.
Sheet. 5
Q.EA Page 5 EZD-04-1 0-76-POO 1
Contract No.EZ-GCC-04/2010 Doc No.EZD-04-10-76-P001
Feeding EZDAN and International Housing Group Project in Wukhair Area Fire Alarm Detection &
COMMON SUBSTATIONS Fire Fighting Design Philosophy
• Fire sealant work shall be carried out where cables enter the building, ducts and
trenches sealed with fire and water resistant material. Also all fire zones, sleeves
shall be sealed with fire resistance materials.
• The Fire Alarm Detection and Fire Fighting System design shall be carried out based
on the following:
• The Fire Alarm Detection and Fire Fighting equipment shall be co-ordinated with the
following:
Sheet. 6
Q.E':"A. Page 6 EZD-04-1 0-76-POO 1
Contract No.EZ-GCC-04/2010 Doc No.EZD-04-10-76-P001
Feeding EZDAN and International Housing Group Project in Wukhair Area Fire Alarm Detection &
COMMON SUBSTATIONS Fire Fighting Design Philosophy
• The Fire Alarm System shall be interfaced with the A.C. equipment where, in case of
fire, the fire alarm control panel shall generate commands to shut-off relevant
ventilation and air-conditioning systems under certain conditions.
• Smoke duct detector shall be installed in return air duct for HVAC and in main extract
duct in basement from the 66 kV GIS to cut off the power supply to package unit and
to basement extract fan in case of fire.
• Fire alarms of Battery Room shall activate relevant alarm bells as shown on Cause
and Effect Schedule and shutting-off Battery Room exhaust fans and A.C. package
units.
• The main fire alarm panel shall remotely transmit fire alarm and fault signals to
National Control Centre (NCC) via RTU.