Contents
Protection Function of Trip Unit (50/100 AF) 1 Rated Current Setting Threshold (Ir)
2 Short Time Delay Current Setting Threshold (Im)
General Type
Rated Current (A) 3, 5, 10, 15, 20, 30 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50
Rated Insulation Voltage (V) Ui 690
Rated Operational Voltage (V) Ue 660
Rated Impulse Withstand Voltage (kV) Uimp 6
Ics=(%Icu) 50 50 50 50 50
Ultimate Breaking AC 660 V 2.5 5.0 2.5 5.0 10
Capacity AC 600 V 2.5 5.0 2.5 5.0 10
Icu (kA rms) AC 480/500 V 2.5 7.5 2.5 7.5 14
KS C 8321 AC 440/460 V 5.0 10 5.0 10 25
IEC 60947-2 AC 380/415 V 7.5/5.0 14/10 7.5/5.0 14/10 30/25
NEMA AB-1 AC 220/240 V 10 25 10 25 50
DC 250 V 2.5 5.0 2.5 5.0 14
Trip Mechanism
Hydraulic-Magnetic
Fixed Thermal & Fixed Magnetic
Fixed Thermal & Adjustable Magnetic
Connection & Mounting
Front Terminal Screw (A)
Connected Attached Flat Bar (B)
Plug-in Both Line & Load Side(K) - - - - - - - -
Line Side Only (L) - - - - - - - -
Accessories
Internally Shunt Trip (SHT)
Mounted Undervolt Trip (UVT)
Auxiliary Switch (AUX)
Alarm Switch (ALT)
Externally Operating Breaker
Mounted (TFG) - - - - -
Mounted Handle Panel
Mounted (TFH) - - - - -
Interpole Barrier (TQQ)
Terminal Cover (TCF)
Dimensions (mm) and Weights (Kg)
a 50 75 50 75 50 75 100 50 75 100 60 90 120
b 130 130 130 130 155
c 60 60 60 60 60
d 82 82 82 82 84.5
Weights (Standard Type) 0.45 0.65 0.45 0.65 0.45 0.65 0.85 0.45 0.65 0.85 0.7 1.0 1.2
: Standard, this configuration will be selected, unless specified : Optional standard, specify when ordering - : Stands for No or Not available
General Type
Rated Current (A) 5, 10, 15, 20, 30, 40, 50, 60 5, 10, 15, 20, 30, 40, 50, 60, 75, 100
Rated Insulation Voltage (V) Ui 690
Rated Operational Voltage (V) Ue 660
Rated Impulse Withstand Voltage (kV) Uimp 6
Ics=(%Icu) 50 50 50
Ultimate Breaking AC 660 V 2.5 5.0 5.0
Capacity AC 600 V 2.5 5.0 5.0
Icu (kA rms) AC 480/500 V 2.5 7.5 7.5
KS C 8321 AC 440/460 V 5.0 10 10
IEC 60947-2 AC 380/415 V 7.5/5.0 14/10 14/10
NEMA AB-1 AC 220/240 V 10 25 25
DC 250 V 2.5 5.0 5.0
Trip Mechanism
Hydraulic-Magnetic
Fixed Thermal & Fixed Magnetic
Fixed Thermal & Adjustable Magnetic
Connection & Mounting
Front Terminal Screw (A)
Connected Attached Flat Bar (B)
Plug-in Both Line & Load Side (K) - - - - - -
Line Side Only (L) - - - - - -
Accessories
Internally Shunt Trip (SHT)
Mounted Undervolt Trip (UVT)
Auxiliary Switch (AUX)
Alarm Switch (ALT)
Externally Operating Breaker
Mounted (TFG) - - -
Mounted Handle Panel
Mounted (TFH) - - -
Interpole Barrier (TQQ)
Terminal Cover (TCF)
Dimensions (mm) and Weights (Kg)
a 50 75 100 50 75 100 50 75 100
b 130 130 130
c 60 60 60
d 82 82 82
Weights (Standard Type) 0.45 0.65 0.85 0.45 0.65 0.85 0.45 0.65 0.85
: Standard, this configuration will be selected, unless specified : Optional standard, specify when ordering - : Stands for No or Not available
100 225
HiBS 100 HiBH 100 HiBE 225 HiBS 225 HiBH 225
2 3 4 2 3 4 2 3 4 2 3 4 2 3 4
15, 20, 30, 40, 50, 60, 75, 100 125, 150, 175, 200, 225
690
660
6
50 50 50 50 50
10 18 7.5 10 18
10 18 7.5 10 18
14 25 10 14 25
25 35 18 25 35
30/25 42/35 25/18 35/25 42/35
50 65 35 50 65
14 18 10 14 18
- - - - - - -
- - - - - - -
- -
- -
Adjustable Type
Rated Current (A) 15, 20, 30, 40, 50 20 ~ 50 15, 20, 30, 40, 50 20 ~ 50 15, 20, 30, 40, 50, 60, 75, 100
Rated Insulation Voltage (V) Ui 750 750
Rated Operational Voltage (V) Ue 690 690
Rated Impulse Withstand Voltage (kV) Uimp 8 8
Ics=(%Icu) 100 100 100 100 100
Ultimate Breaking AC 660 V 22 22 60 60 22
Capacity AC 600 V 35 35 65 65 35
Icu (kA rms) AC 480/500 V 65 65 100 100 65
KS C 8321 AC 440/460 V 85 85 100 100 85
IEC 60947-2 AC 380/415 V 85 85 130 130 85
NEMA AB-1 AC 220/240 V 125 125 150 150 125
DC 250 V 85 - 85 - 85
Long Time Delay Adjustable (0.8-0.9-1.0) In 9 Setting (0.8 0.9 1.0) In 9 Setting (0.8 0.9 1.0) In
Short Time Delay Adjustable - 2-3-4-5-6-7-8-9-10 Ir - 2-3-4-5-6-7-8-9-10 Ir -
Fixed 10 In 11 In 10 In 11 In 10 In
Protection Instantaneous
Adjustable - - - - -
Characteri
Ground Fault Trip - - - - -
stics
Pre-trip Alarm - - -
I2T Ramp - - - - -
Pick-up LED - - -
Trip Thermal Magnetic - -
Mechanism Electronic - - -
Front Terminal Screw (A)
Connection Connected Attached Flat Bar (B) - - - - -
& Mounting Both Line & Load Side (K) - - - - -
Plug-in
Line Side Only (L) - - - - -
Shunt Trip (SHT)
Internally
Mounted
40 ~ 100 15, 20, 30, 40, 50, 60, 75, 100 40 ~ 100 12.5~16, 16~20, 20~25, 25~32, 32~40, 40~50, 125, 150, 175, 200, 225 90~225
50~63, 63~80, 80~100 Adjustable
750 690 750
690 660 690
8 6 8
100 100 100 50 50 100 100
22 60 60 10 18 22 22
35 65 65 10 18 35 35
65 100 100 14 18 65 65
85 100 100 25 35 85 85
85 130 130 30/25 42/35 85 85
125 150 150 50 65 125 125
- 85 - 14 18 85 -
9 Setting (0.8-0.9-1.0) In 9 Setting (0.8-1.0) In (0.8-1.0) In (0.8-0.9-1.0) In 9 Setting
2-3-4-5-6-7-8-9-10 Ir - 2-3-4-5-6-7-8-9-10 Ir - - - 2-3-4-5-6-7-8-9-10 Ir
11 In 10 In 11 In 15 In 15 In - 11 In
- - - - - 5-6-7-8-9-10 In -
- - - - - - -
- - - -
- - - - - - -
- - - -
- - Adjustable Thermal Fixed Magnetic -
- - - -
- - - - -
- - - - - - - - -
- - - - - - - - -
- -
- -
- - - - -
105 140 105 140 105 140 60 90 120 60 90 120 105 140 105 140
165 165 165 155 155 165 165
87.5 87.5 87.5 60 60 87.5 87.5
105 105 105 84.5 84.5 105 105
1.6 2.0 1.1 1.6 2.0 1.6 2.0 0.7 1.0 1.2 0.7 1.0 1.2 1.3 1.8 2.2 1.6 2.0
Adjustable Type
Rated Current (A) 125, 150, 175, 200, 225 90~225 100~125, 125~160, 160~200, 200~250 Adjustable
Rated Insulation Voltage (V) Ui 750 690
Rated Operational Voltage (V) Ue 690 660
Rated Impulse Withstand Voltage (kV) Uimp 8 6
Ics=(%Icu) 100 100 50 50 50
Ultimate Breaking AC 660 V 60 60 7.5 10 18
Capacity AC 600 V 65 65 7.5 10 18
Icu (kA rms) AC 480/500 V 100 100 10 14 25
KS C 8321 AC 440/460 V 100 100 18 25 35
IEC 60947-2 AC 380/415 V 130 130 25/18 35/25 42/35
NEMA AB-1 AC 220/240 V 150 150 35 50 65
DC 250 V 85 - 10 14 18
Long Time Delay Adjustable (0.8-0.9-1.0) In 9 Setting (0.8-1.0) In (0.8-1.0) In (0.8-1.0) In
Short Time Delay Adjustable - 2-3-4-5-6-7-8-9-10 Ir - - -
Fixed - 11 In 15 In 15 In 15 In
Protection Instantaneous
Adjustable 5-6-7-8-9-10 In - - - -
Characteri
Ground Fault Trip - - - - -
stics
Pre-trip Alarm - - - -
I2T Ramp - - - - -
Pick-up LED - - - -
Trip Thermal Magnetic - Adjustable Thermal Fixed Magnetic
Mechanism Electronic - - - -
Front Terminal Screw (A)
Connection Connected Attached Flat Bar (B) - - -
& Mounting Both Line & Load Side (K) - - - - -
Plug-in
Line Side Only (L) - - - - -
Shunt Trip (SHT)
Internally
Mounted
200 ~ 400 200 ~ 400 200 ~ 400 200 ~ 400 302 ~ 600 302 ~ 600 302 ~ 600
750
690
8
100 100 100 100 100 100 100
16 22 22 60 22 22 35
22 30 35 65 30 35 42
25 35 50 100 45 50 50
35 50 85 100 50 65 85
35 50 85 130 50 65 85
50 85 100 150 85 100 125
- - - - - - -
15 Setting 15 Setting 15 Setting 15 Setting 15 Setting 15 Setting 15 Setting
2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1
- - - - - - -
3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT
- - - - - - -
- - -
- - - - - - -
- - - - - - -
- - - - - - -
140 210 140 210 140 210 140 210 140 210 140 210 140 210
255 255 225 225 255 255 255
117 117 117 117 117 117 117
154 154 154 154 154 154 154
4.2 6.0 7.8 4.2 6.0 7.8 4.2 6.0 7.8 6.0 7.8 4.2 6.0 7.8 4.2 6.0 7.8 4.2 6.0 7.8
Adjustable Type
Rated Current (A) 302 ~ 600 405 ~ 800 405 ~ 800 405 ~ 800 405 ~ 800
Rated Insulation Voltage (V) Ui 750
Rated Operational Voltage (V) Ue 690
Rated Impulse Withstand Voltage (kV) Uimp 8
Ics=(%Icu) 100 50 50 50 50
Ultimate Breaking AC 660 V 60 22 22 35 50
Capacity AC 600 V 65 30 35 42 65
Icu (kA rms) AC 480/500 V 100 45 50 50 100
KS C 8321 AC 440/460 V 100 50 65 85 100
IEC 60947-2 AC 380/415 V 130 50 65 85 130
NEMA AB-1 AC 220/240 V 150 85 100 125 150
DC 250 V - - - - -
Long Time Delay Adjustable 15 Setting 15 Setting 15 Setting 15 Setting 15 Setting
Short Time Delay Adjustable 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1
Fixed - - - - -
Protection Instantaneous
Adjustable 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT
Characteri
Ground Fault Trip
stics
Pre-trip Alarm
I2T Ramp
Pick-up LED
Thermal Magnetic - - - - -
Mechanism
Electronic
Front Terminal Screw (A) - - - -
Connection Connected Attached Flat Bar (B)
& Mounting Both Line & Load Side (K) - - - - -
Plug-in
Line Side Only (L) - - - - -
Shunt Trip (SHT)
Internally
Mounted
505 ~ 1000 505 ~ 1000 505 ~ 1000 605 ~ 1200 605 ~ 1200 605 ~ 1200
750
690
8
50 50 50 50 50 50
30 40 60 30 40 60
45 50 65 45 50 65
50 75 100 50 75 100
65 75 100 65 75 100
65 100 130 65 100 130
100 100 150 100 100 150
- - - - - -
15 Setting 15 Setting 15 Setting 15 Setting 15 Setting 15 Setting
2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1 2-4-6-8-10 I1
- - - - - -
3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT 3-6-9-10-12 ICT
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
210 280 210 280 210 280 210 280 210 280 210 280
370 370 370 370 370 370
110 110 200 110 110 200
159 159 249 159 159 249
13 17 13 17 25 33 13.5 17.5 13.5 17.5 25.5 33.5
Internal accessories can be easily installed and removed inside the auxiliary cover.
Carries out the electrical remote Automatically trips the breaker when
trip of the breaker. control voltage drops below
predetermined value.
Control Voltage
Also, UVT can be used for the
AC 100~125 V, AC 200~230 V,
electrical remote trip of the breaker.
AC 380~415 V, AC 440~480 V,
DC 24 V, DC 100~110 V Control Voltage
AC 100~125 V, AC 200~230 V
AC 380~415 V, AC 440~480 V
DC 24 V, DC 100~110 V
Externally mounted Accessories
External accessories provide MCCBs with safe operation and easy maintenance.
Operates the MCCB from the panel door. Enhances the insulation between poles of
Indicates the three positions, O(OFF), the MCCB in the line side and load side.
I(ON) and TRIP Can be attached easily onto the MCCB.
Can lock the MCCB at OFF position
through the padlock.
Prevents the panel door from opening at
the ON position of the MCCB.
TFG
Extended type (Panel mounted type) Prevents direct contact on the terminals
The MCCB can be installed inside the panel. for the protection purpose.
The operating mechanism is attached on the MCCB,
and the external operating handle is mounted on the
panel door; where the handle and the mechanism
are mechanically connected by a shaft.
www.hyundai-elec.com