for new commercial buildings
Steven Kang
Certified Energy Manager,
Certified Green Mark Professional
LEED Accredited Professional
Green Mark Rating System
For New Buildings
NRNB V4.0
Effective 1-Dec-2010
Legislation
12pts for baseline of 15pts for baseline of 10pts for baseline of 12pts for baseline of
0.80KW/RT 0.70KW/RT 0.90KW/RT 0.80KW/RT
0.45pts for every % 0.25pts for every % 0.6pts for every % 1.3pts for every %
improvement over improvement over improvement over improvement over
baseline baseline baseline baseline
Max: 20 pts Max: 20 pts Max: 20 pts Max: 20 pts
(= 0.66KW/RT) (= 0.56KW/RT) (= 0.75KW/RT) (= 0.75KW/RT)
Baseline Baseline
3 3
1.7 KW / m /s 2.4 KW / m /s
0.47 W/CMH 0.67 W/CMH
b) 1 point for use of refrigerant leak detection system at critical areas of plant rooms
containing chillers and other equipment with refrigerants.
14 Confidential and Proprietary Property of Trane
Pre-requisite for Gold Plus and Platinum
Chillers Full load @ ARI 6.1 COP Chillers Full load @ 6.1 COP
std condn ARI std condn
0.58 Kwi / RT 0.58 Kwi / RT
Part load - No requirement for part load Part load - No requirement for part load performance
performance
- -
CHWP Full load 30 KWc / Kwi CHWP Full load 349 KW/cms
56% more
0.12 Kwi / RT 0.053 Kwi / RT
efficient
Part load - No requirement for part load Part load - Motors exceeding 15KW must modulate to
performance 50% of design flow @ no more than 30%
of design KWi
CWP Full load 40 KWct / Kwi CWP Full load 301 KW/cms
37% more
0.09 Kwi / RT 0.057 Kwi / RT efficient
Part load - No requirement for part load Part load - Motors exceeding 15KW must modulate to
performance 50% of design flow @ no more than 30%
of design KWi
CT Full load 3.23 L/S / Kwi CT Full load 3.23 L/S / Kwi
Part load - No requirement for part load Part load - No requirement for part load performance
performance
GreenMark v3 GreenMark v3
Reference building (CP13) Reference building (SS553)
Type Condition Min Eff Units Remarks Type Condition Min Eff Units Remarks
Constant volume Full load 0.47 W / CMH Constant Full load 0.47 W / CMH Allowable nameplate motor KW
system volume system
Variable volume Full load 0.74 W/ CMH Variable Full load 0.67 W/ CMH Allowable nameplate motor KW
system volume system
Part load - No requirement for part Part load - Motor >= 11kw must able to
load performance modulate to 50% design flow at less
than 30% of design KW
For VAV
system, 9.5%
more eff than
CP13