Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Instruction Manual
BV-H2407 GB
Legal Notice
Table of Contents
2 Safety notes................................
notes................................................................
................................................................................................
................................................................................................
..........................................................................
..........................................3
..........3
2.1 Signal Words .........................................................................................................................................4
2.1.1 Signal Words for Safety Warnings ................................................................................................4
2.1.2 Signal Words for Application Notes ..............................................................................................5
2.2 Five Safety Rules of Electrical Engineering ..........................................................................................6
2.3 Damaged / Defective Electrical Components ........................................................................................6
4 Operation................................................................
................................................................................................
................................................................................................
............................................................................
............................................17
4.1 Behavior after Connecting the Power ................................................................................................. 17
4.2 Operating and Control Access............................................................................................................ 17
4.2.1 Connecting an operating panel (VHM) with a scale controller (VCU) ........................................ 18
4.2.1.1 Connection via Ethernet Cable .................................................................................................. 18
4.2.1.2 Connection via Bluetooth ........................................................................................................... 18
4.2.1.3 Connection via RS485 ............................................................................................................... 19
4.2.2 Connecting EasyServe (PC) with the scales controller (VCU) .................................................. 19
4.2.2.1 Connection via Ethernet ............................................................................................................. 19
4.2.2.2 Connection via WLAN ................................................................................................................ 20
4.2.2.3 Connection via Bluetooth ........................................................................................................... 20
4.2.2.4 Connection via RS-232 .............................................................................................................. 20
4.2.3 Connecting the web browser with the scales controller (VCU) .................................................. 21
4.2.4 The web server in the scales controller (VCU) .......................................................................... 21
4.3 VHM operating panel .......................................................................................................................... 23
4.3.1 Display and Operation Fields ..................................................................................................... 24
4.3.1.1 Name of the Device .................................................................................................................... 24
4.3.1.2 Event messages ......................................................................................................................... 24
4.3.1.3 Selecting the operating range .................................................................................................... 25
4.3.1.4 On/Off Operation ........................................................................................................................ 25
4.3.1.5 Detail Selection .......................................................................................................................... 26
4.3.1.6 Measured Values and Graphics ................................................................................................. 26
5 Startup ................................................................
................................................................................................
................................................................................................
................................................................................
................................................53
5.1 Mechanical Prerequisites ................................................................................................................... 53
5.2 Assembling the Electrical Components .............................................................................................. 54
5.3 Electrical Connections ........................................................................................................................ 54
5.4 Entering Basic parameters ................................................................................................................. 54
5.5 Test that the Control is Functioning .................................................................................................... 54
5.6 Scale calibration ................................................................................................................................. 55
5.7 The Setting Regulation ....................................................................................................................... 55
5.7.1 Adjusting the external flow rate controller .................................................................................. 55
5.7.2 Adjusting the feeding controller .................................................................................................. 56
5.8 Setting belt run monitoring.................................................................................................................. 56
5.9 Activating belt influence compensation (BIC) ..................................................................................... 58
5.10 Activating measurement and feeding with reference to the discharge point (VAP) ........................... 58
5.11 Setting Control .................................................................................................................................... 59
5.11.1 Function Check .......................................................................................................................... 59
5.11.2 Checking the scale with calibration weights ............................................................................... 59
5.11.3 Belt Velocity Check .................................................................................................................... 59
5.12 Check with bulk solids ........................................................................................................................ 60
5.13 Calibrating bin weighing ..................................................................................................................... 61
7 Parameters ................................................................
................................................................................................
................................................................................................
.........................................................................
.........................................65
7.1 Abbreviations ...................................................................................................................................... 66
7.2 Configuring the Interfaces .................................................................................................................. 66
7.3 Configuring Event Messages.............................................................................................................. 68
7.4 Parameter List .................................................................................................................................... 69
7.4.1 Parameter Overview .................................................................................................................. 69
7.4.2 Parameter Details ...................................................................................................................... 93
7.4.2.1 Parameter Block 01 - Hardware Modules .................................................................................. 93
7.4.2.2 Parameter Block 02 - Dialog Behaviour ..................................................................................... 96
7.4.2.3 Parameter Block 03 - Feeder Definition ................................................................................... 101
7.4.2.4 Parameter Block 04 - Control Sources .................................................................................... 103
7.4.2.5 Parameter Block 05 - Rated Data ............................................................................................ 106
7.4.2.6 Parameter Block 06 - Feeder control ....................................................................................... 109
7.4.2.7 Parameter Block 07 - Feeder Monitoring ................................................................................. 114
7.4.2.8 Parameter Block 08 - Filters..................................................................................................... 117
7.4.2.9 Parameter Block 09 - Limit Values ........................................................................................... 118
7.4.2.10 Parameter Block 10 - Calibration Data .................................................................................... 120
7.4.2.11 Parameter Block 11 - Rate controller ....................................................................................... 121
7.4.2.12 Parameter Block 12 - Analog Outputs ..................................................................................... 128
7.4.2.13 Parameter Block 13 - Digital Inputs ......................................................................................... 131
7.4.2.14 Parameter Block 14 - Digital Outputs ....................................................................................... 136
7.4.2.15 Parameter Block 15 - Batch Mode ........................................................................................... 139
7.4.2.16 Parameter Block 16 - Maintenance interval ............................................................................. 143
7.4.2.17 Parameter Block 17 - VAP ....................................................................................................... 144
7.4.2.18 Parameter Block 18 - Belt Monitoring ...................................................................................... 144
7.4.2.19 Parameter Block 19 - Communication EasyServe ................................................................... 148
7.4.2.20 Parameter Block 20 - Communication Fieldbus....................................................................... 148
7.4.2.21 Parameter Block 21 - Fixed mode configuration ...................................................................... 153
7.4.2.22 Parameter Block 22 - Ethernet ................................................................................................. 157
7.4.2.23 Parameter Block 23 - PLC Outputs .......................................................................................... 157
9 Appendix ................................................................
................................................................................................
................................................................................................
..........................................................................
.......................................... 257
9.1 Setpoint and switch-on sources........................................................................................................ 257
9.2 Measuring the flow rate (M) .............................................................................................................. 260
9.3 Flow rate controller ........................................................................................................................... 262
9.4 Batch Operation Control ................................................................................................................... 267
9.5 Belt slip identification ........................................................................................................................ 268
9.5.1 Belt Slippage with Belt Marking ............................................................................................... 268
9.5.2 2-sensor slip monitoring ........................................................................................................... 269
9.6 Local operation ................................................................................................................................. 270
9.6.1 Controlling with VLG ................................................................................................................ 270
9.6.2 Controlling with VMO ............................................................................................................... 271
9.6.2.1 Local operation logic for rotating drives and valves ................................................................. 273
9.6.2.2 The logic for position-controlled feed gates ............................................................................. 275
9.7 Belt load regulation of the velocity-controlled weighfeeder .............................................................. 276
9.8 Bin weigher: Scaling and Limit ......................................................................................................... 281
9.9 Continuous bin fill level control ......................................................................................................... 282
9.10 Details and flow chart control measurement (KME) ......................................................................... 284
9.11 Linearization ..................................................................................................................................... 285
9.12 Correction of the foreign substance portion (moisture) .................................................................... 285
Index ................................................................
................................................................................................
................................................................................................
................................................................................
................................................ 301
The following software releases or later must be available to ensure that a DISOCONT Tersus sys-
tem will operate correctly with this software version:
▪
VHM 20170-006 → VHM operating panel
▪
VPC 20150-021 → Schenck Process EasyServe
▪
For the sake of simplicity, the DISOCONT Tersus system will also be called the weighing elec-
tronics, controller, scale or unit hereinafter.
– The BV-H2406 system manual contains information on its electronic structure.
– DISOCONT is a registered trademark of Schenck Process GmbH, Darmstadt.
▪
The Windows-based Schenck Process EasyServe program is a service tool for conveniently
handling continuous scales based on weighing electronics such as DISOCONT Tersus.
– For the sake of simplicity, this tool will also briefly be called EasyServe here.
– The BV-H2185 operating manual describes EasyServe's functionality.
2 Safety notes
To avoid personal injury and material damage, follow the safety regulations stated below.
Additionally you should also observe:
▪
Safety information given in order-specific documentation
▪
Safety information relating to mechanical components
▪
Instructions and safety instructions for parts manufactured by thrid-party suppliers or parts that are not
part of Schenck's scope of delivery.
When performing installation, commissioning and service work, observe all applicable local regulations.
Intended Use
The measuring system and connected mechanical components is intended solely for weighing tasks and
related control applications. It is not intended for any other use.
Risks
If properly installed and put into service the measuring system itself does not represent a hazard.
Hazards may arise when the system is used for control operations or for transporting weighed goods. Po-
tential sources of danger would then be add-on equipment that the material weighed is transported or me-
tered in. Residual risks may originate from the measuring system if unskilled operators improperly handle
the system.
This measuring system may be a component of a more complex system. The operating company is fully
responsible for overall plant safety.
Personnel
Preparation, assembly, commissioning, operation, maintenance and servicing may only be carried out by
qualified personnel.
All persons working on the system are required to observe the safety hints and know the parts of the tech-
nical documentation relevant to their work.
The operating company is responsible for instructing his operators to observe all regulations and instruc-
tions given.
Changing parameters
The parameters dictate how the measuring system functions. Only personnel familiar with the device's mode
of operation may alter these parameters (e.g. after training by Schenck Process). Parameters incorrectly set
may cause injuries or damage to the machine whenever a control system is connected. They can also ad-
versely affect weighing operation.
Password
Passwords safeguard the parameters against unauthorized alteration. The measuring system operating
company has to ensure safe password handling.
Design Modifications
Unauthorized modifications to the system and/or use of replacement parts not supplied by Schenck Process
voids Schenck Process's liability for any resulting damages. This especially applies to alterations which
could affect the operating safety of the system.
Replacing Components
Spare parts must meet the technical specifications indicated by Schenck Process. To ensure this require-
ment is met, only genuine Schenck Process spare parts should be used. When using other spare parts, the
warranty will be void.
2.1 Signal
Signal Words
In this manual the following signal words will indicate hazards that may arise when using this machine:
DANGER
This signal word indicates a danger that can immediately cause the
most severe injuries up to and including death.
Follow all instructions to prevent this from occurring.
WARNING
This signal word indicates a danger that can cause serious injuries up
to and including death.
Follow all instructions to prevent this from occurring.
CAUTION
This signal word indicates a danger that can cause slight or medium
injuries.
Follow all instructions to prevent this from occurring.
Signal words for information on material damages and on the optimal use of the machine
STRICTLY OBSERVE
Signal word used to identify situations in which material or environ-
mental damage could occur.
Follow all instructions to prevent this from occurring.
HINT
Signal word used to identify information on using the product eco-
nomically and at an optimal level of efficiency.
These fives safety rules must be followed in the order shown before work is begun on electrical systems.
Once the work is finished, they are to be applied in reverse order.
DANGER
Electric shock from live components.
There is a danger of life from an electric shock.
– Take all possible precautions to ensure safety before work is begun on
live components. Observe, among other things, the following:
1. Disconnect the components.
2. Secure them against inadvertent restart.
3. Ensure that the components have been de-energized.
4. Above 1 KV: earth and bypass the cables.
5. Cover or shield adjacent, live components.
DANGER
Live damaged or defective components
There is a danger of life from an electric shock.
– Always have qualified personnel ensure that the components are nei-
ther damaged nor defective.
1. Qualified personnel must immediately replace or, if possible, repair
damaged or defective electrical components.
3 General Diagram
The basic functions of the DISOCONT Tersus in combination with a feeder or measuring equipment will be
explained in this chapter.
The DISOCONT Tersus has been designed for continuous measurement and control tasks or for disconti-
nuous batching.
All weighing-related functions and process functions for measuring and feeding bulk solids are performed by
the DISOCONT Tersus system.
The DISOCONT Tersus is customizable and very flexible in terms of its physical layout and interconnection.
DISOCONT Tersus can be used in the following areas with specific software for weighing and feeding job
applications:
▪
Steel
▪
Cement production
▪
Chemical industry
▪
Foodstuffs industry
▪
Power plants
It supports the following plant systems in connection with the right mechanical equipment:
▪
Beltweighers
▪
Weighfeeders
▪
Loss-in-weight feeders
▪
Filling plants
▪
Feeder with weighing discharge screw (MULTIFLEX)
▪
Mass flow rate measuring devices and mass flow rate feeders that operate on the basis of the Coriolis
® ®
principle (MULTICOR ) or the principle of inertia (MULTISTREAM )
I Actual flow rate Material quantity per unit of time Weight/Time kg/h, t/h
I0 Nominal Flow Rate Maximum gravimetric flow rate the scale is designed Weight/Time kg/h
for. Defined in the P03.01 parameter.
P Flow rate setpoint Preset flow rate against which the actual value is Weight/Time kg/h, t/h
controlled.
Z Flow Rate The material quantity conveyed calculated from the Weight kg, t
integral of the flow rate over the feed time.
v Belt velocity The velocity of the conveyor belt Velocity m/s
v0 Rated velocity The velocity of the conveyor belt at the flow rate Io
and rated belt load
Q Belt load The quantity of bulk solids on the conveyor belt per Weight/Length kg/m
meter of belt length
Qo Rated belt load The rated belt load is calculated from the nominal Weight/Length kg/m
flow rate Io/ rated velocity vo and it can be shown as a
service value.
QB Platform load The load on the weighbridge Weight kg
Y Controller actuating Conveyor element setpoint Amperage mA
variable
Xd Control deviation The difference between the setpoint and actual value % %
with reference to the rated value
n Speed The speed of the drive motor for the conveyor belt Rotations/unit 1/min
of time
Tab. 1 : Definition for formula symbols
You can find the abbreviations for input and output channels for use in parameterization
in the Abbreviations [➙ 66] chapter.
v Material and belt velocity Sv The sensor for belt velocity; designed as a mea-
suring wheel or feeder on the belt drive
M The drive motor of the belt or a prefeeder on the BM Mark in the belt for scanning through the belt
belt scale with feed regulation travel sensor
The bulk solids are conducted over a weighbridge located beneath the belt that is limited by two non-
weighed idlers. The material quantity on the weighbridge exercises a force on the load cell (LC) over one or
several measuring idlers (MR). The measuring idlers are linked to a frame structure such as with a parallel
leaf-spring system.
The load cell output voltage is proportional to the platform load. It is amplified and sent to the microproces-
sor of the weighing electronics through an analog/digital converter. The force progression on a single-idler
weighbridge is indicated by the triangle in the figure. Only a fraction of the force of the weight of the bulk
solids is introduced into the measuring idler MR.
The effect of the force of weight over the weighbridge is shown with the Effective Platform Length Leff para-
meter with belt scales. If the belt load Q in kg/m is even, the measuring force QB is calculated on the load
cell LC by:
QB = Q * Leff (1)
For the design shown here with one measuring idler and the measured length L of the weighbridge WB, the
effective bridge is calculated with:
Leff = L / 2
The calculation of the effective bridge length is shown in the appendix for scales with several
measuring idlers.
From equation (1), the system determines the actual belt load Q through the bulk solids on the belt from the
mass QB measured through the load cell via:
Q = QB / Leff
The second important measured value is belt velocity v, that is recorded by the velocity sensor Sv and con-
verted into a frequency f proportional to the velocity. The weighing electronics calculates the flow perfor-
mance I in kg/h according to the formula:
I = Q * v = QB / Leff * v
flow performance I = actual flow rate
▪
Gravimetric Mode (regulated)
The actual feed rate is adjusted to the setpoint. The maximum possible setpoint is the same as Nominal
Flow Rate (P03.01). An event message is generated if the input value is too large.
▪
Volumetric Mode (unregulated)
The conveyor element setting is proportional to the feed rate setpoint. Measurement of the actual feed
rate has no effect on the conveyor element adjustment. The feed rate approximately equals the speci-
fied setpoint under nominal conditions.
The setpoint is limited to three times the nominal feed rate. An event message will be generated if this
limit is exceeded.
▪
Volumetric Synchronous Mode (unregulated)
This mode of operation is a special form of volumetric operation. It ensures a seamless transition when
switching from gravimetric to volumetric operation.
P Flow rate setpoint M The drive motor of the feed belt including an external drive controller
If the bulk solids are fed to the feed belt with a controlled prefeeder, the belt load can be additionally con-
trolled through the prefeeder.
v Belt velocity M The drive motor of the feed belt including an external drive controller
The weighfeeder guarantees feeding accuracy, i.e., the belt velocity evens out irregularities in the belt load
from fluctuations in feeding performance.
Fig. 4: The belt scale with feed control as the control principle
If the prefeeder is designed as a position-controlled feed gate, the continuous controller is designed with a
three-point controller with the outputs of Open and Close. Then it will give feedback on its current position to
the controller.
Another weighbridge can be built into the mechanism with slow-moving or long belts for capturing the load
closer to the feeding point.
The feed control can be linked with the function of a velocity-controlled weighfeeder for bulk solids that are
inclined to flooding.
These recurring patterns can be observed even when the belt is loaded.
The belt is given a mark to identify its position that is captured using a stationary sensor. The system learns
the recurring load progression through the belt influence over several belt circuits even with a loaded belt
and automatically corrects its influence. Since the belt influence changes over the transit time (in particular
over idle times), it has to be captured on a regular basis. This is why correction is adaptive.
3.8 Batching
In batch mode a preset quantity of material is discharged and the feeding is subsequently switched off.
Once the batch setpoint has been reached the batch operation is complete. A subsequent start command to
the feeder will begin a new charge.
Batch filling can be carried out in all modes and variants of operation.
The general procedure for batch operation is shown in the following figure:
Fig. 8: Feeding
4 Operation
The DISOCONT Tersus and an attached weighfeeder can be operated in one of several ways:
▪
Operation under normal circumstances using one or more local VHM operating panels. The features of
the different panel versions can be found in system manual BV-H2406. The sides with the operating di-
alogs are also available via web interface for a browser .
▪
Operation using a higher-order plant control system where the control commands are either exchanged
conventionally by means of binary and analog signals or by means of a fieldbus such as PROFIBUS.
▪
Operation for service work by means of a wireless VHM operating panel.
▪
Operation for service work by EasyServe on a PC/notebook with a cable or wireless access.
▪
Local operation by means of an optional service operating level and the VLG or VMO operating units
specifically for work performed on the mechanism. The special characteristics of this operating panels
can be found in the system manual BV-H2406.
Notes:
▪
The following are retained during a power failure:
– Parameter settings
– Setpoints
– The status of all internal counters
– Counting pulses not yet output to external counters
– Date and time
– All important process values
▪
A specific start command is always required to begin feeding.
DANGER
Feeding can be started using the operating panel. This switches the
drives on, allowing bulk material to flow. Before turning it on, the op-
erator has to make sure that turning it on cannot cause any damage.
Interrupting communications when operating on a non-permanent line
(pluggable cable or radio) may cause dangerous situations. There-
fore, such methods of accessing control should be reserved for ser-
vice work only.
You have to select the Ethernet channel (Configuring the Communication Path (Com)) in the operating pan-
el configuration.
Once the first connection has been made, the operating panel searches in the network for VCU control units
and shows its findings on the Feeder operating page. A button belonging a scale that is displayed is used to
select the scale and establish the data connection.
The Bluetooth channel has to be selected (Configuring the Communication Path (Com)) in the configuration
of the operator panel.
Once the communication path has been selected, the console will search for Bluetooth adapters within
range. Other Bluetooth adapters can be found and displayed along with controllers (VCUs). The outcome is
shown on the Feeder [➙ 39] operating page.
Note: A complete search for Bluetooth adapters can take several seconds. A progress indicator is
displayed during the search. There will also be Bluetooth adapters shown to which no con-
nection can be established, either because they are not DISOCONT Tersus controllers or
they are already otherwise connected.
You can select the scale and establish a data connection by pressing the key belonging to the scale dis-
played. It may take several seconds before a connection is established. The respective status will be shown
in the header of the operating panel while a connection is being established.
Note: It can only establish a connection to one scale (assuming the scale is not simultaneously
connected to another Bluetooth adapter). It might be necessary to close the other connection
first. The operating panel will continue to attempt to establish a connection if another connec-
tion already exists.
If Bluetooth is used, the scales to whose Bluetooth adapter a connection has been established is the only
scales with which communication can be made. The Ethernet destination address may not be changed in
the VHM.
Note: The operating panel is the master on the bus. This is why only one operating panel may be
connected on the bus at any one time.
Note: Either use a non-coded socket of the VCU for this connection or a special (yellow) cable
when using the red-coded socket.
The EasyServe address must be in the same Ethernet subnetwork as the scales' address. It might be poss-
ible to adapt the address in the scanner dialog of EasyServe. A scales can also be addressed using a router
if the network has already been configured. The scale address is input manually and not via scanner dialog.
The PC must then have an IP address in the directly connected subnetwork.
The easiest way to select is with the EasyServe Connection | Ethernet (Scanner) item on the menu. This
shows all of the scales available in the network. The scales' connection parameters can be adjusted here
and a connection to the scales can be established.
If the scales are connected to a different subnet, they are selected manually using Connection|Ethernet
(Manual)' and entering the scale's IP address.
38400 baud, 8-O-1 is the only permissible communication format. Select the Com port available at the PC
and the scales' address. The address is stored in parameter P19.01 Own Address in the scales.
Note: A software update via RS232 interface can take as much as 20 minutes. Other functions run
slower than would be usual if the connection was made using Ethernet.
Establishing a connection:
The URL of the operator interface homepage must be entered into the browser address line. This URL is
composed of the following:
http://<address>/hmi/<display factor>.html
Example: http://192.168.240.1/hmi/start.html
NOTES:
▪
The user interface in the browser corresponds largely to the display on the VHM operating panel.
▪
The field used to select a different scales and the configuration dialogs for the VHM operating panel
itself are not available.
▪
Keyboard and mouse are used for operation so the entry keyboard is not shown on the screen.
Various data from the scales controller can be called up on the left-hand navigation bar.
Navigation entry Function
HMI Opens at a different size the same controller interface as is in the operating panel.
HMI_2x Also refer to: Connecting the web browser with the scales controller (VCU) [➙ 21]
HMI_3x
HMI_4x
Events Memory of the most recent events (such as alarms or warnings, etc.)
Parameter changes Memory of the most recent changes in parameters
Command log Logs a list of certain commands, e.g. start / stop
Totalizer hourly Table of hourly-saved totalizing integrators / counters. The values are also available
on the VHM operating panel.
The minute of saving the data is set after the full hour in P38.01.
Totalizer daily Table of daily-saved totalizing integrators / counters
The time of saving from 00:00 h is set in P38.02.
Totalizer Table of totalizing integrators / counters saved on the command
DataLogger 1 Table of the measured values recorded. The sampling interval can be set using
DataLogger 2 P38.03. The up to 10 process variables that can be recorded are selected using
P38.04 P38.13. It begins recording when activating in the Mode operating range.
Tab. 3 : Function calls on the scales controller homepage
Memory depth is approx. 1,000 entries. All entries are keyed in stating the entry time. The entries in the
tables are only up-dated when they are called up. The values can be exported into a PC file for analysis with
standard programs using select-copy-paste.
2 Field for event messages 6 Field for measured values and graphics
Notes:
▪
VHM VCU The operating panel works in the Configuration Mode as long as it is NOT in
communication with a scale. Then the [Feeder] buttons are offered in the ‘Se-
lect the Workspace’ (3) range for selecting a scale and [Con. Scale] for estab-
lishing the connection to the scale selected.
Also refer to the Operating and Control Access Chapter.
▪
The communication to a scale has to be interrupted for adjustments to the
display such as brightness and adjusting the touch-sensitive screen. You can
call up the adjustment dialogs for the operating panel with the [Sel. Scale] but-
ton.
Some functions are not available to non-privileged users. Beyond this, access to some func-
tions can be switched off per parameter.
WARNING
A start signal will actuate the motors!
There is a risk of injury to people standing within range of the motors. Bulk
material can be transported and may overwhelm downstream components.
The stop signal is not an emergency stop, but rather will stop the facility
normally.
4.3.1.8
4.3.1.8 Symbol for Running Operation
The symbol for a running feed in the upper-left corner indicates the state of the main drive. A rotating rec-
tangle will be displayed when device is switched on. This symbol appears on all display pages.
Sources for operation under normal conditions can be set for entry at the scales operating panel during ser-
vice work. This mode is called keyboard mode. The VHM operating panel and the analog operating soft-
ware that can be started via a web browser from the scales control homepage are considered to be operat-
ing panels. In keyboard mode the service software tool 'EasyServe' can also be used to control the scales.
4.3.2.2 Restrictions for Operating Panel with Ethernet Connection and Connection Moni-
Moni-
toring
The system can be configured so that normal operation is accessible only to devices with IP addresses that
have been specified by parameters. The corresponding parameters can be found in the parameter group
'Dialog Behaviour' (P02.04 … P02.10).
Operation via 'EasyServe' is not affected by the parameter setting.
The connection to the operating devices with specified addresses can be monitored so that the scales can
be returned to a safe state in case of a malfunction.
'active' Command not restricted. The command may always be called up at the scales
operating panel.
'not active' Command is never allowed. The relevant key is not shown at the operating
panel making it impossible to execute the command.
'Password' The command is accessible only after logging on with password 1. Password 1
is variable and can be changed using P02.12.
This password is principally intended for service access. The basic system set-
tings are always made using this password.
'2nd Password' The command is accessible only after logging on with password 2. Password 2
is variable and can be changed using P02.13.
The parameters for defining access authorizations are in the group of Dialog Behaviour (P02.14 ... P02.21)
parameters. If the user has not registered with sufficient privileges for the desired function, the operating
button appears as non-active (grey) with a star in the lower right-hand corner.
The operating company is responsible for assuring that the passwords are known to those personnel only
who are to receive authorization for the respective control command. The control functions are released
once the user has logged on with the Login key and has entered the password. The Logout key should be
used to log off the privileged user from the system once the work has been completed. The unit falls back by
itself into the non-privileged operating mode after the time set on the operating panel (refer to Setting the
Display [➙ 38]) .
However, the control commands can always be executed via EasyServe regardless of the
parameter setting.
HINT
Limiting the entry
The setpoint is limited to the nominal flow rate in P03.01 in gravimetric op-
eration and to the threefold value of the nominal value in volumetric opera-
tion.
P = Pe × Pr / 100 %
P = effective setpoint
Pe = External setpoint
Pr = Relative setpoint
It is entered the same way as an absolute setpoint (Set setpoint [➙ 28]).
HINT
Limiting the entry
The setpoint is limited to the nominal flow rate in P03.01 in gravimetric op-
eration and to the threefold value of the nominal value in volumetric opera-
tion.
4.3.3.4
4.3.3.4 Resetting (zero setting) the totalizing counter
The DISOCONT Tersus has three totalizing counters that sum up the measured bulk material quantity.
Counters 1 and 2 can be reset. Counter 3 cannot be reset. The counters do not have any independent over-
flow.
How to reset a totalizing counter
Press the Totals button, then press the button for zero setting the desired counter and confirm the com-
mand.
HINT
Other ways to reset the counters
The system can be configured to allow the counters to be reset by means
of an electrical signal. All counters will still be able to be reset via the field-
bus interface by the main computer. All reset commands work
independently of one another.
4.3.3.5 Acknowledging
Acknowledging Event Messages
All of the important functions are monitored. An event message is generated if a malfunction occurs. This
will be displayed in the message field. The event with the highest priority will be displayed if several events
should occur.
The order of priorities is: Alarm (A), Warning 1 (W1), Warning 2 (W2).
HINT
Displaying earlier events
To display older events, open the 'Values' screen and select 'Event Log'.
Earlier events can be called up using the navigation keys in the event field.
The list of events can also be viewed via web server and can be exported
for an external evaluation.
DANGER
Event messages indicate unusual and/or dangerous states.
For reasons of safety, the causes of any malfunctions must be corrected
before an event message is acknowledged.
To acknowledge an event message press the 'Ack Event' key, available on many screens e.g. in 'HOME'.
Once acknowledged, any blinking messages will be displayed continuously. When the cause of the malfunc-
tion has been corrected the event will be cleared from the message line but can be displayed again using
'EreignisLog'.
A troubleshooting list can be found in section Event Messages.
Serve corresponds to operating with the keyboard on the operating unit, this switch also has an impact on
operating via EasyServe.
Note: When switching to keyboard from an external source (e.g. serial fieldbus), the ON/OFF status of the
scales, the setpoint and the batch setpoint are maintained. The external signals are effective when switching
in the opposite direction.
How to set up keyboard mode
Pressing the Mode buttons, changing to the second display page via arrow key and Keyboard mode there.
Display
The ON, OFF' buttons and the setpoint input space are visible in the keyboard mode. These fields are only
visible in normal mode if the operating sources have been set to the operating panel (OP).
4.3.4.3 Trend
The trend is a graphical depiction on the VHM operating panel of the course of process values over time.
HINT
It is easier with EasyServe
EasyServe allows you to adjust trend depictions much more comfortably
and to export measured data. The trend in the VHM is intended to offer
permanent and simple trend depiction.
The trend depiction, stored values from previous weighings and the configuration of the trend will be deleted
if the operating panel suffers a power failure or if it connects to a different scales.
Button Function
<< Open older values into the display window, large increments
< Open older values into the display window, small increments
> Open more recent values into the display window, small increments
>> Open more recent values into the display window, large increments
Settings Enter the configuration dialog (see below)
Z- Increase time period shown
Z+ Decrease time period shown
Tab. 5 : Control keys
The process values selected for display are shown in the left table (1). The first time it is called up the list
will be empty.
In order to configure the display of a value, click on the value in table 1 to select it. This will show the value's
reference number (ID), its thresholds and the color of the line. Touching fields (3) to (5) will open the corres-
ponding adjustment dialog box.
Button Function
Remove Delete the values selected in (1) and (2).
Back Close the configuration window and return to the trend display. Altered settings will not
be activated.
Update Activate the configuration shown for the trend depiction.
Add Open the dialog to select the value to be displayed.
Tab. 6 : Keys in the lines configuration
Click on a value in list (5) to select it. The properties of the trend line are transferred to the right-hand col-
umn, the reference number (ID) shown in field (4).
The value is transferred with the keys 'Add' or 'New' into list 1 of the values to be displayed.
You can not only see the current bin weight, but also the limits set per parameter. The parameters can be
adapted right on the screen if you register with sufficient privileges.
Parameters No. Meaning
Bin Level MAX P26.18 Upper threshold of the permissible fill level. Generates an event if exceeded.
Control Level MAX P26.13 Fill level at which the filling will be stopped.
Control Level MIN P26.12 Filling is started if the fill level falls below this threshold.
Bin Level MIN P26.15 Lower threshold of the permissible fill level. Generates an event if level falls
below this level.
Tab. 8 : Bin weigher parameters
Button Effect
Auto The filling is regulated automatically by means of the threshold values 'Control Level MIN'
and 'Control Level MAX' set.
Manual The filling of the hopper is controlled by the operator using the keys 'Start' and 'Stop'. For
reasons of safety filling is automatically stopped if the limit 'Control Level MAX' is ex-
ceeded.
Start Begin filling the hopper.
Stop End filling the hopper.
Tab. 9 : Operating keys for controlling hopper fill level
Refer to Adjustment Functions for information on adjusting the bin weigher.
NOTE: The following description applies to a visible and write unprotected parameter accessed by a user
with sufficient user privileges.
The parameter group is displayed and selected in the upper part of display area 6 (see VHM operating pan-
el [➙ 23]). Use the arrow keys to scroll through the groups. Individual parameters in a group can be se-
lected in the lower half of display area 6.
A parameter can be selected directly with the keyboard symbol.
The value of the parameter is shown in display area 7 (see VHM operating panel [➙ 23]) of the command
and edit keys.
The Edit button calls up the dialog for changing the selected parameters. The parameter's identifier will ap-
pear in the focus of the upper part of display area 6 and its current value in the lower part. Depending on the
type of parameter the arrow keys can be used either to assign a new value to the parameter or a value can
be entered for it. A changed value is written into the parameter via Store resident. An alternative is discard-
ing the change with the Exit or Back button. In the latter case the parameter value will remain unchanged.
Active parameter set Set controller behaviour Individual parameter values can be altered (see
Reading and Setting Parameters [➙ 35]).
Backup set Pre-prepared parameter set for By pressing 'Setup', right arrow and then 'Custom'
certain applications or settings you can begin a complete rewrite of the active para-
after commissioning meter set.
Factory settings Unalterable set of parameters for By pressing 'Setup', right arrow and then 'Factory'
the basic configuration you can begin a complete rewrite of the active para-
meter set.
Tab. 10 : Parameter sets: Usage and activation
WARNING
Irretrievable loss of adjusted parameters
Loading the backup parameter set or the factory settings will overwrite all of
the parameters in the active parameter set. The overwrite cannot be re-
versed. We recommend you to use EasyServe to save a copy of the cur-
rent parameter set to the PC drive before overwriting.
WARNING
Output signals are set in simulation mode. This allows externally
connected motors to start. The system will show that material is flow-
ing.
The starting motors may represent a hazard. The on signal can activate
systems upstream of the feeder whether the feeder is prepared to receive
the bulk material or not.
Button Function
Inactivity Inactivity ti- Length of time from the most recent activity until the bright- 20 min
timeout meout ness of the screen is automatically reduced. The screen will
return to normal brightness once the screen is touched. This
contact will not be interpreted as communication with the
scales.
Logout timeout Length of time from the most recent entry before a privileged 600 min
user is automatically logged out of the system security rea-
sons.
Working Display brightness during operation. At full brightness the display has a life expectancy of approximately
brightness 5 years. This expectancy can be increased to over 10 years by dimming the brightness a little.
Sleeping Brightness after a longer period with no activity.
brightness Note: If the display touchscreen is not to be used and the display is intended to be permanently fully
legible, the sleeping brightness can be set to the same level as the operating brightness.
Save Save the changes made. Changes are discarded without prompting if they were not saved beforehand.
Tab. 14 : Parameters for the display
URL of homepage Address of the scales' web server homepage. A web http://192.168.240.1/hmi/start.html
browser on a PC can open the scales' user interface
at this address.
Under normal circumstances the scales are selected
on the 'Feeder' page. The start address is entered
automatically.
Communication will be automatically established to
the last address entered here once power resumes
after a power failure.
Start timeout Length of time between command to connect to a 7s
scales and the start of connection. This period can
be used to access the operating panel configuration
[➙ 37].
Save Save the settings. The entries are discarded if they
are not saved before the page is left.
Tab. 16 : Setting startup routine
4.3.6.6 Configuring
Configuring the Communication Path (Com)
Select the medium of communication here. The key is accessible only to a user with privileged access
[➙ 40].
Ethernet Communication via Ethernet interface and The complete IP address of the x
the RJ45 plug. scales will be used when selected.
Bluetooth Communication via Bluetooth will be auto- All Bluetooth adapters within range
matically activated if a Bluetooth adapter is are listed in the 'Feeder' selection.
connected (wireless interface for portable Each scales must be equipped with its
devices). own adapter. Scales connected to
each other via Ethernet can commu-
nicate via Bluetooth only to the scales
to whose adapter the operating panel
has been connected.
A subordinate IP connection is estab-
lished in a separate subnetwork.
Therefore the IP subnetwork address
displayed in the VHM differs from the
scales' subnetwork address stored in
the parameter.
RS485 Communication via serial interface The last part of the scales' IP address
(1 ... 254) will be used when selected.
The IP address must therefore also
be set when using an interface of this
kind.
Tab. 17 : Alternatives
The select scales page will automatically open if the communication path is changed. The scales stores its
addresses in a parameter.
Details on possible alternative cablings of operating panel and scales are described in the system manual
BV-H2406.
NOTE: Even if there is a belt sensor, the time for one belt circuit should be keyed in to ensure that
the display of mean belt velocity supplies a correct value at the end of the calibration pro-
gram.
NOTE: Taring by belt sections (BIC) is set to zero. If a second weighbridge is installed, it also cal-
culates and sets the tare for this bridge wherever necessary.
NOTE: The effective calibration weight is equal to the value to be ascertained on a separate static
scale on weighing modules with parallel leaf-spring guides. In other cases, you can find the
effective calibration weight in the data sheet. The inclination of the conveyor belt has no
effect on the effective calibration weight.
Display when finished The display of the simulated quantity of bulk solids
The ratio of E from the targeted weight and measured weight value (on an ideal scale =
1.0000).
Parameters changed None
when results are accepted
Potential events and Aborted !:
messages The program was canceled without any changes in parameters.
Volumetric !:
The scale is in gravimetric mode, while the program can only run in volumetric mode.
Batch Active !:
The program cannot run in batching operation. Batching operation is finished.
Tab. 20 : The details and course
It can be manually corrected depending upon the results and boundary conditions:
Results (ratio) E Error Task
E = 0.99 ... 1.01 <1% The scales are in good working order and no further actions are necessary.
E = 0.95 ... 1.05 <5% Key in the value E for the P10.02 parameter if the findings of a material inspection
have not yet been taken into account with the P10.02 parameter.
E < 0.95 or >5% Deviations of several percent indicate that technical data was incorrectly entered (for
E > 1.05 instance, a belt inclination or lever arms are not precisely known) or indicate me-
chanical faults (such as alignment or tension).
Tab. 21 : Handling the results of control
NOTE: P10.02 is not taken into account in the control or it is set to 1. This is why the control pro-
gram displays the same error quotient E after the correction.
Potential reasons for the measured value deviating greatly from the actual value
▪
Mechanical tension in the weighbridge
▪
Shunt forces due to bulk solid particles between the weighed and solid component
▪
Imprecise alignment
▪
Disturbances to the load cell cable
NOTE: We recommend further tests with different weights if you suspect one of these causes to be
the fault. Non-linear deviations indicate the aforementioned reasons while linear deviations
indicate incorrect data.
NOTE: The zero setting function can also be started via digital input (refer to P13.23). It is started
with a positive flank on the signal and it automatically carries over the results when it is
within the allowed boundary (5 % of the rated belt load Qo). Otherwise, the results are
automatically rejected.
The successful completion of the zero setting program can be monitored with the digital output (P14.16).
The digital output is made inactive when starting the zero setting program. After completing the control, the
contact is set active again if the results are within the allowed boundaries.
Display when finished Deviation in percent of the rated load cell load as per P26.04
Tare in percent of the rated load cell load as per P26.04
Parameters changed New value of tare in P26.25
when results are accepted
The second weight value is now taken and checked for plausibility.
Display when finished Set/Act shows the quotient from the change in mass entered in P26.25 and the measured
change in mass.
Parameters changed Enter in P26.24
when results are accepted P26.24new = P26.24old * 'Set/Act'
Condition The conveying element constant of the filling or emptying element entered into P27.06.
The dead time (transit time) from the conveying element to the bin into P27.07
To call up select and start the BIN: Controller Optimization calibration program
Program runtime 10 s
display when running CO: P-Component = recently calculated parameters P27.08
I-Component TN = recently calculated parameters P27.09
Parameters changed Recently calculated values are entered into P27.08 and P27.09. The parameters are au-
when results are accepted tomatically accepted without taking further action.
Potential events and Aborted !:
messages The program was finished. although the parameters remain unchanged.
Feeder Constant:
The P27.06 parameter has an incorrect value (P27.06 = 0.0 (kg/h)/mA). The program is
canceled.
Tab. 25 : The details and course
NOTE: The calculated values of the parameters in P27.08 and P27.09 can be further adapted ma-
nually. The optimization program does not have any impact on the rest of the parameters of
the bin level controller (such as D portion, bypass and lift, etc.).
The error of the continuous scale may contain constant shares, i.e. the tare error and errors dependant
upon the flow rate (the range errors). When correcting the continuous scale, the user has to decide what
type of error it is. It is necessary to distinguish the individual types of errors when operating at different flow
rates. Correct classification is less important if continuous measurement is carried out at approximately
equal flow rates. After all, it is not possible to give a general recommendation for classifying errors due to
the different bulk solids and local conditions.
DISOCONT Tersus is adapted to the technical design in a plant via P29.01 Type of Check System (select-
ing the control strategy).
You can find the parameters for adjusting the control measurement unit in the Check System block of para-
meters. There are further explanations on the process of control in the appendix.
Depending upon the design, the bin weight also takes in the weight of the mass flow meter and the mass
within the unit.
Normally, the bin weight no longer takes in the bulk solids on the transport distance.
The separate unit measures the bin weight and distributes the errors calculated over the continuous mea-
surements. The correction parameters of the continuous scales are correspondingly adjusted.
Preconditions:
▪
The P29.01 Type of Check System parameter have to be unequal to NO.
▪
The P29.08 Check Start Tare parameter has to be on OP to be able to start from the operating panel or
EasyServe.
Proceed to start tare correction from the VHM operating panel:
Call up the KME page starting from the main page (HOME).
Testing and additive correction of the zero point are called up with the Check Start Tare button and testing
and multiplicative correction of the measuring unit can be called up by Check Start Span.
After start, control goes through the phases shown in Details and flow chart control measurement (KME)
[➙ 284]. These phases are shown in the operating panel.
The following process quantities are displayed during the measurement until starting the next measurement:
Note:
If P29.02 Auto Correction = YES, the continuous scale is automatically corrected if the results of control are
within the boundaries defined via P29.32 to P29.35.
If automatic correction was not selected or if the results of control are outside of the specified boundaries,
the Apply function can be used to correct the continuous scale. The Cancel function ends control without
changing continuous scale adjustment. The result is maintained to the next control.
If tare is corrected, the correction is carried out through P10.06 Tare Correction and the results of a zone
correction is calculated into P10.02 Range Correction. The correction is documented in the log files.
You can find more detailed information in the Types of control measurement [➙ 48] section and a flow chart
in the appendix.
5 Startup
During assembly, make especially sure that the alignment and impact tolerance of the measuring idlers and
carrying idlers agree in the scale's range of influence. Imprecise alignment would cause a zero point error
depending upon the belt tension. This is why precise alignment is necessary for a precision scale. Non-
spheric idler running can cause errors.
Alignment
The following figure shows the points with a triangle where the weigh idler and the relevant carrying idlers
have to be aligned.
Fig. 17: Belt scale alignment points: A for troughed belts, B for flat belts
The idlers in the scale's range of influence have to be lifted 3 ... 5 mm in relation to the other idlers. They
have to be aligned among one another to a height difference of less than 0.4 mm. They should be aligned at
several points depending upon the idler station equipment as per the figure.
Impact tolerance
The out-of-round error for the idlers (impact tolerance) may be as much as 0.4 mm in the scale's range of
influence. In addition, the idler stations have to be secured against displacement once aligned. Higher-
quality idlers are used especially on weighfeeders in the scale's range of influence.
Maintenance
All idlers have to be easy to operate. It might be good to replace defective idlers with original quality idlers. If
idlers are remounted or overhauled they should be positioned at their previous locations. This is why the
idlers and idler stations should be marked before maintenance.
After maintenance, alignment has to be checked and the scale retared.
NOTE: If you have purchased components, please read the DISOCONT Tersus BV-H2406 system
manual where you will find information on the installation dimensions and architecture of
the DISOCONT Tersus system.
The total of the rated load cell loads P05.03 LC Rated Capacity
The transmission parameter for the load cells P05.02 LC Characteristic Value
The lever ratio of force application into load cells wherever P05.05 Lever Ratio
available
Nominal flow rate Io P03.01 Nominal Flow Rate
The characteristic value of the velocity sensor P05.01 Pulses per length
Effective Weighing Platform Length P05.04 Effective Platform Length
The conveyor belt inclination provided it is inclined against the P05.06 Angle
horizon
Belt circuit time P10.03 Belt Circuit Time
Rated Velocity P03.02 Nominal Speed
Tab. 26 : Basic parameters
The controller parameters should be entered in accordance with the motor's rated data. The motor is gener-
ally operated on the 50 Hz supply network at an approximate rated speed of 1,450/min and at a frequency
of as much as 110 Hz, meaning a speed of as much as 3,000/min. The maximum permissible speed may be
lower for motors used for applications in the explosive zone. You can find precise data in the motor manual.
Wherever provided for in this application, the temperature sensor in the motor has to be connected to the
measurement processing system.
Since the motors are operated in feed units in a wide adjustment range, it is especially important to focus on
its behaviour at low speeds. The setting suggested by the controller is often not optimum due to the motor's
reduced internal cooling. This is why the motor's temperature should be observed at a lower speed of ap-
proximately 20/min over a longer operating period. It might be necessary to reduce the voltage given by the
controller for low speeds. On the other hand, it is not advisable to reduce it too much since there might oth-
erwise be start-up problems when operating with bulk solids.
Slip compensation is generally not necessary in frequency converters since the feed controller provides
sufficient superset speed regulation. However, if it is activated, settings at a level of compensation lower
than provided for in the converter's standard produce a more stable run.
The ramp to the drive run up is set to the fastest run-up while the ramp for motor run-down is set to approx-
imately 2 s.
The feeder is engineered to ensure that the belt's rated velocity is set clearly below the motor's maximum
speed to maintain sufficient reserve for correcting deviations in rated conditions, especially in case of a low
belt load. This is why the motor speed will be approximately 70 % of maximum speed at rated velocity. Logi-
cally, the controller magnitude on the controller will also be approximately 70 % of its maximum value in this
working point. This setting is generally made by keying in the maximum frequency on the controller.
We recommend not applying any rise in the controller magnitude. Therefore, a setting of 0 ... 20 mA (instead
of 4 ... 20 mA) should be preferred with current input.
NOTE: The behaviour of the external controller can generally be checked in a controller operating
mode with a fixed speed specification without the involvement of the electronic feeding
mechanism.
N Normal operation
L The belt skew to the left R The belt skew to the right
x The belt length covered T The belt mark and the duration of the belt mark at
a medium belt position
V The sensor for capturing the mark in the belt Sig The course of the signal on the sensor
W The width of the belt mark at right angles to Le The length of the belt mark in the direction of belt
the direction of belt travel travel
T_rev The duration of a belt circuit T-t1 Reduced duration from belt run to the left
T+t2 Extended duration from belt run to the left T_rev+t3 Extended duration of a belt circuit due to belt slip
DISOCONT Tersus calculates the belt position from at least two full belt circuits and shows them on the
operating panel and in EasyServe as a Belt Drift service value. The measured drift is given in cm from the
mid-position of the belt mark relative to the sensor.
It can be roughly calibrated mechanically by displacing the sensor. Then, it can be precisely calibrated via
P18.06.
Afterwards, the event classes should be adjusted or checked for the events of belt drift and belt skew in the
P18.08 and P18.10 parameters.
In order to activate, the ratio of the route from the center of the weighbridge to the bulk solids discharge
should be entered into P17.02 in percent at the ratio of the entire belt length. Then, this function can be acti-
vated via P17.01.
NOTE: If Loadcell or Utilization LC is unusual, the load cell input can be checked [➙ 300] with a
test plug.
Preconditions:
▪
Precisely identified and available calibration weight
▪
The calibration weight ranges between 30 % and 100 % of the rated load
Refer to Checking the continuous scale with a calibration weight [➙ 43] for carrying out controlling.
In the former case, the value of the P05.01 Pulses per length parameter entered is dependant upon the
precise diameter of the frictional wheel; in the second case, the value is dependant upon the gear and loop-
ing factor of the conveyor belt on the drive pulley. So the velocity measurement accuracy should be
checked.
NOTE: It is also possible to apply this process if the characteristic value is not known from the data
sheet. In this case, it is advisable to start off by obtaining a rough setting based upon the
default setting and then do fine adjustment following the principle described above.
Major deviations between Vg and Va indicate a faulty velocity measurement. In that case, check the velocity
sensor.
NOTE: The feeder's function can be checked with the display in EasyServe or the LED in the VCU
20100. In addition, you can use an ammeter to check the current i in the circuit of the sen-
sor. This should produce the following measured values:
Zahn recorded the sensor: i = 0.1 ... 1.65 mA
Zahn did not record the sensor: i = 1.65 ... 8 mA
The mechanism should be slowly rotated by hand.
5. The bins or vehicles in which the material is transported onto a (legal-for-trade) commercial scale must
be cleaned and re-weighed (tared) before each filling. The commercial scales must be sufficiently accu-
rate to measure the MW quantity.
The new value P10.02new is calculated as follows from the prior value P10.02old from the MA counter pro-
gression of continuous measurement and the MW mass ascertained on the control scale:
P10.02new = P10.02old * MW / MA
For example:
Old value of P10.02 = 1
A material quantity of MW = 4.9 t is conveyed over a period of 15 minutes. The MA counter progression
read off the device is 5.0 t.
P10.02new = 1 * 4.9/5.0 = 0.98
The calculated value should be entered into P10.02.
▪
NOTES If checking zero point stability has given rise to major errors, there are generally also errors
: between the actual and displayed weight for bulk solids.
▪
The proportionality between the actual and displayed weight can be checked with the adjust-
ment program CB: Weight Check and corrected [➙ 46].
▪
The rated value for the bin fill level should be set into P26.09 for theoretical considerations,
the data sheet or an optic check with a full bin.
▪
If the bin fill level is regulated by turning a prefeeder on and off, the P26.12 and P26.13 pa-
rameters should be adjusted for filling control.
▪
Regulation should be streamlined [➙ 46] after keying in the parameters if the fill level is
created with a prefeeder continually controlled in its flow performance.
Periodically, e.g. every 3 Turn off bulk solids conveying Most errors in the measuring unit can be identified in
months and tare the measuring unit. changes in tare.
A substantial change in the tare indicates friction in
the measuring unit. It might make sense to check the
unit for unacceptable foreign particles and material
build-up of bulk solids on the belt and idlers in the
area of the weighbridge.
Inspecting the belt The conveyor belt should be checked for damage
and center run.
Check the belt tension and correct it wherever ne-
cessary (refer to the operating instructions for the
mechanical equipment).
If available: check the bin The bin should be set vibrating for a brief period of
weight acquisition. time. The weight values shown before and after
these vibrations provide a measure of shunt forces.
This can also be checked with an empty bin. The
results of taring provide a measure of the bulk solids
remaining in the bin when emptying.
Change of bulk material With weighfeeders: You may need to adjust the rated output and possi-
Adjust the external output bly the fill limits for a bin.
controller
Periodically as per the operating Do the maintenance work The interval may depend on the bulk solids.
instructions of the mechanical listed in the manual.
measuring equipment and other
mechanical parts of the unit
Tab. 29 : Suggested measures
7 Parameters
The DISOCONT Tersus is adapted to each application via parameters. No special programing knowledge is
therefore necessary.
default settings Complete parameter set Copy into the active para- Cannot be changed
Non-alterable basic set- meter set using EasyServe,
ting the software the VHM oper-
ating console [➙ 36] or a
web server
Backup set Complete parameter set Copy into the active para- Only using EasyServe in
Pre-setting for a group of meter set using EasyServe, expert mode
applications or a setting the software the VHM oper-
stored during commis- ating console [➙ 36] or a
sioning web server
Tab. 30 : Using parameter sets in the DISOCONT Tersus
Note: parameters not required for an application can be faded out or declared 'read only' using EasyServe
in expert mode. EasyServe compiles a list of visible parameters that form an integral part of the system do-
cumentation. They, together with this manual, make up the relevant documentation of the control system for
an application. The parameter list in the operating manual contains all of the parameters, regardless of their
actual use in an application.
In addition to the parameter set stored in the scales, we recommend that after commissioning you keep a
copy of the parameter set in a mass storage medium using EasyServe.
The parameters are arranged into blocks to for clarity. A parameter is uniquely identified by its block and
number within that block in the respective scales software version:
P01.03: block of parameters 1 → Parameter 3
Note: Each parameter also has a unique number (ID) with which it can be addressed over the serial inter-
face. This number can be seen as a tooltip in EasyServe when passing over the parameter and can be out-
put in the parameter printout.
Gaps can appear between block numbers and parameters within the blocks.
In rare cases, the number of a parameter may change.
7.1 Abbreviations
Source Description
FB Fieldbus
OP Operating panel
DI Digital Input
DO Digital Output
AI Analog Inputs
AO Analog Outputs
LS Logical signal for using internally available signals
Event Event. The reaction to an event can be configured.
W1 Warning 1 (requires acknowledgement)
W2 Warning 2 (does not require acknowledgement)
ALARM Alarm (requires acknowledgement)
IGNORE Ignore: do not show any event message but switch the corresponding contact outputs
LC Load cell
I Flow rate
v Belt velocity
VCU VCU 20100 system unit of DISOCONT Tersus. Refer to the BV-H2406 manual for details.
VHM DISOCONT Tersus operating panel. Refer to the BV-H2406 manual for details.
VMO Machine operating console for service work. Refer to the BV-H2488 manual for details.
Tab. 31 : Abbreviations frequently used in parameters
Step Task
The source parameter defines whether a more precise signal path setting is also necessary. The linking
parameters only offer technically meaningful interfaces.
Source Unit Channel Level Purpose
n/a The internal signal is not assigned to any interface. Input signals adopt automatically a
state that does not interfere with the
program flow.
FB Fieldbus, no additional details required Controlled by signals or fieldbus
OP VHM operating panel, no additional details required Controlled by operating panel entries
v Speed, no additional details required Link with an internal signal
Tab. 33 : Signal sources and their descriptions
Low Voltage = 0 V across the Current at the input > 3 mA High resistance, relay contact open
input terminals (sensor not covered)
High Voltage > 18 VDC across Current at the input < 1 mA Low resistance, relay contact closed
the input terminals (sensor covered)
Tab. 35 : The meaning of the Level parameter segment for an internal True signal
The DI: External Event 1 signal is connected at input DI1 of VCU1. If the input is open (low), this is inter-
preted as logically True (or 1).
Event class Description Impact on Feeding Acknowledgement required Color on the VHM
NOTE: An external binary output channel is set that may have been assigned to the event regard-
less of the event class.
A recently pending alarm- or warning 1-class event will be shown on the operating panel blinking and in
color. The blinking stops when acknowledged. Acknowledged event messages are cleared from the display
for currently pending events when the event is no longer pending. Each event is stored with a time-stamp in
the internal memory [➙ 34] for later analysis.
01 - Hardware Modules
Number: Name Default Customer Sys ID
P01.01 [➙ 93] Analog Channel A10 NO 5746
02 - Dialog Behaviour
Number: Name Default Customer Sys ID
P02.01 [➙ 96] Language * DEUTSCH 4224
03 - Feeder Definition
Number: Name Default Customer Sys ID
P03.01 [➙ 101] Nominal Flow Rate * 10000 kg/h 4226
04 - Control Sources
Number: Name Default Customer Sys ID
P04.01 [➙ 103] Feeder Start * FB 4241
05 - Rated Data
Number: Name Default Customer Sys ID
P05.01 [➙ 106] Pulses per length * 10000 I/m 4256
06 - Feeder control
Number: Name Default Customer Sys ID
P06.01 [➙ 109] Afterflow Totalizer 3s 4274
07 - Feeder Monitoring
Number: Name Default Customer Sys ID
P07.01 [➙ 114] Event: Stand-By W2 4289
08 - Filters
Number: Name Default Customer Sys ID
P08.01 [➙ 117] Filter: Actual Flow Rate 3s 4328
09 - Limit Values
Number: Name Default Customer Sys ID
P09.01 [➙ 118] Limit: Actual Flow Rate MIN 5 % Io 4337
10 - Calibration Data
Number: Name Default Customer Sys ID
P10.01 [➙ 120] LC Filter 0.25 s 4334
11 - Rate controller
Number: Name Default Customer Sys ID
P11.01 [➙ 121] Optimize Controller STANDARD 4368
12 - Analog Outputs
Number: Name Default Customer Sys ID
P12.01 [➙ 128] AO: Setpoint n/a 4385
13 - Digital Inputs
Number: Name Default Customer Sys ID
P13.01 [➙ 131] Event: External Event 1 A 4417
14 - Digital Outputs
Number: Name Default Customer Sys ID
P14.01 [➙ 136] DO: Scale Start DO 4433
15 - Batch Mode
Number: Name Default Customer Sys ID
P15.01 [➙ 139] Batch Mode NO 4448
16 - Maintenance interval
Number: Name Default Customer Sys ID
P16.01 [➙ 143] Maintenance Electric 3000 h 4465
17 - VAP
Number: Name Default Customer Sys ID
P17.01 [➙ 144] VAP Active NO 4480
18 - Belt Monitoring
Number: Name Default Customer Sys ID
P18.01 [➙ 144] Belt Sensor Active NO 4496
19 - Communication EasyServe
Number: Name Default Customer Sys ID
P19.01 [➙ 148] Own Address 1 4520
20 - Communication Fieldbus
Number: Name Default Customer Sys ID
P20.01 [➙ 148] Protocol Type NO 4528
22 - Ethernet
Number: Name Default Customer Sys ID
P22.01 [➙ 157] IP Address 192.168.240.1 6235
23 - PLC Outputs
Number: Name Default Customer Sys ID
P23.01 [➙ 157] DO: PLC 1 n/a 4662
24 - Interlocking
Number: Name Default Customer Sys ID
P24.01 [➙ 159] DI: Event Mechanics 1 n/a 4760
26 - Bin Weigher
Number: Name Default Customer Sys ID
P26.01 [➙ 170] Bin Weigher Active NO 4704
28 - 2nd Weighbridge
Number: Name Default Customer Sys ID
P28.01 [➙ 182] 2nd Weighbridge active NO 4905
29 - Check System
Number: Name Default Customer Sys ID
P29.01 [➙ 187] Type of Check System NO 4861
30 - Moisture
Number: Name Default Customer Sys ID
P30.01 [➙ 200] Moisture Active NO 5386
31 - Dead Time
Number: Name Default Customer Sys ID
P31.01 [➙ 203] Dead Time Active NO 5403
32 - Linearization
Number: Name Default Customer Sys ID
P32.01 [➙ 205] Linearization ON * NO 4577
33 - Flow Gate
Number: Name Default Customer Sys ID
P33.01 [➙ 207] AI: Position Flow Gate n/a 4691
34 - 2-Sensor Slip
Number: Name Default Customer Sys ID
P34.01 [➙ 208] 2-Sensor Slip active NO 5433
35 - Pressure Compensation
Number: Name Default Customer Sys ID
P35.01 [➙ 210] Compensation Active NO 5479
38 - Data Logging
Number: Name Default Customer Sys ID
P38.01 [➙ 221] Hourly Total Time 0 min 5743
Caution:
For reasons of safety, it is imperative that the relevant communication error messages should register an
alarm (A) when originating from units that are actively involved in the control loop.
This event is identified when communication with the VCU input/output expansion with VIO
software and local bus address 2 is disrupted. The cables and the address setting should
be checked if an error occurs.
This event is identified when communication with the VCU input/output expansion with VIO
software and local bus address 3 is disrupted. The cables and the address setting should
be checked if an error occurs.
This event is identified when communication with the first local operating terminal VMO
201xx with local bus address 11 is disrupted. Check the cables and the address setting if
an error occurs.
This event is identified when communication with the second local operating terminal VMO
201xx with local bus address 12 is disrupted. Check the cables and the address setting if
an error occurs.
Letters and characters can be used. The name appears in the upper row of the operating
console and when searching through networks for controllers.
Remark: The characters ";" and "=" are not accepted. During the saving procedure these
characters will automatically be deleted.
Address of the first operating panel from which control commands should be given.
The value 127.0.0.1 must be entered into at least one parameter of P02.05, P02.07 or
P02.09 if a VHM is used for controlling via RS485.
Address of the second operating panel from which control commands are to be given.
The value 127.0.0.1 must be entered into at least one parameter of P02.05, P02.07 or
P02.09 if a VHM is used for controlling via RS485.
The address of the third operating panels that control commands are supposed to be given
from.
The value 127.0.0.1 must be entered into at least one parameter of P02.05, P02.07 or
P02.09 if a VHM is used for controlling via RS485.
This event is detected when the connection via the serial RS485 interface to a VHM operat-
ing panel is interrupted.
Steps:
- check cable connection
- check that operating console is correctly functioning
- check the operating console settings
- check the addresses of the scales at the RS485 data bus (P01.11 VHM RS485 Address)
If the pulses duration is shorter than 10 ms the impulse output is disabled. All impulses not
issued yet are cleared.
The digital input is flank-controlled, i.e., the ON signal must be removed and then reapplied
if the scale becomes inoperative because of something like an alarm.
No release signal from the source determined by P04.03 Source Run Enable.
If this event is pending then the downstream transport equipment is most likely not switched
on.
If the setpoint is given as per P04.02 by the operating console (P04.02 = OP) or the scales
are in keyboard mode P04.05 will have no effect, i.e. the setpoint entered at the operating
console works as entered.
Dependant upon P04.11 Difference Function, further signal processing uses the difference
from the actually measured flow rate and the already known flow rate, meaning the still
unknown flow rate. Therefore, the totalizing counters only add together the additional quan-
tity of bulk solids. The flow rate regulator might receive the additional quantity of bulk solids
as the actual input quantity so that it can be controlled through the prefeeder.
Current at the analog input for 100 % entry of the nominal feed rate in P03.01 Nominal Flow
Rate
The signals from up to two measuring points can be logged separately for extended diag-
nostic (compare P05.09 Source Load Cell 2).
Note: Both load cells must have the same rated load and sensitivity!
Q-MIN: Start-up mode is finished when the load has exceeded the threshold value P09.05
Limit: Load MIN, however no later than after any belt progress defined by P11.15 Volume-
tric Start-Up.
Circuits: Start-up mode continues until the belt has run the portion defined by P11.15 Volu-
metric Start-Up on the complete belt circuit (belt progress).
FAST: In this mode, the drive is operated at rated speed until at least one of the following
conditions is met:
a) load > P09.05 Limit: Load MIN
b) belt progress > P11.15 Volumetric Start-Up
c) measured flow rate > flow rate setpoint
Once start-up mode has been completed, feeding switches to gravimetric operation if volu-
metric mode has not been explicitly selected.
This parameter defines the output channel for the trigger signal for the cleaning equipment.
This event is identified when the cleaning equipment was switched on below the feeder
scale, although there are not any feedback impulses over a time longer than the tolerance
period.
Possible cause:
- the cleaning equipment is blocked
- the supply voltage is lacking for the equipment
- there is a defect on the impulse sensor
Steps to be taken:
Check the cleaning equipment mechanically and electrically
The maximum permissible amount of the sum of all zeroing operations of automatic ze-
roing.
This event is identified if the change in tare identified by the automatic zeroing system ex-
ceeds the threshold value in P06.12 Zeroing Limit.
Possible causes:
- low quantities of bulk material on the belt
- error in the weighing mechanics
Actions:
- visual inspection of the belt and the weighing system.
- run the base tare adjustment program
- check weight measuring using test weights
This is only relevant if two weighing channels are used for recording the belt load at the
main weighbridge.
This event is identified when the scale has switched to volumetric operation because of a
defect in measured value acquisition. This defect is only identified when two weighing
channels are used for main measured value acquisition and the measured values of both
channels depart from one another by more than 13 %.
Possible causes:
- blocked material in the weighing range
- non-symmetrical belt loading
Scales are in standby operation, i.e. the controller magnitude to the feed drive is smaller
than the threshold value set in P07.02 Stand-By Limit Value. The feeder drive is switched
off. The 'running' state will still be displayed outwards.
This function protects the motor from overheating at very low speeds or when idling.
Actions:
Key in the larger setpoint and check P07.02 Stand-By Limit Value.
The signals at the feeder drive's impulse speedometer input are outside of the specified
range.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wiring)
- the sensor has been incorrectly calibrated
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Measures:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales cannot be switched on
even after the error has been rectified.
The load cell load is less than 3 % of the sum of the load cell nominal loads.
Possible causes:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
The load acting on the load cell is greater than 110 % of the sum of the nominal loads of
the load cells.
Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell
The scales will not switch on automatically, regardless of the event class. The event must
first be acknowledged and the command to start given again before the scales will restart.
The program and parameters memory are checked cyclically. An error has occurred during
that. The scales will no longer function correctly.
Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.
One of the analog inputs has a smaller signal than the zero-point offset that was set.
A tolerance of 0.4 mA has been set to avoid constant setting and clearing of the input sig-
nal, in case this input signal should happen to be unsettled.
Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.
The actual feed rate is lower than the minimum value P09.01 Limit: Actual Flow Rate MIN.
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low
Actual feed rate higher than the maximum value set in P09.03 Limit: Actual Flow Rate MAX
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too large
The belt load is less than the minimum value set in P09.05 Limit: Load MIN
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
The belt load is greater than the maximum value set in P09.07 Limit: Load MAX
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
The belt speed is less than the minimum value set in P09.09 Limit: Speed MIN
The belt speed is greater than the maximum value set in P09.11 Limit: Speed MAX
Note: filtering the load cell signal also effects the regulating action.
The appendix contains a detailed wiring diagram and applications for special cases.
Caution! The parameters from P11.19 are reset to the factory settings when changing from
UNIVERS to STANDARD.
TN is the reciprocal value of the integration constants KI, i.e. a larger value means a slower
controller.
KI = 1/TN
TN in%/(mA/s)
Simultaneously P11.05 Time Deviation functions as a time constant for the filter that con-
tains the value of the control deviation. A 'control deviation' event is also identified if the
filtered result exceeds the threshold value P11.08 Deviation abs. max..
Maximum Deviation exceeded. The actual feed rate has deviated to far from the setpoint
over too long a period of time.
Possible causes:
- material has been incorrectly handled:
- the bulk material is flowing irregularly or cannot be discharged satisfactorily
- arching in the feed hopper
- there is a backup on the discharge side
- a large quantity of material continues to trickle from the feeder
- calibration error: during initial calibration the regulator was set at such a critical value that
minor changes in the overall properties of the system lead to unreliable operation.
Also refer to: P11.08 Deviation abs. max., P11.07 Factor Deviation, P11.06 Threshold Dev-
iation, P11.05 Time Deviation
The Controller Magnitude of the feed rate regulator has reached the upper response thre-
shold. After a time message HI05 (P11.09) will be output.
1. No material is flowing or material flow is irregular.
2. The external output regulator has been incorrectly set.
Step to take: check the material discharge and the Controller Magnitude (service value Y).
At Nominal Flow Rate Y should be between about 10...14 mA.
If transfer is made with currents from 4 ... 20 mA, the parameter should be set at least to
4 mA. P11.13 Controller Magnitude Offset must be set to a value equal to or greater than
P11.11 Lower Limit.
With inputs lower than 20 mA the limit depends on the size of the threshold value.
Generally the same values are chosen for P11.13 Controller Magnitude Offset as for
P11.11 Lower Limit.
Optimization:
- fill the feeder hopper with bulk material
- calculate the actuating variable Y1, the value at which the discharge unit begins to work
- calculate the actuating variable Y2, the value at which reduction of the feed is suspended.
For feeders that are operated with feed rate setpoints of 0:
P11.13 Controller Magnitude Offset = Y2
All other feeders:
P11.13 Controller Magnitude Offset = Y1
Note: P11.13 Controller Magnitude Offset must be equal to or greater than P11.11 Lower
Limit.
This parameter takes effect only if P04.02 Feedrate Setpoint has been set to AI.
The range and offset parameters take effect only if P04.02 Feedrate Setpoint has been set
to AI.
For further details see the section 'Details: Regulation' in the appendices.
One value is superimposed additively on the actuating variable, proportionally to the preset
setpoint. This parameter gives the bypass value for the nominal setpoint.
The adaption means that the controller can be adapted to variable route reinforcements or
the
guidance behavior can be improved.
Also refer to: P12.05 Flow Rate Offset, P12.06 Flow Rate Range
Possible cause: depends on the external cabling. Usually: an error in the main drive
The input is also linked to the internal interference logic (block: interlocking).
The input is also linked to the internal interference logic (block: interlocking).
The input is also linked to the internal interference logic (block: interlocking).
The input is also linked to the internal interference logic (block: interlocking).
Caution: the level is static and may not be on permanently (otherwise continuous acknowl-
edgement).
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
The event is identified when the belt limit switch has responded.
Possible causes:
- extreme belt off-center run
- contaminated limit switch
- defect on automatic belt tracking
- defect on the belt
Actions:
- make a visual check of the belt run
- correct the belt run with the belt tightening equipment
- check the belt tightening and automatic belt tracking
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
An output should be selected on the main VCU (local bus address 1) if there is active belt
load regulation of the P25.01 type = "PULSE" .
(The DISOCONT Tersus is operated using the operating console VHM or EasyServe).
Interim values result in filtered adjustment; this should be used in particular for systems with
poor reproducibility.
The result of the event is stored in P15.04 Correction Amount.
The printout can be made only after a batch has ended automatically or manually. The
printout is stored to a file that can be read using the Web-Server.
The batch setpoint resulting for an input flow corresponding to the parameter P15.12 Batch
Setpoint Range.
For example:
P15.11 = 1000 kg
P15.12 = 20 mA
P15.13 = -20 mA
0 ... 20 mA then correspond to 500 ... 1000 kg
Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces
Erroneously entered batch setpoint. The value entered is reduced to the permissible upper
limit in P15.18 Batch Setpoint Limit.
Possible causes:
- incorrect entry
- incorrect upper threshold
Cancel: the batch begun before the power down is aborted. A new batch is begun with the
current setpoint.
The sum of the times during which the mains voltage is on is greater than the time P16.01
Maintenance Electric.
A message occurs after each expired time interval. The message may indicate service work
required.
The sum of the runtimes of the conveying elements is greater than the time P16.03 Main-
tenance Feeder Run.
A message occurs after each expired time interval. The message may indicate service work
required.
Note for the weighfeeders: if VAP is active, we recommend switching on automatic belt influence compensa-
tion BIC.
The conditions: The ratio of the 'distance from the center of the weighbridge to material discharge' to the
'total belt length' is known.
The belt sensor must be activated and the signal input defined in order to apply adaptive
belt influence compensation (P18.03 BIC Active), basic slip control (P18.12 Event: Slip) and
basic belt motion monitoring (P18.08 Event: Belt Drift).
See also:
P18.02 DI: Source Belt Sensor
P18.04 Sensor Length
P18.05 Sensor Width
P18.06 Sensor Offset
Note:
Initial startup is made without active BIC.
Characteristics:
After belt influence compensation is activated the influence that the conveyor belt has on
weight measurement is offset after approximately ten belt circuits.
This event is identified if the belt motion does not correspond to that predicted by the motor
revolutions.
Possible causes:
- belt is slipping at the drive pulley
- withdrawal forces are too high
- gearing is defective
- belt or drive pulley heavily soiled
Steps:
- visual inspection of the belt and the bulk material flow
The output operates independently of the event class of the corresponding event.
The output operates independently of the event class of the corresponding event.
The output operates independently of the event class of the corresponding event.
All devices connected to the communicatio bus must have disjunct addresses.
Data transfer speed. This parameter is used for information only. The speed cannot be
changed.
Formats the serial data. The value is used for information only and cannot be altered.
DISOCONT Tersus: Further details on card installation can be found in the system manual
BV-H2406. Manual 'Data Communication' (BV-H2448) contains further information on the
data structures.
INTECONT Tersus: Manual 'Data Communication' (BV-H2474) contains further information
on the data structures.
NO: Modbus-TCP can be used to read but write-accesses will not be processed.
Modbus-RTU: RS232, RS422 or RS485 interface; fieldbus interface card VSS 28020 must
be installed.
Modbus-TCP: Complete communication (read/write) using Ethernet and the main VCU
RJ45 plug.
Ethernet/IP: Communication via Ethernet and the RJ45 plug on the main VCU.
The red-coded RJ45 socket X96 may not be used for communication with the host comput-
er.
A telegram from the host system will be expected within the time set if the timeout value in
P20.02 is greater than zero.
Cyclical serial communication with the higher-order plant control system has been inter-
rupted for longer than the timeout-period in P20.02.
The contents of the data has to be set on the scale and opposite point in a way that is com-
patible to one another!
N = No parity
O = Odd parity
E = Even parity
The number of freely selectable measuring and status values (scales→ master) that are
queried in a telegram.
NO: No restrictions
FIRST WRITE: The subscriber that transmits the first write access gets the control rights.
The other subscribers may read only.
REMOTE IP: Control commands from the subscriber with the IP address given in P20.23
Remote IP Address FB only will be carried out.
For the available data and their Ids see the separated communication manual:
Selecting the first control command with ID 320 (decimal) in the fieldbus telegram. It cannot
be changed in this parameter.
The following values in the telegram can be configured as per the ID list in the data com-
munication manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468
Selecting the first value to be read from weighing electronics in the fieldbus telegram. The
number of the value (ID) can be found in the Data Communication manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468
IP address of the weighing electronics. If the control system is integrated into an Ethernet
network, the address must be chosen in agreement with the network administrator. In iso-
lated networks we recommend the factory setting 192.168.240.x. "x" allows for selection of
the system on the bus.
The DISOCONT Tersus allows physical output signals to be controlled directly by the control system com-
puter via fieldbus. The parameters of this group assign physical channels to the fieldbus commands.
Please also refer to: status of fieldbus protocol commands in manual 'DISOCONT Tersus Data Communica-
tion' (BV-H2448).
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Alternatives:
NO: no belt loading regulation
YES: The integral component of the controller magnitude reached just before turning off is
maintained at restart
YES-A: Like YES, however setting the integral component to zero if feeding has been be-
come inoperative due to an alarm
The parameter only functions when using the main weighbridge to belt load regulation. The
behavior is as with YES when using the second weighbridge.
Definition of the output channel for the controller magnitude to the material prefeeder.
An output on the main VCU (local bus address 1) should be selected with active belt load
regulation of the P25.01 = PULS type.
The integral component of the position controller for the position-controlled prefeeder.
The minimum waiting periods between two adjustment steps. This parameter can be used
to prevent continuous vibration of the prefeeder around the operating point.
The definition of the output channels for opening the position-controlled prefeeder. With
DISOCONT Tersus the output should be on the main VCU (local bus address 1).
The definition of the output channel for closing the position-controlled prefeeder. With
DISOCONT Tersus the output should be on the main VCU (local bus address 1).
The load setpoint = nominal belt loading (service value) is at P25.16 QA Setpoint Source =
n/a
Refer to the following when norming the input and adjusting AI:
- P25.17 QA Setpoint Range
- P25.18 QA Setpoint Offset
Input flow for a load setpoint of 100 % of nominal belt loading (service value).
Note:
Speed regulation for the feed belt to compensate belt loading fluctuations remains active in
all cases.
States
a) flow rate setpoint in percent of the nominal flow rate (P03.01) < P25.20 (operation with
minimum belt loading):
belt loading setpoint = P25.20
b) flow rate setpoint in percent of the nominal flow rate (P03.01) > P25.20 and flow rate
setpoint in percent of the nominal flow rate (P03.01) < P25.19 (operation at reduced belt
loading):
belt loading setpoint = flow rate setpoint in percent of the nominal flow rate / P25.19
c) flow rate setpoint in percent of the nominal flow rate (P03.01) > P25.19 (normal opera-
tion):
belt loading setpoint = P03.01 / P03.02
Examples of settings:
A) flow rate regulation via belt loading at the rated speed of the feed belt
The weighfeeder should be run at the operating point
of the rated speed “independant of the conveying capacity setpoint”.
P25.19: 100 %
P25.20: 0 %
NO: The bulk density is assumed to be almost constant. The correlation between controller
magnitude and the feed rate of the prefeeder is entered in P25.02 Controller Magnitude
Adaption.
YES-1.WB: This coefficient is ascertained with the aid of the belt load and feed rate ascer-
tained via the main weighbridge.
YES-2.WB: This coefficient is ascertained with the aid of the belt load and feed rate ascer-
tained via weighbridge on the material feed. This process can ascertain the coefficient more
quickly due to the lower amount of time between prefeeders and measuring point. Of
course, this measuring point is generally less precise than the main weighbridge. This ad-
justment is used with long and slow-running feed belts and long scales.
The prerequisite: The feeder scale has a second weighbridge. Refer to the 2nd
Weighbridge group of parameters.
You can find details in the block circuit diagram in the appendix.
P25.24 Yz Dead Time = 0s is set if the speed of the transport equipment is regulated syn-
chronously to the prefeeder.
P26.01 = Simulation:
Bin regulation and min/max regulation are simulated.
The continuous scale draws off material and filling is done with 4 × P03.01.
If FB or AI are selected the external value will be converted to a value with mV/V units that
corresponds to a measurement from a load cell. The following signal processing calculates
weight in kg from the signal in mV/V and is identical for all input types.
As there is generally always an initial load on the load cell it is usually sufficient to analyze
the signal in the direction of compression only. The YES setting is needed in rare special
cases only, e.g. if a measuring eye is used to record weight.
Bipolar measurement reduces the resolution of the measuring signal.
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Steps to take :
- check the cabling and the load cell
- if the cabling is intact: replace the load cell amplifier VME in the VCU
Note:
The power supply must be switched off and on again if the scales still cannot be switched
on even after the error has been rectified.
The load cell load is greater than 110 % of the sum of the load cell nominal loads.
Possible reasons:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
The output is set to 'do not fill' each time a scales alarm is triggered.
Also refer to: P26.12 Control Level MIN, P26.13 Control Level MAX
Also refer to: P26.16 Event: Bin Level MIN, P26.17 DO: Bin Level MIN
Possible cause:
- refilling working incorrectly
The output becomes active if the fill level underruns the lower threshold value. It operates
independent of the event class of the corresponding event.
Also refer to: P26.19 Event: Bin Level MAX, P26.20 DO: Bin Level MAX
Possible cause:
- refilling not switching off correctly
The output operates independently of the event class of the corresponding event.
See also:
P26.21 AO: Bin Load
P26.23 AO: Range
P26.09 Nominal Bin Load
The fill level sensor reports a too-high fill level in the hopper.
Possible causes:
- the weight of the bulk material is very low so that the weight-controlled filling is not shut-
ting off soon enough.
- the refill equipment is not closing correctly.
- the upper fill threshold level P26.13 Control Level MAX has been set too high.
An overfilled hopper can lead to inaccurate check measurements and so to false adjust-
ment of the calculation of the feed rate.
Converting the analog value into the voltage signal corresponding to a load cell:
The measured value [mV/V] = (input flow – P26.30) / (P26.31 – P26.30) * P26.03
where:
P26.30 = Bin Level analog Input Offset
P26.31 = Bin Level analog Input Range
P26.03 = LC Characteristic Value
Precondition: weight measurement of the separate bin has been activated (P26.01 Bin Weigher Active =
YES).
Digital control of the separate bin filling can be found in the Bin Weigher block.
Details on the controller and the controller block diagram can be found in the appendix.
The output is set to off, the controller magnitude is set to 0 and the controller is put into the
base position with every scale alarm. The automatic check system does the regulating dur-
ing its measuring phase.
An I controller results at KP = 0 that leads to a control circuit with an instable structure with
this regulation. This setting should therefore be avoided.
This value should not be greater than the D component. 0.1 ... 0.3 * P27.10 is normal.
The bypass is adjusted so that the fill level of the bin is retained (outflow = inflow) if the
controller is switched off (P27.08 P-Component KP, P27.09 I-Component TN, P27.10 D
Portion TV = 0) and the scale is switched on.
The bypass can be changed in small increments until the service value yBi oscillates
around 0, even if the controller is active.
(The designs with different signs apply correspondingly to P27.02 Filling Type = NO.)
The value set is automatically taken into account by the calibration program BIN: Controller
Optimization'.
Note: filtering the load cell signal has an impact on the control characteristics of belt load
regulation.
The load cell cable is improperly connected, not connected at all or has been disconnected.
The load cell may be faulty.
Actions:
- check the cabling and the load cell
- check the load cell
The load on the second weighbridge has fallen below the threshold value.
Possible causes:
- no bulk solids
- defect on the prefeeder
- weighing station stuck
- belt load regulation poorly adjusted
- defect in load cell
Actions:
- make a visual check of the bulk solids on the belt
- use a calibration weight to check the weighing station
Possible causes:
- the belt is covered
- defect on the prefeeder
- weighing station stuck
- belt load regulation poorly adjusted
- defect in load cell
Actions:
- make a visual check of the bulk solids on the belt
- use a calibration weight to check the weighing station
This value is automatically ascertained and entered by the calibration program TW: Tare.
7.4.2.29
7.4.2.29 Parameter Block 29 - Check System
The check system controls and corrects a continuous scales using the change in bin weight; the changes in
weight result only from the bulk material passing over continuous scales. During measurement all other in-
and outflows must be stopped.
NO:
No check system
Single unit:
The continuous feeder scale and control weighing bin form a mechanical unit and are
weighed together. The continuous weighfeeder discharges from the hopper.
Separated Units:
The continuous feeder scale and control weighing bin are decoupled both mechanically and
with regards to weighing. The continuous weighfeeder discharges from the hopper.
Filling system:
The continuous weighfeeder fills the control bin during the check.
External:
The control procedure is controlled by a higher-order system. The DISOCONT Tersus only
supplies the relevant measured values.
The following parameters only are effective:
- P29.27 DO: Check Measurement Active
- P29.30 Absolute Range
- P29.31 Relative Range
The following parameter description relates primarily to the 'single unit' and 'separated
units' types.
NO:
No automatic start
Tare:
Automatic start for controlling and correcting tare or additive effects of errors.
Span:
Automatic start for controlling and correcting the proportionality factor between the meas-
ured value and actual feed rate. Correction of multiplicatively acting effects of errors.
It starts after a pause preselected with the parameters P29.04 Cycle Time. It also makes
sense to preselect automatic correction (P29.02 Auto Correction = YES).
This event is identified if a check has been started but the plant control has not authorized
one.
Generally, no steps need to be taken. The event serves only as an indication of the missing
authorization.
Once measurement has ended the check system moves to the acknowledgement phase
and waits for the correcting command, when P29.02 Auto Correction = NO. Corrections can
also by made manually if the tolerances P29.30 Absolute Range or P29.31 Relative Range
have been exceeded. Correction is triggered by the input flank.
The check must be canceled if the measuring system is in acknowledgement phase and if
the control outcome is not to be used to correct the continuous scales.
Quantity: The measurement is finished when the quantity of bulk solids given in P29.13
Check Quantity has been conveyed.
Circuits: The measurement is finished when the belt has progressed the belt length given in
P29.13 Check Quantity.
The quantity selected should be large enough to minimize the effects of errors when deter-
mining the control quantity. By the same token the hopper should have sufficient capacity
for the control quantity.
Conditions:
1. The storage quantity must be smaller than the maximum control fill level: P29.14 <
P29.19 Maximum Fill Weight.
If this condition is not met, the check will end after starting with the message CH 03 (max.
check fill level).
2. The storage quantity must be greater than the sum of the check quantity, the minimum
check fill level and an excess allowance: P29.14 Storage Quantity > P29.13 Check Quanti-
ty + P29.17 Minimum Fill Weight + MT + MB
If this condition is infringed the fill level will fall below the min. control fill level during the
check. The measurement would then cancel with the message CH 02 (min. check fill level).
MT = losses caused by the settling time P29.21 Damping Time.
MB = losses caused by the blind distance P29.22 Blind Distance (only with P29.01 Type of
Check System = single unit).
The event is identified when the control measurement was finished after the given number
of belt circuits before the given minimum quantity of bulk solids has been discharged.
Possible cause:
The belt load is less than expected. The result of the check might be afflicted with an im-
permissibly large defect.
Remedy:
Increase the belt load
The measurement would cancel with the message CH 02 (min. check fill level) if the ma-
terial quantity falls below this amount.
The fill level has fallen below the threshold value in P29.17 Minimum Fill Weight during a
check.
Possible cause:
- bulk material density higher than specified
- unfavorable settings in P29.13 Check Quantity or P29.12 Check Circuits, P29.17 Mini-
mum Fill Weight or P29.14 Storage Quantity
The maximum fill level was exceeded during the check. The control measurement is fi-
nished early.
Possible cause:
The storage quantity (P29.14 Storage Quantity) is greater than the maximum control fill
level (P29.19 Maximum Fill Weight). The check will be canceled just after it starts. In case
of an error, check the magnitude of both parameters.
The signal is active from the start of the control until successful correction or cancellation.
The check will be canceled without a response if the conveying element On feedback is
received after starting settling time.
The control waits until conveyance into the control bin is stopped.
Possible cause:
- long time required to end filling
- incorrect control sequence for bin filling
The check procedure is in the filling phase or settling time or the fill level is still greater than
the maximum check fill level (P29.19 Maximum Fill Weight).
At the end the check system waits for a decision by the operator:
Correction will not be made automatically if the threshold would be exceeded by a check.
An event will be identified in each case.
See also:
P29.32 Event: Absolute Tare Correction Error
P29.34 Event: Absolute Span Correction Error
Correction will not be made automatically if the error overshoots the threshold. An event will
be identified in each case.
See also:
P29.33 Event: Relative Tare Correction Error
P29.35 Event: Relative Span Correction Error
The current correction would make the sum of all zero-point corrections greater than the
threshold value P29.30 Absolute Range since the last basic tare calibration. There is no
automatic correction. The operator can acknowledge the message and enter the result
manually. Monitoring and messaging occur in the acknowledgement phase. The correction
weighting factor P29.36 Correction Evaluation is not taken into account in the error analy-
sis.
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unloading)
The result of the current correction deviates more greatly than the threshold value P29.31
Relative Range from that of the last measurement. There is no automatic correction. The
operator can acknowledge the message and enter the result manually. It is monitored and
reported in the acknowledgement phase. The correction weighting factor P29.36 Correction
Evaluation is not taken into account in the error analysis.
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unloading)
The threshold in P29.30 Absolute Range was exceeded by the sum of all corrections for
multiplicative errors.
Bprod = (1 - B * K) * 100 %
The multiplicative error just ascertained exceeds the threshold value in P29.31 Relative
Range.
Brel = (1 - B )× 100
P29.36 = 1 is normally set for the first control measurement to make a basic setting. Sub-
sequent corrections, in particular when checks are automatically started, are normally car-
ried out with P29.36 < 1. This makes it possible to filter the control results and eliminate
random measuring errors in the control measurement.
Procedure: the control gate will divert the material either through the normal conveyance
path or into the control bin. The correct position of the control gate can be monitored by the
digital input 'Echo Control Gate' (P29.40 Check Gate Feedback).
Defines the input channel for the position return signal from the control gate. The return
signal is not monitored with the setting 'n/a'.
If there is no feedback from the control gate within the monitoring time (P29.41 Check Gate
Time), the control gate error event is set and the KME is canceled.
Also refer to: P29.39 DO: Check Gate, P29.42 Event: Check Gate Error
Tolerated time allowed for the control gate to move between command and position return
signal.
This parameter relates only to the check by increase in weight of the bin (P29.01 Type of
Check System = Filling System).
The control gate did not reach its end position within the tolerance time.
Possible cause:
- gate has no power
- gate is stuck
If the malfunctions exceed the threshold value in P29.43, another attempt at measuring will
be started after a time defined by P29.21 Damping Time. However, if this attempt also re-
turns excessively high malfunctions, the check will be canceled, the result discarded and an
event identified (P29.44 Event: Bin Error). Disturbances are not monitored if the setting is
0%.
How to set:
1. set the threshold to 10,000 %
2. Monitor the service display 'KME Window' during the check procedure
and note the max. value.
3. enter approximately 3 times the value in the parameter P29.43 Limit Max. Bin Error.
Large disturbances in the weight signal of the control bin were detected during the check.
The check was canceled and the result discarded. It is also canceled if the event class has
been set to IG.
Possible cause:
- force bypasses at the control bin
- pressure forces acting on the control bin
- wind forces acting on the control bin
The measuring system can correct bulk solid properties such as these. This requires that the disturbance
variable, e.g. the moisture or ash content, be measured and the result sent to the system. The measuring
system then calculates the bulk solid components relevant to the process and feeds it instead of the total
weight.
NO: No correction
YES: Weight signal is corrected
The parameters relevant to moisture correction are visible only when correction is active.
Also refer to: P30.03 AI: Moisture Measurement, P30.06 Moisture Range
Also refer to: P30.03 AI: Moisture Measurement, P30.05 Moisture Offset
Also refer to: P30.09 DO: Moisture MAX, P30.10 Event: Moisture MAX
Also refer to: P30.08 Moisture MAX, P30.10 Event: Moisture MAX
The measured value of the interference quantity (for instance, the moisture) has been ex-
ceeded. Feeding errors may arise.
Possible cause:
- extremely damp bulk material
- moisture measurement measuring error
Also refer to: P30.08 Moisture MAX, P30.09 DO: Moisture MAX
Also refer to: P30.12 AO: Flow Rate Offset, P30.13 AO: Flow Rate Range
4 points along the characteristic curve are used for linearization. The points are determined from the actual
(correct) value of the quantity of bulk solids conveyed over a period of time, ascertained by a separate
check scale at the appropriate belt load, and the quantity of bulk solids added up by the weighfeeder over
the period of the measurement. Another point of the characteristic curve is the origin (0% / 0%). The charac-
teristic curve is continued at a continuous gradient above the highest point.
The reference for all linearizing points is nominal belt loading (service value).
Consider the location of the linearization in the signal processing (--> appendix).
Detailed calibration instructions are in the appendix.
The event is identified when the prefeeder has run past the limit switch for the minimum
position. It is used to protect the mechanical equipment.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
The event is identified when the prefeeder has run past the limit switch for the maximum
position. It is used to protect the mechanical equipment.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
7.4.2.34
7.4.2.34 Parameter Block 34 - 2-Sensor Slip
The slippage of the feed belt can be ascertained either with a mark put into the belt or by measuring the
speed at two different points. In general, one measuring point is mounted on the belt drive and the second
measuring point is mounted on a roll moved by the belt. Monitoring them ascertains the ratio of the two
speeds and reports any deviations that indicate that the belt is slipping through or tearing.
Slippage can be identified more quickly through the second sensor and the appendix contains details on
evaluating it.
The event is identified when the slippage exceeds the set threshold value.
Possible causes:
- contamination on the belt, the head pulley or the pulley with the second sensor
- the belt slips on the head pulley (higher draw-off strength and bulk solids stuck in the inlet)
- sluggish pulley with the second sensor
Actions:
- make a visual check of the bulk solids situation
- check the drive motor and gear
- check the second pulley
If compensation is not activated, the associated parameters will not be displayed in Easy-
Serve.
The event is identified if there is a substantial defect in the signal of the pressure sensor
and the pressure signal is read in through the VME interface.
Possible causes:
- defective sensor cable
- sensor improperly connected
This event is identified when the output signal of the pressure measuring sensor is over its
nominal value.
Possible causes:
- overload on the pressure sensor
- defective sensor
The event is identified when the output signal of the pressure measuring sensor is substan-
tially below zero.
Possible causes:
- sensor improperly connected
- unexpected pressure conditions
- defective sensor
Setting:
P35.09 = 0
Read off the service value of the pressure with atmospheric pressure on the sensor
Adjust the value read in P35.09
Finally, the service display should display the value 0 for pressure.
Setting:
- initially adjust P35.09
- note the weight m0 of the bin at the pressure = 0
- impinge the bin with any (although constant) pressure
- read the service value of the pressure (p1)
- note the weight m1 of the bin
- adjust P35.10 = (m1 - m0) / p1
The bin weight shown should now always be m0 regardless of the pressure.
The pressure in the bin has fallen below the lower threshold.
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
The output functions independant of the selection of event class in P35.12 Event: Pressure-
MIN.
The pressure in the bin has exceeded the upper threshold value.
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
The output functions independant of the selection of event class in P35.15 Event: Pressure-
MAX.
Name of the required function block link. This name is automatically transferred to the pa-
rameter when a new link is loaded. When the system is started after turning on the voltage,
it checks to see whether the name of the function block link loaded is the same as the
name entered in the parameter. Event P36.22 Event: FCB-Error is identified if the names
are different.
This check serves as a control if a replacement part is used.
This event is identified if the function block link loaded does not correspond to the link
stored in the parameter.
Caution: It probably does not have the full functionality. Unreliable operating states
may arise.
Possible causes:
- it forgot to load the correct link after exchanging the VCU.
- the name in the parameter was changed manually.
Steps to be taken:
- load the function block link with the correct name.
Select the process value for recording. You can find the identification number of a value in
the data communication manual.
EasyServe can be used for easy configuration or the settings can be made with the help of the allocation
map in the data description of the serial interface in the operating panel.
You can find the characteristic values (ID) belonging to the process variables in the manual on data com-
munication:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468
Each VMO can control as many as 5 drives. The parameters for these drives are marked with block num-
bers 1 ... 5 in this group of parameters.
You can find a logic diagram of the local control unit in the appendix.
Note: Communication to the VMO has to be activated via parameters P01.12 to P01.15 Event: Communica-
tion VMO20100-Unit 2.
Furthermore, the parameters in the VMO should also be adjusted accordingly in addition to the pa-
rameters in the VCU. This is generally done at the manufacturer's.
n/a: The drive in VMO is not linked with any signal. This motor should be deactivated in
VMO.
n/a: The drive is not linked to any signal. This setting is selected when the drive is operated
at a constant speed.
YES: When there is an alarm, the motor can still be started in local operation of VMO.
However, it only runs until the start button is pressed. This operating mode only makes
sense with belt drives that have to be started with belt drift to move the belt into normal
position again.
You can find a logic diagram of the local control unit in the appendix.
Note: Communication to the VMO has to be activated via parameters P01.12 to P01.15 Event: Communica-
tion VMO20100-Unit 2.
Furthermore, the parameters in the VMO should also be adjusted accordingly in addition to the pa-
rameters in the VCU. This is generally done at the manufacturer's.
8 Event Messages
DANGER
Events register abnormal states, e.g. malfunctions or exceeded thre-
shold values.
A running feeder can be a hazard to people or to property.
The cause of event messages must be corrected before events are ac-
knowledged!
Note:
In the following list, parameters related to the indicated event are shown in parentheses.
Measures:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales cannot be switch-
ed on even after the error has been rectified.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wir-
ing)
- the sensor has been incorrectly calibrated
Steps to take :
- check the cabling and the load cell
- if the cabling is intact: replace the load cell amplifier VME in the VCU
Note:
The power supply must be switched off and on again if the scales still cannot be
switched on even after the error has been rectified.
Actions:
- check the cabling and the load cell
- check the load cell
Possible causes:
- low quantities of bulk material on the belt
- error in the weighing mechanics
Actions:
- visual inspection of the belt and the weighing system.
- run the base tare adjustment program
- check weight measuring using test weights
Possible causes:
- defective sensor cable
- sensor improperly connected
Possible cause:
The belt load is less than expected. The result of the check might be afflicted with an
impermissibly large defect.
Remedy:
Increase the belt load
Possible cause:
- bulk material density higher than specified
- unfavorable settings in P29.13 Check Quantity or P29.12 Check Circuits, P29.17
Minimum Fill Weight or P29.14 Storage Quantity
Possible cause:
The storage quantity (P29.14 Storage Quantity) is greater than the maximum control
fill level (P29.19 Maximum Fill Weight). The check will be canceled just after it starts.
In case of an error, check the magnitude of both parameters.
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unload-
ing)
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unload-
ing)
Bprod = (1 - B * K) * 100 %
Brel = (1 - B )× 100
Possible cause:
- long time required to end filling
- incorrect control sequence for bin filling
Generally, no steps need to be taken. The event serves only as an indication of the
missing authorization.
The control gate did not reach its end position within the tolerance time.
Possible cause:
- gate has no power
- gate is stuck
Possible cause:
- force bypasses at the control bin
- pressure forces acting on the control bin
- wind forces acting on the control bin
Step to take: check the material discharge and the Controller Magnitude (service
value Y). At Nominal Flow Rate Y should be between about 10...14 mA.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
Possible causes:
- the weight of the bulk material is very low so that the weight-controlled filling is not
shutting off soon enough.
- the refill equipment is not closing correctly.
- the upper fill threshold level P26.13 Control Level MAX has been set too high.
Possible causes:
- blocked material in the weighing range
- non-symmetrical belt loading
The scales will not switch on automatically, regardless of the event class. The event
must first be acknowledged and the command to start given again before the scales
will restart.
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
If this event is pending then the downstream transport equipment is most likely not
switched on.
Caution: It probably does not have the full functionality. Unreliable operating
states may arise.
Possible causes:
- it forgot to load the correct link after exchanging the VCU.
- the name in the parameter was changed manually.
Steps to be taken:
- load the function block link with the correct name.
Possible cause:
- extremely damp bulk material
- moisture measurement measuring error
Also refer to: P30.08 Moisture MAX, P30.09 DO: Moisture MAX
Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces
Possible causes:
- incorrect entry
- incorrect upper threshold
Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too large
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
Possible causes:
- material has been incorrectly handled:
- the bulk material is flowing irregularly or cannot be discharged satisfactorily
- arching in the feed hopper
- there is a backup on the discharge side
- a large quantity of material continues to trickle from the feeder
- calibration error: during initial calibration the regulator was set at such a critical
value that minor changes in the overall properties of the system lead to unreliable
operation.
Also refer to: P11.08 Deviation abs. max., P11.07 Factor Deviation, P11.06 Thre-
shold Deviation, P11.05 Time Deviation
Possible reasons:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
Possible cause:
- refilling not switching off correctly
Possible causes:
- the belt is covered
- defect on the prefeeder
- weighing station stuck
- belt load regulation poorly adjusted
- defect in load cell
Actions:
- make a visual check of the bulk solids on the belt
- use a calibration weight to check the weighing station
Possible causes:
- overload on the pressure sensor
- defective sensor
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
Possible causes:
- extreme belt off-center run
- contaminated limit switch
- defect on automatic belt tracking
- defect on the belt
Actions:
- make a visual check of the belt run
- correct the belt run with the belt tightening equipment
- check the belt tightening and automatic belt tracking
Possible causes:
- belt is slipping at the drive pulley
- withdrawal forces are too high
- gearing is defective
- belt or drive pulley heavily soiled
Steps:
- visual inspection of the belt and the bulk material flow
Possible causes:
- contamination on the belt, the head pulley or the pulley with the second sensor
- the belt slips on the head pulley (higher draw-off strength and bulk solids stuck in
the inlet)
- sluggish pulley with the second sensor
Actions:
- make a visual check of the bulk solids situation
- check the drive motor and gear
- check the second pulley
Steps to be taken:
Check the cleaning equipment mechanically and electrically
Possible causes:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too low
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
Possible causes:
- sensor improperly connected
- unexpected pressure conditions
- defective sensor
Possible cause:
- refilling working incorrectly
Possible causes:
- no bulk solids
- defect on the prefeeder
- weighing station stuck
- belt load regulation poorly adjusted
- defect in load cell
Actions:
- make a visual check of the bulk solids on the belt
- use a calibration weight to check the weighing station
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
This function protects the motor from overheating at very low speeds or when idling.
Actions:
Key in the larger setpoint and check P07.02 Stand-By Limit Value.
A message occurs after each expired time interval. The message may indicate ser-
vice work required.
A message occurs after each expired time interval. The message may indicate ser-
vice work required.
Possible cause: depends on the external cabling. Usually: an error in the main drive
Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.
Steps:
- check cable connection
- check that operating console is correctly functioning
- check the operating console settings
- check the addresses of the scales at the RS485 data bus (P01.11 VHM RS485
Address)
9 Appendix
Details of special functions are described in this chapter.
The sources are preselected with parameters in the 'Control Sources' group.
You can use the OP Mode function to switch back and forth between the pre-selected sources and the key-
board (Keyboard Mode ON/OFF [➙ 30]).
The effective setpoint is displayed on the operating panel. The setpoint input field is only available if the
inputs from the operating panel are allowed by parameter.
A new window for entering the relative component will open when the setpoint field is touched if the relative
setpoint qualifier was pre-selected with the operating panel.
Setpoint Synchronization:
The external setpoint will be taken if the source of the setpoint is switched from an external source to the
keyboard (OP). The external source will take effect in the opposite direction.
On / Off Synchronization:
The on/off switch status is retained when switching from an external source to the keyboard (OP). The ex-
ternal source will take effect in the opposite direction.
Mains Power OFF:
The keyboard setpoints are stored.
Time Condition
1 Feeding does not begin with the on command since the all-clear signal has not been given.
2 To start, the scale requires the rising slope of a start command.
3 Feeding is started with the rising slope.
4 Flow rate control will operate in volumetric operation (also refer to: Volumetric / (Volumetric Syn-
chronous) / Gravimetric Modes of Regulator Operation [➙ 30]) during the start up time defined by T1
= P11.15.
5 Changing over in normal gravimetrically controlled feeding operation (assuming gravimetric mode
was previously selected). Control stays in volumetric mode (assuming it was previously selected by
the operator).
6 Feeding will be switched off if there is no all-clear signal (or if the switch on command was removed).
7 Flow rate recording continues over the time set by T2 = P06.01 to capture trickling bulk solids. After-
wards, the flow rate is no longer calculated; the counter stays at the level already achieved.
Tab. 39 : States and points in time in the flow chart
Parameters Function
Fig. 23: The module for measuring the belt load, belt velocity and flow rate
The controller structure is extended in the setting via P11.01 = UNIVERS as per the following figure. It can
be used to achieve the The beltweigher with feed control [➙ 12] and Beltweigher with a constant load
[➙ 13] control structures.
Gravimetric The measured belt load Q is used to ascertain the corresponding setpoint speed. The setpoint
is restricted to the value in P03.01.
Volumetric Mode The setpoint speed develops under the assumption of the rated belt load. The setpoint is re-
stricted to three times the value in P03.01.
Volumetric The most recently measured belt load Qa is used to ascertain the appropriate setpoint speed.
Synchronous The setpoint is limited to three times the value in P03.01.
Tab. 41 : Controller Modes
The controller operating mode is displayed on the operating panel by VOL and GRAV.
NOTE: The speed controller is active in all controller operating modes. If a controller magnitude
that is independant of the actual speed is supposed to be given for test purposes, this can
be done with the increase in P11.13 for flow rate setpoint = 0.
Volumetric Start-Up The operating mode for starting up an empty belt. The duration is determined by the P06.04,
P09.05 and P11.15 parameters.
The load set in P09.05 for P06.04 = FAST is used to ascertain the correct setpoint speed.
Otherwise, the rated belt load is used.
The switch-on command immediately sets the prefeeder and drive outputs to ON. The belt
velocity is controlled proportional to the setpoint. After the start up period, it automatically
switches to the measured value of the belt load, which means that the flow rate is controlled.
Volumetric Clearance The prefeeder is immediately switched off when the switch-off command is given, although the
belt continues to run in the Volumetric Synchronous operating mode for the belt route given in
P11.16 to transport the rest of the bulk solids from the belt.
A switch-on command when running empty triggers a new start up period while alarms turn the
belt drive off immediately.
P07.01 The external controller is turned off after 3 s at a controller magnitude below the boundary
defined by P07.02 to protect the drive motor and external flow rate controller from excess tem-
peraturs where the feeder scale continues to indicate running feeding to the control system
provided by customer. It is switched back into normal operation instantaneously. Stored por-
tions in the controller behave in the same fashion as when feeding is switched off.
Set P07.02 = 0 for permanent operation (even at a lower controller magnitude).
Tab. 42 : Special operating modes
Controller parameters
The relationship between the controller parameters and the actuating variable is shown schematically in the
following diagram.
Fig. 26: Effect of the controller parameters on the controller output with a discontinuous control deviation on t=0
KP P-portion of the feed rate controller related to the nominal feed rate as a % / %
or a dimensionless P-portion of the speed controller.
TN Reset time in seconds.
Tab. 43 : Controller parameters
duration defined in parameter Event: Deviation. Monitoring will restart if the error signal falls below the thre-
shold during this time.
At the same time, the control deviation value is filtered (filter time in parameter P11.05) and the filter output
is monitored. Event 'Event: Deviation' will be identified if the filter output exceeds the threshold value S2.
Threshold values S1 and S2 can be adapted to the current feed rate setpoint by means of the following for-
mulas:
S1 = P11.06 * [P11.07 + (1 - P11.07) * Feed rate setpoint / P03.01]
S2 = P11.08 * [P11.07 + (1 - P11.07) * Feed rate setpoint / P03.01]
The following diagram illustrates the relationship using with examples for threshold value S1.
The upper limit of the controller magnitude can be reduced to prevent excess feeding of hazardous sub-
stances at a low target feed rate.
This figure shows an example of the correlation for three selected settings of the MX parameter.
P11.19 Store The behavior of the integral component when turning off:
NO: do not save. Starting up with integral component = 0
YES: Starting up begins with the integral component saved before turning off.
YES-A: Only save when feeding has not become inoperative due to an alarm.
P11.21 Bypass Additive pre-control of the controller magnitude by the setpoint (bypass). The
controller magnitude stated in the parameter is given for 100 % setpoint.
The controller magnitude is not synchronized when changing the setpoint by-
pass. The bypass should only be changed in small steps or when the scale is
off to avoid larger jumps in feeding.
P11.20 Volumetric Mode Determining the behavior in volumetric operation:
Qconst: as the Volumetric Mode controller operating mode of the standard
controller
Yconst: the controller is switched off. Only bypass is working. This operating
mode is suited for the belt scale with prefeeder control.
P11.22 Setpoint Filter 1st Ord The filter is supposed to simulate the temporal behavior of a simple external
controlled loop. The time constant should be set in accordance with the exter-
nal route so that there are not any major control differences Xd occurring (ser-
vice value) with setpoint jumps during the signal's transit time. Furthermore,
stored portions are reset when the network is connected.
P11.23 Setpoint Filter 2nd Ord The filter is supposed to simulate the temporal behavior of a more complex
external controlled loop. Setting the time constant in accordance with P11.22.
P11.24 Set/Act Sources Selecting the process variables to be controlled:
→
I: Controlling the actual flow rate ( constant flow rate). The operating person-
nel can specify the setpoint.
→
Q: controlling the actual belt load ( constant belt load). The setpoint is speci-
fied by parameters.
P11.25 Adaptation 1 Adapting the controller with the setpoint. Adaptation adapts the control velocity
and stored integral component to the setpoint. Adaptation has few merits if
P11.21 is set appropriately.
It is not synchronized when changing adaptation. Adaptation should only be
changed when the scale is switched off to avoid greater feeding jumps.
Tab. 45 : The effect of selected parameters of the universal controller
0-5 Transitions in state (see table) T3 The duration of the adaptation period (P15.03)
T2 P06.01 Afterflow Totalizer Measu Recording the actual flow rate and calculating the
re totalizing counter
PR Effective flow rate setpoint Feed The switch-on command to the feeder's discharge
organ
Main_ The command for feeding in full feed Dbl_S The command for feeding in dribble feed
Spd pd
NOTE: The most important settings for batching are made in the Batch Mode block of parameters.
Adaptation
With adaptation, a corrective quantity K is calculated from the error quantity (batch actual weight - weight
setpoint) after each completed batch and stored in the P15.04 parameter. This automatically shifts items 3
to 5 of the diagram with the next batch.
K(new) = K(old) + P15.05 * error
K(new) = new corrective quantity
Error = actual batch weight – batch setpoint
Errors greater than the batching tolerance set by P15.14 are restricted to the set tolerance value. Shortfalls
that are smaller than the smallest display digit are not corrected.
P15.05 acts as a filter parameter to ensure that P15.04 contains a mean for the bulk material overrun with.
Threshold values
The P09.02 Event: Actual Flow Rate MIN event message is suppressed during the rundown time. This does
not apply to the digital output.
However, this method can only produce results after one complete belt circuit. A different method must be
used if more rapid identification is required.
In order to harness this method, the belt drift monitoring, the belt slip threshold (in P18.11) and the reaction
to the event (in P18.12 and P18.15) must be set.
The smallest measurable slip S_MIN is the larger of the values A and B:
A = 2 * 100 * vs / (P_U * S1C)
B = 2 * 100 * vs / (P_U * S2C)
Example
vs = 10,000
P_U = 30,000
S1C = S2C = 100
S_MIN = 0.667 %
If P34.07 < S_MIN: S_MIN has an effect.
NOTE: The impulses and pauses between impulses to S1 and S2 have to be at least 1.2 s long.
The impulse and pause have to be at least 0.2 s long if digital inputs are used on the first
VCU of a scale.
WARNING
There is danger from moving machine parts and flowing bulk solids
Interlocking can be suspended with lowering equipment and a start up warning depending upon settings and
cabling. Special protective measures should be complied with in this operating mode!
It can either be operated in local operation with a VLG model control unit or a VMO model control unit (with
a display).
You can find details on the design forms, connections and functionality of the VLG in the BV-H 2406 system
manual.
As an alternative, the VMO control unit can also be equipped with its own interface and be switched be-
tween VCU and the drive.
Plant Control
Optional:
Gravimetric
DISOCONT Tersus Operator Panel
VCU 20100 VHM 201xx
Local Machine
24VDC Supply Operator Panel
VMO 20101
Actuators/Sensors
(Motors/Valves)
In this case, the VCU can operate the interface of the VMO in automatic operation. It is autonomously con-
troled via VMO in manual operation. In this case, the parameters have to be adjusted in the VMO for local
operation in a way that matches the parameters of the VCU.
In both cases, the logic is wired for local operation in signal engineering between the automatic control via
VCU and the software interface to the drives.
The local operation logic is correspondingly notified what output signal is responsible for a drive.
The appropriate parameters are in the Local Mode (Speed) block for drives controlled by velocity with an
external controller or drives controlled by position as well as for valves or in the Local Mode (Gate) block for
feed gates with the open and close drive circuit.
The LS signal source designates the logical signal issued at an output in normal (automatic) operation. Then
the local operation logic drives the appropriate output in local operation.
The monitoring inputs for local operation are taken in parallel from the inputs for automatic operation.
DO DOx: Start Digital output for starting the drive adjusted as for P14.01 DO: Scale DO-VCU1-
normal operation per parameter. Start DO1
DO DOy: Doubling the signal for reporting Drive is Running P14.02 DO: Feeder DO-VCU1-
start(2) Started DO6
LS DOx: Run Input for the switch-on command in automatic opera- P40.02 ON in Remote LS-VCU1-
tion. This signal is passed onto DO DOx in automatic (Block 1) DO1
operation: Start.
This parameter links the local operation logic with
normal operation logic, thus stipulating which drive is
supposed to be switched in local operation.
Enable jog The parameter that defines whether the drive can be P40.05 JOG enable YES
started for set-up mode even if a malfunction is pend- (Block 1)
ing.
Loc Start Start command triggered by the start button of VMO Button on VMO
Local Mode VMO is in Local Mode signal. The conditions for being The state in VMO
able to switch VMO into local mode depend on the
configuration of VMO.
VMO exists The parameter that stipulates whether there is a VMO P01.12 VMO20100- YES
and if it is linked to the drive. P01.14 Unit 1 NO
P40.01 VMO20100- VMO1 motor
Unit 2 1
Motor Select
(Block 1)
Enable Loc The interlocking signal for switching on the drive in P40.06 Release local
Start local operation Start (Block
1)
DIx: Error1 The drive's error signal. The drive cannot be started P40.07 DI: External DI-VCU1-DI1
DIx: Error1 locally if there is an error. P40.08 Error 1 (Block n/a
1)
DIx: Error1 P40.09 n/a
DI: External
Error 2 (Block
1)
DI: External
Error 3 (Block
1)
Loc Active Local operation is active. The signal may also switch -
the controller magnitude for controlled drives to local
input from VMO.
AO AOx The analog output for specifying the speed to the P12.16 AO: Motor AO-VCU1-
drive, set as for normal operation per parameter. Speed AO1
Control
LS AOx The input for specifying speed in automatic operation. P40.03 Controller LS-VCU1-
The signal is passed onto AO AOx in automatic opera- Magnitude AO1
tion. (Block 1)
The parameter connects local operation logic to nor-
mal operation logic, thus stipulating which controller
magnitude is assigned to the drive in local operation.
LOC Seed Specifying the controller magnitude in local operation VMO input
on the VMO
Tab. 47 : Continuous signals
DO DOx: Open Digital output for opening the feed gate, set as for P25.14 S: DO Open DO-VCU1-
normal operation per parameter. Flow Gate DO1
DO DOx: Close Digital output for closing the feed gate, set as for nor- P25.15 S: DO Close DO-VCU1-
mal operation per parameter. Flow Gate DO2
LS DOx: Open The input for the Open command in automatic opera- P41.02 OPEN in LS-VCU1-
tion. The signal is passed onto DO DOx in automatic Remote DO1
operation: Start.
This parameter links the local operation logic with
normal operation logic, thus stipulating which drive is
supposed to be switched in local operation.
LS DOx: Close The input for the Open command in automatic opera- P41.04 CLOSE in LS-VCU1-
tion. The signal is passed onto DO DOx in automatic Remote DO2
operation: Start.
This parameter links the local operation logic with
normal operation logic, thus stipulating which drive is
supposed to be switched in local operation.
Loc Open The command for opening the valve, triggered by the Button on VMO
button of VMO
Loc Close The command for closing the valve, triggered by the Button on VMO
button of VMO
Local Mode VMO is in Local Mode signal. The conditions for being The state in VMO
able to switch VMO into local mode depend on the
configuration of VMO.
VMO exists The parameter that stipulates whether there is a VMO P01.12 VMO20100- YES
and if it is linked to the drive. P01.14 Unit 1 NO
P40.01 VMO20100- VMO1 motor
Unit 2 1
Motor Select
(Block 1)
Enable Loc The interlocking signal for switching on the drive in P40.06 Release local
Start local operation Start (Block
1)
DIx: Error1 The drive's error signal The drive cannot be started P40.07 DI: External DI-VCU1-DI1
DIx: Error1 locally if there is an error. P40.08 Error 1 (Block n/a
1)
DIx: Error1 P40.09 n/a
DI: External
Error 2 (Block
1)
DI: External
Error 3 (Block
1)
M The Measuring the Belt Load module CPF Continuous conveyor with continually controllable
prefeeder performance
Fig. 38: Loading controller with a coefficient estimate (i.e., two weighbridges)
Fig. 40: Loading setpoint optimization (OPT) and resulting feed belt velocity
The normal scales applies in normal operation. The fill level is regulated by the metering hopper. In intermit-
tent operation the metering hopper is activated when the fill level F-Min is underrun and is deactivated as
soon as the F-Max level is exceeded. If the metering hopper is continuously active (P27.01 = YES), the fill
level is regulated to the fill level setpoint F-Set by means of the changes in the metering hopper flow rate.
The check measurement takes over the fill regulation when a check is started. Wherever necessary, it is
filled until there are sufficient bulk solids in the bin (fill level > C-Check + C-Min). The check starts when the
fill level falls below F-Max and is stopped when the fill level falls below C-Min.
Setup Notes
P27.12 can be determined in a stationary state once the transient oscillations have subsided. In this state,
the value is calculated as follows:
P27.12 = (yB - P27.14 ) × P03.01 / flow rate setpoint
We recommend calling up the Optimizing Hopper Fill Level Regulation [➙ 46] adjustment program for the
control parameter after entering input the P27.07 and P27.12 parameters.
9.11 Linearization
The belt loading does not usually need to be linearized. It only makes sense with major belt load fluctua-
tions.
Repeat work processes 1 ... 3 with increasingly large calibration weights for the other linearization points.
Repeat work processes 1 ... 3 with increasingly large calibration weights for the other linearization points.
Tab. 48 : Legend
The P04.11 parameter decides on whether the correction to the shown actual flow rate and quantity integra-
tion derived from that or/and to the input signal of the optional controller has an impact. This makes it possi-
ble to easily control the bulk solids component B even in this architecture.
Fig. 46: Logic diagram of the links between events and ready messages
Explanations:
All signal levels can be inverted by setting the associated source parameter (also refer to Configuring the
Interfaces [➙ 66]). The factory default is given in the diagram.
▪
LOW: closed contact in standby, i.e. power is on. The contact is open if the signal is active (functions as
opener).
▪
HIGH: open contact in standby, i.e. power is not on. The contact is closed if the signal is active (func-
tions as closer).
E: event message
DI: digital input
DO: digital output
NOTE: When an input source parameter accepts the value n/a, the signal is internally assumed to
be True.
The effective weighing platform length "L" is an important value for calibration. It is determined by the design
of the weighing platform and can usually be found in the technical data sheets. However, it is always expe-
dient to measure the length manually and to enter the exact value as a parameter. The hatched area shows
the load distribution on the weighing platform.
Single-Idler Platform
The load on the weighing platform is conducted via a weighing idler into the load cell. This can be done by
means of a lever system or without levers by means of a parallel leaf-spring system.
Multiple-Idler Platform
Several weighing idlers are combined into one mechanical unit, the measuring bridge.
Buckled Platform
The weighing platform consists of two parts. The force is conducted centrally into the load cell. A split mea-
suring table can also be used in place of the weighing idlers.
Single-idler platform
α
tan( )» 0.018 * a
Angle
α=0:K=0
α
Angle = neg : K = neg
Multiple-idler platform
Buckled platform
The calibration weight usually has an effect in the center.
QPRF = QP
The following applies if the entire belt is supported on one side only:
If the belts are inclined, the extension or shortening of the calibration lever corresponding to the single-idler
platform must be taken into account.
0 ... 9 ms 10 ms … 1 s >1s
DO8 No pulse 10 ms … 1 s >1s
DO1 … DO7 No pulse 1s >1s
Tab. 49 : Long counting pulse
9.17 Using alternative signals (such as analog or fieldbus) for DMS inputs
It is usual for some signals to be read in through sensors with strain gauges (DMS) such as weight, force or
pressure signals. In special cases, these signals are recorded with other types of sensors or reshaped ex-
ternally so that they are available in the form of standard signals (such as 4 ... 20 mA). DISOCONT Tersus
provides the option of reading in some sources of input signals via standard signals. The standard signal is
read in through an analog VAI 20100 interface and reshaped to make it correspond to the signal of a DMS
sensor. The remaining signal processing is identical for the DMS signal and standard signal.
Some measuring signals can also be read in by fieldbus to prevent faults on the transmission path. These
are also processed like DMS signals after appropriate conversion.
Fig. 47: Alternative inputs using the example of a weight signal for an additional bin
LC DMS load cell output voltage 0-20 mA Input current from the external sensor
FB:kg The weight value in kg transmitted from [mV/V] A signal with the dimension mV/V
the fieldbus
Adjust Handing over the signal to the set-up LC [mV/V] The service value of the load in the dimension mV/V
program
LC_0 The rated load cell load in P26.04 LC [%] The service value of the load in percent of LC_0
V Transmission factor of the load cell in x, y Input and output values of the calculating blocks
P26.03
Error Error signal if the physical signal is out of Source Selecting the source for the signal in P26.02
range
Corr Multiplicative correction of the transmis- Tare Zero signal in P26.25 such as determined by the set-
sion factor in P26.24 up program
This figure uses recording the weight of an additional bin as an example of the form the signals of sources
other than DMS load cells are processed in. The set-up programs and service displays (including the para-
meters for tare and correcting sensitivity) remain in manual override, even though they show some values
such as for the DMS load cells. The figure applies accordingly to other signals such as force or pressure.
The corresponding parameters are in the group that also contains the parameter for selecting the signal
source.
NOTE: Please bear the fact in mind that the value resolution of a value read in through the stan-
dard signal is reduced by the resolution of the external transmitter and the VAI 20100 inter-
face assembly in relation to the input for DMS via interface VME0120 (VME0120: 24 bits
and VAI 20100: 16 bits). In addition, there can also be a temporal offset of the signal due to
scanning.
There can be additional errors in particular when forming the difference of signals (such as
differentiating) or a compensator (such as pressure compensation).
In this example, a binary input signal (for instance, an input contact of DISOCONT Tersus) is being read in
through the GP-Din 1 input block and the Delay 1 delay while an inverter is given to the And1-4 AND gate.
The other inputs are linked with the constant 1 and a Cycle 1 frequency generator. This provides the output
with a cyclical signal when the waiting period has elapsed after setting the input. The output of the AND gate
is linked to an output of the DISOCONT Tersus standard control. The physical output requires connecting
the signal with a digital output through P37.01 FCB_DO 01.
CAUTION: Creating and modifying links is reserved solely to Schenck Process person-
nel.
Configurations can be read out of and loaded into the control. They can be filed on the hard disk of PCs and
called up from there. Links have to be given a name. The empty link (as a factory default) has the name
Empty and should not be used for other links.
WARNING
Possible loss of function when exchanging the VCU.
Function blocks are not automatically stored with the parameters in
EasyServe. If a function block link is loaded, it will be necessary to store it
separately in EasyServe. If the VCU is exchanged, both the parameters
and the function block link have to be loaded separately to restore full func-
tionality. Alternatively, you can use the additionally installed tool
DISOPLAN (that contains both the parameters and the function block links)
to make a complete backup. However, this backup can then no longer be
used for setting a more recent version of the program in the scale.
It is not necessary with a system with the Empty link (refer to Cleaning the Screen and Information [➙ 41])
to reload the link after exchanging the VCU since there is no expansion to the functions from the function
blocks.
Loading the function software or loading default settings or the locking set of the parameters does not have
any impact on the function blocks loaded. In other words, any link that is already loaded is retained. Any
loaded link cannot be deleted; it can only be overwritten. If you want to make a link ineffective, it can be
overwritten with a new link that has to contain at least one block.
A loaded link does not have any effect on scales operation as long as the outputs for the link are not
coupled to the scales software with the corresponding parameters P36.01 to P37.20.
1 Binary inputs 20 Process variable as per the de- Connection between the function
'GP-DIn' scription of the fieldbus data inter- block logic and the function of the
face standard program
2 Binary output 20 - Makes output signals available. Con-
'GP-Dout' nect using the parameter in the 'FCB
digital outputs' block. All outputs are
available as status information in the
fieldbus interface.
3 Clock generator 2 Periodic time Signal generator for a periodic signal
'Cycle'
5 Pulse generator 1 Time for the pulse The timer has three outputs that
'Time' supply an pulse of 0.1 seconds dura-
tion at the time set.
6 AND 6 - And-link of two input signals
'And'
AND 4 - And-link of four input signals
'And 4'
7 OR 6 - Or-link of two input signals
'Or'
OR 8 - Or-link of four input signals
'Or 4'
8 Negation 10 - Invert the signal
'Not'
9 Delay 8 Delay time in seconds Delays the input signal by the speci-
'Delay' fied time
Tab. 51 : Blocks available for processing binary signals
1 Analog input 20 Process variable as per Input for a variable with a continuous value.
'GP-AIn' the description of the
fieldbus interface
2 Analog output 20 - Makes output signals available. Connecting via
'GP-Aout' parameters in the FCB analog outputs block. Only 5
FKB outputs can be configured to physical outputs.
All outputs are available as measured values in the
fieldbus interface.
3 Comparator 6 Upper and lower com- Supplies the value 'True' if the input signal lies out-
'Comparator' parative value side of the threshold values.
4 'Limit' 10 Upper and lower thre- Limits the input signal and becomes True when the
shold value limiter arises.
5 Multiplicator 5 - Supplies the product of the input values at the out-
'Multiplicator' put
9 Counter 6 Start value Supplies the counted input impulses at the output
The test connector is plugged into the load cell cable input on the DISOCONT Tersus instead of the load
cell cable.
Once plugged in, the raw measured value can be read off at the service values of the measuring electron-
ics. It must have the following value: raw measured value 1.5 mV/V ± 3 %.
Note: The raw measured data can be calculated according to the formula: raw measured data ~ 500 *
R2 / R1 [mV/V] if other resistance values should be used in the test connector
The measuring amplifier is working properly if the raw measuring value lies within this range.
The measured load display in kg depends on the way the scale's rated data are set.
Index
2. Password ..................................................................................................................................................................... 99
2nd Bridge analog Input Offset....................................................................................................................................... 186
2nd Bridge analog Input Range...................................................................................................................................... 187
2nd Bridge MAX ............................................................................................................................................................. 184
2nd Bridge MIN .............................................................................................................................................................. 184
2nd Bridge Offset ........................................................................................................................................................... 186
2nd Bridge Range .......................................................................................................................................................... 186
2nd Weighbridge ............................................................................................................................................................ 183
2nd Weighbridge ............................................................................................................................................................ 182
2nd Weighbridge active .................................................................................................................................................. 182
2-Sensor Slip.................................................................................................................................................................. 209
2-Sensor Slip active ....................................................................................................................................................... 209
2-sensor slip monitoring ................................................................................................................................................. 269
Abbreviations ................................................................................................................................................................... 66
About This Manual ............................................................................................................................................................. 1
Absolute Range.............................................................................................................................................................. 195
Accept Correction ........................................................................................................................................................... 189
Access Rights Limitation FB........................................................................................................................................... 153
Access Rights Limitation HMI........................................................................................................................................... 97
Access to Special Functions ............................................................................................................................................ 27
Accessing the Configuration............................................................................................................................................. 37
Acknowledging Event Messages...................................................................................................................................... 29
Activating belt influence compensation (BIC) ................................................................................................................... 58
Activating measurement and feeding with reference to the discharge point (VAP) .......................................................... 58
Adaptation 1 ................................................................................................................................................................... 128
Adaptation Factor ........................................................................................................................................................... 140
Adaptation Time ............................................................................................................................................................. 140
Additional Bin Weighers ................................................................................................................................................... 15
additional containers ........................................................................................................................................................ 15
Address .................................................................................................................................................................. 151, 152
Adjusting the external flow rate controller......................................................................................................................... 55
Adjusting the feeding controller ........................................................................................................................................ 56
Afterflow Totalizer .......................................................................................................................................................... 109
AI Moisture Measurement ............................................................................................................................................. 201
AI Offset ........................................................................................................................................................................ 207
AI Position Flow Gate .................................................................................................................................................... 207
AI Range ....................................................................................................................................................................... 207
Analog Channel A10 ........................................................................................................................................................ 93
Analog Channel A11 ........................................................................................................................................................ 94
Analog Output 2nd Bridge .............................................................................................................................................. 186
Analog Outputs .............................................................................................................................................................. 128
Analog Setpoint Relat..................................................................................................................................................... 141
Angle .............................................................................................................................................................................. 107
AO Actual Flow Rate ..................................................................................................................................................... 128
AO Belt Load ................................................................................................................................................................. 129
AO Bin Load .................................................................................................................................................................. 176
AO Check Measurement Result .................................................................................................................................... 198
AO Controller Magnitude Bin Level ............................................................................................................................... 179
AO Deviation ................................................................................................................................................................. 130
AO Flow Rate corrected ................................................................................................................................................ 202
AO Flow Rate Offset ..................................................................................................................................................... 203
AO Flow Rate Range .................................................................................................................................................... 203
AO Motor Speed Control ............................................................................................................................................... 131
AO Offset .............................................................................................................................................................. 176, 207
AO PLC 1 ...................................................................................................................................................................... 159
AO PLC 2 ...................................................................................................................................................................... 159
AO Position Flow Gate .................................................................................................................................................. 207
AO Range ............................................................................................................................................................. 176, 208
AO Setpoint ................................................................................................................................................................... 128
AO Speed...................................................................................................................................................................... 129
Appendix ........................................................................................................................................................................ 257
Assembling the Electrical Components ............................................................................................................................ 54
Authorization for Control Commands ............................................................................................................................... 26
Index